Correspondence I
July 11, 1995 i,, k
CITY OF TIGARD
Richard Chang OREGON
c/o Express Permits
1327 Post Ave. Suite H
Torrance, CA 90501
Re: The Gap
9724 Washington Square Rd.
P.R. 6 -46C (BUP 95 -0251)
Dear Sirs:
The plans have been reviewed for conformity to the applicable codes. Please submit the
following items to complete the review process.
ACCESSIBILITY
1. The plan did not illustrate a cashier station or customer service counters.
Accessible check out aisles shall be on an accessible route complying with Section
3109(s). Counters in accessible check out aisles shall not be more than 36 inches
high and not less than 36 inches in length [OSSC, Section 3109(w) 2 & 3].
Provide illustration.
FIRE AND LIFE SAFETY
1. The wall type specified for the exit corridor is not of one -hour construction. (see
sheet A 6.0). Specify the correct design.
2. Access to the exit corridor shall not pass through the stock room or fitting room
area [OSSC, Section 3303(e)]. Provide immediate access to a rate corridor from
the sales area. -
3. Illustration 14/A6.5 shall specify 5/8" type X fire resistive gypsum board.
4. Provide exit illumination having an intensity of not less than one foot candle at floor
level, and provide a separate power source, such as an on -site generator or
storage batteries to operate the lighting system in the exiting system [Section
3313(a)(b)]. -
5. The width of aisles leading to required exits shall be provided from all portions of
the tenant space. Provide a 44 inch wide aisle front to back, cross aisle and aisle
to the exit corridor [Section 3315(a)(b) 2]. Submit a floor plan showing placement
of fixtures and racks provide required aisle width.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
1
•
July 11, 1995
Express Permits
Page 2
6. Provide an exit sign at the exit corridor entrance incorporating the international
symbol of accessibility [OSSC, Section 3109(o) 6].
7. Provide size 2A fire extinguishers throughout so that the maximum travel distance
shall not exceed 75 feet [NFPA 10, Section 3 -2].
STRUCTURAL
1. Provide the design, specifications and calculation prepared by a licensed structural
engineer for the suspended gypsum board ceiling in illustration 14/A6.0. Include
a review of structural roof elements supporting the additional load.
Provide the valuation of the project for permit fee calculations. Provide three copies of
the applicable revised plan sheet.
If you have any questions regarding these items, feel free to call.
Sincerely,
A/7"/P
James Funk
Plans Examiner
H1LOGINUIM GAP
tJ 95 - cr0 25!
9 7 �Lf lt/� -r!, S� ►�d
I I L
®gin
Incorporated
July 13, 1995
The GAP Store Planning
900 Cherry Avenue
San Bruno, CA 94066
Attn: Mary Wiley
Re: Gap #2805
Washington Square
Tigard, Oregon
Dear Mary:
We have reviewed the Plan Review from the City of Tigard dated July 11, 1995 for the
subject project and have the following response:
Item #14 The exit illumination of the store has an intensity of not less than one foot
candle at floor level. Enclosed are three pages of typical GAP photometric
calculations on emergency lighting. Emergency I' hting is equipped with
emergency battery pack, see General Sheet Note
•
Very truly yours,
BELDEN, Inc.
J rn Estabillo
JE /sc
Enclosure
cc: Thaddeus Ballentine - Encon
95 -188
•
Electrical Consulting Engineers
395 MacArthur Boulevard, San Leandro, California 94577 -2110 (510) 635 -6053
FAX (510) 635 -6142