Series TY -FRB — 28, 4.2, 5.6, and 8.0 K- factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli- '
Description cable approval agencies, the testing is „_. -' )1...I
not representative of all possible cor-
The Series TY-FRB, 2.8, 4.2, 5.6, and rosive atmospheres. Consequently, it -
8.0 K- factor, Upright and Pendent is recommended that the end user be ” 1
r - 116 .
Sprinklers described in this data sheet consulted with respect to the suitability R .
are quick response - standard cover- of these coatings for any given corro-
age, decorative 3 mm glass bulb type sive environment. The effects of ambi- .,.
spray sprinklers designed for use in ent temperature, concentration of = y "
. light or ordinary hazard, commercial chemicals, and gas /chemical velocity, ~ 'tea
occupancies such as banks, hotels, should be considered, as a minimum, "`
shopping malls, etc. along with the corrosive nature of the
The recessed version of the Series chemical to which the sprinklers will be
TY-FRB Pendent Sprinkler, where ap- exposed. ice_
plicable, is intended for use in areas An intermediate level versions of the
with a finished ceiling. It uses either a Series TY-FRB Pendent Sprinklers are r "
two -piece Style 10 (1/2 inch NPT) or detailed in Technical Data Sheet , .
Style 40 (3/4 inch NPT) Recessed Es- TFP356, and Sprinkler Guards are de- ( e
cutcheon with 1/2 inch (12,7 mm) of tailed in Technical Data Sheet TFP780
recessed adjustment or up to 3/4 inch } � . j
(19,1 mm) of total adjustment from the WARNINGS
flush pendent position, or a two-piece The Series TY -FRB Sprinklers de-
Style 20 (1/2 inch NPT) or Style 30 (3/4 scribed herein must be installed and ch NPT) R ecessed Escutcheon with "
� ma intained in compliance with this �;�^.�
1/4 inch (6,4 mm) of recessed adjust- document, as well as with the applica-
ment or up to 1/2 inch (12,7 mm) of ble standards of the National Fire Pro- TY3231 - Pendent 5.6K,1/2 "NPT
total adjustment from the flush pen- tection Association, in addition to the TY4131 - U ri ht 8.0K, 3/4 "NPT
dent position. The adjustment provided standards of any other authorities hay- p g „
by the Recessed Escutcheon reduces ing jurisdiction. Failure to do so may TY4231 - Pendent 8.0K, 3/4 NPT
the accuracy to which the fixed pipe impair the performance of these de- T
drops to the sprinklers must be cut. vices. ■ echnical
Corrosion resistant coatings, where The owner is responsible for maintain- Data
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition.
that which would otherwise be ob- The installing contractor or sprinkler Approvals
tained when exposed to corrosive at- manufacturer should be contacted UL and C -UL Listed.
with any questions. FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
IMPORTANT information including corrosion resis-
Always refer to Technical Data tant status.)
Sheet TFP700 for the INSTALLER Model /Sprinkler Maximum Working Pressure
WARNING° that provides cautions
with respect to handling and instal- Identification 175 psi (12,1 bar)
- lation of sprinkler systems and corn- Discharge Coefficient
�/
ponents. Improper handling and in- Numbers K = 2.8 GPM /psi (40,3 LPM/barl
stallation can permanently damage K = 4.2 GPM /psi (60,5 LPM/bar
a sprinkler system or its compo- TY1131 - Upright 2.8K, 1/2 "NPT K = 5.6 GPM /psi (80,6 LPM/barl/
nents and cause the sprinkler to fail TY1231 - Pendent 2.8K,1/2 "NPT K = 8.0 GPM /psi (115,2 LPM /bar
to operate in a fire situation or cause TY2131 - Upright 4.2K, 1/2"NPT Temperature Ratings
it to operate prematurely. TY2231 - Pendent 4.2K, 1/2"NPT Refer to Table A and B
TY3131 - Upright 5.6K,1/2 "NPT
Page 1 of 8 JULY, 2004 TFP171
Page 2 of 8 TFP171
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
• PLATE SEATING 1/2° ** NOMINAL RECESSED SSU*
SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR
,
!=6 5
2 -1/4" imr�� 711m
� �� ( 1 1 ,1 mm)
!, _ NOMINAL MAK 4
(57,2 mm)
- ` E -IN ili
2
1 9116" I I' r�r 2 ,6m I ile I Ft 3
(39,7 mm) FLATS ----=._—_-_- (55,6 mm) .� o � 1
7
SSP DEFLECTOR * - 2 -7/8" (73,0 mm) DIA. 1 1/2" NPT I
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw ** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING 1/2° ** NOMINAL RECESSED SSU*
SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR
6
2- 3/16" _— —� Il�r� 7 m
11
1 = 5
pi (111 mm)
(55,6 mm) = -�� �� NOMINAL ; 4
MAKE -IN I
1-1/2" lig q1111 WREN I H ` =� ! (55,6 mm) 0 I A A 2
(38,1 mm)
1 -- -- . 111 FLATS f' i 3
SSP DEFLECTOR * 2 -7/8" (73,0 mm) DIA. 1/2" NPT i
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K- FACTOR, 1/2 INCH NPT
Y
. Cu
Finishes Bulb Glass m
Sprinkler: Refer to Table A and B Compression Screw Bronze Operation
Recessed Escutcheon: White Coated, Deflector . . . . . . Copper /Bronze
Chrome Plated, or Brass Plated Bushing (K =2.8) Bronze The glass Bulb contains a fluid which m
expands when exposed to heat. When w
the rated temperature is reached, the m
Physical Characteristics fluid expands sufficiently to shatter the Q
Frame Bronze glass Bulb, allowing the sprinkler to c
Button Brass /Copper activate and water to flow. a
Sealing Assembly o
Beryllium Nickel w/Teflont +-
TFPI 71 Page 3 of 8
ESCUTCHEON 7/16° (11,1 mm) STYLE 10 or 20
' PLATE SEATING 1/2" ** NOMINAL RECESSED SSU*
SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR
i�
rC 7/16" ■
e go 5
2- 3/16" �- — —T mr=- (11,1 mm)
(55,6 mm) / EI ,1W! `� I NOMINAL I 4
t — MAKE -IN
(38,1 /mm !I II r!? I ` � �� AD 2
) WRENCH — (55,6 mm) 3
1 - . FLATS =_°
SSP DEFLECTOR * - 2 -7/8" (73,0 mm) DIA. 1/2" NPT **
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40
PLATE SEATING * NOMINAL RECESSED SSU*
SURFACE NPTIN ESCUTCHEON DEFLECTOR
T \___ _ll 6*
1
� .
1/2" 5
2 -5/16" sm. 12,7 mm )
(58,7 mm) ate/ inE I NOMINAL L 4
``�� MAKE -IN '
1 -9/16" 2 -1M" 1 2
(39,7 mm) 110 WRENCH = (57,2 mm) V v
FLATS = l F 3 'SO II II I SS DEFLECTOR �— 2 -7/8" (73,0 mm) DIA. 1 3/4" NPT ** f
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
Listing is based on the requirements of
Design NFPA 13, and FM Approval is based Installation
on the requirements of FM's Loss Pre -
Criteria vention Data Sheets ). Only the Style The Series TY-FRB Sprinklers must be
10, 20, 30, or 40 Recessed Escutch- installed in accordance with the follow -
The Series TY-FRB Pendent and Up- eon, as applicable, is to be used for ing instructions:
right Sprinklers are intended for fire recessed pendent installations.
protection systems designed in ac- NOTES
cordance with the standard installation Do not install any bulb type sprinkler if
rules recognized by the applicable the bulb is cracked or there is a loss of
Listing or Approval agency (e.g., UL liquid from the bulb. With the sprinkler
•
Page 4 of 8 TFP171
SPRINKLER FINISH (See Note 7) inch NPT sprinkler joint should be ob-
K TYPE TEMP. BULB NATURAL CHROME WHITE*" tained with a torque of 10 to 20 ft.lbs.
LIQUID BRASS PLATED POLYESTER (13,4 to 26,8 Nm). A maximum to be of 30
ft.lbs. (40,7 Nm) ) o of torque is to be used
to install sprinklers with 3/4 NPT con -
135°F/57°C Orange nections. Higher levels of torque may
PENDENT 155 °F /68 °C Red distort the sprinkler inlet and cause
(TY1231) 1, 2, 3, 5 leakage or impairment of the sprinkler.
and 175 °F /79 °C Yellow
Do not attempt to make -up for insuffi-
UPRIGHT P00 °F /93 °C Green 131) cient adjustment in the escutcheon
2.8 286 °F /141 °C Blue plate by under- or over - tightening the
1/2" sprinkler. Readjust the position of the
NPT 135 °F /57 °C Orange sprinkler fitting to suit.
RECESSED 155 °F /68 °C Red The Series TY -FRB Pendent and Up-
PENDENT
(TY1231)• 175 °F /79 °C Yellow right Sprinklers must be installed in
Figure 5 200°F/93°C Green 1, 2, 5 accordance with the following instruc-
tions.
135 °F /57 °C Orange Step 1. Pendent sprinklers are to be
RECESSED 155 °F /68 °C Red installed in the pendent position, and
PENDENT upright sprinklers are to be installed in
(TY1231)° 175 °F /79 °C Yellow the upright position.
Figure 6 200 °F /93 °C Green Step 2. With pipe thread sealant ap-
135 ° F %57 °C Orange plied to the pipe threads, hand tighten
PENDENT the sprinkler into the sprinkler fitting.
(TY2231) 155 °F /68 °C Red Step 3. Tighten the sprinkler into the
and 175 °F /79 °C Yellow sprinkler fitting using only the W -Type
UPRIGHT 200 °F /93 °C Green 6 Sprinkler Wrench (Ref. Figure 13).
2131 With reference to Figures 1, 2, 3, and
4.2
(TY2131) 286 °F /141 °C Blue 2 4, the W -Type 6 Sprinkler Wrench is to
1/2° be applied to the sprinkler wrench
NPT 135 °F /57 °C Orange flats.
RECESSED 155 °F /68 °C Red
PENDENT
(TYfl31p 175 °F /79 °C Yellow The Series TY -FRB Recessed Pen -
Flgure 7 200 °F /93 °C Green dent Sprinklers must be installed in
accordance with the following instruc-
135°F/57°C Orange tions.
RECESSED 155 °F /68 °C Red Step A. After installing the Style 10.
PENDENT 20, 30, or 40 Mounting Plate, as appli-
(TY2231)'• 175 °F /79 °C Yellow cable, over the sprinkler threads and
Figure 8 200 °F /93 °C Green with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
NOTES: kler into the sprinkler fitting.
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. Step B. Tighten the sprinkler into the
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response sprinkler fitting using only the W -Type
Sprinklers. 7 Recessed Sprinkler Wrench (Ref.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin
klers. Figure 14). With reference to Figure 1,
5. Approved by the City of New York under MEA 354 -01 -E. 2, 3, and 4, the W -Type 7 Recessed
7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- Sprinkler Wrench is to be applied to
kiers are UL and C -UL Listed as Corrosion Resistant Sprinklers. the sprinkler wrench flats.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Step C. After the ceiling has been in-
Recessed Escutcheon, as applicable. stalled or the finish coat has been ap-
" Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment plied, slide on the Style 10, 20, 30, or
Recessed Escutcheon, as applicable. 40 Closure over the Series TY FRB
— Frame and Deflector only. Listings and approvals apply to color (Special Order). Sprinkler and push the Closure over
N/A: Not Available p p
the Mounting Plate until its flange
TABLE A comes in contact with the ceiling.
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K- FACTOR SPRINKLERS
held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint
should be present. The diameter of the should be obtained with a torque of 7
air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi -
(1,6 mm) for the 135 °F /57 °C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque
inch (2,4 mm) for the 286 °F /141 °C may be used to install sprinklers with
temperature ratings. 1/2 NPT connections. A leak tight 3/4
1
•
TFP171 Page 5 of 8
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL CHROME WHITE*** LEAD
LIQUID BRASS PLATED POLYESTER COATED
135 °F /57°C Orange
PENDENT 155 °F /68 °C Red
(TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5
and 175 °F /79 °C Yellow
UPRIGHT P00 °F /93 °C Green
5.6 (TY3131)
286 °F /141 °C Blue
1/2°
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 4, 5 N/A
(TY3231)* 175 °F179 °C Yellow
Figure 9 200 °F /93 °C Green
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1,2,3,4,5 1,2,4,5 N/A
(TY3231)** 175 °F /79 °C Yellow
Figure 10 200 °F /93 °C Green
135 °F /57 °C Orange
P N 155 °F /68 °C Red
(TY42 1, 2 5
and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7
UPRIGHT 200 °F /93 °C Green
8.0 (TY4131)
286 °F /141 °C Blue
3/4°
NPT 135 °F /57 °C Green
RECESSED 155 °F /68 °C Orange
PENDENT 1, 2, 4, 5 N/A
(TY4231)* 175 °F /79 °C Red
Figure 11 200 °F /93 °C Yellow
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4231)** 175 °F /79 °C Yellow
Figure 12 200 °F /93 °C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31-53-428-3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
• Installed with Style 10 (1/2° NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2° NPT) or Style 30 (3/4" NPT) 1/2° Total Adjustment Recessed Escutcheon, as applicable.
*** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K- FACTOR SPRINKLERS
Page 6 of 8 TFP171
2 - 7/8° DIA. 2 -7/8° DIA. _
• 5/8±1/4° (73,0 mm) 3/4° (19,1 mm) 1/2±1/8" (73,0 mm) 1/2° (12,7 mm)
(15,91-6,4 mm) 2 -1/4' DIA. 1/4' (6,4 mm) (12,7±3,2 mm) 2 -1/4' DIA. 1/4' (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm)
MOUNTING
SPRINKLER
PLATE SPRINKLER PLATE
FITTING FITTING
1/8° 1/8°
lU (3,2 mm) � 1�11! i ( 3,2 mm)
f 1 ' i
WI 4r. , �,�, SURFACE
� '
MOUNTING II .
SURFACE • rirwo�
CLOSURE SERIES 1-5/16' (33,3 mm) CLOSURE SERIES 1 -5/16" (33,3 mm)
TY -FRB 13/16° (20,6 mm) TY-FRB 1 -1/16° (27,0 mm)
FIGURE 5 FIGURE 6
SERIES TY-FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT
2 -7/8' DIA. 2 -7/8" DIA. _
5/8±1/4' ( mm) 3/4' (19,1 mm) 1/2±1/8° (73,0 mm) 1/2° (12,7 mm)
(15,9±6,4 mm) 2 -1/4' DIA. 1 1/4° (6,4 mm) (12,7±3,2 mm) 2 -1/4° DIA. J 1/4' (6,4 mm)
- FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) I MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8° 1/8"
.. ( mm) � M -' 111 ; " (3,2 m) I-; // - -] w MOUNTING SURFACE 1'
SURFACE - ■ -. • .
CLOSURE SERIES 1 -1/4' (31,8 mm) CLOSURE SERIES 1 -1/4° (31,8 mm)
TY-FRB 3/4° (19,1 mm) TY-FRB 1' (25,4 mm)
FIGURE 7 FIGURE 8
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT
used to cover a clearance hole, may and after installation. Sprinklers dam -
Care and delay the time to sprinkler operation in aged by dropping, striking, wrench
a fire situation. twist/slippage, or the like, must be re-
Maintenance Sprinklers that are found to be leaking has a crackedpbulb or any sprinkler
t has lost
The Series TY-FRB Sprinklers must be or exhibiting visible signs of corrosion liquid from its bulb. (Ref. Installation
maintained and serviced in accord- must be replaced. Section).
ance with the following instructions: Automatic sprinklers must never be Frequent visual inspections are rec-
' painted, plated, coated or otherwise q P
NOTES altered after leaving the factory. Modi- ommended to be initially performed for
Before closing a fire protection system fled sprinklers must be replaced. corrosion resistant coated sprinklers,
main control valve for maintenance Sprinklers that have been exposed to after the installation has been corn-
work on the fire protection system that corrosive products of combustion, but
pleted, to verify the integrity of the cor-
it controls, permission to shut down the have not operated, should be replaced rosion resistant coating. Thereafter,
affected fire protection system must be if they cannot be completely cleaned annual inspections per NFPA 25
obtained from the proper authorities by wiping the sprinkler with a cloth or should suffice; however, instead of in-
and all personnel who maybe affected by brushing it with a soft bristle brush. specting from the floor level, a random
by this action must be notified. sampling of close -up visual inspec-
Care must be exercised to avoid dam- tions should be made, so as to better
Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi-
TFPI 71 Page 7 of 8
2 -7/8° DIA. 2 -7/8° DIA.
5/8±1/4° (73,0 mm) 3/4° (19,1 mm) 1/2±1/8° (73,0 mm) 1/2° (12,7 mm)
(15,9±6,4 mm) 2 -1/4' DIA. 1/4' (6,4 mm) (12,7±3,2 mm) 2 -1/4' DIA. 1/4' (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm)
MOUNTING
SPRINKLER
PLATE SPRINKLER PLATE
FITTING FITTING
1!8' 1/8°
•M i (3,2 mm) ... 1 (3,2 mm)
a--- =.114! , 1E1 - 7111M=i,=-_, 49' f
� t _._J
MOUNTING 11,
MOUNTING �, , SURFACE
SURFACE –�.: -
CLOSURE SERIES 1 -1/4' (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm)
TY -FRB 3/4' (19,1 mm) TY-FRB 1' (25,4 mm)
FIGURE 9 FIGURE 10
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT
2 -7/8' DIA. 2 -7/8" DIA. _
5/811/4° (73,0 mm) 3/4' (19,1 mm) 1/2±1/8' (73,0 mm) 1/2° (12,7 mm)
(15,9±6,4 mm) 2 -1/4' DIA. 1/4' (6,4 mm) (12,7±3,2 mm) 2 -1/4° DIA. 1/4° (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8°
" 1/8°
■ (3,2 mm) (3,2 mm)
• — rll r r ���'
, ' MOUNTING 11 j f
MOUNTING � SURFACE
.
SURFACE i 1
CLOSURE SERIES 1 -5/16° (33,3 mm) CLOSURE SERIES 1 -5/16° (33,3 mm)
TY-FRB 13/16° (20,6 mm) TY-FRB 1 -1/16° (27,0 mm)
FIGURE 11 FIGURE 12
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may WRENCH
be affected by the corrosive conditions Ll RECESS
present.
WRENCH RECESS F°.
The owner is responsible for the in- (END °A° USED FOR 1
JO? ,),
spection, testing, and maintenance of 1/2° NPT MODELS)
their fire protection system and de- �.
vices in compliance with this docu-
ment, as well as with the applicable S
• standards of the National Fire Protec- WRENCH RECESS
USH WRENCH
Lion Association (e.g., NFPA 25), in (END °B° USED FOR PN TO ENSURE
addition to the standards of any other 3/4' NPT MODELS) ENGAGEMENT
authorities having jurisdiction. The in- WITH SPRINKLER
stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA
facturer should be contacted relative to W - TYPE 6 SPRINKLER
any questions. WRENCH
It is recommended that automatic FIGURE 14
sprinkler systems be inspected, local requirements and /or national W - TYPE RECESSED
tested, and maintained by a qualified codes. SPRINKLER WRENCH
Inspection Service in accordance with
Page 8 of 8 TFP171
P/N 57 - XXX - X - XXX
I I
TEMPERATURE
MODEUSIN RATING
SPRINKLER
330 2.8K UPRIGHT (1 /2 "NPT) TY1131 135 135 °F /57 °C
331 2.8K PENDENT (1 /2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C
340 4.2K UPRIGHT (1 /2 1NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C
341 4.2K PENDENT (1 /2 "NPT) TY2231 3 WHITE (RAL9010)• 200 200 °F /93 °C
370 5.6K UPRIGHT (1 /2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C
371 5.6K PENDENT (1 /2 "NPT) TY3231 7 LEAD COATED
390 8.0K UPRIGHT (3 /4 "NPT) TY4131
391 8.0K PENDENT (3/4 "NPT) TY4231 • Eastern Hemisphere sales only.
TABLE C
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
• ORY, FOR INCIDENTAL, INDIRECT, Recessed Escutcheon:
Limited SPECIAL OR CONSEQUENTIAL Specify: Style (specify) Recessed Es-
DAMAGES, INCLUDING BUT NOT cutcheon with (specify finish), P/N
. Warranty LIMITED TO LABOR CHARGES, RE- (specify).
GARDLESS OF WHETHER TYCO
Products manufactured by Tyco Fire FIRE PRODUCTS WAS INFORMED 1/2' (15 mm)
Products are warranted solely to the ABOUT THE POSSIBILITY OF SUCH Style 10
original Buyer for ten (10) years DAMAGES, AND IN NO EVENT Chrome Plated P/N 56- 701 -9-010
against defects in material and work- SHALL TYCO FIRE PRODUCTS' LI- White Coated P/N 56- 701 -4 -010
manship when paid for and properly ABILITY EXCEED AN AMOUNT Brass s Plated Plated 0' P/N 56-701-3-010
Bras P/N 56- 701 -2 -010
installed and maintained under normal EQUAL TO THE SALES PRICE.
use and service. This warranty will ex- THE FOREGOING WARRANTY IS 1/2" (15 mm)
pire ten (10) years from date of ship- MADE IN LIEU OF ANY AND ALL, Style 20
ment by Tyco Fire Products. No war-
OTHER WARRANTIES EXPRESS OR Chrome Coated P /n 56-705-4-010
4-
ranty is given for products or
components manufactured by compa- IMPLIED, INCLUDING WARRANTIES White RAL9010• P/N 56- 705 -3-010
Hies not affiliated by ownership with OF MERCHANTABILITY AND FIT- Brass Plated P/N 56 -705 -2 -010
Tyco Fire Products or for products and NESS FOR A PARTICULAR PUR 3/4• (20 mm)
components which have been subject POSE Style 30
to misuse, improper installation, corro- Chrome Plated P/N 56- 705 -9-011
sion, or which have not been installed, White Coated P/N 56 -705 -4 -011
maintained, modified or repaired in ac- White RAL9010• P/N 56- 705 -3-011
cordance with applicable Standards of Ordering Brass Plated P/N 56- 705 -2 -011
the National Fire Protection Associa- Procedure 3/4" (20 mm)
tion, and /or the standards of any other Style 40
Authorities Having Jurisdiction. Mate- Osintacitvgkin local distributor for avail- Chrome Plated P/N 56- 700 -9-010
rials found by Tyco Fire Products to be abq indicate the White Coated P/N 56 -700 -4 -010
defective shall be either repaired or ful White RAL9010" P/N 56 -700 -3 -010
replaced, at Tyco Fire Products' sole name. Refer to Brass Plated P/N 56 -700-2 -010
option. Tyco Fire Products neither as- the complete List for
o
p y complete listing 'Eastern Hemisphere sales only.
sumes, nor authorizes any person to of Part Numbers.
• assume for it, any other obligation in Sprinkler Wrench:
connection with the sale of products or Sprinkler Assemblies with NPT Specify: W -Type 6 Sprinkler Wrench,
parts of products. Tyco Fire Products Thread Connections: P/N 56- 000 -6 -387.
. shall not be responsible for sprinkler Specify: (Specify Model /SIN), Quick
system design errors or inaccurate or Response, (specify K- factor), (specify Specify: W -Type 7 Sprinkler Wrench,
incomplete information supplied by temperature rating), Series TY-FRB P/N 56- 850 -4 -001.
Buyer or Buyer's representatives. (specify Pendent or Upright) Sprinkler
IN NO EVENT SHALL TYCO FIRE with (specify type of finish or coating),
PRODUCTS BE LIABLE, IN CON- P/N (specify from Table C).
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE -