Series TY -B — 5.6 K- factor
Horizontal and Vertical Sidewall Sprinklers
Standard Response, Standard Coverage
Corrosion resistant coatings, where
General applicable, are utilized to extend the
life of copper alloy sprinklers beyond
Description that which would otherwise be ob- pe "
�_ - , r
tained when exposed to corrosive at- 4:1 / `
The Series TY-B, 5.6 K- factor, Horizon- mospheres. Although corrosion resis- „ " ' '
tal a Vertical Sidewall Sprinklers de- tant coated sprinklers have passed the , 1 er !. 'nt, ' " ,
scribed in this data sheet are standard standard corrosion tests of the appli- 1 i ' ",' : "-
response - standard coverage, deco- cable approval agencies, the testing is .€ 4 i,w ?Cr `
rative 5 mm glass bulb type spray not representative of all possible cor- •` : ,r;
sprinklers designed for use in light and rosive atmospheres. Consequently, it :
ordinary hazard, commercial occupan- is recommended that the end user be
cies such as banks, hotels, shopping consulted with respect to the suitability
malls, etc.They are designed for instal- of these coatings for any given corre-
lation along a wall or the side of a beam sive environment. The effects of ambi-
and just beneath a smooth ceiling. ent temperature, concentration of
Sidewall sprinklers are commonly chemicals, and gas /chemical velocity,M
used instead of endent or upright
P should be considered, as a minimum, %���.�,�, {
sprinklers due to aesthetics or building along with the corrosive nature of the i
construction considerations, where chemical to which the sprinklers will be {
piping across the ceiling is not desir- exposed.
able. 'i ,
The recessed version of the Series WARNINGS "1,.,��, ;
TY B Horizontal Sidewall Sprinkler Is The Series TY -B Sprinklers describe ° r
intended for use in areas with a fin- r FK,f
herein must be installed and main-
ihed wall. It uses a two-piece Style 10 tamed in compliance with this docu - r� R
Recessed Escutcheon. The Recessed ment, as well as with the applicable °,��
Escutcheon provides 1/2 inch (12,7 standards of the National Fire Protec- ��.
mm) of recessed adjustment or up to tion Association, in addition to the
3/4 inch (19,1 mm) of total adjustment standards of any other authorities hav
from the flush sidewall position. The ing jurisdiction. Failure to do so ma y
adjustment provided by the Recessed impair the performance of these de- Technical
Escutcheon reduces the accuracy to vices Data
which the fixed pipe nipples to the The owner is responsible for maintain-
sprinklers must be cut. ing their fire protection system and de- Approvals
vices in proper operating condition. UL and C -UL Listed.
The installing contractor or sprinkler FM, LPCB, and NYC Approved.
manufacturer should be contacted (Refer to Table A for complete approval
with any questions. information including corrosion resis-
tant status)
IMPORTANT Maximum Working Pressure
Always refer to Technical Data
Sheet TFP700 for the `INSTALLER Model /Sprinkler 175 psi (12,1 bar)
WARNING" that provides cautions Discharge Coefficient
with respect to handling and instal- identification K = 5.6 GPM /psi (80,6 LPM/barli
lation of sprinkler systems and com-
ponents. Improper handling and in- Numbers Refer Temperature
Table A g
stallation can permanently damage
,- a sprinkler system or its compo- TY3351 - Horizontal Finishes
nents and cause the sprinkler to fail TY3451 - Vertical Sprinkler: Refer to Table A
to operate in a fire situation or cause Recessed Escutcheon: White Coated,
it to operate prematurely. Chrome Plated, and Brass Plated
Page 1 of 6 JULY, 2004 TFP161
Page2of6
TFP161
SPRINKLER FINISH (See Note 10)
K TYPE TEMP. BULB NATURAL CHROME WHITE*" LEAD WAX WAX OVER
LIQUID BRASS PLATED POLYESTER COATED COATED LEAD COATED
135 °F /57 °C Orange
HORIZ. SIDEWALL 155 °F /68 °C Red
(TY3351)
175 °F /79 °C Yellow 1,2,3,4,9 1,2,3,9 1,2,3,9 1,2,3,9 1,2,3,9
200 °F /93 °C Green
5.6 286 °F /141 °C Blue
1", 2•° 3•• 9 ** 1", 2° 3• *, g•+
1/2"
NPT 360 °F /182 °C Mauve 1, 2, 4, 9 1, 2, 9 N/A
RECESSED 135 °F /57 °C Orange
HORIZ. 155 °F /68 °C Red
SIDEWALL
(TY3351)' 175 °F /79 °C Yellow 1, 2, 3, 9 N/A
Figure 3 200 °F /93 °C Green
135 °F /57 °C Orange
VERTICAL 155 °F /68 °C Red
5.6 SIDEWALL 4, 5, 6, 7, 8, 9 5, 6, 7, 9 5, 6, 7, 9 5, 6, 7, 9
1/2" (TY3451) 175 °F /79 °C Yellow
NPT Installed 200 °F /93 °C Green
Pendent
or 286 °F /141 °C Blue 5'•, 6 ", 7", 9" 5•', 6 ", 7'• 9"
Upright 360 °F /182 °C Mauve 4, 5, 6, 8, 9 N/A
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm)
top of deflector to ceiling distance.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) for use in Light and Ordinary Hazard Occupancies at a 4 to 12
inch (100 to 300 mm) top of deflector to ceiling distance.
3. Approved by Factory Mutual Research Corporation (FM) for use in Light Hazard Occupancies at a 4 to 12 inch (100 to 300 mm)
top of deflector to ceiling distance.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05 & 007k103) at a 4 to 6 inch (100 to 150 mm) deflector
to ceiling distance.
5. Listed by Underwriters Laboratories, Inc. (UL) for use in Light and Ordinary Hazard Occupancies.
6. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL:) for use In Light and Ordinary Hazard Occupancies.
7. Approved by Factory Mutual Research Corporation (FM) for use in Light Hazard Occupancies.
8. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05 & 007k/03).
9. Approved by the City of New York under MEA 354 -01 -E.
10. Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C -UL Listed,
the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead
Coated Sprinklers are noted to be. FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers.
' Installed with Style 10 (1/2° NPT) 3/4" Total Adjustment Recessed Escutcheon.
•' 150 °F /66 °C Maximum Ceiling Temperature.
"' Frame and deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS
Physical Characteristics
Frame Bronze operation
Button Brass /Copper
Sealing Assembly The glass Bulb contains a fluid which
Beryllium Nickel wfTeflont expands when exposed to heat. When -E
Bulb Glass the rated temperature is reached, the
Compression Screw Bronze fluid expands sufficiently to shatter the
HSW Deflector Bronze glass Bulb, allowing the sprinkler to
VSW Deflector Copper activate and water to flow.
Patents m
U.S.A. 5,810,263 m
.
a
0
C
TFP161 Page 3 of 6
Design DEFLECTOR
Criteria HAT \ 5 ,womb
The Series TY B Horizontal and Verti- I t '
cal Sidewall Sprinklers are intended
) : ��'�`M
for fire protection systems designed in
accordance with the standard installa- 6* • 4 2 3 1
tion rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of 9/16' WRENCH 1/2° **
NFPA 13, and FM Approval is based (14,3 mm) FLATS NPT
on the requirements of FM's Loss Pre-
vention Data Sheets). Only the Style ...10, 11 II
10 Recessed Escutcheon is to be used ` O 7 / I IlleIIIIIII��IIIIIY
for recessed horizontal installations.
= • = II,nllllllllllllllll) -ix Installation � � I
_ 1 13/16° 7/16°
The Series TY-B Sprinklers must be (46,0 mm) (11,1 mm)
installed in accordance with the follow- CENTERLINE NOMINAL f ..]
ing instructions: OF SPRINKLER MAKE -IN
NOTES WATERWAY f 11/2°
Do not install any bulb type sprinkler if (38,1 mm)
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler _ 2 - 3/16° _
held horizontally, a small air bubble (55,6 mm)
should be present. The diameter of the ESCUTCHEON
air bubble is approximately 1/16 inch STYLE 10 — PLATE SEATING
(1,6 mm) for the 135 °F /57 °C to 3/32 RECESSED I S
inch (2,4 mm) for the 360 °F /182 °C ESCUTCHEON
temperature ratings. 1- Frame mem
2 - Button
A leak tight 1/2 inch NPT sprinkler joint 3 - Sealing '_ ALI! �
should be obtained with a torque of 7 4 - BAs 2.7/8• DIA. I ■ I�'� ,�IIIIIIIIIIII
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- 5 - �
mum of 21 ft. lbs. (28,5 Nm) of torque Screw
may be used to install sprinklers with 6 - Deflector
1/2 NPT connections. Higher levels of
torque may distort the sprinkler inlet
and cause leakage or impairment of
the sprinkler.
Do not attempt to make -up for insuffi-
cient adjustment in the escutcheon * Temperature rating is indicated on deflector or adjacent to orifice seat on frame.
plate by under or over - tightening the * *Pipe thread connections per ISO 7/1 can be provided on special request.
sprinkler. Readjust the position of the
sprinkler fitting to suit. FIGURE 1
The Series TY -B Horizontal and Ver- 5.6 K- FACTOR STANDARD RESPONSE
tical Sidewall Sprinklers must be in- SERIES TV-B HORIZONTAL SIDEWALL (TY3351) SPRINKLERS
stalled in accordance with the follow-
ing instructions.
1. Horizontal sidewall sprinklers Step 3. Tighten the sprinkler into the bare metal to the corrosive environ-
Step 1
are 1 be installed sprinkler fitting using only the W -Type ment. The jaws of the wrench should
to with their centerline in in the of e horizontal ont l 6 Sprinkler Wrench (Ref. Figure 4), be opened sufficiently wide to pass
position ithi rth back of ter- except that an 8 or 10 inch adjustable over the wrench flats without damag-
way perpendicular
p o ndlan to the e The ck wall
" l T Crescent wrench is to be used for wax ing the wax coating. Before wrench
parallel
on the l oft the ceiling. tor is to face word "T OP" the coated sprinklers. With reference to tightening the sprinkler, the jaws of the
ceiling. Figure 1 or 2, the W -Type 6 Sprinkler wrench are to be adjusted to just con -
Wrench or the Crescent wrench, as tact the sprinkler wrench flats. After
Vertical sidewall sprinklers are to be applicable, is to be applied to the wrench tightening the sprinkler, loosen
installed in the pendent or upright po- wrench flats. the wrench jaws before removing the
sition with the arrow on the D eflector When installing wax coated sprinklers wrench.
pointing away from the wall. with the adjustable Crescent wrench, After installation, the sprinkler wrench
Step 2. With pipe thread sealant ap- additional care needs to be exercised flats and frame arms must be in-
plied to the pipe threads, hand tighten to prevent damage to the wax coating spected and the wax coating re-
the sprinkler into the sprinkler fitting. on the sprinkler wrench flats or frame touched (repaired) whenever the coat -
arms and, consequently, exposure of ing has been damaged and bare metal
Page4of6 TFP161
is exposed. The wax coating on the ,
wrench flats can be retouched by gen- ARROW MUST `
tly applying a heated 1/8 inch diameter POINT AWAY
steel rod to the areas of wax that have 7/16° FROM AND BE O
p been damaged, to smooth it back over ESCUTCHEON (11,1 mm) PERPENDICULAR /0"
O
areas where bare metal is exposed. PLATE SEATING ° ** NOMINAL TO THE BACK
SURFACE 1/2 MAKE - IN WALL SURFACE
1
NPT
NOTES
Only retouching of the wax coating ap _ _ , *l; \ * s
plied to the wrench flats and frame
arms is permitted, and the retouching ��� i� % 5
� —
is to be performed only at the time of 2 - 3/16' ■ 2 -3/16°
the initial sprinkler installation. (55,6 mm) I dIL�Ih (55,6 mm) I I 4
The steel rod should be heated only to di
the point at which it can begin to melt 1 -1/2° WRENCH 11 =MIP r ' < - 2
the wax, and appropriate precautions (38,1 mm) FLATS
I P ' �
7 'V
need to be taken, when handling the 3
heated rod, in order to prevent the -'._. I 4 1
installer from being burned.
If attempts to retouch the wax coating SHOWN SHOWN CROSS
with complete coverage are unsuc- PENDENT UPRIGHT SECTION
cessful, additional wax can be ordered
in the form of a wax stick (the end of 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector
which is color coded). Only the correct 2 - Button Assembly 5 - Compression 7- Ejection Spring
color coded wax is to be used, and Screw
retouching of wrench flats and frame
arms is only permitted at the time of
initial sprinkler installation. With the * Temperature rating is indicated on deflector or adjacent to orifice seat on frame.
steel rod heated as previously de- **Pipe thread connections per ISO 7/1 can be provided on special request.
scribed, touch the rod to the area re-
quiring additional wax with the rod an- FIGURE 2
gled downward, and then touch the 5.6 K- FACTOR STANDARD RESPONSE
wax stick to the rod approximately SERIES TY-B VERTICAL SIDEWALL
one -half inch away from the area re- (TY3451) SPRINKLERS
quiring retouching. The wax will melt
and run down onto the sprinkler.
The Series TY -8 Recessed Horizon-
tal Sidewall Sprinklers must be in- corrosive products of combustion, but
stalled in accordance with the follow- Care and have not operated, should be replaced
ing instructions. if they cannot be completely cleaned
Step A. Recessed horizontal sidewall Maintenance by wiping the sprinkler with a cloth or
sprinklers are to be installed in the by brushing it with a soft bristle brush.
horizontal position with their centerline The Series TY B Sprinklers must be
of waterway perpendicular to the back maintained and serviced in accord- Care must be exercised to avoid dam -
wall and parallel to the ceiling. The ance with the following instructions: age to the sprinklers - before, during,
word "TOP" on the Deflector is to face and after installation. Sprinklers dam
towards the ceiling. NOTES aged by dropping, striking, wrench
Before closing a fire protection system twist/slippage, or the like, must be re
Step B. After installing the Style 10 main control valve for maintenance placed. Also, replace any sprinkler that
Mounting Plate over the sprinkler work on the fire protection system that has a cracked bulb or that has lost
threads, hand tighten the sprinkler into it controls, permission to shutdown the liquid from its bulb. (Ref. Installation
the sprinkler fitting. affected fire protection system must be Section).
Step C. Tighten the sprinkler into the obtained from the proper authorities Frequent visual inspections are rec-
sprinkler fitting using only the W -Type and all personnel who may be affected ommended to be initially performed for
7 Recessed Sprinkler Wrench (Ref. by this action must be notified. corrosion resistant coated sprinklers,
Figure 5). With reference to Figure 1, Absence of an escutcheon, which is after the installation has been com-
the W -Type 7 Recessed Sprinkler used to cover a clearance hole, may pleted, to verify the integrity of the cor-
Wrench is to be applied to the sprinkler delay the time to sprinkler operation in rosion resistant coating. Thereafter,
wrench flats. a fire situation. annual inspections per NFPA 25
should suffice; however, instead of in-
. Step D. After the ceiling has been in- Sprinklers that are found to be leaking specting from the floor level, a random
stalled or the finish coat has been ap- or exhibiting visible signs of corrosion sampling of close -up visual inspec-
plied, slide on the Style 10 Closure must be replaced. tions should be made, so as to better
over the Series TY B Sprinkler and determine the exact sprinkler condi-
s push the Closure over the Mounting Automatic sprinklers must never be be p
Plate until its flange comes in contact painted, plated, coated or otherwise tion and the long term integrity of the
with the ceiling. altered after leaving the factory. Modi- corrosion resistant coating, as it may
fled sprinklers must be replaced. be affected by the corrosive conditions- -
Sprinklers that have been exposed to present.
TFP161 Page 5 of 6
5/8±1/4" L,
(15,9±6,4 mm)
FACE OF WRENCH RECESS
MOUNTING SPRINKLER 1 1 E /2 D NPT MODE S
SURFACE FITTING
FIGURE 4
CLOSURE A W -TYPE 6 SPRINKLER WRENCH
I
2 -7/8" DIA. WRENCH
SERIES (73,0 mm) RECESS
TY B I v`+ II 2 -1/4" DIA.
(57,2 mm) !�
MOUNTING I ` • r ��
1
PLATE I _
PUSH WRENCH
r L 1/8" IN TO ENSURE
(3,2 mm) ENGAGEMENT
WITH SPRINKLER
1 - 1/4" (31,8 mm) _ 3/4" (19,1 mm) WRENCHING AREA
3/4" (19,1 mm) 1/4" (6,4 mm)
FIGURE 5
FIGURE 3 W -TYPE 7 RECESSED
SERIES TY-B RECESSED HORIZONTAL SIDEWALL SPRINKLER SPRINKLER WRENCH
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
assume for it, any other obligation in
. connection with the sale of products or
parts of products. Tyco Fire Products
The owner is responsible for the in- Limited parts not be responsible for sprinkler
spection, testing, and maintenance of system design errors or inaccurate or
their fire protection system and de- w arranty incomplete information supplied by
vices in compliance with this docu- Buyer or Buyer's representatives.
ment, as well as with the applicable Products manufactured by Tyco Fire IN NO EVENT SHALL TYCO FIRE
standards of the National Fire Protec- Products are warranted solely to the PRODUCTS BE LIABLE, IN CON -
tion Association (e.g., NFPA 25), in original Buyer for ten (10) years TRACT, TORT, STRICT LIABILITY OR
addition to the standards of any other against defects in material and work- UNDER ANY OTHER LEGAL THE -
authorities having jurisdiction. The in- manship when paid for and properly
ORY, FOR INCIDENTAL, INDIRECT,
stalling contractor or sprinkler manu- installed and maintained under normal SPECIAL OR CONSEQUENTIAL
facturer should be contacted relative to use and service. This warranty will ex- DAMAGES, INCLUDING BUT NOT
any questions. pire ten (10) years from date of ship- LIMITED TO LABOR CHARGES, RE-
It is recommended that automatic ment by Tyco Fire Products. No war- GARDLESS OF WHETHER TYCO
sprinkler systems be inspected, ranty is given for products or FIRE PRODUCTS WAS INFORMED
tested, and maintained by a qualified n not i ted bytu by ow n s ship wnh p wit ABOUT THE POSSIBILITY OF SUCH
Fire Prod
Inspection Service in accordance nies rdance with Ties DAMAGES AND IN NO EVENT
local requirements and /or national Tyco Fire Product ucts or for products and SHALL TYCO FIRE PRODUCTS' LI-
codes. components which have been subject ABILITY EXCEED AN AMOUNT
to misuse, improper installation, corro-
sion, or which have not been installed, EQUAL TO THE SALES PRICE.
maintained, modified or repaired in ac- THE FOREGOING WARRANTY IS
cordance with applicable Standards of MADE IN LIEU OF ANY AND ALL,
the National Fire Protection Associa- OTHER WARRANTIES EXPRESS OR
tion, and /or the standards of any other IMPLIED. INCLUDING WARRANTIE$
Authorities Having Jurisdiction. Mate OF MERCHANTABILITY AND FIT-
' rials found by Tyco Fire Products to be NESS FOR A PARTICULAR PUR-
defective shall be either repaired or POSE.
replaced, at Tyco _ Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
Page6of6 TFP161
P/N 57 -XXX -X- XXX
I I
• SPRINKLER TEMPERATURE
MODEL/SIN RATING
578 HORIZONTAL SIDEWALL TY3351 1 NATURAL BRASS 135 135 °F /57 °C
575 VERTICAL SIDEWALL TY3451 4 WHITE POLYESTER 155 155 °F /68 °C
3 WHITE (RAL9010)• 175 175 °F /79 °C
9 CHROME PLATED 200 200 °F /93 °C
7 LEAD COATED 286 286 °F /141 °C
6 WAX COATED 360 360 °F /182 °C
286 °F /141 °C MAX.
8 WAX OVER LEAD
286 °F /141 °C MAX.
• Eastern Hemisphere sales only.
TABLE B
PART NUMBER SELECTION
SERIES TY-B HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS
Ordering
Recessed Escutcheon: Wax Sticks:
Procedure Specify: Style (specify) Recessed Es- (for retouching wrench damaged
cutcheon with (specify finish), P/N wax coating)
When placing an order, indicate the full (specify). Specify: (Specify color) color coded
product name. Refer to the Price List Wax Stick for retouching (specify tern -
for complete listing of Part Numbers. 1/2' (15 mm) perature rating) temperature rated Se-
Style 10 ries TY B Sprinklers, P/N (specify).
Contact your local distributor for avail- Chrome Plated P/N 56- 701 -9-010
ability. 1/2' (15 mm)
Style 10 Black for 135 °F P/N 56 -065 -1 -135
Sprinkler Assemblies with NPT White Color Red for 155 °F P/N 56-065-1-155
Coated P/N 56- 701 -4-010 Yellow for 175 °F P/N 56 -065 -1 -175
Thread Connections: 1/2' (15 mm) Blue for 200 °F and
Specify: (Specify Model /SIN), Stand- Style 10 286 °F P/N 56- 065 -1 -286
and Response, (specify K- factor), While RAL9010• P/N 56- 701 -3-010
(specify temperature rating), Series 1/2° (15 mm) NOTES
T B (specify Horizontal Sidewall or Style 1 0
Y Each wax stick is suitable for retouch -
Vertical Sidewall) Sprinkler with (spec- Brass Plated P/N 56- 701 -2 -010 ing up to twenty-five sprinklers.
ify type of finish or coating), P/N (spec- • Eastern Hemisphere sales only. The wax used for 286 °F sprinklers is
ify from Table B). the same as for 200 °F sprinklers, and,
Sprinkler Wrench: therefore, the 286 °F sprinkler is limited
Specify: W -Type 6 Sprinkler Wrench, to the same maximum ceiling tempera -
P/N 56- 000 -6 -387. ture as the 200 °F sprinkler (i.e.,
Specify: W -Type 7 Sprinkler Wrench, 150 °F).
P/N 56- 850 -4 -001.