Specifications 96,,e,_51r / . Al d_ 7
tqco Fire & Building
Products
, ak-oT r,-
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 / ; _ P ! w
44 /1Y
Series RFII — 5.6 K- factor curv"_
"Royal Flush II" Pendent Concealed 1.` tria Ores
Quick & Standard Response, Standard Coverage
General Cap. The Protective Cap is temporarily
removed for installation, and then it
can be replaced to help protect the
Description sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro -
The Series RFII Quick Response tective Cap can also be used to mark __ _ _
(3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas- _
mm bulb), 5.6 K- Factor, "Royal Flush ter board, ceiling tiles, etc. by gently
II" Concealed Pendent Sprinklers are pushing the ceiling product against the �,,,.r-a '--
decorative sprinklers featuring a flat Protective Cap. When the ceiling in-
cover plate designed to conceal the stallation is complete the Protective
sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate
tecturally sensitive areas such as hotel Assembly installed.
lobbies, office buildings, churches, As an option, the Series RFII Standard
and restaurants. Response (5 mm bulb) "Royal Flush II"
Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be
sembly that conceals the sprinkler op- fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175
erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM.
The separable two -piece design of the intended for sensitive areas where it is
Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical
blies allows installation of the sprin- through the cover plate from the area
klers and pressure testing of the fire above the ceiling. Data
protection system prior to installation WARNINGS
of a suspended ceiling or application The Series RFII Concealed Pendent Approvals for Series RFII
of the finish coating to a fixed ceiling.
Sprinklers described herein must be UL and C -UL Listed. FM A roved.
and maintained They also permit removal of sus- installed d intaid in compli- NYC under MEA 353 -01 -E. LPCB Ref.
pended ceiling panels for access to p "
building service equipment without ance w ith this document, as well as No. 094a/09 for TY3551 & 094a/10 for
having to first shut down the fire pro- with the appl standards of the TY3531) Approved.
hav system and remove sprinklers. National Fire Protection Association, The approvals apply only to the serv-
wo pig i addition to the standards of any ice conditions indicated in the Design
Also, the separable two-piece design f the the Sprinkler other authorities having jurisdiction. Criteria section and maximum pres-
inch the th mm) of vertical p provides i two-piece des for ign for 1/2 Failure to do so may impair the per- sure ratings indicated in the
formance of these devices. Model/Sprinkler Identification Num-
to reduce the accuracy to which the p
length of fixed pipe drops to the sprin The owner is responsible for maintain- bers section.
klers must be cut. i ng their fire protection system and de- Approvals for Air & Dust Seal
vices in proper operating condition. Part #10908100
The Series RFII Sprinklers are The installing contractor or sprinkler U L and C -UL Li for use with the
shipped with a Disposable Protective manufacturer should be contacted
RFII (TY3551 & TY3504) Standard Re-
with any questions. sponse Concealed Sprinkler.
IMPORTANT Temperature Ratings
Always refer to Technical Data Model /Sprinkler 155F/68C Sprinkler - 135F/57C Plate
Sheet TFP700 for the "INSTALLER 200F/93C Sprinkler - 165F/74C Plate
WARNING" that provides cautions Identification Discharge Coefti,cient
with respect to handling and instal- K = 5.6 GPM /psi (80,6 LPM/bar
lation of sprinkler systems and com- Numbers Adjustment
ponents. Improper handling and in- 1/2 inch (12,7 mm)
stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm Finishes
a sprinkler system or its compo- bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass
. nents and cause the sprinkler to fail UL, C -UL, FM, LPCB and NYC. Plated, or White Painted (Custom paint
to operate ina fire situation or cause TY3504 (5 mm bulb) & TY3505 (3 mm matches and colors other than white
it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by
are available on request.)
Page 1 of 4 JULY, 2004 TFP181
Page 2 of 4 TFP181
Physical Characteristics i /z" NPr 1 SEALING
Frame Bronze ASSEMBLY
Support Cup . Chrome Plated Steel
Guide Pins Stainless Steel FRAME ` ` ��/
Deflector Bronze , ` l fAd a____�
Compression Screw Brass i 1 (� CAP
p / In �
Bulb Glass t �% `�
Cap Bronze or Copper SUPPORT )
Sealing Assembly CUP WITH BULB
Beryllium Nickel w/Teflon' ROLL FORMED )
Cover Plate Brass THREADS
Retainer Brass (I COMPRESSION
Ejection Spring .... Stainless Steel , ill -wal �l SCREW
GUIDE Patents PINS (2) 1 I � FA � �
U.S.A. 4,014,388 I I -
DEFLECTOR
Opera tion DEFLECTOR L - , i (DROPPED
�eii E==.-2_'7,- ; J ; POSITION)
I
When exposed to heat from a fire, the SPRINKLER/SUPPORT CUP
Cover Plate, which is normally sol- ASSEMBLY
dered to the Retainer at three points,
falls away to expose the Sprinkler As THREAD INTO ' I RETAINER
SUPPORT CUP ( , WITH THREAD
sembly. At this point the Deflector sup- UNTIL MOUNTING ` O O DIMPLES
ported by the Guide Pins drops down SURFACE IS
to its operational position. FLUSH WITH EJECTION
The glass Bulb contains a fluid that CEILING SPRING
expands when exposed to heat. When
the rated temperature is reached, the ■ fluid expands sufficiently to shatter the - ,
glass Bulb, activating the sprinkler and
allowing water to flow. SOLDER COVER
TABS (3) COVER PLATE /RETAINER PLATE
ASSEMBLY
Design FIGURE 1
Criteria SERIES RFII CONCEALED SPRINKLER
ASSEMBLY
The RFII (TY3551 & TY3504), 5 mm
Bulb Type, Concealed Pendent Sprin- Step 1. The sprinkler must only be
klers are UL and C -UL Listed as stand- Installation installed in the pendent position and
and response - standard spray sprin- with the centerline of the sprinkler per -
klers for use in accordance with the The Series RFII must be installed in pendicular to the mounting surface.
current NFPA standard. They are FM accordance with the following instruc- Step 2. Remove the Protective Cap.
Approved as standard response - tions: Step 3. W ith pipe thread sealant a
standard spray sprinklers for use in P P P P
accordance with the current FM Loss NOTES plied to the pipe threads, hand tighten
Prevention Data Sheets. Do not install any bulb type sprinkler if the sprinkler into the sprinkler fitting.
The RFII (TY3531 & TY3505) 3 mm the bulb is cracked or there is a loss of Step 4. Wrench tighten the sprinkler
liquid from the bulb. With the sprinkler usin onl the REM S rinkler Wrench
Bulb Type, Concealed Pendent Sprin- held horizontally, a small air bubble g y P
(Ref. Figure
klers are UL and C -UL Listed as quick should be present. The diameter of the be The RFII he S
W -
kler as
response - standard spray sprinklers air bubble is approximately 1/16 inch re w to in n Figur 3. . the Sprin
for use in accordance with the current (1,6 mm) for the 155 °F /68 °C and 3/32 shown i
NFPA standard. They are FM Ap- inch (2,4 mm) for the 200 °F /93 °C tem- Step 5. Replace the Protective Cap
proved as standard response - stand- perature ratings. (Ref. Figure 4) by pushing it upwards
and spray sprinklers for use in accord- until it bottoms out against the Support
ance with the current FM Loss Aleaktightl /2inchNPTsprinklerjoi Cup. The Protective Cap helps prevent
Prevention Data Sheets. should be obtained with a torque o 7 damage to the Deflector and Arms dur-
The Series RFII Concealed Pendent to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- ing ceiling installation and /or during
mum of 21 ft.lbs. (28
Sprinklers are only listed and a (28,5 Nm) of torque application of the finish coating of the
P y p is to be used to install sprinklers. ceilin It ma also be used to locate
proved with the Series RFII Concealed Higher levels of torque may distort the g ' y
the
Cover Plates having a metallic or white sprinkler inlet with consequent leak- gently pus n of the clearance eria u p
• painted finish. gently pushing the ceiling material up
age or impairment of the sprinkler. against the center point of the Protec-
The Series RFII must not be used in Do not attempt to compensate for in- tive Cap.
applications where the air pressure sufficient adjustment in the Sprinkler
above the ceiling is greater than that Assembly by under- or over - tightening NOTE
below. Down drafts through the Sup- the Sprinkler /Support Cup Assembly. A.s long as the Protective Cap remains
port Cup could delay sprinkler opera- Readjust the position of the sprinkler in place, the system is considered to
tion in a fire situation. fitting to suit. be "Out of Service ".
* Registered Trademark of DuPont
TFP181 Page 3 of 4
- FACE OF CLEARANCE HOLE CLEARANCE
SPRINKLER I DIAMETER HOLE
FITTING DIMENSION C I
► =i
SPRINKLER i 1 j
SUPPORT CUP \ 1I - -- - � 'P
ASSEMBLY c ZAI MIS re
1/2" (12,7 mm) II__
THREADED
D ADJUSTMENT 1'
FACE OF CEILING, -
RETAINING RING � ' F 4
MOUNTING DISPOSABLE PROTECTIVE CAP
SURFACE j i
i \i /iv Step 6. After the ceiling has been com-
pleted with the 2 -1/2 inch (63,5 mm)
=.. diameter clearance hole and in prepa-
; ; ; r ;
V ration for installing the Cover Plate As-
I I I '-=
sembly, remove and discard the Pro -
z- - _r - - z - r tective Cap, and verify that the
3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE Deflector moves up and down freely. If
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER the Sprinkler has been damaged and
REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY the Deflector does not move up and
down freely, replace the entire Sprin-
COVER PLATE COVER PLATE kler assembly. Do not attempt to mod-
- PROFILE DEPTH DIAMETER ify or repair a damaged sprinkler.
DIMENSION B DIMENSION A Step 7. When installing an Air and
Dust Seal, refer to Figure 5, otherwise
proceed to Step 8. To attach the Air and
A: 3 -1/4" (82,6 mm) C: 2 -3/8" to 2 -5/8" (60,3 to 66,7 mm) Dust Seal, verify the angle of the out -
B: 3/16" (4,8 mm) D: 1 -3/4" to 2 -1/4" (44,5 to 57,2 mm) side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
FIGURE the Retainer in the grooved slot of the
SERIES RFII CONCEALED SPRINKLER Air and Dust Seal and continue around
INSTALLATION DIMENSIONS the retainer until the entire Air and
Dust Seal is engaged.
NOTE
The Air and Dust Seal is only to be
installed on the periphery of the Re-
tainer.
ljt�ll - - -- FRAME ;l =l'.
' Step 8. Screw on the Cover Plate /Re-
I I W .j ARM r � tainer Assembly until the Retainer -
\ Fig CuP � _ I l ure 2 contacts (or Alr with and the Dust ceiling. Seal Do Figure
SUPPORT j not continue to screw on the Cover
P 5) late /Retainer Assembly such thait EMI lifts a ceiling panel out of its normal
lit >,,,^� position. If the Cover Plate /Retainer
�`� Assembly cannot be engaged with the
O Support Cup or the Cover Plate /Re-
7/8" (23 mm) tainer Assembly cannot be engaged
SQUARE sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
ALIGN J L , iit
ARROWS WITH Care and
FRAME ARMS
Maintenance
ACCEPTS �' The Series RFII must be maintained
0 1/2" SOCKET r and serviced in accordance with the
DRIVE following instructions:
NOTES
FIGURE 3 Absence of the Cover Plate Assembly
RFII SPRINKLER WRENCH may delay sprinkler operation in a fire
situation.
Page 4 of 4 TFPI g1
. When properly installed, there is a SUPPORT SPRINKLER FACE OF ORIENT
nominal 3/32 inch (2,4 mm) air gap cuP CEILING SEAL
l �
between the lip of the Cover Plate and j BEVEL AS
the ceiling, as shown in Figure 2. This �` covER / j, SHOWN
air gap is necessary for proper opera- , PLATE �1
'• .
tion of the sprinkler. If the ceiling is to lif ) RETAINER - be repainted after the installation of i1. ASSEMBLY 'gym'
the Sprinkler, care must be exercised 1 ' - - •
to ensure that the new paint does NOT , _
seal off any of the air gap. Ell !� CLEAN
_ I//i ROOM
Factory painted Cover Plates MUST .��_ __ SEAL
NOT be repainted. They should be re-
_ _ - -' - - LIP OF COVER
placed, if necessary, by factory RETAINER PLATE
painted units. FIGURE 5
Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504)
the Enclosure. Separation may result.
Before closinga fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT
main control valve for maintenance local requirements and /or national SHALL TYCO FIRE PRODUCTS' LI-
work on the fire protection system that codes. ABILITY EXCEED AN AMOUNT
it controls, permission to shutdown the EQUAL TO THE SALES PRICE.
affected fire protection system must be
Limited THE FOREGOING WARRANTY IS
obtained from the proper authorities MADE IN LIEU OF ANY AND ALL,
and all personnel who may be affected Wa rrant OTHER WARRANTIES EXPRESS OR
by this action must be notified. y IMPLIED. INCLUDING WARRANTIES
Sprinklers that are found to be leaking OF MERCHANTABILITY AND FIT -
or exhibiting visible signs of corrosion Products manufactured by Tyco Fire NESS FOR A PARTICULAR PUR-
must be replaced. Products are warranted solely to the POSE.
Automatic sprinklers must never be original Buyer for ten (10) years
ver
painted, plated, coated s or otherwise erwise be against defects in material and work- manship when paid for and properly Ordering
altered after leaving the factory.
a p must be replaced. Modi- installed and maintained under normal
fied d sprinklers lea i kl d. use and service. This warranty will ex- Procedure
Sprinklers
corrosive inkler products that have ve been exposed of combustion, but pire ten (10) years from date of ship -
have not operated, should be replaced ment by Tyco Fire Products. No war- When placing an order, indicate the full
ranty is given for products or product name. Contact your local dis-
if they cannot be completely cleaned P Y
components manufactured by comps- tributor for availability.
by wiping the sprinkler with a cloth or nies not affiliated by ownership with ty
by brushing it with a soft bristle brush. Sprinkler Assembly:
Tyco Fire Products or for products and
Caren be exercised a iduring, dam- components which have been subject rating) y : Semi Series (specify temperature
Pen -
9 the sprinklers before,
to misuse, improper installation, corro- dent Sprinkler, P/N s
and after installation. Sprinklers dam- sion, or which have not been installed, (specify).
aged by dropping, striking, wrench maintained, modified or repaired in ac-
applicable Standards of 1 - 1-1 200F/93C
twist/slippage, or the like, must be re- cordance with a 1-2
placed. Also, replace any sprinkler that PP TY3551 51-790-1-155 51-790-1-200
P P Y P the National Fire Protection Associa- rr35o4 51- 796 -1 -155 51- 796 -1 -200
has a cracked bulb or that has lost tion, and /or the standards of any other TY3531 51- 792 -1 -155 51- 792 -1 -200
liquid from its bulb. (Ref. Installation Authorities Having Jurisdiction. Mate - TY3505 51- 797 -1 -155 51- 797 -1 -200
Section). rials found by Tyco Fire Products to be
If a sprinkler must be removed, do not defective shall be either repaired or Separately Ordered Cover Plate:
reinstall it or a replacement without replaced, at Tyco Fire Products' sole Specify: (specify temperature rating)
reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate
If a Cover Plate Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify).
dislodged during service, replace it im- assume for it, any other obligation in
mediately. connection with the sale of products or 135F/57C(a) 165F/74C•(b)
parts of products. Tyco Fire Products Brass 56- 792 -1 -135 56- 792 -1 -165
P P Y Bright Brass 56- 792 -2 -135 56- 792 -2 -165
The owner is responsible for the in- shall not be responsible for sprinkler Chrome 56- 792 -9 -135 56- 792 -9 -165
spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome - -- protection system and de- incomplete information supplied by White 56 56- 792 792 -3 8 -135 135 5566:779922:80:116655
their fire
P Y P PP Y White (RAL9010)' 56- 792 -3 -135 56- 792 -3 -165
vices in compliance with this docu- Buyer or Buyer's representatives. Bright White 56- 792 -4 -135 56- 792 -4 -165
ment, as well as with the applicable IN NO EVENT SHALL TYCO FIRE Off White 56- 792 -5 -135 56- 792 -5 -165
standards of the National Fire Protec- PRODUCTS BE LIABLE, IN CON- Black 56- 792 -6-135 56- 792 -6-165
Custom 56- 792 -X -135 56- 792 -X -165
tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR (a) For use with 155F/68C sprinklers.
addition to the standards of any other UNDER ANY OTHER LEGAL THE- (b) For use with 200F /93C sprinklers.
. authorities having jurisdiction. The in- ORY, FOR INCIDENTAL, INDIRECT, • Eastern Hemisphere sales only.
stalling contractor or sprinkler manu- SPECIAL OR CONSEQUENTIAL
facturer should be contacted relative to DAMAGES, INCLUDING BUT NOT Sprinkler Wrench:
any questions. LIMITED TO LABOR CHARGES, RE- Specify: RFII Sprinkler Wrench,
It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56-000-1-075.
sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal:
tested, and maintained by a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal,
P/N 56- 908 -1 -001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
. tqcci I Fire & Building
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K- factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli- - .
Description cable approval agencies, the testing is ,,,, "
not representative of all possible cor- _ ,, ,
The Series TY -FRB, 2.8, 4.2, 5.6, and rosive atmospheres. Consequently, it d4.1
8.0 K- factor, Upright and Pendent is recommended that the end user be i II
Sprinklers described in this data sheet consulted with respect to the suitability j
are quick response - standard cover- of these coatings for any given corro- fii
age, decorative 3 mm glass bulb type sive environment. The effects of ambi ,
spray sprinklers designed for use in ent temperature, concentration of -
light or ordinary hazard, commercial chemicals, and gas /chemical velocity, . — - 4.,_
occupancies such as banks, hotels, should be considered, as a minimum, `" __, ° -
shopping malls, etc. along with the corrosive nature of the
The recessed version of the Series chemical to which the sprinklers will be
TY-FRB Pendent Sprinkler, where ap- exposed.
plicable, is intended for use in areas An intermediate level versions of the 4---.,
with a finished ceiling. It uses either a Series TY-FRB Pendent Sprinklers are
two -piece Style 10 (1/2 inch NPT) or detailed in Technical Data Sheet - N4 'N
Style 40 (3/4 inch NPT) Recessed Es- TFP356, and Sprinkler Guards are de- (`
cutcheon with 1/2 inch (12,7 mm) of tailed in Technical Data Sheet TFP780 i .
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the WARNINGS
flush pendent position, or a two -piece The Series TY -FRB Sprinklers de- , ., r
5
Style 20 (1/2 inch NPT) or Style 30 (3/4 scribed herein must be installed and s -
inch NPT) Recessed Escutcheon with maintained in compliance with this -0
1/4 inch (6,4 mm) of recessed adjust- document, as well as with the applica-
ment or up to 1/2 inch (12,7 mm) of ble standards of the National Fire Pro TY3231 - Pendent 5.6K, 1/2 "NPT
total adjustment from the flush pen- tection Association, in addition to the
dent position. The adjustment provided standards of any other authorities hay- TY4131 - Upright 8.0K, 3/4 "NPT
by the Recessed Escutcheon reduces ing jurisdiction. Failure to do so may TY4231 - Pendent 8.0K, 3/4 "NPT
the accuracy to which the fixed pipe impair the performance of these de - T
drops to the sprinklers must be cut. vices. ■ echnical
Corrosion resistant coatings, where The owner is responsible for maintain- Data
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition.
that which would otherwise be ob- The installing contractor or sprinkler Approvals
tained when exposed to corrosive at- manufacturer should be contacted UL and C -UL Listed.
with any questions. FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
IMPORTANT information including corrosion resis-
Always refer to Technical Data tant status.)
Sheet TFP700 for the "INSTALLER Model /Sprinkler Maximum Working Pressure
WARNING" that provides cautions
with respect to handling and instal- Identification 175 psi (12,1 bar)
. lation of sprinkler systems and com- Discharge Coefficient
ponents. Improper handling and in- Numbers K = 2.8 GPM /psi (40,3 LPM/bar
stallation can permanently damage K = 4.2 GPM /psi (60,5 LPM/barl
a sprinkler system or its compo- TY1131 - Upright 2.8K, 1/2 "NPT K = 5.6 GPM /psi (80,6 LPM /bar
nents and cause the sprinkler to fail TY1231 - Pendent 2.8K, 1/2 "NPT K = 8.0 GPM /psi (115,2 LPM /barli
to operate in fire situation or cause TY2131 - Upright 4.2K, 1/2"NPT Temperature Ratings
it to operate prematurely. TY2231 - Pendent 4.2K,1/2 "NPT Refer to Table A and B
TY3131 - Upright 5.6K, 1/2"NPT
Page 1 of 8 JULY, 2004 TFP171
Page 2 of 8 TFP171
- ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING ** NOMINAL RECESSED
SURFACE 1/2 MAKE -IN ESCUTCHEON SSU
NPT DEFLECTOR
r --- 6
i =----
MEM- 1 ■1 = � 7/16" 1�, 5
(57,2 mm) ( 11,1 mm) I 4
`� I N I I 2
i 1I W MAKE -IN
1 9/16" `�� 2- 3/16" `�
� rr 3
(39,7 mm) WRENCH (55,6 mm) i
II 1
FLATS �_ + �� 1
7
SSP DEFLECTOR * 2 -7/8" (73,0 mm) DIA. 1/2" NPT **
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING ** NOMINAL RECESSED
SURFACE NP MAKE-IN ESCUTCHEON DEFLECTOR
6
} MW-Mill TT e:i7*1;� iVaN 7/16" 2- 3/16" } 1■ M (11,1 mm) I (55,6 mm) f - ,W NOMINAL ; 7 11 MAKE -IN 1 1/2" I �I' WRENCH __ ! 2- 3/16" �' r,, 2
(38,1 mm) (55,6 mm) 0 ,�
1. FLATS - ---.----=------
; ' � 3
SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. f 1/2" NPT 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K- FACTOR, 1/2 INCH NPT
0
E
Finishes Bulb Glass 0
Sprinkler: Refer to Table A and B Compression Screw Bronze Operation
Recessed Escutcheon: White Coated, Deflector . . . . . . . Copper /Bronze
Chrome Plated, or Brass Plated Bushing (K =2.8) Bronze The glass Bulb contains a fluid which
expands when exposed to heat. When y
Physical Characteristics the rated temperature is reached, the 'm
Frame Bronze fluid expands sufficiently to shatter the ec
Frame Brass /Copper glass Bulb, allowing the sprinkler to E
Sealing Assembly activate and water to flow. a
0
Beryllium Nickel w/Teflont }
TFP171 Page 3 of 8
• ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING ** NOMINAL RECESSED
SURFACE I1 /2 MAKE -IN ESCUTCHEON
(I DEFLECTOR
_ 6*
�= / %// /�� \W ' /i�>'� %lam \.u\
rr 7/16" 1.=, 5
2-3/16" } I�1:'�� (11,1 mm) i (55,6 mm) A=1 —���— I N MAKE -IN O I 4
1 —
1 -1/2" I II r _r
i i .. r 2
(38,1 mm) �� 2- 3/16" D , � � ' WREN (5 5,6 mm) L 3
' i - - _ FLATS — _ 1
Y
74 a
1
SSP DEFLECTOR — 2-7/8° (73,0 mm) DIA. 1/2" NPT **
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw ** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40
PLATE SEATING * * NOMINAL RECESSED
SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR
6
— ' :';TTY *�'T -
+ . 1
" � �
2- 5/16" — I MVO. (12,7 mm) I
(58,7 mm) �■ ����- I NOMINAL
i
` �1� MAKE -IN 11 ,
1- 9/16" 1_1 1/2 5
21/4" p . - 4
, 2
(39,7 mm) ko J FLATS . WRENCH = (5 4'
. 3
SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. — 3/4" NPT 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
* * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
Listing is based on the requirements of
Design NFPA 13, and FM Approval is based Installation
on the requirements of FM's Loss Pre-
- Criteria vention Data Sheets ). Only the Style The Series TY -FRB Sprinklers must be
10, 20, 30, or 40 Recessed Escutch- installed in accordance with the follow -
The Series TY -FRB Pendent and Up- eon, as applicable, is to be used for ing instructions:
right Sprinklers are intended for fire recessed pendent installations.
protection systems designed in ac- NOTES
cordance with the standard installation Do not install any bulb type sprinkler if
rules recognized by the applicable the bulb is cracked or there is a loss of
Listing or Approval agency (e.g., UL liquid from the bulb. With the sprinkler
Page 4 of 8 TFP171
SPRINKLER FINISH (See Note 7) inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
K TYPE TEMP. BULB NATURAL CHROME WHITE* (13,4 to 26,8 Nm). A maximum of 30
LIQUID BRASS PLATED POLYESTER ft.lbs. (40, 7 Nm) of torque is to be used
135 °F /57 °C Orange to install sprinklers with 3/4 NPT con -
PENDENT nections. Higher levels of torque may
155 °F /68 °C Red distort the sprinkler inlet and cause
( TY1231 ) 1, 2, 3, 5 leakage or impairment of the sprinkler.
and 175 °F /79 °C Yellow
Do not attempt to make -up for insuffi-
UPRIGHT 200 °F /93 °C Green cient adjustment in the escutcheon
2.8 286 °F /141 °C Blue plate by under- or over - tightening the
1/2" sprinkler. Readjust the position of the
NPT 135 °F /57 °C Orange sprinkler fitting to suit.
RECESSED 155 °F /68 °C Red
PENDENT The Series TY -FRB Pendent and Up-
(TY1231)* 175 °F /79 °C Yellow right Sprinklers must be installed in
Figure 5 accordance with the following instruc-
g ure 200 °F /93 °C Green 1, 2, 5 Lions.
135 °F /57 °C Orange Step 1. Pendent sprinklers are to be
RECESSED 155 °F /68 °C Red installed in the pendent position, and
PENDENT upright sprinklers are to be installed in
(TY1231)** 175 °F /79 °C Yellow the upright position.
Figure 6 200 °F /93 °C Green Step 2. With pipe thread sealant ap-
135 °F /57 °C Orange plied to the pipe threads, hand tighten
PENDENT the sprinkler into the sprinkler fitting.
155 °F /68 °C Red
(TY2231) Step 3. Tighten the sprinkler into the
and 175 °F /79 °C Yellow sprinkler fitting using only the W -Type
UPRIGHT 200 °F /93 °C Green 6 Sprinkler Wrench (Ref. Figure 13).
4.2 (TY2131) With reference to Figures 1, 2, 3, and
286 °F /141 °C Blue 2 4, the W -Type 6 Sprinkler Wrench is to
1/2" be applied to the sprinkler wrench
NPT 135 °F /57 °C Orange flats.
RECESSED 155 °F /68 °C Red
PENDENT
(TY2231)* 175 °Ff79 °C Yellow The Series TY -FRB Recessed Pen -
Figure 7 200 °F /93 °C Green dent Sprinklers must be installed in
accordance with the following instruc-
135°F/57°C Orange tions.
RECESSED 155 °F /68 °C Red Step A. After installing the Style 10.
PENDENT
(TY2231)•* 175°F/79°C Yellow 20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
Figure 8 200 °F /93 °C Green with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
NOTES: kler into the sprinkler fitting.
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. Step B. Tighten the sprinkler into the
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response sprinkler fitting using only the W - Type
Sprinklers. 7 Recessed Sprinkler Wrench (Ref.
3. by Factory Mutual Research Corporation (FM) as Quick Response Sprin Figure 14). With reference to Figure 1,
5. Approved by the City of New York under MEA 354 -01 -E. 2, 3, and 4, the W - Type 7 Recessed
7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the spin Sprinkler Wrench is to be applied to
klers are UL and C - UL Listed as Corrosion Resistant Sprinklers. the sprinkler wrench flats.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Step C. After the ceiling has been in-
Recessed Escutcheon, as applicable. stalled or the finish coat has been ap
Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
plied, slide on the Style 10, 20, 30, or
Recessed Escutcheon, as applicable. p y
"' Frame and Deflector only. Listings and approvals apply to color (Special Order). 40 Closure over the Series TY-FRB
N /A: Not Available Sprinkler and push the Closure over
TABLE A the Mounting Plate until its flange
comes in contact with the ceiling.
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K- FACTOR SPRINKLERS
held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint
should be present. The diameter of the should be obtained with a torque of 7
air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi -
(1,6 mm) for the 135 °F /57 °C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque
inch (2,4 mm) for the 286 °F /141 °C may be used to install sprinklers with
temperature ratings. 1/2 NPT connections. A leak tight 3/4
TFP171 Page 5 of 8
•
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL CHROME WHITE *** LEAD
LIQUID BRASS PLATED POLYESTER COATED
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5
and 175 °F /79 °C Yellow
UPRIGHT 200 °F /93 °C Green
5.6 (TY3131)
286 °F /141 °C Blue
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155"F168°C Red
PENDENT 1, 2, 4, 5 N/A
(TY3231)* 175 °F /79 °C Yellow
Figure 9 200 °F /93 °C Green
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A
(TY3231) ** 175"F/79°C Yellow
Figure 10 200 °F /93 °C Green
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY4231) 1, 2, 5
and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7
UPRIGHT 200 °F /93 °C Green
8.0 (TY4131)
286 °F /141 °C Blue
3/4"
NPT 135 °F /57 °C Green
RECESSED 155 °F /68 °C Orange
PENDENT 1, 2, 4, 5 N/A
(TY4231)* 175 °F /79 °C Red
Figure 11 200 °F /93 °C Yellow
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4231) ** 175 °F /79 °C Yellow
Figure 12 200 °F /93 °C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428 - 3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
* ** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K- FACTOR SPRINKLERS
Page 6 of 8 TFP171
- 2 -7/8" DIA. 2 -7/8" DIA
(73,0 mm) 3/4" (19,1 mm) (73,0 mm)
5/811/4"
1/211/8" 1/2" (12,7 mm)
(15,916,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2 -1/4" DIA. ���{{{ 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) 1 MOUNTING
SPRINKLER PLATE SPRINKLER I PLATE
FITTING FITTING
1/8" 1/8"
•�' (3,2 mm) •� (3,2 mm)
go- i _ `i _
f M OUNTING VP MOUNTING . S URFACE
SURFACE '
rir!ti '
CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1- 5/16" (33,3 mm)
TY -FRB 13/16" (20,6 mm) TY -FRB 1- 1/16" (27,0 mm)
FIGURE 5 FIGURE 6
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT
2 -7/8" DIA. _ 2 -7/8" DIA.
5/811/4" (73,0 mm) 3/4" (19,1 mm) 1/2+1/8" (73,0 mm) 1/2" (12,7 mm)
(15,916,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2 -1/4" DIA 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm)
MOUNTING
SPRINKLER
PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
■ �� ( 3,2 mm) �� -� i s i /I.' (3 2 m m)
I = I ,,_�.
—� i
\ � . ,�, SURFACE �
MOUNTING . •
SURFACE .- .. .. ..
CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm)
TY -FRB 3/4" (19,1 mm) TY -FRB 1" (25,4 mm)
FIGURE 7 FIGURE 8
SERIES TY -FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT
used to cover a clearance hole, may and after installation. Sprinklers dam -
Care and delay the time to sprinkler operation in aged by dropping, striking, wrench
M aintenance a fire situation. twist/slippage, or the like, must be re-
that are found to be leaking ha a cracked Also, replace bulb or th t has lost
The Series TY -FRB Sprinklers must be or exhibiting visible signs of corrosion liquid from its bulb. (Ref. Installation
maintained and serviced in accord- must be replaced. Section).
ance with the following instructions: Automatic sprinklers must never be
painted, plated, coated or otherwise Frequent visual inspections are rec
NOTES altered after leaving the factory. Modi- ommended to be initially performed for
Before closinga fire protection system fied sprinklers must be replaced. corrosion resistant coated sprinklers,
main control valve for maintenance Sprinklers that have been exposed to after the installation has been corn-
work on the fire protection system that corrosive products of combustion, but pleted, to verify the integrity of the cor-
it controls, permission to shutdown the have not operated, should be replaced rosion resistant coating. Thereafter,
affected fire protection system must be if they cannot be completely cleaned annual inspections per NFPA 25
obtained from the proper authorities by wiping the sprinkler with a cloth or should suffice; however, instead of in-
- and all personnel who maybe affected by brushing it with a soft bristle brush. specting from the floor level, a random
by this action must be notified. sampling of close -up visual inspec-
Care must be exercised to avoid darn- tions should be made, so as to better
Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi-
TFP171 Page 7 of 8
. 2 -7/8" DIA. _ 2 -7/8' DIA
5/8±1/4" (73,0 mm) 3/4 (19,1 mm) 1/2±1/8° (73,0 mm) 1/2° (12,7 mm)
(15,9 ±6,4 mm) 2 -1/4° DIA y 1/4' (6,4 mm) (12,7±3,2 mm) 2 -1/4° DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm)
MOUNTING
SPRINKLER
PLATE SPRINKLER PLATE
FITTING FITTING
1/8° 1/8"
= � 1 i ) (3,2 mm) i - -- I •• (3,2 mm) ■
Ax
/ �- •I } \
MOUNTING
VI �• SURFACE
�
SURFACE _ =-_ -- ' ^ _� ,- ■
CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm)
TY -FRB 3/4° (19,1 mm) TY -FRB 1' (25,4 mm)
FIGURE 9 FIGURE 10
SERIES TY-FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT
2 -7/8 DIA. 2 -7/8" DIA. _
5/8 ±1/4° (73,0 mm) 3/4 (19,1 mm) 1/2 ±1/8" (73,0 mm) 1/2' (12,7 mm)
(15,9±6,4 mm) 1/4" (6,4 mm) 1/4 (6,4 mm)
( ) 2 -1/4" DIA. y (12,7 ±3,2 mm) 2 -1/4° DIA.
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8° 1/8'
(3,2 mm) mm) VIA
•
AM no "Z '
ANT" } \ - MOUNTING
MOUNTING � . SURFACE
SURFACE , 1 v
CLOSURE SERIES 1- 5/16" (33,3 mm) CLOSURE SERIES 1 -5/16° (33,3 mm)
TY -FRB 13/16° (20,6 mm) TY -FRB 1 -1/16' (27,0 mm)
FIGURE 11 FIGURE 12
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may WRENCH
L
be affected by the corrosive conditions ' RECESS
present.
WRENCH RECESS)
The owner is responsible for the in- (END "A" USED FOR i
spection, testing, and maintenance of 1/2 NPT MODELS) n
their fire protection system and de- � 1 I
vices in compliance with this docu- IIIJJJ
ment, as well as with the applicable WRENCH RECESS %re
standards of the National Fire Protec-
tion Association FPA 25 , in (END "B" USED FOR PUSH WRENCH
(e.g., g 3 /4" NPT MODELS) IN TO ENSURE
addition to the standards of any other ENGAGEMENT
authorities having jurisdiction. The in- WITH SPRINKLER
. stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA
facturer should be contacted relative to W -TYPE 6 SPRINKLER
any questions. WRENCH
- It is recommended that automatic FIGURE 14
sprinkler systems be inspected, local requirements and /or national W -TYPE RECESSED
tested, and maintained by a qualified codes. SPRINKLER WRENCH
Inspection Service in accordance with
Page 8 of 8 TFP171
P/N 57 - XXX - X - XXX
I I
TEMPERATURE
MODEUSIN RATING
SPRINKLER
330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135 °F /57 °C
331 2.8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C
340 4 2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175F/79°C
341 4.2K PENDENT (1/2 "NPT) TY2231 3 WHITE (RAL9010)* 200 200 °F /93 °C
370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C
371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED
390 8.0K UPRIGHT (3/4 "NPT) TY4131
391 8.0K PENDENT (3/4 "NPT) TY4231 * Eastern Hemisphere sales only.
TABLE C
PART NUMBER SELECTION
SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS
ORY, FOR INCIDENTAL, INDIRECT, Recessed Escutcheon:
Limited SPECIAL OR CONSEQUENTIAL Specify: Style (specify) Recessed Es-
Warra DAMAGES, INCLUDING BUT NOT cutcheon with (specify finish), P/N
Viarranty LIMITED TO LABOR CHARGES, RE- (specify).
GARDLESS OF WHETHER TYCO
Products manufactured by Tyco Fire FIRE PRODUCTS WAS INFORMED 1/2" (15 mm)
Products are warranted solely to the ABOUT THE POSSIBILITY OF SUCH Style 10
original Buyer for ten (10) years DAMAGES, AND IN NO EVENT Chrome Plated P/N 56- 701 -9 -010
' against defects in material and work- SHALL TYCO FIRE PRODUCTS' LI- White Coated P/N 56- 701 -4 -010
manship when paid for and properly ABILITY EXCEED AN AMOUNT Whde Plated 0'. P/N 56-701-3-010
installed and maintained under normal EQUAL TO THE SALES PRICE. Brass Plated P/N 56- 701 -2 -010
- use and service. This warranty will ex- THE FOREGOING WARRANTY IS 1/2' (15 mm)
pire ten (10) years from date of ship- Style 20
ment by Tyco Fire Products. No war- MADE IN LIEU OF ANY AND ALL. Chrome Plated . P/N 56- 705 -9 -010
ranty is given for products or OTHER WARRANTIES EXPRESS OR White Coated P/N 56- 705 -4 -010
components manufactured by compa IMPLIED. INCLUDING WARRANTIES White RAL9010' . P/N 56- 705 -3 -010
Hies not affiliated by ownership with OF MERCHANTABILITY AND FIT- Brass Plated . P/N 56- 705 -2 -010
Tyco Fire Products or for products and NES FOR A PARTICULAR PUR 3/4" (20 mm)
components which have been subject POSE Style 30
to misuse, improper installation, corro- Chrome Plated . ... P/N 56- 705 -9 -011
sion, or which have not been Installed, White Coated P/N 56- 705 -4 -011
maintained, modified or repaired in ac- Ordering White Plated 0' P/N 56- 705 -3 -011
cordance with applicable Standards of ®�� Brass Plated P/N 56- 705 -2 -011
the National Fire Protection Associa- Procedure 3/4" (20 mm)
tion, and /or the standards of any other Style 40
Authorities Having Jurisdiction. Mate- Otartantygiuri tecal distributor for avail- Chrome Plated P/N 56- 700 -9 -010
rials found by Tyco Fire Products to be abq .indicate the White Coated P/N 56- 700 -4 -010
defective shall be either repaired. or ful product White RAL9010' P/N 56- 700 -3 -010
replaced, at Tyco Fire Products' sole name. Refer to Brass Plated P/N 56 -700 -2 -010
option. Tyco Fire Products neither as- the complete Price List for
o
P Y complete listing 'Eastern Hemisphere sales only
sumes, nor authorizes any person to of Part Numbers
assume for it, any other obligation in Sprinkler Wrench:
connection with the sale of products or Sprinkler Assemblies with NPT Specify: W -Type 6 Sprinkler Wrench,
parts of products. Tyco Fire Products Thread Connections: P/N 56- 000 -6 -387.
shall not be responsible for sprinkler Specify: (Specify Model /SIN), Quick
system design errors or inaccurate or Response, (specify K- factor), (specify Specify: W -Type 7 Sprinkler Wrench,
incomplete information supplied by temperature rating), Series TY -FRB P/N 56- 850 -4 -001.
Buyer or Buyer's representatives. (specify Pendent or Upright) Sprinkler
IN NO EVENT SHALL TYCO FIRE with (specify type of finish or coating),
PRODUCTS BE LIABLE, IN CON P/N (specify from Table C).
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE -
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446