Correspondence / / /r‘IV0 I I\ • October 4, 2004 CITY OF TIGARD' Wyatt Fire Protection ORE 9095 SW Burnham Tigard, OR 97223 RE: MODIFY FIRE SPRINKLER SYSTEM Project Information Building Permit: BUP2004 -00456 Occupancy Type: M Tenant Name: Friedlanders Construction Type: VN Address: 9650 SW Washington Square Road Occupant Load: 46 Area: 1,675 Sq Ft Stories: 1 Hazard: Ordinary, Group 2 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. • Inspector to verify coverage in existing corridors at rear exit. GENERAL 1. A minimum of 18 inches shall be maintained between top of storage and ceiling sprinkler deflectors. Standard 9 -1, section 4 -4.1.6 OSSC 2. Sidewall sprinkler deflectors shall be located not more than 6 inches or less than 4 inches from walls and ceilings. Standard 9 -1, section 4- 4.2.3.3 OSSC 3. Clearances shall be provided around all piping extending through walls, floors, platforms and foundations. Minimum clearance for pipe sizes 1 inch through 3 '/2 inches shall be not less than 1 inch. Standard 9 -1, section 4- 5.4.3.4 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Respectfully, rian Blalo Senior P ►. Examiner 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772