Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
December 23, 2009 II
RE: TENANT IMPROVEMENT
v
Project Information
Building Permit: BUP2009 -00197 Construction Type: 2 -B
Address: 9677 SW Washington Sq. Occupancy Type: M
Area: 4131 Sq. Ft. Stories: 1
Name: Aeropostale Sprinklers: Yes
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2007 edition; 2007 Oregon Fire Code. Please respond to conditions below.
1) Please provide a permit valuation based on the total work being performed.
Permit valuations shall include total value of work, including materials and
labor, for which the permit is being issued, such as electrical, gas,
mechanical, plumbing equipment and permanent systems. If, in the opinion of
the building official, the valuation is underestimated on the application, the
permit shall be denied, unless the applicant can show detailed estimates to
meet the approval of the building official. Final building permit valuation shall
be set by the building official.
When responding, provide an itemized letter stating in what way each numbered
issue has been addressed in the revision.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Resp-:tfully
o
/% 40'/
an Nelson
Senior Plans Examiner
(503) 718 -2436
dann @tigard - or.gov
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard or.gov • TTY Relay: 503.684.2772
TRANSMISSION VERIFICATION REPORT
TIME : 12/23/2009 10:37
NAME : TIGARD BUILDING DEPT
FAX : 5036243681
TEL .
SER.# : BROD4J479592
DATE,TIME 12/23 10:36
FAX NO. /NAME 14123711586
DURATION 00:00:28
PAGES) 01
RESULT OK
MODE STANDARD
City of f Tigard, Oregon • 13225 SW Hall Blvd. • Tigard, OR 97223
December 23, 2009
•
RE: TENANT IMPROVEMENT
TIGARD
Project Information
Building Permit: BUP2009 -00197 Construction Type: 2 -B
Address: ` 9677 SW Washington Sq. Occupancy Type: M
Area: 4131 Sq. Ft. Stories: 1
Name: Aeropostale Sprinklers: Yes
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2007 edition; 2007 Oregon Fire Code. Please respond to conditions below.
1) Please provide a permit valuation based on the total work being performed.
Permit valuations shall include total value of work, including materials and
labor, for which the permit is being issued, such as electrical, gas,
mechanical, plumbing equipment and permanent systems. If, in the opinion of
the building official, the valuation is underestimated on the application, the
permit shall be denied, unless the applicant can show detailed estimates to
meet the approval of the building official. Final building permit valuation shall
be set by the building official.
When responding, provide an itemized letter stating in what way each numbered
issue has been addressed in the revision.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Resp tfully
City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
November 13, 2009
• FY
• . 4
• -. ..b
w,4
RE: TENANT IMPROVEMENT {T?=
0A RD
Proiect Information o
Building Permit: BUP2009 80t9 Construction Type: 2 -B
Address: 9677 SW Washington Sq. Occupancy Type: M
Area: 4131 Sq.Ft. Stories: 1
Name: Aeropostale Sprinklers: Yes
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC) 2007 edition; 2007 Oregon Fire Code. Please respond to conditions below.
1) Please provide engineered design for the ceiling supports, including seismic
struts, taking into consideration the approximate 17 -20 ft. of interstitial space
between the ceiling tile and the roof. Please include all calculations for
engineered designs with all submittals. OSSC106.1
2) Provide calculations and construction details (including seismic bracing
details for non full height partitions) for all walls. Note: The roof structure is
approximately 30' above the finished floor. OSSC 106.1
3) Please provide calculations and construction details for the soffit construction.
Every structure, and portion thereof, including non structural components that
are permanently attached to structures and their supports and attachments,
shall be designed and constructed to resist the effects of earthquake motions
in accordance with ASCE 7 as modified by Section 1613.7. The seismic
design category for a structure is permitted to be determined in accordance
with Section 1613 or ASCE 7. OSSC 1613.1
4) Please submit plans and calculations for steel storage racks that comply with
the design requirements of ASCE7 (15.5.3).
When responding, provide an itemized letter stating in what way each numbered
issue has been addressed in the revision.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectfully,
) / 1 .6)1 0
• ` a
Dan Nelson
Senior Plans Examiner
(503) 718 -2436
dann @tigard - or.gov
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772