Specifications w l Ilo S / w V ` i Kdc' .,C s 4-1-
S -
Zfl 4,., p,,-,_k 2 Mk.,-..,k) /(O / � �alSh�.
FEB 23 2006 „,J1 0 (L . �I�'zZ�
�, lvlec_ c - 61^5 V'( -� J2 I
�
, Rk,�o V P�-■ 1 s �e , (t5.t_ss) B OF TIGARD
ING DIVISION
cL5 �1L L'`k S 360
System Size. ANSUL 30/3.0 Total FP required' 20
Hood It L L4' 9' Long x 48' Vide x 24' High .
, Hood fi 3 3' 0' Long x 39' Vide x 24' High Riser 1i L Size• 10' x l9'
-' Riser It L Size: 7' x 7' Riser 0 2 Size; 10' x L9' Job Nane Panda Fxore Tigard, OR <WASH SO MAI I ) <N -317)
CT
cr,
z r - - - -� O o• ® I I ( / I I I I / ed \ 1 // j- -��,»o C J O, Pot
,5,
7 --'- — \ fil — - 1 r — i
L__ JL__J \ -.. _
‘. * 4 i. vi a
;T: f J
Qw4a _
2V 0 .
r ''� c ` z • % is, - y�
— r - - -- , L; r�^ y
_J L_JTL__ - -- 1 ®L - -it L 1_I__+_ — — - --�
® ""` lam � j• Q� g
�� i I. e LN �/ 7 9 •
X2 00 29.00 16.00 22.00 34.00 19.00 3700
Q
0 230 260 0
v
a
c-> .
A ' i.
3( =' tiS '. Zi ' =1r7" Z7 - -/ S ors' ” 3s' - y�-" 7 Ys
M
M
∎ ■p "
1 1
;teener WO ...,< ,.,K a l v� .Vow `x'Pk FACTORY PIPING
CV 24.00 L x24.00' 0 00• Moneta sr. e 00' D ionet l4 •Da7;17 Mit ill ,mo ni
.o J vr G . � ' �-. — — — FIELD PIPING
M FN,� MNC
7 b0 16v
�( .
' td
sr/ chi
IIIIII
■
-; '‘
LEASE LIn ❑ 1
°e l
49 ■((■
04 0 j
W P;
Z /
J
43) C 42)
orgzazialmommosism ep
immimmimilimmiwilmil
-arum mums _ rii■ Fill
y
es , o = 9L•O iifL�
• - _ 1 . , �.� , ,, i __wall lira Hi I owa V a
iLn1t>z�1 m 10;11 LI • . ® 0
0o Si nn' d X GOO ! oil) emir t*.= �o in
/Ii Met' n \ \ e
�•�■ ,.,..rte �.....r : -
_ RI
tY =Y v v VSV��►�i 42A X - -
Immmummosurilir _
0 _g_p 4a)
4F 'gi: ® T ., BELL
4Ca� ow. Q =N M ^ -
MI ire: n,. . ' � ���::,: 0 T malroln
imPliwinimimi1 ICE: 0 El
�aIMa� -..�� r..z 11 %— ∎S 5 +64 +64 AS, � - A *132 f , i .-•
GI> 6ENID +44.
E3
H BUTTON
Washington Square Mall, Portland, OR #N -317
876 SQ. SF., 0 SEATS, 27 L.F. SHELVES, 05/31 /05, REV #2, (HL)
• S/S 'd E66E •IvIIV sul as iy_ani l'i D WdEti :E 9002 . 9l .aa
•
/-�f 7
;• `, L, DESIGN R -�02 RESTAURANT
TTRESSION
RECHARGE INS ALLA ION AND SYSTEM
E (Standard FIRE SUPP UL 3 0 0 Lis
MANUAL
=,4 <F v y >: �' - s'3 .,s t - ^ '-'S" s �` ro- rFi x t ,
1F bt s 1 „ c
N
u s 114 r � !
y.. 1 F � S r} m n, r5r
j z y 7 r 3 :, i k
.� _ V i ,
+- a S - -.' ; k v X X , 2 k �rf
c l y :r ; 5 ; at
r - �, � i . 4. ...., 0, �4 'fi C
P
r a r 3 s r r r� =sra a
y - I.P is c a , s
' _ -7 r J�� fi
T
y 4 y .z 4 f• Mai
•
M ;':',''''' � . ,..,'x ;;-
rs
c n F
4 :
.: r 7 --e f4i
1
ti
} r b
.✓ a tx' d : .� x S�
fi
ti T
f r
r .,: 5 } _ G 4,.
.. .... t 1, itF
- - 7
}
t �
r
Ta y 4
o 3
x .
1. 001108
i
' 1
SECTION II — SYSTEM DESCRIPTION
UL EX. 3470 ULC CEx747 Page 2 -1
3 -1 -04 REV. 3
TOTAL SYSTEM
There are three types of R -102 Restaurant Fire Suppression Double -Tank System
Systems: The R -102 double -tank system is available with a stainless steel
1. Single -tank System enclosure and consists of:
2. Double -tank System 1. ANSUL AUTOMAN Regulated Release Assembly (Electrical
3. Multiple -tank System or Mechanical)
The type of system required for the particular installation will be 2. Nitrogen Cartridge and/or Carbon Dioxide Cartridge
determined through the guidelines covered in "System Design." 3. ANSULEX Low pH Liquid Fire Suppressant
Additional equipment which may be required to complete the sys- 4. Enclosure or Bracket Assembly
tern design is explained in the "System Components" section.
Additional devices covered are: remote manual pull stations, 5. Discharge Nozzles
mechanical and electrical gas shut -off valves, electrical switches, 6. Detection Components
and pressure switches.
7. Additional Devices (As Required)
Single -Tank System The regulated release assembly contains the regulated release
The R -102 single -tank system is available with a stainless steel • mechanism, agent tank, expellant gas hose for agent tank hookup,
enclosure and consists of: and enclosure knockouts to facilitate installing expellant piping,
1. ANSUL AUTOMAN Regulated Release Assembly (Electrical detection system, and additional equipment.
or Mechanical) The enclosure or bracket assembly is mounted separately but
2. Nitrogen Cartridge and /or Carbon Dioxide Cartridge within the guidelines of the regulated release assembly expellant
gas piping requirements to ensure simultaneous actuation of the
3. ANSULEX Low pH Liquid Fire Suppressant system. Refer to "System Components° section for individual com-
4. Discharge Nozzles ponent descriptions.
5. Detection Components
6. Additional Devices (As Required)
sThe regulated release assembly contains the regulated release
ue -
• mechanism, agent tank, expellant gas hose for agent tank hookup,
and enclosure knockouts to facilitate installing detection system
and additional equipment Refer to "System Components" section
for individual component descriptions. /
•
AC)
r
®
cD FIGURE x 2
FIGURE 1
000133
SECTION II — SYSTEM DESCRIPTION
UL EX. 3470 ULC CEx747 Page 2 -2
REV.4 3 -1-04
TOTAL SYSTEM (Continued)
Multiple -Tank System
The R -102 multiple -tank system is available with a stainless steel
enclosure and consists of:
1. ANSUL AUTOMAN Regulated Release Assembly
(Electrical or Mechanical)
2. Nitrogen Cartridges) and /or Carbon Dioxide Cartridge(s)
3. Regulated Actuator Assembly(ies)
4. ANSULEX Low pH Liquid Fire Suppressant
5. Enclosure or Bracket Assembly(ies)
6. Discharge Nozzles
7. Detection Components
8. Additional Devices (As Required)
The regulated release assembly contains the regulated release
• mechanism, agent tank, expellant gas hose for agent tank hookup,
and enclosure knockouts to facilitate installing actuation piping,
expellant piping, detection system, and additional equipment.
Each regulated actuator assembly is mounted separately but with-
in the guidelines of the regulated release assembly actuation/
expellant gas piping requirements to ensure simultaneous actua-
tion of the system. The assembly contains the pneumatic actuator,
• regulator, agent tank, expellant gas hose for agent tank hookup,
and enclosure plugs to facilitate installing expellant piping.
Each enclosure or bracket assembly is mounted separately but
within the guidelines of the regulated release assembly or regulat-
ed actuator assembly expellant gas piping requirements to ensure
simultaneous actuation of the system. Refer to "System
Components" section for individual component descriptions.
ill aiii m oo lil l iallipl■
%
ro D
�
FIGURE 3
000135
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -28
REV.4 3 -1-04
Nozzle Application Chart
The following chart has been developed to assist in calculating the
quantity and type of nozzle required to protect each duct, plenum,
or appliance.
NOTICE
This chart is for general reference only. See
complete details for each type of hazard.
Minimum Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping —
Hazard Dimensions Quantity Heights Part No. Flow No.
Duct or Transition Length — Unlimited 1 — 430912 1100
(Single Nozzle) Perimeter — 50 in. (127 cm)
Diameter — 16 in. (40.6 cm)
Duct or Transition Length — Unlimited 1 — 419337 2W
(Single Nozzle) Perimeter — 100 in. (254 cm)
Diameter — 31 7/8 in. (81 cm)
Duct or Transition Length — Unlimited 2 — 419337 2W
(Dual Nozzle) Perimeter — 150 in. (381 cm)
Diameter — 48 in. (122 cm)
Electrostatic Precipitator Individual Cell 1 — 419334 1/2N
(At Base of Duct)
Plenum Length — 10 ft (3.1 m) 1 — 419335 1N
(Horizontal Protection)
Plenum Length — 6 ft. (1.8 m) 1 — 430192 1100
(Horizontal Protection) Width — 4 ft (1.2 m) 1 — 419336 1W
Plenum Length — 4 ft. (1.2 m) 1 — 419336 1W
(Vertical Protection) Width — 4 ft. (1.2 m)
► Fryer (Split or Maximum Size
• Non -Split Vat)* (without drip board)
15 in. (38 cm) x
14 in. (36 cm)
High Proximity 1 27 — 47 in. 419339 230
Medium Proximity 1 20 — 27 in. 419340 245
► Fryer (Non -Split Vat Only) Maximum Size
(without drip board)
19 1/2 in. (49.5 cm) x
19 in. (48.2 cm)
High Proximity 1 21 — 34 in. 419338 3N
Low Proximity 1 13 — 16 in. 419342 290
Maximum Size
(without drip board)
18 in. (45.7 cm)
x 18 in. (45.7 cm)
High Proximity 1 25 — 35 in. 419338 3N
(64 -89 cm)
• For mulhple nozzle protection of single fryers. see detailed information on Pages 4-12 through 4-14
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -29
3 -1 -04 REV. 4
Nozzle Application Chart (Continued)
Minimum Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping —
Hazard Dimensions Quantity Heights Part No. Flow No.
• Fryer (Non -Split Maximum Size
► Vat Only)* (with drip board)
21 in. (53 cm) x
14 in. (36 cm)
(Fry Pot must not exceed
15 in. x 14 in.
(38 cm x 36 cm))
High Proximity 1 27 — 47 in. 419339 230
Medium Proximity 1 20 — 27 in. 419340 245
Maximum Size
(with drip board)
25 3/8 in. (64.4 cm)
x 19 1/2 in. (49.5 cm)
(Fry pot side must not
exceed 19 1/2 in.
(49.5 cm) x 19 in.
(48.2 cm)
High Proximity 1 21 — 34 in. 419338 3N
Low Proximity 1 13 — 16 in. 419342 290
Maximum Size
(with drip board)
18 in. (45.7 cm)
x 27 5/8 in. (70.2 cm)
High Proximity 1 25 — 35 in. 419338 3N
(64-89 cm)
• Range Longest Side 1 30 — 40 in. 419335 1N
32 in. (81 cm) (76 — 102 cm)
Area — 384 sq. in.
(2477 sq. cm)
Longest Side 40 — 48 in. 419333 1F
28 in. (71 cm) (102 — 122 cm)
Area — 336 sq. in. (With Backshelf)
(2168 sq. cm)
Longest Side (High Proximity) 1 40 — 50 in. 419340 245
28 in. (71 cm) (102 —127 cm)
Area — 672 sq. in.
(4335 sq. cm)
Longest Side
(Medium Proximity) 1 30 — 40 in. 419341 260
32 in. (81 cm) (76 — 102 cm)
Area — 768 sq. in.
(4955 sq. cm)
Longest Side (Low Proximity) 2 15 — 20 in. 419342 290
36 in. (91 cm) (38 — 51 cm)
Area — 1008 sq. in.
(6503 sq. cm)
• For multiple nozzle protection of single fryers, see detailed information on Pages 4-7 through 4-11
SECTION IV – SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -30
REV. 3 10 -1 -02
Nozzle Application Chart (Continued)
Minimum Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping –
Hazard Dimensions Quantity Heights Part No. Flow No,
Griddle Longest Side (High Proximity) 1 30 – 50 in. 419341 260
48 in. (122 cm) (76 – 127 cm)
Area – 1440 sq. in. (perimeter
(9290 sq. cm) located)
Longest Side (High Proximity) 1 30 – 50 in. 419342 290
30 in. (76 cm) (76 – 127 cm)
Area – 720 sq. in. (center located)
(4645 sq. cm)
Longest Side (High Proximity) 1 35 — 40 in. 419335/417332 1 N/1 NSS
36 in. (91 cm) (89 – 102 cm)
Area – 1080 sq. in. (perimeter located)
(6968 sq. cm)
Longest Side 1 20 – 30 in. 419342 290
(Medium Proximity) (51 – 76 cm)
48 in. (122 cm) (perimeter
Area – 1440 sq. in. located)
(9290 sq. cm)
Longest Side (Low Proximity) 1 10 – 20 in. 419343 2120
48 in. (122 cm) (25 – 51 cm)
Area – 1440 sq. in. (perimeter
(9290 sq. cm) located)
Chain Broiler' Longest Side – 34 in. (86 cm) 2 10 – 26 in. 419336/417333 1 W/1 WSS
(Overhead Protection) Area – 1088 sq. in. (25 – 66 cm)
(7019 sq. cm)
Chain Broiler Length – 43 in. (109 cm) 2 1 – 3 in. 419335/417332 1 N/1 NSS
(Horizontal Protection) Width – 31 in. (79 cm) (3 – 8 cm)
Gas - Radiant Char - Broiler Longest Side – 36 in. (91 cm) 1 15 – 40 in. 419335/417332 1 N/1 NSS
Area – 864 sq. in. (38 – 102 cm)
(5574 sq. cm)
Electric Char - Broiler Longest Side – 34 in. (86 cm) 1 20 – 50 in. 419335/417332 1 N/1 NSS
Area – 680 sq. in. (51 –127 cm)
(4388 sq. cm)
Lava -Rock Broiler Longest Side – 24 in. (61 cm) 1 18 – 35 in. 419335/417332 1 N/1 NSS
Area – 312 sq. in. (46 – 89 cm)
(2013 sq. cm)
Natural Charcoal Broiler Longest Side – 24 in. (61 cm) 1 18 – 40 in. 419335/417332 1 N/1 NSS
Area – 288 sq. in. (46 –102 cm) -
(1858 sq. cm)
Lava -Rock or Natural Longest Side – 30 in. (76 cm) 1 14 – 40 in. 419338 3N
Charcoal Char - Broiler Area – 720 sq. in. (36 –102 cm)
(4645 sq. cm)
• Minimum chain broiler exhaust opening — 12 in. x 12 m. (31 cm x 31 cm), and not less than 60% of internal broiler size.
•
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-31
3 -1 -04 REV. 6
Nozzle Application Chart (Continued)
Minimum Nozzle Tip
Maximum Hazard Nozzle Nozzle Nozzle Stamping —
Hazard Dimensions Quantity Heights Part No. Flow No.
Wood Fueled Char - Broiler Longest Side — 30 in. (76 cm) 1 14 — 40 in. 419338 3N
Area — 720 sq. in. (36 —102 cm)
(4645 sq. cm)
Upright Broiler Length — 32.5 in. (82.5 cm) 2 — 419334 1/2N
Width — 30 in. (76 cm)
Salamander Length — 32.5 in. (82.5 cm) 2 — 419334 1/2N
Broiler Width — 30 in. (76 cm)
Wok 14 in. — 30 in. (36 — 76 cm) 1 35 — 45 in. 419341 260
Diameter (89 — 114 cm)
3.75 — 8.0 in. (9.5 — 20 cm)
Deep
11 in. — 24 in. (28 — 61 cm) 30 — 40 in. 419335/417332 1 N/1 NSS
• Diameter (76 — 102 cm)
3.0 — 6.0 in. (8 — 15.2 cm)
Deep
•
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -1
10 -1 -02 REV. 5
SYSTEM DESIGN • GENERAL INFORMATION
The Ansul R -102 Restaurant Fire Suppression System may be 1. Nozzles must be located 2-8 in. (5 -20 cm) into the center of the
used on a number of different types of restaurant cooking appli- duct opening, discharging up. See Figure 1.
ances and hood and duct configurations. The design information
listed in this section deals with the limitations and parameters of
this pre - engineered system. Those individuals responsible for the
design of the R -102 system must be trained and hold a current
Ansul certificate in an R -102 training program.
The R -102 and the PIRANHA systems use compatible agents and
components, therefore, they may be used together for cooking
appliance, hood, and duct protection. The primary ANSUL
AUTOMAN Release can be either an R -102 or a PIRANHA
ANSUL AUTOMAN Release and can actuate up to two additional 1111
R -102 or PIRANHA Regulated Actuators. In systems utilizing a
101 remote release, any combination of the maximum number of
regulated actuators can be used. 2-8 W. m)
• Both systems must actuate simultaneously. I
• Each system must be designed and installed per its appropri- FIGURE 1
ate manual. 00017'
• Adjacent appliances requiring protection must be protected 2. In installations where a UL listed damper assembly is
with the same type of system, either R -102 or PIRANHA, employed, the duct nozzle can be installed beyond the 8 in.
unless the center -to- center spacing between the adjacent (20 cm) maximum, to a point just beyond the damper assem-
R -102 and PIRANHA nozzles is no less than 36 inches. bly that will not interfere with the damper. Exceeding the max-
• When appliances are protected with R -102 nozzles, the hood imum of 8 in. (20 cm) in this way will not void the UL listing of
and connecting duct above those appliances cannot be pro-
the system.
tected with PIRANHA nozzles. 3. Previously listed 3 flow number and 5 flow number duct pro-
• Mixing systems in a common plenum is not allowed. tection detailed in earlier published manual, Part No. 418087 -
One of the key elements for restaurant fire protection is a correct 06, can also still by utilized.
system design. This section is divided into ten sub - sections: Noz- DUCT SIZES UP TO 50 IN. (127 cm)
zle Placement Requirements, Tank Quantity Requirements, Actu- PERIMETER/ 16 IN. (41 cm) DIAMETER
ation and Expellant Gas Line Requirements, Distribution Piping
Requirements, Detection System Requirements, Manual Pull Sta- • One 1100 nozzle (Part No. 430912) = one flow number
lion Requirements, Mechanical Gas Valve Requirements, Electri- • 50 in. (127 cm) perimeter maximum
cal Gas Valve Requirements, Electrical Switch Requirements, and
Pressure Switch Requirements. Each of these sections must be • 16 in. (41 cm) diameter maximum
completed before attempting any installation. System design
sketches should be made of all aspects of design for reference DUCT SIZES UP TO 100 IN. (254 cm)
during installation. PERIMETER/ 32 IN. (81.3 cm) DIAMETER
• NOZZLE PLACEMENT REQUIREMENTS • One 2W Nozzle (Part No. 419337) = two flow numbers
This section gives guidelines for nozzle type, positioning, and • 100 in. (254 cm) perimeter maximum
quantity for duct, plenum, and individual appliance protection. This • 32 in. (81.3 cm) diameter maximum
section must be completed before determining tank quantity and A 2WH nozzle (Part No. 78078) must be substituted for a 2W
• piping requirements.
nozzle for any installation using Option 2 of the 1.5 gallon sys-
Duct Protection — Single Nozzle tern coverage (duct and plenum protection only). A 2WH nozzle
is limited to a maximum of 75 in. (190 cm) perimeter or a maxi -
All duct protection is UL listed without limitation of maximum duct mum diameter of 24 in. (61 cm) of coverage.
length (unlimited length). This includes all varieties of ductworks
both horizontal and vertical including ducts that run at angles to The chart below shows the maximum protection available from
the horizontal and ducts with directional bends. each duct nozzle.
The R -102 system uses different duct nozzles depending on the Part 3.0 Gallon 1.5 Gallon
size of duct being protected. Description No. System System
2W Nozzle 419337 Maximum Maximum
100 in. (254 cm) 100 in. (254 cm)
Perimeter Perimeter
1100 Nozzle 430912 Maximum Maximum
50 in. (127 cm) 50 in. (127 cm)
Perimeter Perimeter
•
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -2
REV. 3 10 -1 -02
• Duct Protection - Multiple Nozzle
DUCT SIZES UP TO 135 IN. (343 cm) PERIMETER - 3
FLOW OPTION
• One 1100 Nozzle (Part No. 430912) and one 2W Nozzle
(Part No. 419337) = three flow numbers
• 135 in. (343 cm) perimeter maximum
• No round duct option available
• Follow design table in Figure 2 to determine maximum module
size for each nozzle
1100 Module 2W Module
Side A Side B Side B Side B
Maximum Maximum Maximum Maximum
in. (cm) in. (cm) in. (cm) in. (cm)
4 (10) 60.0 (152) 23.0 (58) 37.0 (94)
5 (13) 60.0 (152) 23.0 (5B) 37.0 (94)
6 (15) 59.5 (151) 22.5 (57) 37.0 (94)
7 (18) 59.0 (150) 22.0 (56) 37.0 (94)
8 (20) 58.5 (149) 22.0 (56) 36.5 (93)
9 (23) 58.0 (147) 21.5 (55) 36.5 (93)
10 (25) 57.0 (145) 21.0 (53) 36.0 (91)
11 (28) 56.0 (142) 20.5 (52) 35.5 (90)
12 (31) 55.5 (141) 20.0 (51) 35.5 (90)
13 (33) 54.5 (138) 19.5 (50) 35.0 (89)
14 (36) 53.5 (136) 18.5 (47) 35.0 (89)
15 (38) 52.0 (132) 18.0 (46) 34.0 (86)
16 (41) 51.0 (130) 17.0 (43) 34.0 (86)
17 (43) 49.5 (126) 16.0 (41) 33.5 (85)
18 (46) 47.5 (121) 14.5 (37) 33.0 (84)
19 (48) 46.0 (117) 13.5 (34) 32.5 (83)
20 (51) 43.5 (111) 12.0 (31) 31.7 (81)
21 (53) 41.0 (104) 10.0 (25) 31.0 (79)
22 (56) 38.0 (97) 7.5 (19) 30.5 (78)
23 (58) 33.5 (85) 4.0 (10) 29.5 (75)
Side B
I
Side A I •
1 1100 I 1 2W
FIGURE 2
Example: Protection is required for a duct that has an "A" dimen-
sion of 8.0 in. (20 cm) wide and a "B" dimension of 55 in. (140 cm)
long.
Referring to the table in Figure 2, if the "A" dimension is 8.0 in. (20
cm), the "B" dimension must not exceed 58.5 in. (149 cm). In this
example, the "B" dimension is 55 in. (140 cm), therefore, this duct
can be protected with a three flow application.
Read over from the 8.0 in. (20 cm) line on the table to the 1100
Module column. At that point, the chart shows that the "B" module
length for the 1100 nozzle can be 22.0 in. (56 cm). Center the 1100
nozzle in that module. The 2W module can now be centered with-
. in the remaining module.
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-4
REV. 5 3 -1 -04
Transition Protection
Transitions are protected at a point in the transition where the
• perimeter or the diameter is equal to or less than the maximum The 1 /2N nozzle (Part No. 419334) must be centered 10 to 26 in.
• size duct that can be protected. The nozzle must be located in the (25 to 66 cm) below the precipitator and aimed to discharge at the
center of the transition opening where the maximum perimeter or center of each precipitator cell. However, if it is physically impos-
diameter begins. See Figure 4. sible to mount the nozzle at 10 to 26 in. (25 to 66 cm) due to pre-
cipitator placement, the nozzle may be mounted closer than 10 in.
�� (25 cm). See Figure 5.
� DUCT
TRANSITION
DUCT SEE DUCT FOR
•_��� NOZZLE TRANSITION
PROTECTION
1114
II
PRECIPITATOR
10-26 IN.*
(2566 cm)
FIGURE 4
000176
NOZZLE FOR
Electrostatic Precipitator Protection PRECIPITATOR
PROTECTION
Some restaurant ventilating ducts have an electrostatic precipita-
tor installed at or near the base. These precipitators are used to • IF PHYSICALLY IMPOSSIBLE AT 10 TO 26 IN. (25 TO 66 cm). NOZZLE MAY BE MOUNT -
aid in the cleaning of exhaust air. ED CLOSER THAN 10 IN. (25 cm).
Normally electrostatic precipitators do not require protection but FIGURE
should the "authority having jurisdiction° require protection, use
the following guidelines.
Ducts with precipitators located at or near the base can be pro-
tected using duct nozzle(s) above the precipitator and 1/2N noz-
zle(s) (Part No. 419334) for the precipitator. One 1 /2N nozzle must
be used for each cell being protected. This nozzle tip is stamped
with 1/2N, indicating that it is a 1/2 -flow nozzle and must be count-
ed as 1/2 flow number.
When protecting ducts equipped with precipitators, the duct noz-
zle(s) must be installed above the precipitator and aimed to dis-
charge downstream. If the area above the precipitator is a duct,
the nozzle(s) must be positioned according to duct protection
guidelines. If the area above the precipitator is a transition, the
transition guidelines must be followed.
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -5
10 -1 -02 REV. 3
Plenum Protection
The R -102 system uses the 1W Nozzle (Part No. 419336) or the
• 1100 Nozzle (Part No. 430192) or the 1N Nozzle (Part No. t
419335) for plenum protection. The 1W nozzle tip is stamped with 20 IN. (51 cm)
• 1W and the 1N nozzle tip is stamped with 1N, indicating they are Ma x II IMUM
one -flow nozzles and must be counted as one flow number each. i
When protecting a plenum chamber, the entire chamber must be .a }
. protected regardless of filter length. 1 IN. (2.5 cm)
MINIMUM
•
• VERTICAL PROTECTION - GENERAL
- 4-:- --
► One 1W nozzle or 1100 nozzle will protect 4 linear feet (1.2 m) of 1 t
plenum. The maximum distance from the end of the hood to the 20 IN. (51 cm)
MAXIMUM
first and last nozzle must be no more than 2 ft. (.6 m). After the first i
nozzle, any additional nozzles must be positioned at a maximum ,
of 4 ft. (1.2 m) apart down the entire length of the plenum. The t
. plenum width must not exceed 4 ft. (1.2 m). (The 1W or 1100 noz- 1 IN. (2.5 an)
zle can be used on single or V -bank filter arrangements.) See MINIMUM
Figure 6.
2FT(.6m)
•• FIGURE 7
MAXIMUM . 000199
4 FT. (1.2 m) Option 2: The 1W or 1100 nozzle must be placed perpendicular,
MAXIMUM
►
4 FT. (12 m) /\4 FT. (12 m) 8 -12 in. (20 -30 cm) from the face of the filter and angled
2 FT. (.6 m) MAXIMUM MAXIMUM to the center of the filter. The nozzle tip must be within
MAXIMUM 2 in. (5 cm) from the perpendicular center line of the fil-
-v ter. See Figure 8. i.
,\\ ,�� f 12 IN. (30 cm)
0 C e•f MAXIMUM
' ';.. _ '.1..,...1..,' 4 IN. j
, \a
8 1NIN. (20 cn)
� �i � / -/ i� MINIMUM
�� NOZZLE TIP 4 N• °
D. G MUST BE WITHIN . a .
FIGURE 6 THIS AREA
000141 i ; . ■
.N'
. When protecting plenums with the 1W or 1100 nozzle, two options ..
of coverage are available: FIGURE 8
•
• Option 1: The 1100 or 1W nozzle must be on the center line of the C00200
single or "V" bank filter and positioned within 1 -20 in. HORIZONTAL PROTECTION - OPTION 1
(2.5-51 cm) above the top edge of the filter. See ►
1N NOZZLE - PART NO. 419335 - SINGLE BANK PROTEC-
. Figure 7. TION
One 1N nozzle will protect 10 linear feet (3.1 m) of single filter bank
• plenum. The nozzle(s) must be mounted in the plenum, 2 to 4 in.
(5 to 10 cm) from the face of the filter, centered between the filter
height dimension, and aimed down the length. See Figure 9.
F ..•°'d. 2 -4 IN. 10 FT. (3.1 m)
.....
(5- 10 cm) MAXIMUM
`I ii0111
1
( __, ,,- -- '
1 0
• FIGURE 9
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -6
REV. 4 10 -1-02
Plenum Protection (Continued)
• HORIZONTAL PROTECTION — OPTION 2 For a plenum, either single or "V" bank, with a linear extension
1100 NOZZLE — PART NO. 430912 — "V" BANK PROTECTION longer than 10 feet (3.1 m), each bank may be protected using one
1W NOZZLE — PART N0.419336 1N nozzle every 10 ft (3.1 m) or less depending on the overall
length of the plenum. See Figure 12. The nozzles may point in the
One 1100 or 1W nozzle will protect 6 linear feet (1.8 m) of "V" bank opposite directions as long as the entire plenum area is protected,
plenum. The nozzle must be mounted horizontally, positioned 1/3 and the 10 ft. (3.1 m) limitation is not exceeded. See Figure 13.
the filter height down from the top of the filter. Nozzles can be locat- The nozzle positioning shown in Figure 14 is not an acceptable
ed at 6 ft. (1.8 m) spacings on longer plenums. See Figure 10. method of protection because the plenum area directly under the
1100 NOZZLE OR 1W NOZZLE tee is not within the discharge pattern of either nozzle.
10 FT. (3.1m)
MAXIMUM
7 I 1/3 (H) t 10 FT. (3 1 m)
HEIGHT OF
MAXIMUM 01110
FILTER (H) 6 FT (1.8 m)< MAXIMUM 10 FT (3 1 m) ��� \
I MAXIMUM \
MAXIMUM c_ / )'\ 4,-
ter \� 30 FT (9 1 m) •
1(4/11 FIGURE 12
000zas
1
10 FT (3.1 m).-
FIGURE 10 MAXIMUM
006524
1N NOZZLE — PART NO. 419335 — "V" BANK PROTECTION 10 FT. (3.1 m)
MAXIMUM
Two IN nozzles will protect 10 linear feet (3.1 m) by 4 ft (1.2 m) �!
wide of "V" bank plenum. The nozzles must be mounted in the 10 FT. (3.1 m) \
plenum, 2 to 4 in. (5 to 10 cm) from the face of the filter, centered MAXIMUM ',
between the filter height dimension, and aimed down the length. u !
See Figure 11. y
2 - 4 IN. y 30 FT. (9.1 m)
( ) (5 - 10 cm) 1'
2 - 4 IN.
(5 - 10 cm) 3:.
y i. i .' r ' `
44.. '
',4 0' 000203
; FIGURE 13
000207
MAX IMUM , -
- elp,_ ,..,
10 FT. (3.1 m) ��
MAXI
. /
4
INCORRECT
ooczo4
FIGURE 14
I FIGURE 11 000203
1
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-7
10 -1 -02 REV.3
Appliance Protection
The following pages detail types of appliance protection. Each
design requires several factors: correct nozzle choice, correct noz-
zle height above hazard, correct nozzle location and correct aim-
ing point
Fryer — Single Nozzle Protection
1. Design requirements for fryers are broken down into two
types.
A. FRYERS WITHOUT DRIPBOARDS
If the fryer does not include a dripboard, measure the
internal depth (horizontal dimension from front to back)
and length of the frypot.
B. FRYERS WITH DRIPBOARDS
If the fryer includes any dripboard areas, measure both
the internal depth (horizontal dimension from front to
back) and length of the frypot portion, and then measure
the internal depth and length of the overall hazard area
including any dripboard areas.
2. Using Table, "Maximum Cooking Area Dimension — Single
Nozzle Fryer Protection," determine which nozzle is needed
to protect the fryer based on the maximum dimensions listed.
A. If the fryer does not include a dripboard, use the maxi-
mum dimensions listed in the first column of the table to
select the correct nozzle.
B. If the fryer includes any dripboard areas, use both the
maximum frypot dimensions in the first column of the
table, and the maximum overall dimensions in the second
column of the table to select the correct nozzle. None of
the maximum dimensions in either column may be
exceeded.
3. If either the maximum frypot or the overall sizes are exceed-
ed, an additional nozzle(s) will be required. Refer to the mul-
tiple nozzle requirements.
Example: A flyer with a dripboard. The inside of the frypot without
the dripboard measures 18 in. in depth x 18 in. in length (46 cm x
46 cm) and the inside of the overall area including the dripboard
measures 18 in. in depth x 24 in. in length (46 cm x 61 cm). From
the Table Maximum Cooking Area Dimension — Single Nozzle
Fryer Protection, "either the 3N or the 290 nozzle should be select-
ed to protect the fryer, depending on the maximum nozzle height
above the fryer and the positioning requirements allowed. Refer to
appropriate Figures.
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-40
REV.3 3 -1 -04
• OVERLAPPING NOZZLE COVERAGE •• All appliance protection currently listed in the R -102 Design
Hazard Zone Manual, Part No. 418087, is also approved protection. Zone pro-
tection can be considered optional protection.
The hazard zone is defined as a theoretical, flat and level, rectan-
gular surface, that includes all of the cooking hazards of the pro- TABLE 1
tected appliances under a common hood(s). The purpose of the
hazard zone is to provide a means of locating the appliances and Overlapping Nozzle Coverage (Zone Protection)
the overlapping nozzles, as well as aiming the overlapping noz- Appliance Type Maximum Cooking Hazard
zles. The hazard zone measures 28 in. (711 mm) deep by the Fryer 34 In. (864 mm) Deep x 5.8 sq. ft.
length of the cooking hazard(s). The centerline of the hazard zone
must bisect the 28 in. (711 mm) depth (from front to back) and run (•54 sq. m)
from right -to-left for the full width of the hazard zone. Griddle 30 in. (762 mm) Deep x Unlimited Length
Overlapping Nozzle Appliance Protection Range 28 in. (711 mm) Deep x Unlimited Length
Wok, Maximum 30 in. (762 mm) Diameter x 8 in.
Overlapping Nozzle Appliance Protection is defined as protection (203 mm) Deep
of cooking appliances by nozzles spaced uniformly at uniform ele-
vations under a common hood(s). Overlapping protection of appli- Wok, Minimum 11 in. (279 mm) Diameter x 3 in.
ances is continuous for the full length of the hood or divided when (76 mm) Deep
group(s) of protected appliances are separated by counters or Braising Pan(Tlt 34 in. (864 mm) Deep x Unlimited
appliances not requiring protection. Skillet` Length
Full hood continuous protection is defined as overlapping noz - Lava Rock 32 in. (813 mm) Deep x Unlimited
zle appliance protection that covers the appliance line -up located Char - Broiler Length
under the total hood length. All appliances requiring protection are Charcoal Broiler 32 in. (813 mm) Deep x Unlimited Length
the appliances under the hood that can be an ignition source of (4 in. (102 mm) Maximum Fuel Depth)
grease in the hood, grease removal device or the duct. Mesquite Wood 32 in. (813 mm) Deep x Unlimited Length
Group protection is defined as overlapping nozzle appliance pro- Broiler (12 in. (305 mm) Maximum Fuel Depth)
tection that protects individual hazard zones located under a com- Gas Radiant 36 in. (914 mm) Deep x Unlimited
mon hood. These "groups" of appliances may be separated by Char - Broiler Length
appliances not requiring protection, such as steam equipment or
work tables, or by dedicated appliance protection, such as sala- Electric Char Broiler 34 in. (864 mm) Deep x 20 in. (508 mm)
mander broilers. • See Figure 73 for nozzle location
See Figure 76 (full hood continuous protection) and Figure 77
(multiple group protection).
Dedicated Nozzle Appliance Protection I II
Appliance protection using dedicated nozzle coverage is defined / 0-6 IN. (0-15 cm)
as protection of cooking appliances with enclosed cooking haz- IN WITFOT I I
ards, such as upright broilers, which cannot be protected with EDGE OF l
overlapping nozzles and therefore must be protected with nozzles DISCHARGE I 40-45 IN.
dedicated to the appliance. ; (1-1.1 m)
General Design Limitations ;
• Maximum depth of zone is 28 in. (711 mm). r
• The 245 nozzle, Part No. 419340, is the only approved nozzle 1 ZONE
for overlapping (zone) protection. f -
• Nozzle must be located 0 in. to 6 in. (0 mm to 152 mm) forward gait:
zone centerline, aimed back at the zone centerline.
• Nozzles must be spaced a maximum of 6 in. (152 mm) from
each end of hazard and then a maximum of 12 in. (305 mm) on ZONE CENTER LINE
center for the remaining overlapping nozzles until the complete
hazard is covered.
FIGURE 73
• For appliance hazard surfaces with listed protection exceed-
ing the standard hazard zone of 28 in. (71 cm) in depth, the haz-
ard surface(s) must be aligned with the back edge of the hazard
zone, with the front edge overhanging the front edge of the
zone. See Appliance Chart, Table 1.
• For appliance hazard surfaces that exceed the listed protec-
tion sizes, multiple zones must be utilized. Align entire hazard
surface area within the multiple zones.
• All hood, duct, individual appliance, and piping limitations are as
specified in the R -102 Design, Installation, Recharge and
► Maintenance Manual, Part No. 418087.
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-41
3 -1 -04 REV.3
• OVERLAPPING NOZZLE COVERAGE (Continued) • 4. The overlapping appliance nozzles must be located 0 in. to
6 in. (0 mm to 152 mm) forward of the centerline or aimline of
Overlapping Appliance Nozzle and Hazard Zone Locations the selected hazard zone. See Figure 75.
1. All overlapping appliance nozzles must be the "245" nozzle, 245 NOZZLE - NOZZLE MUST BE AIMED STRAIGHT
Part No. 419340, and must be located under a common hood
I DOWN OR BACK AT CENTERLINE OF
at the same height above the hazard zone, in a straight line - HAZARD ZONE
from right to left and aimed at the centerline of the hazard
zone. The overlapping nozzle is used for both continuous
overlapping and multiple group overlapping protection.
2. The hazard zone must be positioned (located) so that all appli-
ance hazard surfaces are within the zone. For appliance (
haz-
and surfaces with listed protection exceeding the standard f- 45 IN.
(1552 2 mm) (1.1 m)
hazard zone size of 28 in. (71 cm) in depth (see Table 1), the
hazard surface(s) must be aligned with the back edge of the 40 m
hazard zone, with the front edge overhanging the front of the
zone.
3. The overlapping appliance nozzles must be located 40 in. to
45 in. (1 m to 1.1 m) above the top surface of the protected
appliances. See Figure 75. / /d / / / ///
FRONT BACK OF ZONE
Exception No. 1: Nozzle dimensions for wok protection are OF ZONE
measured to bottom of wok. Exception No. 2: When using CENTERLINE OF
overlapping appliance nozzles in areas where there is a back 28 IN. HAZARD ZONE
PP (711 mm)
shelf, the nozzle cannot be positioned in the shaded area as ZONE
shown in Figure 74. FIGURE 75
OD ®15
Also, back shelf must not extend more than 11 in. (279 mm)
over the hazard zone and cannot be less than 20 in. (508 mm)
above the hazard zone. See Figure 74.
/- OVERLAPPING NOZZLE(S)
CANNOT BE POSfTIONED
45 IBM IN THIS SHADED AREA
ui
41 iii
40 ■ ■I•■
6 5 4 3 2 1
+- CENTER LINE OF
HAZARD ZONE
BACK
SHELF
1 t_
I
11 IN. (279 mm)
MAXIMUM
20 IN.
(508 mm)
MINIMUM
1 7 „are
F- 28 IN. (711 mm) ►I
FIGURE 74
006914
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -42
REV. 4 3 -1 -04
• OVERLAPPING NOZZLE COVERAGE (Continued) • 2. When obstructions are located adjacent to appliance(s) pro-
Overlapping Appliance Nozzle and Hazard Zone Locations — tected by overlapping nozzles, the overlapping appliance noz-
Group Protection zle spacing must start with the appliance(s) adjacent to the
obstruction. See Figure 78.
1. For each group of protected appliances under a common
hood(s), the overlapping nozzles must be located from right to 12 IN. � 12 IN L� 12 IN. 12 IN.
6 IN. I (305 mm) I( mm) I(3 mm) (305 mm)I
left so that each end nozzle is located a maximum of 6 in. (152 mm) _ MAMAX. _ MAX MAX. _ f 6IN
MAX. (152 mm) inside the outside edge of the cooking hazard of MAX + (152 mm)
MAX
each end appliance, and the inside overlapping nozzles must
be located between the two end nozzles at a maximum spac-
ing of 12 in. (305 mm). See Figures 76 and 77.
OUTSIDE
EDGE OF
12 IN. (305 mm) MAXIMUM COOKING
SPACING(S) BETWEEN HAZARD
OVERLAPPING NOZZLES
1 Ill 11 '`1 1�I f
/ IN. ■ / 1 / \ \ / \ / i \ / ■
6 -{r / \ / \ \ r 6 IN.
(152 IN ) /
MAXIMUM / \ \\ / \ / \ \ V \ \ \ / \ \ / \ \ ( MAXIM M t I- . HAZARD AR -I
FROM / V / \� \ FROM OBSTRUCTION
EDGE OF / OF
COOKING / \ n \ / \ \ / \ \ EDGK COOKING
HAZARD / ,, / \ / \ / . // \ • \ C \ HAZARD FIGURE
3. When an appliance requires dedicated protection with a pro-
tected area intended for overlapping appliance nozzle protec-
tion, the group protection option will be required for appliances
on either side of the appliances using dedicated protection.
Group protection using overlapping appliance nozzles must
FULL HOOD CONTINUOUS APPLIANCE PROTECTION begin with the protected appliance(s) adjacent to the dedicat-
FIGURE 76 ed appliance protected. An overlapping appliance nozzle(s)
001710 must be positioned within 6 in. (152 mm) of the edge(s) of the
_ appliance hazard surface area(s) adjacent to the dedicated
nozzle protection. See Figure 79.
1
12 IN. (305 mm) 6 IN. (152 mm)
MAXIMUM MAXIMUM EDGE OF COOKING
HAZARD
i f i\ t If I / \1
6IN. --► �- H ► I 6IN.
(152 mm) 12 IN. (152 mm) 6IN. + 12 1N. + 1 y ` 12 IN. 12 IN. I
MAXIMUM (305 mm) MAXIMUM (152 mm x mm) (305 mm) (305 mm) 6 IN.
FROM R MAXIMUM FROM MAX I 1 A MAX MAX. ( 152 mm)
EDGE OF • . \ t • EDGE OF t MAX.
COOKING COOKING EDGE -,- 6IN. (152 mm) 6IN. (152 mm) EDGE
HAZARD EDGE OF HAZARD OF MAXIMUM MAXIMUM
OF
COOKING COOKING - - COOKING
HAZARD HAZARD 1 HAZARD
GROUP APPLIANCE PROTECTION
FIGURE 77 III / IL
001779 DEDICATED NOZZLE
APPLIANCE
. ■ FIGURE 79
001758
•
•
•
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -43
3 -1 -04 REV.
• OVERLAPPING NOZZLE COVERAGE (Continued)
Overlapping Appliance Nozzle and Hazard Zone Locations —
Group Protection (Continued)
4. On protected appliances, all hazard surfaces located in a
group must be within 40-45 in. (102 -114 cm) from the noz-
zle(s). Once that dimension is exceeded, a new group must
be started. See Figure 80.
Note: The supply pipe feeding nozzle groups is to be at the
same elevation. Adjust height for each group only by varying
lengths of nozzle drops.
6 IN (152 mm) I 6 IN. (152 mm)
MAXIMUM I I MAXIMUM
1 1 Y f i I
I NOZZLES t I
I l NOZZLES I 1
45 I I 40 1N. ) i
(114 cm) I (102 cm) i 40 IN I (10 45 IN.
�rm) (114 cm)
lB//E ra /d/ % //////// /////!/ G 1
GROUP 'A' ' GROUP
FIGURE 80
006917
Detection Requirements For Overlapping Appliance
Protection
When utilizing overlapping appliance protection, fusible link detec-
tors must be installed on a maximum of 2 ft. (.61 m) centers,
starting with detectors located in (under) the duct opening(s).
Starting from the detector under the duct opening, add detectors
on 2 ft. (.61 m) maximum spacing until the complete length of the
plenum area is covered, from one end to the other. The location of
the last detector on each end of the plenum must not exceed
2 ft. (.61 m) from end of plenum.
NOTE: Standard detector coverage, as specified in "Design
Section," is acceptable when utilizing dedicated nozzle
► coverages.
SECTION IV — SYSTEM DESIGi •
UL EX. 3470 ULC CEx747 Page 4-47
3 -1-04 REV. ?
DISTRIBUTION PIPING REQUIREMENTS (Continued)
Supply and Branch Line Identification SUPPLY LINE
The R -102 distribution piping network is broken down into four The Supply Line is defined as the length of pipe which runs from
specific pipe runs: the Supply Line, the Duct Branch Line, the agent tank outlet to the last branch line (whether a duct, appli-
the Plenum Branch Line, and the Appliance Branch Line. See ance, or plenum branch line). This includes all supply line fittings
• Figure 87. except for the tees or elbows leading to the branch lines. See
DUCT • Figures 87 and 88.
BRANCH LINE t
4f,
SUPPLY - - iiii -LINE � ..1 �
4 ! ______
1
PLENUM APPLIANCE
BRANCH LINE BP.ANCH UNE
NOTE: THIS IS A CONCEPTUAL DRAWING ONLY.
THIS IS NOT AN ACTUAL INSTALLATION.
FIGURE 87
030779 _ END OF
SUPPLY LINE
NOTE: THESE ARE EXAMPLES ONLY. OTHER CONFIGURATIONS CAN BE DESIGNED.
r <
Q END OF PPLY LINE ..- SU� END OF
SUPPLY LINE
<� f t END OF
SUPPLY LINE p
i 9
r ,
L.,
9
Y S UPPLY (NOZZLES FOR
LINE TEE PLENUM
PROTECTION)
END OF
Q SUPPLY LINE _ -
fit
9`
v i ,� v
/ , - .,
P (NOZZLES FOR
SUPPLY , PLENUM
LINE TEE PROTECTION)
BRANCH LINE CANNOT - BRANCH LINE CANNOT AHEAD OF A SUP- START AHEAD OF A SUP-
2. PLY LINE TEE I PLY LINE TEE
• FIGURE 88
WO]BO
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -48
REV.3 3 -1 -04
DISTRIBUTION PIPING REQUIREMENTS (Continued)
Supply and Branch Line Identification (Continued) PLENUM BRANCH LINE
NOTICE The Plenum Branch Line is defined as the length of pipe which
Branch lines cannot start ahead of a supply line runs from the supply line to the plenum nozzle(s). This includes all
tee. branch line fittings as well as the tee or elbow used to start the
DUCT BRANCH LINE • branch line. See Figures 87 and 90.
The Duct Branch Line is defined as the length of pipe which runs '
9th PP '
from the supply line to the duct nozzle(s). This includes all branch - - T ..®
line fittings as well as the tee or elbow used to start the branch line. -rte t
• See Figures 88 and 89. f,-- I
PLENUM BRANCH LINE
1 (TEE INCLUDED)
DUCT BRANCH LINE •
I
(ELBOW INCLUDED) ( " -- PLENUM BRANCH LINE
? (TEE INCLUDED)
DUCT BRANCH LINE
(TEE INCLUDED)
FIGURE 90
030782
DUCT BRANCH LINE
(TEES INCLUDED) APPLIANCE BRANCH LINE
The Appliance Branch Line is defined as the length of pipe which
runs from the supply line to the appliance nozzle(s). This includes
,l 4 all branch line fittings as well as the tee or elbow used to start the
. -�
• branch line. See Figures 88 and 91.
•
(TEES INCLUDED) LINES
► FIGURE 89
000781
FIGURE 91
000783
6
•
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -49
3 -1 -04 REV. 3
DISTRIBUTION PIPING REQUIREMENTS (Continued) START OF LAST
BRANCH LINE
Distribution Piping Requirements —1.5 Gallon System START OF FIRST
DUCT, PLENUM, AND APPLIANCE PROTECTION BRANCH LINE
1. This option allows for duct protection, plenum protection,
appliance protection, or any combination. SUPPLY -
2. When using a combination of plenum and duct protection only, LINE TEE TOTAL LENGTH
MUST NOT
only one duct nozzle, either a 1W, 1100, or a 2W, may be ^ • EXCEED B FT.
Used. ( 7 , (24 m)
• 3. The previous Option 2 (using 2WH nozzle for plenum and duct
protection) still can be utilized. For detailed design information,
see previous version of this manual, Part No. 418087 -06.
Note: When using this option, all design parameters must be
followed as listed in manual version -06. START OF LAST
• BRANCH LINE
4. All distribution piping, supply and branch, must be 3/8 in. O ST ANCO FIRST
Schedule 40 black iron, chrome- plated, or stainless steel. FIGURE 92
5. Each 1.5 gallon tank allows a maximum of five flow numbers.* ppp784
• 6. The pipe length between the start of the first branch line and
the start of the last branch line must not exceed 8 ft. (2.4 m). 1W NOZZLE
When the supply line is split, the combined length of both
legs of the supply line (start of first branch line to start of last
• branch line) must not exceed 8 ft. (2.4 m). See Figure 92.
7. The combined length of all branch lines must not exceed 22 ft.
(6.7 m). See Figure 93. IN NOZZLE
• 8. The requirements of the following table must not be exceeded:
li ,.
1N NOZZLE
(BRANCH LINES IN BOLD) COMBINED LENGTH MUST
NOT EXCEED 22 FT. (6.7 m)
FIGURE 93
000785
Duct Plenum Appliance
Requirements Supply Branch Line Brach Line Branch Line
Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in.
Maximum Length 40 ft. 6 ft. 4 ft. 10 ft.
(12.2 m) (1.8 m) (1.2 m) (3 m)
Maximum Rise 6 ft 4 ft. 2 ft. 2 ft
(1.8 m) (1.2 m) (.6 m) (.6 m)
Maximum 90° Elbow 9 4 4 6
Maximum Tees 1 1 2 3
Maximum Flow Numbers 5* 2 2 3
► • Exceptions:
1. Six (6) flow numbers are allowed when a duct branch line is the last branch line on the piping network and no IN nozzles are used to protect woks or gnddles
.. 2. Six (6) flow numbers are allowed when six (6) IN nozzles are used and none of the nozzles are used to protect woks and gnddles NOTE Only five (5) flow numbers are allowed if
a IN nozzle is used for wok or gnddle protection.
3 Six (6) flow numbers are allowed when only two (2) 3N nozzles are used
•
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -50
REV.3 3 -1 -04
DISTRIBUTION PIPING REQUIREMENTS (Continued)
Distribution Piping Requirements — 3.0 Gallon System
1. The maximum length between the start of the first branch line SUPPLY
and the start of the last branch line must not exceed 24 ft TEE ~ i
(7.3 m). When the supply line is split, the combined total of
both legs of the supply line (from the start of the first branch -40111"
line to the start of the last branch line) must not exceed 24 ft.
• (7.3 m). See Figure 94. R oo
COMBINED LENGTH OF \
2. The total length of all branch lines must not exceed 36 ft. '' BOTH LEGS OF SUPPLY
• (10.9 m). See Figure 94. LINE MUST NOT 3 BRANCH LINES
EXCEED 24 FL (7.3 m)
3. Use a 3/8 in. union to connect the tank adaptor to the 3/8 in.
supply line.
4. A maximum of two nozzles are allowed per duct branch line.
1N NOZZLE
5. The requirements of the following table must not be exceeded: 2w NOZZLE \�
1N NOZZLE
230 NOZZLE /
245 NOZZLE 1/2N NOZZLE
(BRANCH LINE IN BOLD)
COMBINED LENGTH MUST o
NOT EXCEED 36 FT. (10.9 m)
► FIGURE 94
Duct Plenum Appliance
Requirements Supply Line Branch Line Branch Line Branch Line
Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in.
Maximum Length 40 ft. 8 ft. 4 ft. 12 ft.
(12.2 m) (2.4 m) (1.2 m) (3.7 m)
Maximum Rise 6 ft. 4 ft. 2 ft. 2 ft.
(1.8 m) (1.2 m) (.6 m) (.6 m)
Maximum 90° 9 4 4 6
Elbows
Maximum Tees 1 2 2 4
Maximum Flow 11* 4 2 4
Numbers
'Exceptions:
► 1. Twelve (12) flow numbers are allowed in any one tank not containing two-flow appliance nozzles, and/or, a 1N nozzle for wok or griddle protection, and /or, a if or 1N nozzle for
range protection, and/or, a 3N nozzle for fryer protection.
• 2. Twelve (12) flow numbers are allowed in any one tank for duct and plenum protection only.
3. Twelve (12) flow numbers are allowed with any one tank using only two-flow appliance nozzles.
4. Twelve (12) flow numbers are allowed with any one tank using only three -flow applance nozzles.
Special Instructions:
► 1. Twelve (12) flow numbers are allowed when four (4) Dean Industries GTI Gas Fryers are protected at low proximity as shown in Figure 59 on Page 4-32. The discharge piping
► must be as shown in Figure 59 on Page 4-32.
2 For certain McDonald's applications, 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 12N electrostatic precipitator nozzle,
one (1) 1N plenum nozzle, and four (4) two-flow appliance nozzles. Contact Ansul Apprcalons Engineering Department for additional information.
•
4
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -51
3 -1 -04 REV. 3
DISTRIBUTION PIPING REQUIREMENTS (Continued)
LENGTH OF PIPING MUST NOT EXCEED 24 FT
Distribution Piping Requirements — 6.0 Gallon Manifolded (7.3 m) FROM START OF FIRST BRANCH LINE
System TO START OF LAST BRANCH LINE
As an option to piping two (2) 3.0 gallon tanks separately, two (2)
3.0 gallon tanks can be manifolded together to share a common
agent distribution line. Only (2) 3.0 gallon tanks connected to the
same regulator can be manifolded. The following requirements
must be met when manifolding:
1. All I in must be 3/8 in. Schedule 40. or START OF LAST
p p g mus BRANCH LINE
■ 2. See Figure 96 for tank connections. V '
3. The length of supply line piping between the start of the first
branch line and the start of the last branch line must not
▪ exceed 24 ft. (7.3 m). See Figure 95. When the supply line is
split, the combined total of both legs of the supply line (from
the start of the first branch line to the start of the last branch
line) must not exceed 24 ft. (7.3 m). ONZZ FS 1N
4. The combined length of all branch lines must not exceed 36 ft. / Nrn" F
I. (10.9 m). See Figure 95. r /
5. A maximum of 22 flow numbers are allowed.
6. The requirements of the following table must not be exceeded. 1N
NOZZLE
IN
NOZZLE
V NOZZLE
2 FLOW APPLIANCE NOZZLE
(BRANCH LINES IN BOLD)
COMBINED LENGTH MUST NOT EXCEED 36 FT. (10.9 m)
FIGURE 95
Duct Plenum Appliance
Requirements Supply Line Branch Line Branch Line Branch Line
Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in.
Maximum Length 32 ft 8 ft. 4 ft. 12 ft.
(9.7 m) (2.4 m) (1.2 m) (3.7 m)
Maximum Rise 6 ft 4 ft. 2 ft. 2 ft
(1.8 m) (1.2 m) (.6 m) (.6 m)
Maximum 90° 8 4 4 6
Elbows
Maximum Tees 2 2 2 4
Maximum Flow 22 4 2 4
Numbers
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -52
REV.2 3 -1-04
DISTRIBUTION PIPING REQUIREMENTS (Continued)
Distribution Piping Requirements — 6.0 Gallon Manifolded • Distribution Piping Requirements — 6.0 Gallon System with
System (Continued) Independent Pipe Runs
This configuration consists of two 3 gallon tanks. Both tanks are Independent pipe runs can also be used with the regulated release
connected to a common manifold tee and are pressurized from a assembly and the tank/enclosure assembly. See Figure 97. When
single double tank (Part No. 73022) nitrogen cartridge in the reg- manifolding is not used, each of the two (2) 3 gallon tanks utilize
b. ulated release assembly. See Figure 96. Note: A tank mounting • the piping limitations of a single tank system.
bracket can be utilized instead of the tank/enclosure assembly.
► See Figure 98.
3/8 IN I ii] = \ \
BRANCH
3/8 IN 3/8 IN
SUPPLY SUPPLY
43 ,
SEE
USE HOSE/ ~ NOTE HOSE/ �}- -
GROMMET GROMMET �( — �
PACKAGE 1 1 -4— 3/8 IN BRANCH PACKAGE
(PART NO. SUPPLY W' (PART NO.
�
418511) '� i SUPPLY 418511) SEE . I
6 , NOTE
!
Mb-- 11111011V
111 III
1 III T _
r
3.0 3 0 3.0 GALLON 3.0 GALLON
GALLON GALLON 'E TANK TANK
I TANK TANK OR OR
L_ DOUBLE TANK
NITROGEN
1.5 GALLON 1.5 GALLON DOUBLE TANK
TANK TANK NITROGEN
CARTRIDGE OR CARTRIDGE OR
(LT A -101 -30 101-30 CO2
CARTRIDGE
CARTRIDGE–
REGULATED (LT- A- 101 -30
3.0 GALLON REGULATED RELEASE ACTUATOR ONLY) REGULATED RELEASE ASSEMBLY OR CARTRIDGE –
ASSEMBLY OR 3.0 GALLON REGULATED REGULATED ACTUATOR ASSEMBLY REGULATED
ACTUATOR ASSEMBLY • TANK/ENCLOSURE ACTUATOR ONLY)
ASSEMBLY
FIGURE 97
TANK/ENCLOSURE 000786
ASSEMBLY
NOTE 1: THE PIPE CONNECTION FROM TANK CENTER TO TANK
CENTER CANNOT EXCEED 8-1/2 IN. (21 5 cm). ALSO.
OEM RELEASE/BRACKET ASSEMBLY CAN BE UTILIZED
WHEN MANIFOLDING 3 0 GALLON TANK.
NOTE 2: ONLY 3 GALLON TANKS CAN BE MANIFOLDED.
► FIGURE 96
030272
SECTION IV - SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4-53
3 -1-04 REV.2
DISTRIBUTION PIPING REQUIREMENTS (Continued)
Distribution Piping Requirements - 9.0 Gallon System \ - 1
This optional configuration consists only of three 3- gallon tanks, all
pressurized from a single double -tank nitrogen cartridge with r(
• expellant gas hoses connected as shown in Figure 98. Tanks No. _� • }���
1 and No. 2 must be connected directly to the regulator with sep-
arate expellant gas hoses and Tank No. 3 must be connected to
• Tank No. 2 with a third expellant gas hose as shown in Figure 98.
Each tank must be connected to an independent distribution pip-
► ing network as shown in Figure 98. Distribution piping require-
ments for each network must be as follows:
1. The maximum length between the start of the first branch line
and the start of the last branch line must not exceed 24 ft .1•
(7.3 m). When the supply line is split, the combined total of
both legs of the supply the start of the first ft ❑ ❑
line to the start of f thethe last branch anch line) must not excceed d 24 24 ft
• (7.3 m). See Figure 94. t,
2. The total length of all branch lines must not exceed 36 ft. 3.0 3.0 ; 3.0
• (10.9 m). See Figure 94. GALLON GALLON GALLON
TANK TANK TANK
3. Use a 3/8 in. union to connect the tank adaptor to the 3/8 in. NO.3 NO.2 NO. 1
supply line.
4. A maximum of two nozzles are allowed per duct branch line.
5. When using this 9.0 gallon system configuration, no mani-
folding of distribution piping is allowed. TWO TANK ENCLOSURE 3 GALLON REGULATED DOUBLE TANK NITROGEN
ASSEMBLY PART NO. RELEASE ASSEMBLY, CARTRIDGE OR
6. When an ANSUL AUTOMAN Regulated Release is utilized in ► 430324 (INCLUDES (2) OR 3 GALLON LT- A- 101 -30 CARTRIDGE
configuration, additional regulator actuators cannot be
HOSES AND (2) REGULATED (REGULATED ACTUATOR
this confi
9 9 GROMMETS) ACTUATOR ASSEMBLY ONLY)
used. NOTE IF TWO TANK ENCLOSURE ASSEMBLY, PART NO. 430324, IS CONNECTED
7. Only 3 gallon tanks can be utilized in this configuration. TO THE 3 GALLON REGULATED RELEASE ASSEMBLY, NO ADDITIONAL
REGULATED ACTUATOR(S) ASSEMBLIES CAN BE USED.
8. The requirements of the following table must not be exceeded FIGURE 98
for each 3 gallon tank: C000e'
Duct Plenum Appliance
Requirements Supply Line Branch Line Branch Line Branch Line
Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in.
Maximum Length 40 ft. 8 ft. 4 ft. 12 ft
(12.2 m) (2.4 m) (1.2 m) (3.7 m)
Maximum Rise 6 ft 4 ft. 2 ft. 2 ft
(1.8 m) (1.2 m) (.6 m) (.6 m)
Maximum 90° 9 4 4 6
Elbows
Maximum Tees 1 2 2 4
Maximum Flow 11' 4 2 4
Numbers
*Exceptions:
• 1. Twelve (12) flow numbers are allowed in any tank not containing two-flow appliance nozzles. and/or, a 1N nozzle for wok or griddle protection, and/or, a 1F nozzle or a 1N nozzle
for range protection, and/or, a 3N nozzle for fryer protection.
2. Twelve (12) flow numbers are allowed in any one tank for duct and plenum protection ONLY
3. Twelve (12) flow numbers are allowed with any one tank using only two-flow appliance nozzles.
► 4. Twelve (12) flow numbers are allowed with any one tank using only three -flow appliance nozzles.
Special Instructions:
1. When four (4) Dean Industries Gil Gas Fryers are protected at low proximity as shown in Figure 59 on Page 4-32, the discharge piping must be as shown in Figure 59 on
Page 4-32.
2. For certain McDonald's applications. 11.5 flow numbers are allowed when using a combination of one (1) 2W duct nozzle, one (1) 1/2N electrostatic precipitator nozzle,
one (1) 1N plenum nozzle, and four (4) two-flow appliance nozzles. Contact Ansul Applications Engineering Department for additional information.
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -54
REV.2 3 -1-04
DETECTION SYSTEM REQUIREMENTS
Once the fire suppression system design has been determined, a Detector Placement Requirements
detection system design must be completed. This section contains EXHAUST DUCTS
guidelines and limitations for detection system installation.
Each exhaust duct must have at least one detector installed in the
Detector Identification duct entrance, located in the airstream of the cooking vapors, or at
The two types of detectors are distinguished from each other by a maximum of 20 fL (6.1 m) into the duct opening. See Figure 99.
their location in the detection system.
1. The Terminal Detector (Part No. 56838, 15375, or 417368) is
the last in a series of detectors, or the only detector used in a
single-detector system. This detector is thus named because _ '' `Fi`
it is at the point at which the wire rope ends, or "terminates."
2. A Series Detector (Part No. 56837, 15373, or 417369) is any I
detector located in -line between the regulated release mech-
anism and the terminal detector.
20 FT. (6 m)
Detector /Pulley Elbow Quantity MAXIMUM
The quantity of detectors used in the system will vary depending
on the style of detector used.
1. Conduit runs, pulley elbows, and number of detectors per sys-
tem must be within the approved system guidelines. The fol- 1
lowing requirements must not be exceeded:
Maximum Maximum Maximum
Number of Number of Length of 1/2 FI GURE 99
Detectors Elbows in. Condui
per System per System per System NOTICE
Clip on Style 12 18 125 ft. (38.1 m) When gas appliances are used and the flue
Detector gases from the burner are exhausted into the
Hinge Style 5 8 103 ft. (31.3 m) duct, the detector must be kept out of the air
Detector stream of these exhaust gases. These gases
Scissors Style 15 20 150 ft. (45.7 m) can be very hot and could actuate the system
Detector unnecessarily.
2. If hinge style detectors are mixed in a system with either dip- Duct openings that are long and narrow or large
on or scissor style, 4 series and 1 terminal is the maximum enough to require multiple duct nozzles may
number allowed. If dip-on style are mixed with scissor style, require additional detectors.
the maximum allowed is 11 series and 1 terminal. ELECTROSTATIC PRECIPITATOR
NOTICE If an electrostatic precipitator is located at or near the base of the
When using the "clip -on" style detector, the ter- exhaust duct, it is necessary to locate a detector below the pre -
minal detector may use the "hinged° style cipitator, at the base of the duct, and also locate one in the duct,
mounting bracket with the "clip-on" style linkage. • just above the precipitator. See Figure 100.
This is only allowed with the terminal detector. When installing the detector bracket and system conduit, make
No other linkages are allowed to be mixed certain they do not interfere with the operation of the precipitator.
with other brackets. When using this option,
the total number of "clip-on" style detectors (11
series and 1 terminal) is still allowed.
3. If hinge style detectors are mixed in a system with either dip -
on or scissor style, the maximum length of wire rope must not
exceed 103 ft. (31.4 m) and the maximum number of pulley \
elbows must not exceed 8. If dip-on style are mixed with scis-
sor style, the maximum length of wire rope must not exceed
125 ft. (3.81 m) and the maximum number of pulley elbows
must not exceed 18. rfr
4. If the hazard requires more than 15 detectors, up to five 101
Remote Releases (Part No. 12029) can be used for system
actuation. Each 101 remote release allows the use of a maxi-
mum of 15 "scissor" style detectors (14 series and 1 terminal) I
for a total of 75 detectors if needed.
FIGURE 100
000268
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -55
3 -1 -04 REV. 2
Detector Replacement Requirements (Continued)
COOKING APPLIANCES
If the cooking appliance is located under an exhaust duct where a
detector has been mounted, it is normally not necessary to utilize
another detector for that cooking appliance, provided the detector
• is not more than 12 in. (30 cm) into the duct. See Figure 101.
�^ c
fTSI
I
APPLIANCE APPLIANCE APPLIANCE APPLIANCE
REQUIRES COVERED BY COVERED BY REQUIRES
SEPARATE DETECTOR DETECTOR SEPARATE FIGURE 102
DETECTOR UNDER DUCT UNDER DUCT DETECTOR 000270
Fusible Link Selection
FIGURE 101 When possible, temperature readings should be taken at each
°D026' detector location to determine correct fusible link temperature rat-
ing. Temperature can be recorded using either a maximum regis-
Each cooking appliance with a continuous cooking surface not tering thermometer, Part No. 15240, temperature tape or any other
exceeding 48 in. x 48 in. (122 x 122 cm) can be protected by a accurate thermometer.
minimum of one detector. Cooking appliances with a continuous
cooking surface exceeding 48 in. x 48 in. can be protected by at » O
least one detector per 48 in. x 48 in. cooking area. Detectors
► used for cooking appliances must be located above the protected O
appliance toward the exhaust duct side of the appliance. The
TEMPERATURE RATING
detector should be located in the air stream of the appliance to
enhance system response time. O STAMPED ON FUSIBLE
• Note: For overlapping detector coverage, see Page 4-43 for C7 B LINK BODY
► design requirements. O � f
Detection Line Requirements •
CONDUIT K STYLE X170 ML STYLE 000177
500 °F (260 °C) ONLY
Rigid conduit or 1/2 inch EMT thin -wall conduit may be used.
Standard steel conduit fittings (compression type are recommend-
ed) must be employed to properly install the detection system. All ' FIGURE 103
conduit or pipe must be firmly supported. When using pipe, make Select correct UL Listed fusible link(s) for installation in detector(s)
certain that all ends are carefully reamed, deburred and blown according to the temperature condition. Two styles are available.
clear of chips and scale before assembly. See Figure 103. See Component Section for detailed temperature
NOTICE • ratings.
The conduit offset can be used at the top or bot-
tom of the regulated release to change direction
of the conduit The conduit offset cannot be
used with pulley tees. All other changes in direc-
tion must be made by using Ansul approved pul-
ley elbows, Part No. 423254 or 415670. See
Figure 102.
SECTION IV — SYSTEM DESIGN
UL EX. 3470 ULC CEx747 Page 4 -56
REV.2 3 -1 -04
fJIANUAL PULL STATION REQUIREMENTS Metal Stamped Style — Part No. 4835 or 54011
A remote manual pull station allows the R -102 system to be man- Parts that may be used for installation of a metal stamped remote
ually operated at some point distant from the regulated release manual pull station are:
assembly. The pull station should be installed at a maximum Description Part No.
height of 60 in. (152 cm) and located in the path of exit. The pull Remote Manual Pull Station Assembly* 54011
station is the only source of manual actuation of the regulated Remote Manual Pull Station Assembly 4835
release assembly. Pulley Elbow 423250
The total length of the cable used for each manual pull station Pulley Elbow 415670
within a system must not exceed 150 ft. (46 m). Pulley Tee 427929
The maximum number of pulley elbows that may be used per pull Assembly includes parts listed below:
station is 20. 1/16 in. Stainless Steel Cable 50 ft. (15 m) 15821
Oval Press - To-Crimp Sleeves 4596
One pulley tee, Part No. 427929, is allowed per system. Glass Break Rod (1) 4834
The maximum length of cable from the AUTOMAN to a pull station
is 150 ft. (45.7 m) with a maximum of 20 pulley elbows used per MECHANICAL GAS VALVE REQUIREMENTS
side of the tee. As the tee is located farther from the AUTOMAN, An Ansul or Ansul approved mechanical gas shut -off valve system
the 150 ft. (45.7 m) maximum must be observed but as pulley can be attached to the R -102 system. The system works both
elbows are placed between the AUTOMAN and the tee, they must mechanically and pneumatically by use of an air cylinder located
be deducted from the available pulley elbows (20) allowed on each inside the regulated release assembly. Upon actuation of the fire
side. suppression system, a pneumatically- operated air cylinder assem-
Example: If 10 pulley elbows are placed between the AUTOMAN bly will mechanically close the gas shut -off valve.
and the pulley tee, the maximum available pulley elbows left for The total length of the cable for each mechanical gas valve must
• use on each side of the tee is 10 per side. See Figure 104 for three not exceed 150 ft. (46 m). The maximum number of pulley elbows
different examples. (Note: Both must be gas valves or both must that may be used is 20 for each valve.
be pull stations. Mixing is not allowed.)
One pulley tee (Part No. 427929) is allowed per system.
TEE CLOSE TO AUTOMAN (EXAMPLE) The maximum length of cable from the AUTOMAN to a gas valve is
PULLEY TEE 150 ft. (45.7 m) with a maximum of 20 pulley elbows used per side
of the tee. As the tee is located farther from the AUTOMAN, the
(3 05 5 mm) 150ft. (45.7 m) maximum must be observed but as pulley elbows
(3
are placed between the AUTOMAN and the tee, they must be
deducted from the available pulley elbows (20) allowed on each
side.
GAS O vE OR AUTOMAN o AVVE OR Example: If 10 pulley elbows are placed between the AUTOMAN
MANUAL PULL MANUAL PULL • and the pulley tee, the maximum available pulley elbows left for
149 FT. (45.4 m) AND 20 PULLEY ELBOWS MAXIMUM use on each side of the tee is 10 per side. See Figure 104 for three
PER EACH SIDE OF TEE different examples.
TEE CLOSE TO GAS VALVES OR MANUAL PULL (EXAMPLE) Parts that may be used for installation of a Mechanical Gas Shut-
off Valve are:
12 IN. 12 IN. Description Part No
(305 mm) (305 mm) Gas Valve /Actuator 3/4 in. Assembly ( Ansul); 55598
0 PULLEY TEE 0 Gas Valve /Actuator 1 in. Assembly ( Ansul)' 55601
GAS VALVE OR GAS VALVE OR Gas Valve /Actuator 1 1/4 in. Assembly ( Ansul)' 55604
MANUAL PULL MANUAL PULL Gas Valve /Actuator 1 1/2 in. Assembly (Ansel)' 55607
AUTOMAN Gas Valve /Actuator 2 in. Assembly ( Ansul)* 55610
149 FT. (45.4 m) AND 20 PULLEY ELBOWS BETWEEN Gas Valve /Actuator 2 1/2 in. Assembly (ASCO)' 25937
AUTOMAN AND TEE Gas Valve /Actuator 3 in. Assembly (ASCO)` 25938
Pulley Elbow 423250
TEE HALFWAY BETWEEN AUTOMAN AND GAS VALVES OR MANUAL PULL (EXAMPLE) Pulley Elbow 415670
75 FT. (22.9 m) AND 10 PULLEY ELBOWS Pulley Tee 427929
1/16 in. Stainless Steel Cable 15821 or
50 ft. (15 m) or 500 ft. (152 m) roll 79653
75 FT. (22.9 m) AND 75 FT. (22.9 m) AND Oval Press - To-Crimp Sleeve 4596
10 PULLEY ELBOWS 10 PULLEY ELBOWS Stop Sleeve (2) 26317
PULLEY TEE �y •Assembly includes parts listed below..
AUTOMAN V Air Cylinder Assembly 15733
GAS VALVE OR GAS VALVE OR Air Cylinder 15521
MANUAL PULL MANUAL PULL
Tubing Assembly 15529
FIGURE 104 Copper Tubing, 1/8 in. 15525
• 034907 Male Elbow 15523
Male Connector 15522
Machine Screw (2) 15421
Hex Nut (2) 15527
Lockwasher (2) 4141
Visual Inspection Seal (2) 197
SECTION IV — SYSTEM DESIGN
► UL EX. 3470 ULC CEx747 Page 4 -57
3 -1 -04
MECHANICAL GAS VALVE REQUIREMENTS (Continued) Description Part No.
All valves above are UL listed and approved. They may be mount- Electric Solenoid Valve, 3/4 in. NPT' 13707
ed in any position. Pipe threads are type NPT. Ambient operating Electric Solenoid Valve, 1 in. NPT* 13708
temperature range of all valves is 32 °F to 120 °F (0 °C to 49 °C). Electric Solenoid Valve, 1 1/2 in. NPT* 13709
The valves are not weatherproof and must be located indoors in Electric Solenoid Valve, 2 in. NPT* 13710
areas approved by the "authority having jurisdiction." Electric Solenoid Valve, 3 in. NPT' 17643
Manual Reset Relay (110 VAC) 14702
ELECTRICAL GAS VALVE REQUIREMENTS 'Valves are normally closed when de-energzed.
A UL Listed electrically- operated gas shut -off valve can be ALARM INITIATING SWITCH REQUIREMENTS
attached to the R -102 system to provide an electrical means of
shutting off the gas line at a predetermined point. If an electric gas The Alarm Initiating Switch can be field mounted within the ANSUL
shut -off valve is used in the system it must be attached with both AUTOMAN release. The switch must be used to close a super -
an electric (snap- action) switch and a manual reset relay. For vised circuit to the building main fire alarm panel when the ANSUL
more information on the types of electric (snap - action) switches, AUTOMAN release actuates. This action will signal the fire alarm
refer to the Electrical Switch, Field Installation section. The manu- panel that there was a system actuation in the kitchen area. The
al reset relay is reviewed in this section. switch kit contains all necessary mounting components along with
All electrical connections should be performed by a QUALIFIED a mounting instruction sheet.
ELECTRICIAN and in accordance with authority having The switch is rated 50 mA, 28VDC.
jurisdiction. Part No. Description
The following is a brief explanation of how the R -102 system oper- 428311 Alarm Initiating Switch Kit
ates with an Electric Gas Shut -off Valve attached:
With the regulated release cocked in the ready condition, the nor- ELECTRICAL SWITCH REQUIREMENTS
mally closed contacts in the snap -action switch allow current to The electric (snap - action) switches for the R -102 system are spe-
flow to the manual reset relay. With the relay coil energized, nor - dally designed to fit the regulated release assembly. The switches
mally open contacts in the reset relay close, allowing the solenoid are intended for use with electric gas valves, alarms, contactors,
in the gas valve to be energized. lights, contractor supplied electric power shut -off devices, and
Once the R -102 system is activated, the normally closed contacts other electrical devices that are designed to shut off or turn on
in the snap -action switch will open, de- energizing the reset relay. when the fire suppression system is actuated. (See Figures
This will, in turn, open the contacts in the relay which will cause the • 105 through 107 for reference.)
gas valve to become de- energized and close. Contractors shall supply "UL listed, enclosed industrial control
The system must be re -armed and the "push to reset" button on equipment or magnetic switch having a rating matching that of the
the reset relay must be operated to reopen the gas valve. cooking appliance, coil 110 VAC /60 Hz or 24 VAC /60 Hz."
It is important to note that a power failure or an electrical power All electrical connections should be performed by a QUALIFIED
interruption will cause the gas valve to close even though the sys- ELECTRICIAN and in accordance with authority having
tem was not fired. jurisdiction.
In either case, whether in a fired condition or when a power failure Electric (Snap - Action) Switches that may be field installed are:
has occurred, the manual reset relay and electric gas shut -off Part No. Description
valve must be reset to resume a normal operating condition. For 423878 One Switch Kit
resetting, refer to the "Recharge and Resetting Procedures" 423879 Two Switch Kit
section in this manual. 423880 Three Switch Kit
Approvals 423881 Four Switch Kit
Ansul gas valves listed in this section are UL listed and approved Each switch has a set of single -pole, double throw contacts rated
for 110 VAC. If more information is required, refer to the Gas and at 21 amp, 1 HP, 125, 250, 277 VAC or 2 HP, 250, 277 VAC.
Oil Equipment List of Underwriters Laboratories, Inc. under NOTE: A relay must be supplied by others if the equipment load
"Electrically Operated Valves Guide No. 440 A5" or consult Ansul exceeds the rated capacity of the switch.
Incorporated, Marinette, Wisconsin 54143 -2542. Electrical wiring and equipment shall be installed in accordance
If other gas valves are used, they shall be "UL listed electrically- with NFPA 70 (National Electrical Code) or the requirements of the
operated safety valves for natural or LP gas as required, of appro- authority having jurisdiction.
priate pressure and temperature rating, 110 VAC /60 Hz." The If a fire alarm system is provided, the fire extinguishing system
information on temperature and type of gas that the valves are shall be connected to the alarm system in accordance with the
suitable for may be found in the Gas and Oil Equipment List of requirements of NFPA 72, National Fire Alarm Code, so that the
Underwriters Laboratories, Inc. under "Electrically Operated actuation of the extinguishing system will sound the fire alarm as
Valves Guide No. 440 A5." well as provide the extinguishing function of the system.
The electrically operated gas valve must be of the type that needs If supervision of the electrical detection, electrical actuation or
to be energized to remain open. electrical power supply circuit is provided, it shall give prompt audi-
Parts that may be used for installation of a 110 VAC Gas Shut -off ble or visual indication of trouble and shall be distinctive from
Valve are: alarms or indicators indicating operation or hazardous conditions
as specified in NFPA 17A.
•
SECTION IV — SYSTEM DESIGN
► UL EX. 3470 ULC CEx747 Page 4 -58
3 -1 -04
ELECTRICAL SWITCH REQUIREMENTS (Continued)
Electric (110 VAC /60 Hz) Gas Shut -off Valve
INSTALLATION OVERVIEW
POWER - +I 0 MANUAL RESET
SOURCE i 0 RELAY
ELECTRIC II
SNAP- ACTION
SWITCH
-.C=1) MI 1 0111J ELECTRIC GAS VALVE
JUNCTION BOXES
(NOT SUPPLIED BY ANSUL) -
V P
WIRING SCHEMATIC
WIRING SCHEMATIC — RELAY PART NO. 426151
BLACK
ANSUL SNAP - ACTION SWITCH
(SWITCH CONTACTS SHOWN WITH ANSUL RED
AUTOMAN IN THE COCKED POSITION) BROWN
I �
I RESET POWER I
INDICATOR
GND I
I r I
I A 1B SCREWI 5
L2 NEUTRAL
L1 HOT 110 VAC /60HZ
RELAY COIL
6
3
3
i 4
I 7
1
MANUAL RESET RELAY
I (PART NO. 426151)
ELECTRIC RATING - -
113 HP, 10 Amp, 120 VAC GAS VALVE
112 HP, 10 Amp, 240 VAC SEE NOTE 3 002462
NOTE: 13 Amp, 28 VDC
1. DENOTES FIELD INSTALLATION
DENOTES FACTORY INSTALLATION. FIGURE 105
3 CONTRACTORS.' UL LISTED ENCLOSED INDUSTRIAL CONTROL EQUIPMENT OR MAGNETIC SWITCH HAVING A RATING MATCHING
• THAT OF THE COOKING APPLIANCE COIL, 110V/60I
4. DO NOT USE BLACK WIRE ON SNAP - ACTION SWITCH IN NORMAL INSTALLATION BLACK WIRE TO BE USED ONLY
FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC.
•
SECTION IV – SYSTEM DESIGN
► UL EX. 3470 ULC CEx747 Page 4-59
3 -1 -04
ELECTRICAL SWITCH REQUIREMENTS (Continued)
Electric (110 VAC /60 Hz) Application with Customer Supplied Contactor and Heating Element Load
INSTALLATION OVERVIEW
POWER O 1 MANUAL RESET
SOURCE O RELAY
m ;
ELECTRIC I
(" SNAP ACTION
C `
SWITCH
CONTACTOR
�/� (CUSTOMER SUPPLIED)
JUNCTION BOX /
..r , L r (NOT SUPPLIED BY �`-
POWER ON-OFF
SWITCH
(CUSTOMER SUPPLIED)
1---- --y 0 ] ,--i
030276
WIRING SCHEMATIC
WIRING SCHEMATIC – RELAY PART NO. 426151
r--- BLACK
__ RED
- -_ BROWN
ANSUL SNAP - ACTION SWITCH
(SWITCH CONTACTS SHOWN WITH ANSUL
AUTOMAN IN THE COCKED POSIION)
r - - - - - -- RESET POWER --
I
INDICATOR
I illti GND
1
-L
A , B SCREW 5
RELAY COIL 1111al 12 NEUTRAL
6 •
L7 HOT 110 VAC/60HZ
9
3 0111111 •
4
7
1 • • CONTACTOR (CUSTOMER SUPPLIED)
I r 1
I I —+ • 1 r 1 POWER ON -OFF SWITCH
MANUAL RESET RELAY I l I I I (CUSTOMER SUPPLIED)
(PART NO. 426151) I I I I I
--- - - - - -- - - -� L - J I 1
ELECTRIC RATING .5-- 0 1' - • TO POWER SUPPLY
1/3 HP, 10 Amp, 120 VAC TO HEATING
NOTE L
1/2 HP, 10 Amy, 240 VAC ELEMENT LOAD + - -J - 220V/440V
1. DENOTES FIELD INSTALLATION. 13 Amp, 28 VDC oozasn
2. DENOTES FACTORY INSTALLATION.
3. GAS VALVES: 'UL LISTED ELECTRICALLY -OPERATED SAFETY VALVE FOR NATURAL, OR LP GAS AS NEEDED OF APPROPRIATE PRESSURE AND TEMPERATURE RATING,
110V/60 HZ' OR ANSUL GAS VALVES, PART NUMBERS 13707, 13708, 13709, 13710, AND 17643.
4. DO NOT USE BLACK WIRE ON SNAP-ACTION SWITCH IN NORMAL INSTALLATION. BLACK WIRE TO BE USED ONLY FIGURE 106
• FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC.
•
SECTION IV — SYSTEM DESIGN
• UL EX. 3470 ULC CEx747 Page 4-60
3 -1 -04
ELECTRICAL SWITCH REQUIREMENTS (Continued)
Electric (110 VAC /60 Hz) Application with Customer Supplied Contactor and Heating Element Load, and Power Supply Switch
INSTALLATION OVERVIEW I
POWER —I O MANUAL RESET
SOURCE 3- 0 RELAY
• ELECTRIC
SNAP - ACTION SWITCH OR
SWITCH THERMOSTAT — - G
.�/ (CUSTOMER SUPPLIED)
JUNCTION BOX
(NOT SUPPLIED BY ANSUL) r j
L CONTACTOR
(CUSTOMER SUPPLIED)
--R E 3 v
WIRING SCHEMATIC
WIRING SCHEMATIC — RELAY PART NO. 426151
-- BLACK
RED
ANSUL SNAP - ACTION SWITCH BROWN
(SWITCH CONTACTS SHOWN WITH ANSUL — — —
AUTOMAN IN THE COCKED POSmON)
RESET POWER I
INDICATOR I
•
GND
r )
A B IAA
L2 NEUTRAL
RELAY COIL 110 VAC/60HZ
L1 HOT
9
3
4 — rep--
7 -
1 1
• -J CONTACTOR
I I SWITCH OR THERMOSTAT (CUSTOMER SUPPLIED)
MANUAL RESET RELAY I (CUSTOMER SUPPLIED) r
L (PART NO. 426151) I
i_1
ELECTRIC RATING
1/3 HP, 10 Amp, 120 VAC
112 HP, 10 Amp, 240 VAC TO HEATING s TO POWER SUPPLY
13 Amp, 28 VDC ELEMENT LOAD r
220V/44DV
002481
NOTE
1. DENOTES FIELD INSTALLATION.
2. DENOTES FACTORY INSTALLATION.
3. CONTRACTORS:' UL LISTED ENCLOSED INDUSTRIAL CONTROL EQUIPMENT OR MAGNETIC SWITCH HAVING A RATING MATCHING THAT OF THE
COOKING APPLIANCE COIL, 110V /60HZ"
■ 4 DO NOT USE BLACK WIRE ON SNAP - ACTION SWITCH IN NORMAL INSTALLATION. BLACK WIRE TO BE USED ONLY FIGURE 107
FOR EXTRANEOUS ALARM, LIGHT CIRCUITS, ETC.
r i tt r - 3 r.. : ,, f y - • ; :r r Tyco SAFELY KM.= VI ANSUL • -•• r QE SfAMW B 5 $T
� u etm 414 3-2542
wamansticom
GENERAL BULLETIN NO. 4927
DATE: ' February 18, 2005
TO: AU Authorized R -102TM Restaurant System Distributors and OEMs
FROM: Mark Neumann — Marketing Manager, Commercial Suppression
SUBJECT: New Salamander Broiler Protection for R-102 TM Restaurant Fire Suppression Systems
Salamander broilers are now standard appliances in most commercial restaurants. As such, we are
pleased to offer a convenient new protection design using the R -102 Restaurant Fire Suppression
System. .
This new design is UL Listed under UL EX 3470 and ULC CEx747 and will be added to the R - 102
Design Manual (Part No. 418087) at next reprint.
Salamander Broiler Protection
The R -102 Restaurant Fire Suppression System uses one 1N Nozzle (Part No. 419335) for
salamander broiler protection. The nozzle tip is stamped with 1N indicating that this is a one -flow
nozzle.
One 1N nozzle will protect a maximum hazard area (internal broiler chamber) of 16 in. (41 cm) deep
x 29 in. (74 cm) wide.
The single 1N nozzle must be located directly in line with either vertical edge of the broiler opening,
6 in. (15 cm) to 12 in. (30 cm) in front of the broiler, and 0 in. to 12 in. (30 cm) above the top of the
broiler. The nozzle must be aimed at the center of the broiler opening. See Figure.
O 'a`f —••••
OPENING : IN NOME
�- -(RAFT NO. 419335)
-4--NOME LOCATION ZONE
•.A•••
12 IN- "" NAwa•■ 6 P
6649n9•• 1
L �
(15 an)
filj
/
• AOI AT cenat OF
AN AT CENTER OF BROKER OPENING
OQ/126
UL EX3470