Fire & Bui1din
g._N_V)
Product CENTRAL
. Customer Service /Sales:
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791- 55g- �1: (2` 5) 362 -0700 / (800) 523 -6512
� �� A � i �� � ®� Fax: (215) 362-5385
A. 0
Series TY -FRB — 2.8, 4.2, ,_ ` . S8 .0 K- factor
Upright, Pendent, and Re 'essed Pendent Sprinklers
Quick Response, Standard Coverage
General mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli- - -
Description cable approval agencies, the testing is .. ., '
not representative of all possible cor- - ,
- The Series TY-FRB, 2.8, 4.2, 5.6, and rosive atmospheres. Consequently, it � "
8.0 K- factor, Upright and Pendent is recommended that the end user be
It f' Sprinklers described in this data sheet consulted with respect to the suitability i
are quick response - standard cover- of these coatings for any given corro-
age, decorative 3 mm glass bulb type sive environment. The effects of ambi- , • 'F
spray sprinklers designed for use in ent temperature, concentration of 4
light or ordinary hazard, commercial chemicals, and gas /chemical velocity, _ — - t•-+;-„0-
occupancies such as banks, hotels, should be considered, as a minimum,
shopping malls, etc. along with the corrosive nature of the ,
The recessed version of the Series chemical to which the sprinklers will be
TY-FRB Pendent Sprinkler, where ap- exposed. ....„,...m.,`
plicable, is intended for use in areas An intermediate level versions of the `
with a finished ceiling. It uses either a Series TY-FRB Pendent Sprinklers are
two -piece Style 10 (1/2 inch NPT) or detailed in Technical Data Sheet ,7�
Style 40 (3/4 inch NPT) Recessed Es- TFP356, and Sprinkler Guards are de-
cutcheon with 1/2 inch (12,7 mm) of tailed in Technical Data Sheet TFP780 l j
recessed adjustment or up to 3/4 inch /
(19,1 mm) of total adjustment from the WARNINGS dt-
flush pendent position, or a two -piece The Series TY -FRB Sprinklers de- , -< r
Style 20 (1/2 inch NPT) or Style 30 (3/4 scribed herein must be installed and - `'a-;
inch NPT) Recessed Escutcheon with maintained in compliance with this ..r._,1' •
1/4 inch (6,4 mm) of recessed adjust- document, as well as with the applica-
ment or up to 1/2 inch (12,7 mm) of ble standards of the National Fire Pro -
total adjustment from the flush pen- tection Association, in addition to the TY3231 - Pendent 5.6K, 1/2 "NPT
TY41 31 - Upright
dent position. The adjustment provided standards of any other authorities hay- 8.0K, 3 /4'NPT
by t he Recessed Escutcheon reduces ing jurisdiction. Failure to do so may TY4231 - Pendent 8.0K, 3/4 NPT
the accuracy to which the fixed pipe impair the performance of these de-
drops to the sprinklers must be cut. vices. Technical
Corrosion resistant coatings, where The owner is responsible for maintain -
applicable, are utilized to extend the ing their fire protection system and de- Data
life of copper alloy sprinklers beyond vices in proper operating condition.
that which would otherwise be ob- The installing contractor or sprinkler Approvals
tained when exposed to corrosive at- manufacturer should be contacted UL and C -UL Listed.
with any questions. FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
IMPORTANT information including corrosion resis-
Always refer to Technical Data tant status.)
Sheet TFP70D for the INSTALLER Model /Sprinkler
WARNING" that provides cautions Maximum Working Pressure
with respect to handling and instal- Identification 175 psi (12,1 bar)
lation of sprinkler systems and com- Discharge Coefficient
ponents. Improper handling and in- Numbers K = 2.8 GPM /psi (40,3 LPM/bar
stallation can permanently damage K = 4.2 GPM /psi (60,5 LPM/barl'
a sprinkler system or its compo- TY1131 - Upright 2.8K, 1/2"NPT K = 5.6 GPM /psi (80,6 LPM/barl'
vents and cause the sprinkler to fail TY1231 - Pendent 2.8K,1/2 "NPT K = 8.0 GPM /psi (115,2 LPM /bar /
to operate in a fire situation or cause TY2131 - Upright 4.2K, 1/2"NPT Temperature Ratings
it to operate prematurely. TY2231 - Pendent 4.2K, 1/2"NPT Refer to Table A and B
TY3131 - Upright 5.6K, 1/2"NPT
Page 1 of 8 JULY, 2004 TFP171
Page 2 of 8 TFPI 71
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING ** NOMINAL RECESSED
SURFACE N /2' MAKE -IN ESCUTCHEON DEFLECTOR
PT
t mt.! j'T 6
97 i' iITl* T�
M=M- 1= 5
7/1 m
(57,2 I (11,1 mm) li
4
1 NOMINAL
Am s_ �1� MAKE -IN 2
" • 1-9/16 I1 Jr 2 3/16„ .,\� 3
ill (39,7 mm) WRENCH 1 (55,6 mm) it
FLATS _ 0: a 1
- 410M4
SSP DEFLECTOR * 2 -7/8" (73,0 mm) DIA. -1 1/2° NPT ** t
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw ** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING ** NOMINAL RECESSED
SURFACE 1/2° MAKE -IN ESCUTCHEON SSU
NPT I DEFLECTOR
6
i .
r 7/16 " ° � 5
2 -3/16" - lorm ( mm
(55,6 mm) 1 =1 W mi NOMINAL 4
1 W 1 p 7t MAKE -IN ,'
1-1/2° I 4I I ` 2 -3/16" �ti 1 0 2
(38,1 mm)
WRENCH 1 (55,6 mm) 0
1 - -- _ . - - ., III FLATS i 3
1
SSP DEFLECTOR * 2-7/8° (73,0 mm) DIA. --, 1/2° NPT ** f i 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K- FACTOR, 1/2 INCH NPT
Y
Finishes Bulb Glass a
Sprinkler: Refer to Table A and B Compression Screw Bronze Operation
Recessed Escutcheon: White Coated, Deflector . . . . . Copper /Bronze
Chrome Plated, or Brass Plated Bushing (K =2.8) Bronze The glass Bulb contains a fluid which m
expands when exposed to heat. When a
Physical Characteristics the rated temperature is reached, the is
Y fluid expands sufficiently to shatter the
F
cc
rame Bronze glass Bulb, allowing the sprinkler to c
Button Brass /Copper activate and water to flow. a
Sealing Assembly ?
Beryllium Nickel w/Teflont
TFP171 Page 3 of 8
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING 1/2° ** NOMINAL RECESSED SSU*
SURFACE NPT MAKE IN ESCUTCHEON DEFLECTOR
r 7/16" 11! 5
2- 3/16" �� -
-
} A
(55,6 mm) � 1I p i NM A� ( 11,OMINAAKE -IN L 1 mm) � � I 1 /2" Ill
(38,1 III 1 2- 3/16" 41 � 2
F LATS
(55,6 mm) 3
i i ---.,....... Pi 1
SSP DEFLECTOR * — 2 -7/8" (73,0 mm) DIA. 1/2" NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw ** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2° (12,7 mm) STYLE 30 or 40
PLATE SEATING ** NOMINAL RECESSED SSU*
SURFACE MAKE-IN ESCUTCHEON DEFLECTOR
? 6*
�'rrrp � ;'sTT1%15,'
.3. 5
2 -5/16°
1/2" iii
'r (12,7 mm)
(58,7 mm) �� -- I NOMINAL
i I 4
�1� MA KE -IN II 1- 9/16" I mg 2 -1/4" y k 2
(39,7 mm) I WRENCH (57,2 OP
. II FLATS 3
SSP DEFLECTOR * - 2 -7/8° (73,0 mm) DIA. - �+ 3/4" NPT ** 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw ** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
Listing is based on the requirements of
Design NFPA 13, and FM Approval is based Installation
on the requirements of FM's Loss Pre-
Criteria
vention Data Sheets ). Only the Style The Series TY-FRB Sprinklers must be
10, 20, 30, or 40 Recessed Escutch- installed in accordance with the follow -
The Series TY-FRB Pendent and Up- eon, as applicable, is to be used for ing instructions:
right Sprinklers are intended for fire recessed pendent installations.
protection systems designed in ac- NOTES
cordance with the standard installation Do not install any bulb type sprinkler if
rules recognized by the applicable the bulb is cracked or there is a loss of
Listing or Approval agency (e.g., UL liquid from the bulb. With the sprinkler
1
Page 4 of 8 TFP171
SPRINKLER FINISH (See Note 7) inch NPT sprinkler joint should be of)-
tained with a torque of 10 to 20 ft lbs.
K TYPE TEMP. BULB NATURAL CHROME WHITE .,. (13,4 to 26,8 Nm). A maximum of 30
LIQUID BRASS PLATED POLYESTER ft.lbs. (40,7 Nm) of torque is to be used
135 °F /57 °C Orange to install sprinklers with 3/4 NPT con -
PENDENT nections. Higher levels of torque may
155 °F /68 °C Red distort the sprinkler inlet and cause
(TY1231) 1, 2, 3, 5 leakage or impairment of the sprinkler.
and 175 °F /79 °C Yellow
UPRIG UPRIGHT Do not attempt to make -up for insuffi-
H T 200 °F /93 °C Green cient adjustment in the escutcheon
2.8 286 °F /141 °C Blue plate by under- or over - tightening the
1/2" sprinkler. Readjust the position of the
NPT 135 °F /57 °C Orange sprinkler fitting to suit.
RECESSED 155 °F /68 °C Red
PENDENT The Series TY -FRB Pendent and Up-
(TY1231)• 175 °F /79 °C Yellow right Sprinklers must be installed in
Figure 5 200 °F /93 °C Green 1, 2, 5 accordance with the following instruc-
tions.
135 °F /57°C Orange Step 1. Pendent sprinklers are to be
RECESSED Red installed in the pendent position, and
PENDENT upright sprinklers are to be installed in
(TY1231)** 175 °F /79 °C Yellow the upright position.
Figure 6 200 °F /93 °C Green Step 2. With pipe thread sealant ap-
135 °F /57 °C Orange plied to the pipe threads, hand tighten
PENDENT the sprinkler into the sprinkler fitting.
155 °F /68 °C Red
(TY2231) Step 3. Tighten the sprinkler into the
and 175 °F /79 °C Yellow sprinkler fitting using only the W -Type
UPRIGHT 200 °F /93 °C Green 6 Sprinkler Wrench (Ref. Figure 13).
4 2 (TY2131) With reference to Figures 1, 2, 3, and
286 °F /141 °C Blue 2 4, the W -Type 6 Sprinkler Wrench is to
1/2° be applied to the sprinkler wrench
NPT 135 °F /57 °C Orange flats.
RECESSED 155 °F /68 °C Red
PENDENT
(TY2231)* 175 °F /79 °C Yellow The Series TY -FRB Recessed Pen -
Figure 7 200°F/93°C Green dent Sprinklers must be installed in
accordance with the following instruc-
135°F/57°C Orange tions.
RECESSED 155 °F /68 °C Red Step A. After installing the Style 10.
PENDENT 20, 30, or 40 Mounting Plate, as appli-
(TY2231)** 175 °F /79 °C Yellow cable, over the sprinkler threads and
Figure 8 200 °F /93 °C Green with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
NOTES: kler into the sprinkler fitting.
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. Step B. Tighten the sprinkler into the
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response sprinkler fitting using only the W -Type
Sprinklers. 7 Recessed Sprinkler Wrench (Ref.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin- Figure 14 ) With reference to Figure 1,
klers.
5. Approved by the City of New York under MEA 354 -01 -E. 2, 3, and 4, the W -Type 7 Recessed
7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- Sprinkler Wrench is to be applied to
kiers are UL and C -UL Listed as Corrosion Resistant Sprinklers. the sprinkler wrench flats.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4° Total Adjustment Step C. After the ceiling has been in-
Recessed Escutcheon, as applicable. stalled or the finish coat has been ap-
Installed with Style 20 (1/2° NPT) or Style 30 (3/4° NPT) 1/2° Total Adjustment plied, slide on the Style 10, 20, 30, or
Recessed Escutcheon, as applicable. 40 Closure over the Series TY FRB
* ** Frame and Deflector only. Listings and approvals apply to color (Special Order). Sprinkler and push the Closure over
N /A: Not Available p p
the Mounting Plate until its flange
TABLE A comes in contact with the ceiling.
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K- FACTOR SPRINKLERS
held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint
should be present. The diameter of the should be obtained with a torque of 7
air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi -
(1,6 mm) for the 135 °F /57 °C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque
inch (2,4 mm) for the 286 °F /141 °C may be used to install sprinklers with
temperature ratings. 1/2 NPT connections. A leak tight 3/4
TFP171 Page 5 of 8
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL CHROME WHITE*** LEAD
LIQUID BRASS PLATED POLYESTER COATED
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5
and 175 °F /79 °C Yellow
UPRIGHT 200 °F /93 °C Green
5.6 (TY3131)
286 °F /141 °C Blue
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 4, 5 N/A
(TY3231)* 175 °F /79 °C Yellow
Figure 9 200 °F /93 °C Green
135 °F /57°C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A
(TY3231)** 175"F179°C Yellow
Figure 10 200 °F /93 °C Green
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY4231)
and 175 °F /79 °C Yellow 1, 2, 5
1,2,3,4,5,6,7
UPRIGHT 200 °F /93 °C Green
8.0 (TY4131)
286 °F /141 °C Blue
3/4"
NPT 135 °F /57 °C Green
RECESSED 155 °F /68 °C Orange
PENDENT 1, 2, 4, 5
N/A
(TY4231)* 175 °F /79 °C Red
Figure 11 200 °F /93 °C Yellow
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4231)** 175 °F /79 °C Yellow
Figure 12 200 °F /93 °C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building - Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53 -428- 3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4° NPT) 3/4° Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2° NPT) or Style 30 (3/4° NPT) 1/2° Total Adjustment Recessed Escutcheon, as applicable.
* ** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K- FACTOR SPRINKLERS
Page 6 of 8 TFP171
2 -7/8° DIA. 2 -7/8° DIA
(73,0 mm)
5/811/4° 3/4° (19,1 mm) 1!2±1/8" (73,0 mm) 1/2° (12,7 mm)
(15,9-16,4 mm) 2 -1/4° DIA. 1/4' (6,4 mm) (12,7±3,2 mm) 2 -1/4' DIA. 1/4° (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm)
SPRINKLER PLATE SPRINKLER MOUNTING
FITTING FITTING PLATE
1/8' 1/8'
� ] l il�!i (3,2 mm) — 111q (3,2 mm)
1 A Si : rA i f \ WIIMIIMMEINII ■., •
MMIWAIMMMi � . , SURFACE 1 MOUNTING
SURFACE ? iirg -N
iretir
CLOSURE SERIES 1-5/16' (33,3 mm) CLOSURE SERIES 1 -5/16° (33,3 mm)
TY-FRB 13/16' (20,6 mm) TY-FRB 1 -1/16° (27,0 mm)
FIGURE 5 FIGURE 6
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT
2 -7/8° DIA. 2 -7/8° DIA.
5/8±1/4°
(73,0 mm) 3/4' (19,1 mm) 1/211/8° (73,0 mm) 1/2' (12,7 mm)
(15,916,4 mm) 2 -1/4° DIA. 1/4 ° (6,4 mm) (12,7±3,2 mm
2 -1/4' DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) (57,2 mm)
MOUNTING FACE OF MOUNTING
SPRINKLER
FITTING PLATE SPRINKLER PLATE
FITTING
1 /8' 1/8°
���� i (3,2 mm) ' / MAR (3,2 mm)
,� + i A - • li - � IS M OUNTING
MOUNTING �: SURFACE
SURFACE ..
CLOSURE SERIES 1 -1/4° (31,8 mm) CLOSURE SERIES 1 -1/4° (31,8 mm)
TY-FRB 3/4' (19,1 mm) TY -FRB 1° (25,4 mm)
FIGURE 7 FIGURE 8
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT
used to cover a clearance hole, may and after installation. Sprinklers dam-
Care and delay the time to sprinkler operation in aged by dropping, striking, wrench
a fire situation. twist/slippage, or the like, must be re-
Maintenance placed. Also, replace any sprinkler that
Sprinklers that are found to be leaking has a cracked bulb or that has lost
The Series TY-FRB Sprinklers must be or exhibiting visible signs of corrosion liquid from its bulb. (Ref. Installation
maintained and serviced in accord- must be replaced. Section).
ante with the following instructions: Automatic sprinklers must never be
painted, plated, coated or otherwise Frequent visual inspections are rec
NOTES altered after leaving the factory. Modi- ommended to be initially performed for
Before closing a fire protection system fled sprinklers must be replaced. corrosion resistant coated sprinklers,
main control valve for maintenance Sprinklers that have been exposed to after the installation has been corn-
work on the fire protection system that corrosive products of combustion, but pleted, to verify the integrity of the cor-
it controls, permission to shut down the have not operated, should be replaced rosion resistant coating. Thereafter,
affected fire protection system must be if they cannot be completely cleaned annual inspections per NFPA 25
obtained from the proper authorities by wiping the sprinkler with a cloth or should suffice; however, instead of
and all personnel who maybe affected by brushing it with a soft bristle brush. spatting from the floor level, a random
by this action must be notified. sampling of close -up visual inspec-
Care must be exercised to avoid dam- tions should be made, so as to better
Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi-
Y TFPI 71 Page 7 of 8
2 -7/8' DIA. 2 -7/8° DIA.
5/8 ±1/4° (73,0 mm) 3/4' (19,1 mm) (73,0 mm)
1/2±1/8' 1/2° (12,7 mm)
(15,9±6,4 mm) 2 -1/4' DIA. 1/4' (6,4 mm) (12,7±3,2 mm) 2 -1/4° DIA. 1/4'(6,4 mm)
FACE OF (57,2 mm) (57,2 mm)
MOUNTING FACE OF MOUNTING
SPRINKLER
• FITTING PLATE SPRINKLER PLATE
FITTING
1/8' 1/8'
'�i (3,2 mm) •� (3,2 mm)
1 116 9m=._- - lfll, �/'
MI 1 A it i
- ii } _ —
,
' , MOUNTING IIP
MOUNTING SURFAC
SURFACE — _, I ;_. _ „_ •
CLOSURE SERIES 1 -1/4' (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm)
TY-FRB 3/4° (19,1 mm) TY -FRB 1' (25,4 mm)
FIGURE 9 FIGURE 10
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT
2 -7/8° DIA. 2 -7/8' DIA.
5/811/4° (73,0 mm) 3/4° (19,1 mm) 1/2±1/8, (73,0 mm) 1/2' (12,7 mm)
(15,9±6,4 mm) 2 -1/4° DIA. 1 1/4° (6,4 mm) (12,713,2 mm) 2 -1/4° DIA. 1/4° (6,4 mm)
FACE OF (57,2 mm) MOUNTING (57,2 mm)
FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8° 1/8°
” (3,2 mm) ' (3,2 mm)
, r IWr W i ■
■ MOUNTING
MOUNTING �I SURFACE
Ili
SURFACE 1 ■
CLOSURE SERIES 1 -5/16° (33,3 mm) CLOSURE SERIES 1 -5/16° (33,3 mm)
TY -FRB 13/16° (20,6 mm) TY -FRB 1 -1/16' (27,0 mm)
FIGURE 11 FIGURE 12
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT
• tion and the long term integrity of the
corrosion resistant coating, as it may WRENCH
be affected by the corrosive conditions L � RECESS
present.
WRENCH RECESS S �1
�
The owner is responsible for the in- ; (END °A° USED FOR if spection, testing, and maintenance of 1/2' NPT MODELS) /�
their fire protection system and de- �� `
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec- WRENCH RECESS PUSH WRENCH
tion Association FPA 25 , in (END °B° USED FOR
(e.g., g 3/4° NPT MODELS) IN TO ENSURE
addition to the standards of any other ) ENGAGEMENT
authorities having jurisdiction. The in- WITH SPRINKLER
stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA
facturer should be contacted relative to W - TYPE 6 SPRINKLER
any questions. WRENCH
It is recommended that automatic FIGURE 14
sprinkler systems be inspected, local requirements and /or national W TYPE 7 RECESSED
tested, and maintained by a qualified codes. SPRINKLER WRENCH
Inspection Service in accordance with
Page 8 of 8 TFPI 71
• P/N 57 -XXX -X- XXX
I I
TEMPERATURE
MODEUSIN RATING
SPRINKLER
330 2.8K UPRIGHT (1 /2 °NPT) TY1131 135 135 °F /57 °C
331 2.8K PENDENT (1 /2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C
340 4.2K UPRIGHT (1 /2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C
341 4.2K PENDENT (1 /2 "NPT) TY2231 3 WHITE (RAL9010)' 200 200 °F /93 °C
370 5.6K UPRIGHT (1 /2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C
371 5.6K PENDENT (1 /2 "NPT) TY3231 7 LEAD COATED
390 8.0K UPRIGHT (3/4 "NPT) TY4131
391 8.0K PENDENT (3/4 "NPT) TY4231 • Eastern Hemisphere sales only.
TABLE C
PART NUMBER SELECTION
SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS
ORY, FOR INCIDENTAL, INDIRECT, Recessed Escutcheon:
Limited SPECIAL OR CONSEQUENTIAL Specify: Style (specify) Recessed Es-
DAMAGES, INCLUDING BUT NOT cutcheon with (specify finish), P/N
Warranty LIMITED TO LABOR CHARGES, RE- (specify).
GARDLESS OF WHETHER TYCO
Products manufactured by Tyco Fire FIRE PRODUCTS WAS INFORMED 1/2° (15 mm)
Products are warranted solely to the ABOUT THE POSSIBILITY OF SUCH Style 10
original Buyer for ten (10) years DAMAGES, AND IN NO EVENT Chrome Plated P/N 56- 701 -9-010
against defects in material and work- SHALL TYCO FIRE PRODUCTS' LI- White Coated P/N 56- 701 -4-010
manship when paid for and properly ABILITY EXCEED AN AMOUNT White RAL9010' P/N 56-701-3-010
Brass Plated P/N 56- 701 -2 -010
installed and maintained under normal EQUAL TO THE SALES PRICE.
use and service. This warranty will ex- THE FOREGOING WARRANTY IS 1/2' (15 mm)
pire ten (10) years from date of ship- Style 20
ment by Tyco Fire Products. No war - M ADE IN LIEU OF ANY AND ALL Chrome Plated P/N 56- 705 -9-010
ranty is given for products or OTHER WARRANTIES EXPRESS OR White Coated P/N 56-705-4-010
components manufactured by compa- IMPLIED, INCLUDING WARRANTIES White RAL9010' P/N 56- 705 -3-010
Hies not affiliated by ownership with OF MERCHANTABILITY AND FIT Brass Plated P/N 56-705-2-010
Tyco Fire Products or for products and NESS FOR A PARTICULAR PUR 3/4° (20 mm)
components which have been subject POSE Style 30
to misuse, improper installation, corro- Chrome Plated P/N 56- 705 -9 -011
sion, or which have not been installed, White Coated P/N 56- 705 -4 -011
maintained, modified or repaired in ac- White Plated 0' P/N 56- 705 -3-011
cordance with applicable Standards of ac- Ordering Brass Plated P/N 58 -705 2 -011
the National Fire Protection Associa- Procedure 3/4° (20 mm)
tion, and /or the standards of any other Style 40
Authorities Having Jurisdiction. Mate- esetattygtui local distributor for avail- Chrome Plated P/N 56- 700 -9-010
rials found by Tyco Fire Products to be ability indicate the White Coated P/N 56- 700 -4-010
defective shall be either repaired or fulrrproduct White RAL9010' P/N 56- 700 -3-010
replaced, at Tyco Fire Products' sole name. Refer to Brass Plated P/N 56 -700 -2 -010
o option. Tyco Fire Products neither as- the complete Price List for
P Y cple listing 'Eastem Hemisphere sales only.
sumes, nor authorizes any person to of Part Numbers.
assume for it, any other obligation in Sprinkler Wrench:
connection with the sale of products or Sprinkler Assemblies with NPT Specify: W -Type 6 Sprinkler Wrench,
parts of products. Tyco Fire Products Thread Connections: P/N 56- 000 -6 -387.
shall not be responsible for sprinkler Specify: (Specify Model /SIN), Quick
system design errors or inaccurate or Response, (specify K- factor), (specify Specify: W -Type 7 Sprinkler Wrench,
incomplete information supplied by temperature rating), Series TY FRB P/N 56- 850 -4 -001.
Buyer or Buyer's representatives. (specify Pendent or Upright) Sprinkler
IN NO EVENT SHALL TYCO FIRE with (specify type of finish or coating),
PRODUCTS BE LIABLE, IN CON- P/N (specify from Table C).
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE -
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
.4■,
tqco Fire & Building
• Products CENTRAL
Customer Service /Sales:
Tel: (215) 362 -0700 / (800) 523 -6512
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Fax: (215) 362-5385
Series RFII — 5.6 K- factor
"Royal Flush 11" Pendent Concealed Sprinklers
Quick & Standard Response, Standard Coverage
1
Cap. The Protective Cap is temporarily
General removed for installation, and then it
can be replaced to help protect the Alik
Description sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro -
The Series RFII Quick Response tective Cap can also be used to mark _
(3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas- : _
mm bulb), 5.6 K- Factor, "Royal Flush ter board, ceiling tiles, etc. by gently
II" Concealed Pendent Sprinklers are pushing the ceiling product against the f.......
decorative sprinklers featuring a flat Protective Cap. When the ceiling in-
cover plate designed to conceal the stallation is complete the Protective
sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate
tecturally sensitive areas such as hotel Assembly installed.
lobbies, office buildings, churches, As an option, the Series RFII Standard
and restaurants. Response (5 mm bulb) "Royal Flush II"
Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be
sembly that conceals the sprinkler op - fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175
erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM.
The separable two -piece design of the intended for sensitive areas where it is
Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical
blies allows installation of the sprin- through the cover plate from the area
klers and pressure testing of the fire above the ceiling. Data
protection system prior to installation WARNINGS
of a suspended ceiling or application The Series RFII Concealed Pendent Approvals for Series RFII
of the finish coating to a fixed ceiling. pp
They also permit removal of sus- Sprinklers described herein must be UL and C -UL Listed. FM Approved.
pended ceiling panels for access to installed and maintained in compli- NYC under MEA 353 -01 -E. LPCB (Ref.
building service equipment without ance with this document, as well as No. 094a/09 for TY3551 & 094a/10 for
having to first shut down the fire pro- with the applicable standards of the TY3531) Approved.
hav system and remove sprinklers. Nat Fire Protection Association, The approvals apply only to the serv-
r-ig in addition to the standards of any ice conditions indicated in the Design
Also, the separable two-piece design of the the Sprinkler provides o for ig n pi other authorities having jurisdiction. Criteria section and maximum pres-
inch the th mm) of er for 1/2 Failure to do so may Impair the per- sure ratings indicated in the
to reduce the accuracy to which the formance of these devices. Model /Sprinkler Identification Num-
length of fixed pipe drops to the sprin- T owner is responsible for maintain- bers section.
klers must be cut. T. their fire protection system and de- Approvals for Air & Dust Seal
The Series RFII Sprinklers are vices in proper operating condition. (Part #10908100)
T
shipped with a Disposable Protective are The installing contractor or sprinkler UL and C -UL Listed for use with the
manufacturer should be contacted RFII (TY3551 & TY3504) Standard Re-
with any questions. sponse Concealed Sprinkler.
IMPORTANT Temperature Ratings
Always refer to Technical Data Model /Sprinkler 155F/68C Sprinkler - 135F/57C Plate
Sheet TFP700 for the "INSTALLER 200F/93C Sprinkler - 165F/74C Plate
WARNING" that provides cautions Identification Discharge Coefficient
with respect to handling and instal- K = 5.6 GPM /psi (80,6 LPM/bar /2 )
lation of sprinkler systems and com- Numbers Adjustment
ponents. Improper handling and in- 1/2 inch (12,7 mm)
stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm Finishes
a sprinkler system or its compo- bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass
vents and cause the sprinkler to fail UL, C -UL, FM, LPCB and NYC. Plated, or White Painted (Custom paint
to operate in a fire situation or cause TY3504 (5 mm bulb) & TY3505 (3 mm matches and colors other than white
it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by are available on request.)
Page 1 of 4 JULY, 2004 TFP181
Page 9 TFPi81
Physical Characteristics 1/2' NPT 2 r- SEALING
. Frame Bronze ASSEMBLY
Support Cup . Chrome Plated Steel
Guide Pins Stainless Steel FRAME ;j% ` ` �4,_
Deflector Bronze 1 l 1 CAP
• Compression Screw Brass i4 -;111a— 1'
Bulb Glass I I IIIII1
Cap Bronze or Copper SUPPORT
Sealing Assembly CUP WITH BULB
Beryllium Nickel wrieflon' ROLL FORMED )
THREADS l
Cover Plate Brass ) _ � I
Retainer Brass \ \ COMPRESSION
Ejection Spring ....Stainless Steel
GUIDE Agri alm l �j
I SCREW
Patents PINS (2) I/ Ea t U.S.A. 4,014,388 I I / —
,_ _______„ DEFLECTOR
Operation ' i ti (DROPPED
D EFLECTOR r_ / POSITION)
G- 1 ]/
When exposed to heat from a fire, the I SPRINKLER/SUPPORTCUP
Cover Plate, which is normally sol- I ASSEMBLY
dered to the Retainer at three points,
falls away to expose the Sprinkler As- THREAD INTO I RETAINER
SUPPORT CUP , WITH THREAD
sembly. At this point the Deflector sup- UNTIL MOUNTING �' 0 O I DIMPLES
ported by the Guide Pins drops down SURFACE IS
to its operational position. FLUSH WITH EJECTION
The glass Bulb contains a fluid that CEILING SPRING
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter then
glass Bulb, activating the sprinkler and
allowing water to flow. SOLDER COVER
TABS (3) COVER PLATE/RETAINER PLATE
ASSEMBLY
Design FIGURE 1
Criteria SERIES RFII CONCEALED SPRINKLER
ASSEMBLY
The RFII (TY3551 & TY3504), 5 mm
Bulb Type, Concealed Pendent Sprin- Step 1. The sprinkler must only be
klers are UL and C -UL Listed as stand- Installation installed in the pendent position and
and response - standard spray sprin- with the centerline of the sprinkler per -
klers for use in accordance with the The Series RFII must be installed in pendicular to the mounting surface.
current NFPA standard. They are FM accordance with the following instruc- Step 2. Remove the Protective Cap.
Approved as standard response - tions:
standard spray sprinklers for use in Step 3. With pipe thread sealant ap-
accordance with the current FM Loss NOTES plied to the pipe threads, hand tighten
Prevention Data Sheets. Do not install any bulb type sprinkler if the sprinkler into the sprinkler fitting.
The RFII (TY3531 & TY3505) 3 mm the bulb is cracked or there is a loss of Step 4. Wrench tighten the sprinkler
Bulb Type, Concealed Pendent Sprin- liquid from the bulb. With the sprinkler using only the RFII Sprinkler Wrench
yp p held horizontally, a small air bubble Ref. Figure 3). The RFII Sprinkler
klers are UL and C -UL Listed as quick should be present. The diameter of the ( g ure )' p
Wrench
. response - standard spray sprinklers air bubble is approximately 1/16 inch as applied to the Sprin-
a
for use in accordance with the current (1,6 mm) for the 155 °F /68 °C and 3/32 kler as showw n in n Figure ed re 3.
NFPA standard. They are FM Ap- inch (Z4 mm) for the 200 °F /93 °C tern- Step 5. Replace the Proteve Cap
proved as standard response - stand- perature ratings. (Ref. Figure 4) by pushing i cti upwards
and spray sprinklers for use in accord- leak tight 1/2 inch NPTs sprinkler Dint until it bottoms out against the Support
A lk i
ante with the current FM Loss g p Cup. The Protective Cap helps prevent
Prevention Data Sheets. should be obtained with a torque o ' damage to the Deflector and Arms dur-
Series RFII Concealed Pendent to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- ing ceiling installation and /or during
The
Sprinklers Seri nl listed mum of 21 ft.lbs. (28,5 Nm) of torque application of the finish coating of the
proved with the are only RFII metallic C c or white Higher levels of torque may distort the the center of the clearance hole by
sprinkler inlet with consequent leak- gently pushing the ceiling material u
painted finish. age or impairment of the sprinkler. g y p g g up
against the center point of the Protec-
The Series RFII must not be used in Do not attempt to compensate for in- tive Cap.
applications where the air pressure sufficient adjustment in the Sprinkler
above the ceiling is greater than that Assembly by under- or over - tightening NOTE
below. Down drafts through the Sup- the Sprinkler /Support Cup Assembly. As long as the Protective Cap remains
port Cup could delay sprinkler opera- Readjust the position of the sprinkler in place, the system is considered to
tion in a fire situation. filling to suit. be "Out of Service".
' Registered Trademark of DuPont
,
.
TFP181 Page 3 of 4
FACE OF CLEARANCE HOLE CLEARANCE
• ` SPRINKLER L DIAMETER HOLE
FITTING i DIMENSION C f
J rte.
11011
° SPRINKLER
SUPPORT CUP \ i ASSEMBLY
1/2 (12,7 mm) 1�' ,/1 I it
THREADED II __ .
D ADJUSTMENT l
FACE OF CEILING, 4
RETAINING RING FIGURE 4
MOUNTING DISPOSABLE PROTECTIVE CAP
SURFACE )' i Ste 6. After the ceilin has been com-
\ / ii
— plet ceiling
d with the 2- 1 /2 inch (63,5 mm)
V r - - -- t diameter clearance hole and in prepa
ration for installing the Cover Plate As-
sembly, remove and discard the Pro -
I I
- r- - -T - -z ':.,=, ' tective Cap, and verify that the
3/16° to 11/16" MANUFACTURER DEFLECTOR COVER PLATE Deflector moves up and down freely. If
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER the Sprinkler has been damaged and
REFERENCE 3/32° (2,4 mm) POSITION ASSEMBLY the Deflector does not move up and
down freely, replace the entire Sprin-
COVER PLATE COVER PLATE kler assembly. Do not attempt to mod-
- PROFILE DEPTH DIAMETER ify or repair a damaged sprinkler.
DIMENSION B DIMENSION A Step 7. When installing an Air and
Dust Seal, refer to Figure 5, otherwise
proceed to Step 8. To attach the Air and
A: 3-1/4° (82,6 mm) C: 2 -3/8" to 2 - 5/8" (60,3 to 66,7 mm) Dust Seal, verify the angle of the out -
B: 3/16" (4,8 mm) D: 1 - 3/4" to 2 - 1/4° (44,5 to 57,2 mm) side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
FIGURE the Retainer in the grooved slot of the
SERIES RFII CONCEALED SPRINKLER Air and Dust Seal and continue around
INSTALLATION DIMENSIONS Dust Seal retainer until the entire Air and
Dust Seal is engaged.
NOTE
The Air and Dust Seal is only to be
installed on the periphery of the Re-
tainer.
1_1, l =. FRAME = � 1 Step 8. Screw on the Cover Plate /Re-
, G tainer Assembly until the Retainer -
To ; % I1Pi -' Figure 2 (or Air and Dust Seal - Figure
SUPPORT j i 0 5) contacts with the ceiling. Do not
CUP ; continue to screw on the Cover
j AR r� i1 , • Plate /Retainer Assembly such that it
i i lifts a ceiling panel out of its normal
•'• �,!•' position. If the Cover Plate /Retainer
1.11 % t A pP
Assembly cannot be engaged with the
--- — — O Support Cup or the Cover Plate /Re-
7/8° (23 mm) tainer Assembly cannot be engaged
SQUARE sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
ALIGN ..- J `�
ARROWS WITH lel' Care and
(11- Ell FRAME ARMS Maintenance
ACCEPTS \ � r - The Series RFII must be maintained
0 1/2° SOCKET and serviced in accordance with the
DRIVE following instructions:
NOTES
FIGURE 3 Absence of the Cover Plate Assembly
RFII SPRINKLER WRENCH may delay sprinkler operation in a fire
situation.
Page 4 of 4 TFP181
When properly installed, there is a SUPPORT SPRINKLER FACE OF ORIENT
nominal 3/32 inch (2,4 mm) air gap CUP CEILING SEAL
between the lip of the Cover Plate and l Ill•ri� j PLATE BEVEL AS
the ceiling, as shown in Figure 2. This i. SHOWN
air gap is necessary for proper opera- �, ��•
' tion of the sprinkler. If the ceiling is to ` + `' R ETAINE R -
be repainted after the installation of ) !AI ;y ASSEMBLY �� , the Sprinkler, care must be exercised --�' ' to ensure that the new paint does NOT
seal off any of the air gap. . - CLEAN
Factory painted Cover Plates MUST /� ����� ' ���' ROOM
r — -- �� LIP OF COVER
• NOT be repainted. They should be re-
SEAL
RETAINER PLATE
placed, if necessary, by factory
painted units. FIGURE 5
Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504)
the Enclosure. Separation may result.
Before closing a fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT
main control valve for maintenance local requirements and /or national SHALL TYCO FIRE PRODUCTS' LI-
work on the fire protection system that codes. ABILITY EXCEED AN AMOUNT
it controls, permission to shut down the EQUAL TO THE SALES PRICE.
affected fire protection system must be THE FOREGOING WARRANTY IS
obtained from the proper authorities L imit ed
and all personnel who maybe affected OTHER IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
by this action must be notified. warranty IMPLIED, INCLUDING WARRANTIES
Sprinklers that are found to be leaking OF MERCHANTABILITY AND FIT -
or exhibiting visible signs of corrosion Products manufactured by Tyco Fire NESS FOR A PARTICULAR PUR-
must be replaced. Products are warranted solely to the POSE
Automatic sprinklers must never be original Buyer for ten (10) years
r against defects in material and work -
painted, plated, le s must never be
altered after leaving the factory. Modi- manship when paid for and properly Ordering
Pied spres must be replaced, installed and maintained under normal
tied inklr
s r kl e have been exposed replaced. use and service. This warranty will ex- Procedure
corrosive products prodts of combustion, but pire ten (10) years from date of ship-
. have not opera should be replaced ment by Tyco Fire Products. No war- When placing an order, indicate the full
if they cannot be complelately eleaced ranty is given for products or product name. Contact your local dis-
by wiping ca the spr om te a cloth or components manufactured by compa- tributor for availability.
by brushing it with a soft bristle brush. Hies not affiliated by ownership with Sprinkler Assembly:
Tyco Fire Products or for products and Specify: (SIN), (specify temperature
Care must be exercised to avoid dam- components which have been subject rating) Series RFII Concealed Pen -
age to the sprinklers - before, during, to misuse, improper installation, corro- dent Sprinkler, P/N ecif s
and after installation. Sprinklers dam- sion, or which have not been installed, P (specify).
aged by dropping, striking, wrench maintained, modified or repaired in ac-
twist/311 a e, Or the like, must be re- 155F/68C 2 790.1 - C
PP 9 cordance with applicable Standards of Ty3551 61- 790 -1 -155 51- 790 -1 -200
placed. Also, replace any sprinkler that the National Fire Protection Associa- TY35°4 51-796-1-155 51 -796 -1 -200
has a cracked bulb or that has lost tion, and/or the standards of any other TY3531 51- 792 -1 -155 51- 792 -1 -200
liquid from its bulb. (Ref. Installation Authorities Having Jurisdiction. Mate - TY35 °5 51- 797 -1 -155 51 -797 -1 -200
Section). rials found by Tyco Fire Products to be
If a sprinkler must be removed, do not defective shall be either repaired or Separately Ordered Cover Plate:
- reinstall it or a replacement without replaced, at Tyco Fire Products' sole Specify: (specify temperature rating)
reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate
If a Cover Plate Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify).
dislodged during service, replace it im- assume for it, any other obligation in 135F/57C(a) 165Fr74C•(b)
mediately. connection with the sale of products or Brass 56- 792 -1- 135 56- 792 -1 -165
parts of products. Tyco Fire Products Bnght Brass 56- 792 -2 -135 56- 792 -2 -165
The owner is responsible for the in- shall not be responsible for sprinkler Chrome 56- 792 -9 -135 56- 792 -9-165
spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome 56- -3- 792 -8-1665 protection system and de- incomplete information supplied by White 56- 792 792 8-1
-3-15 35 56 56- 792 -3-165
their fire
P Y P PP Y Whde (RAL9010)' 56- 792 -3-135 56- 792 -3-165
vices in compliance with this docu- Buyer or Buyer's representatives. Bright White 56- 792 -4 -135 56- 792 -4 -165
ment, as well as with the applicable IN NO EVENT SHALL TYCO FIRE Off White 56- 792 -5- 135 56- 792 -5-165
standards of the National Fire Protec- PRODUCTS BE LIABLE IN CON- C 56- 792 -6- 135 56- 792 -6-165
tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR Custom 56- 792 - X-135 56- 792 -X -165
(a) For use with 155F/68C sprinklers.
addition to the standards of any other UNDER ANY OTHER LEGAL THE- jurisdiction. The in- (b) For use with 200F/93C sales s on ly . ers.
authorities having j ORY, FOR INCIDENTAL, INDIRECT, • Eastern Hemisphere sales only.
stalling contractor or sprinkler manu- SPECIAL OR CONSEQUENTIAL
facturershould be contacted relative to DAMAGES, INCLUDING BUT NOT Sprinkler Wrench:
any questions. LIMITED TO LABOR CHARGES, RE- Specify: RFII Sprinkler Wrench,
It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56- 000 -1 -075.
sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal:
tested, and maintained by a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal,
P/N 56 -908 -1 -001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446