Specifications r7 a/014,4, 5 Jew toe/ 6 c? 6c ? - 60 p F SIEMENS Fire Safety FP -11 FirePrintTM Detector Intelligent Fire Detector for MXL, MXL-IQ, and MXLV Control Panels ENGINEER AND ARCHITECT SPECIFICATIONS • Most Sophisticated "Detector Intelligence" available today • Multi- Criteria fire detection for the price of a photoelectric detector • FirePrintTM Technology to discriminate between deceptive phenomena and an actual fire • Easily programmed to match specific hazard profiles from the control panel • Pre -Alarm reporting based on fire profile selected • Remote sensitivity measurement capability • System logic activation based on any of three inputs from detector (smoke, heat or neural network) • Field cleanable chamber with replaceable chamber��, parts available - • Multi -color detector status LED 00 „ Iwo • Two -wire operation • Compatible with Model DPU or FPI -32 field -- +5 • Supports EnviroLINK software based automatic environmental compensation • Backward compatible with older MXL systems (Rev. 2 and above) • Optional fully programmable relay base , audible base, and duct housing • 03 UL Listed, ULC Listed, CSFM, FM, NYMEA Approved Introduction The FP -11 Intelligent Fire Detector provides the life need for cumbersome, unreliable mechanical program - safety industry with the most highly evolved detection ming methods and reduces installation and service system available today. The FP -11 utilizes advanced costs by electronically programming and testing the detection technology that allows the detector to detector prior to installation. distinguish nonthreatening deceptive phenomena, such as cigarette smoke, from actual fire hazards, while The FP -11 fire detector is compatible with the MXL optimizing detection for the area in which it is in- family of control panels including the MXL, MXLIQ, stalled. No other detection system available today and MXLV. offers a higher level of protection or nuisance The FP -11 detector is Underwriters Laboratories and alarm immunity. The FP -11 uses state -of- the -art Underwriters Laboratories of Canada Listed. microprocessor circuitry with error check, detector self- diagnostics and supervision programs. Description The FP 11 intelligent fire detector is compatible with The FP -11 is a plug -in, two -wire, multi- sensor detector the Siemens Building Technologies, Fire Safety Divi with both photoelectric and thermal inputs and is sion, Model DPU or FPI-32 field programmer /tester, compatible with the MXL family of control panel which is a compact, portable, menu driven accessory systems. Each detector consists of a dust resistant, for electronically programming and testing detectors, field cleanable photo chamber, a solid state easily and reliably. The DPU or FPI -32 eliminates the CATALOG NUMBER 6175 non - mechanical thermal sensor, microprocessor based evaluating this information with sophisticated electronics with a low- profile plastic cover and base. mathematical formulas, or algorithms, comparing this The FP -11 utilizes state -of- the -art ASIC and surface input to characteristics of both threatening fires and mount technology for maximum reliability. Every FP -11 deceptive phenomena that would "fool" any ordinary fire detector is shipped with a protective dust cover. detector. This technology was developed over years of research and reviewing the results of over 20 years of The FP -11 fire detector utilizes an infrared light fire test data in one of the world's most advanced fire emitting diode (IRLED), and light sensing photodiode. research centers. The results of this research are the Under normal conditions, light transmitted by the LED mathematical models that form the algorithms used in is directed away from the photodiode and scattered FirePrint. No other fire detector has this level of through the smoke chamber in a controlled pattern. intelligence or this amount of research and develop - The smoke chamber is designed to manage light ment supporting and extraneous reflections from dust PPorting it's design. particles or other non -smoke airborne contaminants in The microprocessor's software can identify and such a way as to maintain stable, consistent detector disregard false input caused by radio frequency (RFI) operation. When smoke enters the detector chamber, and electromagnetic (EMI) interference, and validates light emitted from the IRLED is scattered by the all trouble conditions before annunciating or reporting smoke particles and is received by the photodiode. to the control panel. The FP -11 detector's microproces- sor uses an integral EEPROM to store the detector's The FP -11 also utilizes a modern, accurate, shock- address and other critical operating parameters which resistant thermistor to sense temperature changes. include the assigned program values for alarm and The "on- board" FirePrint technology allows the trouble thresholds. Communications within the detector to gather smoke and thermal data, and to detector itself and between the FP -11 and the control analyze this information in the detector's "neural panel, or with the FPI -32 field programmer /tester, are network" By comparing data received with the supervised and safeguarded against disruption by common characteristics of fires, or fire fingerprints, reliable, microprocessor based error checking routines. the FP -11 can compare these "Fire Prints" to those of Additionally, the microprocessor supervises all deceptive phenomena that cause other detectors to EEPROM memory locations and provides a high alarm. The advanced FirePrint technology allows the degree of EEPROM failure fault tolerance. FP -11 to accurately determine a true fire hazard from a nonthreatening deceptive phenomena WITHOUT In MXL(V) applications, the FP -11 determines its needing to use alarm delaying verification and confir- operating status to be normal, in alarm, or in trouble mation techniques, which can increase the probability depending on the difference between the alarm of losses due to fire. threshold values stored in the detector's memory and the detector's latest analog measurement. The The FP -11 provides the highest level of detector detector then communicates changes in its status to intelligence available today with a detector /control the control panel. panel link that allows the user to program the detector for the specific hazard profile Detectors are optimized In addition, the MXL(V) control panel will sample the by selecting one of the following applications: value of the FP -11's analog signal over a period of time in order to determine if those values indicate exces- • Office /Retail sive buildup in the photo chamber; if so, the MXL(V) • Lobby will indicate that the particular detector requires • Computer Room maintenance. • Dormitory • Healthcare The FP -11 is listed as a self- testing device. The FP -11's • Parking Garage visible light emitting diode (LED) flashes green every • Utility/Transformer Room 4 seconds to indicate it is communicating with the • Hostile Environment control panel and that it has passed its internal self- • Precious Storage test. Should the detector sense a fault or failure within • Air Duct its systems, the LED will flash amber and the detector • Warehouse /Light Manufacturing will transmit that information to the control panel. The software does the rest; no guessing on detector A quick visual inspection is sufficient to indicate the condition of the detector at any time. If more detailed sensitivities or alarm verification; the control panel information is required, a printed report can be programs the FP -11 detector for the protected area provided from the MXL panel indicating the status without hassle and without confirmation delays. and settings assigned to each individual detector. Once optimized for the hazards in the protected area, the FP -11 provides the best detection you can buy. When the FP -11 moves to the alarm mode, it will flash Should the operator or installer forget to program the amber and transmit that information to the control detector, the FP -11 will revert to a default setting that panel. When the MXL(V) confirms the detectors allows it to operate as a standard photoelectric or condition, the panel will instruct the FP -11 to flash red photothermal detector. and to continue flashing until the system is reset at the control panel. At that same time, any user defined The FP -11's FirePrint technology monitors input from both the photo chamber and the thermal sensor, system alarm functions programmed into the system All FP -11 detectors are approved for operation within are activated. Each FP -11 detector can operate one the UL specified temperature range of 32 to 100 remote alarm indicator, one auxiliary relay, or one degrees F (0 to 38 degrees C). audible base. Detector sensitivity, calibration, and identification are Application Data dynamically supervised by the control panel. Detector Installation of the FP -11 series of fire detectors sensitivity and pre -alarm levels are a function of the requires a two -wire circuit of 18 AWG (minimum) application chosen at the control panel and are thermoplastic fixture wire enclosed in conduit, or 18 controlled by the panel. If an alternate, non - FirePrint AWG limited energy, shielded cable without conduit, mode is selected, then the sensitivity can be changed if permitted by local codes. Field wiring should from the control panel. conform to local and National Electric Codes and the The DPU or FPI -32 Program/Test accessory is used to control panel wiring specifications. program and verify the detector's address. The "T- tapping" is permitted only for Style 4 (Class B) technician selects the accessory's program mode to wiring. enter the desired address. The DPU or FPI -32 auto- matically sets and verifies the address and tests the FP -11 fire detectors can be applied within the maxi - detector. It also allows the user to change the device mum 30 foot center spacing (900 sq. ft. areas) as ID from that of an FP -11 to an older detector ID such as referenced in NFPA 72. This applications guideline is an ILP -1, ILPT -1, ILP -2, ID -60P or ID -60PT to allow for based on ideal conditions, specifically, smooth ceiling easy replacement of older detectors without the need surfaces, minimal air movement, and no physical of reprogramming the control panel. obstructions between potential fire sources and the detector. Do not mount detectors in close proximity The FPI -32 operates on AC power or rechargeable to ventilation or heating and air conditioning outlets. batteries, providing flexibility and convenience in Exposed joints or beamed ceilings may also affect safe programming and testing equipment almost anywhere. spacing limitations for detectors. Should questions When in the test mode, the DPU or FPI -32 will perform arise regarding detector placement, observe NFPA a series of diagnostic tests without altering the 72 guidelines. address or other stored data, allowing technicians to determine if the detector is operating properly. Good fire protection system engineering and common sense dictate how and when fire detectors are The FP -11 fire detector may be installed on the same installed and 'used. Contact your local Siemens initiating circuit with IL or ID series detectors (Photo- Building Technologies, Fire Safety Division authorized electric, thermal, or ionization), MSI series manual sales outlet whenever you need assistance applying stations, TRI series interfaces, ICP output control FirePrint in unusual applications. Be sure to follow devices, or CZM series of addressable, conventional NFPA guidelines, UL /ULC approved installation zone modules. instructions, which are included with every detector, All FP 11 detectors can be cleaned in the field, when and local codes as for all fire protection equipment. required, by simply removing the detector cover and unsnapping the photo chamber. There is also the Dimensions option of cleaning the interior of the detector with a clean, soft cloth or brush, or replacing the labyrinth and I 6" Diameter Base bug screen included in the detector maintenance kit, • model DMK -11. The FP -11 uses the low profile surface mounting base, � � - - model DB -11. This base mounts on a 4 -inch octagon, T -- ,,,.,,,, -1 -.,,,,1 il . , 1 , 1 , i . 1 . 1 . 1 . I square, or a single gang electrical box. The base 2.3" `l utilizes screw clamp contacts for electrical connections overall , 7 j';1 and self- wiping contacts for increased reliability. The Height 1: . r base can be used with the optional LK-11 detector t ry di locking kit which contains 50 detector locks and an `� installation tool, to prevent unauthorized removal of the detector head. The DB -11 base has integral decora- tive plugs to cover the outer mounting screw holes. The FP -11 is electrically compatible with existing MXL detector accessories including relays, remote lamps, duct housings, and audible bases. With duct housings, a base adapter and new detector housing cover are required (order AD -11 UK upgrade kit). To use existing DB -3S base or audible base, the FP -11 requires a DB- ADPT base adapter. Technical Specifications Current Requirements: Normal 750 pa Alarm 750 Na Operating Temperature: +32 °F (0 °C) to 100 °F (38 °C) per UL 268/268A Humidity: 0 -93% Relative Humidity Non - Condensing Ordering Information Part Model Description Number FP-11 Addressable FirePrint Fire Detector 500- 095112 DB -11 Detector Mounting Base for Series 11 500-094151 DB -11E Detector Base (Small) 500- 094151E AD2 -P Air Duct Housing for use with FP -11, HFP -11, HFPD -11, 500- 649706 PE -11 AD2 -XHR Air Duct Housing for use with FP -11, HFP -11, HFPO -11 500- 649708 with relay ADBX -11 Audible Base 500- 096181 DB -X11 RS Relay Base for Series 11 Intelligent Detectors 500-096125 RLI -1 Remote (red) alarm indicator- 4' octagon box mount 500-390673 RU -2 Remote (red) alarm indicator- single gang box mount 500- 390674 LK -11 Base Locking Kit for Series 11 detectors 500- 695350 DMK -11 Series 11 Maint Kit (replacement labyrinth and bug 500- 695338 bug screen) DB -ADPT Base Adapter to DB -3S Base 500-094187 In Canada Order: FP-11C Addressable FirePrint Fire Detector (ULC) 500- 095112C DB -11C Detector Mounting Base for Series 11 (ULC) 500- 095687 AD -11PC Air Duct Housing (ULC) 500-095984 DB- X11RSC Relay Base for Series 11 Intelligent Detectors (ULC) 500- 096125C ADBX -11C Audible Base for Series 11 Intelligent Detector (ULC) 500-096181C Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park. NJ 07932 5/06 Brampton, Ontario Siemens Building Technologies Tel: 1973) 593 -2600 10M Canada L6T 5E4 g 9 FAX: (973) 593 -6670 SFS-IG Tel: (9051 799-9937 May 2006 Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799 -9858 Supersede, sneer dated 6/03 • SIEMENS Fire safety TRI Series Intelligent Initiating Devices Interface Modules for MXL Fire Detection Panels TRI- S,TRI- D,TRI -R ENGINEER AND ARCHITECT SPECIFICATIONS • Interfaces and Supervises Normally Open Contacts • Integral SPDT Relay (up to 4 amps) on TRI -R Model • Dual Input onTRl -D Model • Multi -color L.E.D. indicates status (green, amber, red) - • Easy front access to programming port and wiring terminals • Mounts in 4 inch square 21/4 deep box, or double gang box • Dynamic Supervision • Comes with 5x5 inch faceplate 4 ' = q rt ._ fafi; a 4t • Two wire operation r • Model DPU or FPI -32 Programs and Verifies Device's Address and Tests Device's functionality • • Electronic Address Programming is Easy and Dependable • 0 UL Listed, ULC Listed CFSM, FM, NYMEA Approved Introduction module reports the contact's status to the control The TRI Series Intelligent interface modules are panel. The TRI -S model can only monitor and report the designed to provide the means of interfacing direct status of the contact, while the TRI -R incorporates an shorting devices to the MXL system's ALD loop addressable Form C relay. The TRI -R relay and contact circuit. device input are controlled at the same address. For the MXL system, the relay and input contact can be The TRI Series Intelligent interface modules provide controlled as a separate function.' The relay is typically the market's most advanced method of address used where control or shunting of external equipment programming and supervision, combined with sophis- is required. ticated control panel communication. Each TRI Series interface module incorporates a microcomputer chip. The TRI -D is a dual input module and is designed to The TRI Series microcomputer chip technology and its supervise and monitor two sets of dry contacts. This sophisticated bi-directional communication capabilities interface module requires two address settings. The with the control panel, achieve the state of an "Intelli- TRI -D is ideal for monitoring a waterflow switch and its gent Device." respective valve tamper switch. The TRI has a multi -color Light Emitting Diode that Description flashes green when operating normally, amber if unit The TRI Series Intelligent interface modules are avail- able in three models. The TRI -S and TRI -R are designed to monitor a normally open dry contact. The interface CATALOG NUMBER 6179 is in trouble condition, and red to indicate a change of Mounting Data state. The TRI -D flashes twice, once for each address, Addressable interface Model TRI S, TRI D, TRI -R the TRl R red L.E.D. indicates a change of state in mounts directly into a 4 inch square 21/4 deep box the relay. or a double gang box (user supplied). A 5 inch square The device's microcomputer chip has the capacity of off-white faceplate is included with each TRI. storing, in memory, identification information as well as important operating status information. MOUNTING SLOTS FOR 4 INCH Siemens Building Technologies, Fire Safety Division SWITC1430X innovative technology allows all TRI Series intelligent j interface modules to be programmed by using the r' i !� -/ -ti t model DPU or FPI -32 Programmer/Tester. The Pro - i fat` (2 ,;� 'ti) grammer/Tester is a compact, portable, menu driven " ...: accessory that makes programming and testing an - [7 a 111111 �r TRnSr _B interface device faster, easier and more dependable I 7 2 ��� N ., MODULE than previous methods. GLg• arM O The DPU or FPI -32 eliminates the need for mechanical mechanisms, such as program jumpers, ,. Hot-ES FOR switches or rotary dials, because the Programmer/ I I ` >vOrtlt HPLArT gel; 5 FP Tester electronically sets the TRI interface's address - -- - into the interface's microcomputer chip nonvolatile f 0 / � } memory. Vibration, corrosion and other conditions that I, ` c\ . { [� deteriorate mechanical addressing mechanisms are no / longer a cause for concern. \ / MOUNTING SLOTS The TRI Series is fitted with screw terminals for HUH DOUR EGANG connection to an addressable circuit. SWiTCHBOX The TRI Series is fully compatible on the same MXL Figure A circuit with all intelligent FR IL and ID -60 Series Mounting the TRI -S/-R/-D detectors, MSI Series addressable manual stations or any other addressable intelligent modules, such as the CZM or ICP. Electrical Ratings All TRI Series intelligent interface modules are Current Draw (Active or Standby): 1.5mA UL listed. Environmental operating conditions for all TRI Series R Relay , 125 VAC modules are 32 °F ( °C) to 120 °F (49 °C) with a relative Ree sistive: 4AA, 10VDC humidity of not greater than 93% non - condensating. 4A, 30 Inductive: 3.5A, 120 VAC (0.6PF.) Ordering Information 00 (0.6PE) 3.OA, 120 AC0 PF) Shipping Wt. 2.0A, 120 VAC (0.35P.F.) Model Description Lb. Kg. 2.OA, 30 VDC (0.35PF.) TRI -S Single Input 7 oz. .2 TRI -R Single Input w/Relay 7 oz. 2 TRI -D Dual Input 7 oz. .2 Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 5/06 Brampton, Ontario Siemens Building Technologies Tel: (973) 593 -2600 5M Canada L6T 5E4 g g IeS FAX: (973) 593 -6670 SFS Tel: (905) 799 -9937 May2006 Fire Safety _ Website: www.sbt.siemens.com /fis -. Printed in U.S.A.. FAX:.(905) 799 -9858 Supersedes sheet dated 7/03 - -- COOPER Notification Series E50 Speaker and Speaker Strobes q ; y; 11 1w SERIES E50 SERIES E50 Speaker Strobe Speaker Description Features The Wheelock Series E50 Speakers and Speaker Strobes feature • Approvals include: UL Standard 1971, UL Standard 1480, New high efficiency sound output, with dual voltage (25/70 VRMS) York City (MEA), California State Fire Marshal (CSFM), Factory capability and field selectable taps from 1/8 to 2 watts. They are Mutual (FM) and Chicago (BFP). See approvals by model in designed to provide a sleek, aesthetic appearance for emergency Specifications and Ordering Information voice /alarm communications systems. All Series E50 models ADA/NFPA/ANSI compliant • mount to standard 4" x 2 -1/8" electrical boxes (with no extension ring required) and incorporate a speaker mounting plate for faster • Complies with OSHA 29 Part 1910.165 installation. The grille cover snaps on so no mounting screws are Wall mount speaker strobe models with field selectable candela visible. Attractive surface boxes are also available for surface settings of 15/30/75/110cd or 135/185cd (Multi - Candela installations. models), or 1575cd (Single Candela model) The Series E50 Speaker Strobe models use Wheelock low current Field selectable taps for 25 or 70 VRMS operation from 1/8 watt draw Series RSS strobes for wall mounted applications. Strobe up to 2 watts options include patented MCW multi - candela strobes with field selectable candela settings of 15/30/75/110 cd or high intensity • High efficiency design for maximum output at minimum wattage MCWH strobes with field selectable 135 /185 candela. Models with across a frequency range of 400 to 4000 HZ 1575 candela (75 cd on axis) are also offered. • 24 VDC strobes produce 1 flash per second with wide UL Series E50 Speakers and Speaker Strobes provide high audio output "Regulated Voltage" of 16 to 33 volts using filtered DC or with dear audibility and are designed to meet the critical needs of the unfiltered VRMS input voltage life safety industry for effective emergency voice communications, • Synchronize with Wheelock SM, DSM or Wheelock tone signaling and visible signaling to alert the hearing impaired. PS- 12/24 -8CP and PS- 12124 -8MP Power Supply with built -in The strobe portion of all Series E Speaker Strobes may be sync protocol synchronized when used in conjunction with the Wheelock SM, • Mount to 4" square x 2 -1/8" deep backbox with no extension DSM Sync Modules or the Wheelock's PS- 24-8MC Power Supply ring required with Patented Sync Protocol. Wheelock synchronized strobes offer an easy way to comply with ADA and NFPA regulations concerning • Snap on grille cover with no visible mounting screws photosensitive epilepsy. • Fast installation with IN /OUT screw terminals using #12 to #18 Series E50 Speaker Strobes are UL Listed for indoor use under AWG wires Standard 1971 (Signaling Devices for the Hearing- Impaired) and Standard 1480 (Speaker Appliances). All inputs employ IN /OUT wiring terminals for fast installation using #12 to #18 AWG wiring and are compatible with FACP line supervision. Color options for the Series E50 Speakers and Speaker Strobes are red or off - white. M EA ISO APPROVED S5391 151 -92 -E 7125-0785:165 - - -- - 7320-0785:166 • NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW COOPERWHEELOCK. COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range ". Note that NFPA -72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 °F to 120 °F (0 °C to 49 °C) and maximum humidity of 93% (± 2 %). • Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology "Listed Voltage Range ". Table 1: Average RMS Current * RMS current ratings are per UL average RMS E50 Strobe Current Wall Mount method. UL max current rating is the maximum E50 RMS current within the listed voltage range (16 -33v Speaker 241575W 24MCW 24MCWH for 24v units). For strobes the UL max current is Strobes 1575cd 15cd 30cd 75cd 110cd 135cd 185cd usually at the minimum listed voltage (16v for 24v units). For unfiltered FWR ratings, see installation 24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 instructions. UL max` 0.090 0.060 0.092 0.165 0.220 0.300 0.420 Table 2: E50 UL Reverberant d8A @ 10 Feet** watts 1/8 1/4 1/2 1 2 E50 Speaker 77 79.5 82.5 85 88 E50 Speaker Strobe 77 79.5 82.5 85 88 "dBA ratings are based on UL testing under UL Standard 1480 Wiring Diagram? SERIES E50 SPEAKER & STROBE OPERATE . SERIES E50 SPEAKER STROBES SYNCHRONIZED INDEPENDENTLY (NON -SYNC OR SYNC) WITH MULTIPLE DSM MODULES DSM 1110 - �_ ,,:. F� strobe SAC 01+ . 5 nt`� FNCFA _o -p ,F F27.1,0 0 11 F❑ N20 ^u DDSM =arc o Note: Figure shows A❑ mot,, +� + — — sncC Interconnection to 1 f strobe through sync — n 1 f C❑ DsM N3❑ module. Speaker portion requires 2 IL »' P St robe Sac C r.-8 S y r , ® ®N separate conductors II��1 +LJ El +D- —±� to communications DSM Interconnecting wiring shown. Maximum c system. STROBEO SPEAKERO twenty 12010 SERIES E50 SPEAKER STROBE APPLIANCES SERIES E50 SPEAKER STROBE APPLIANCES & RSS SYNCHRONIZED WITH DSM MODULE SINGLE STROBES SYNCHRONIZED WITH PS- 12/24 -8CP and CLASS A" DSM❑ PS- 12/24 -8MP Series PS -12/24 -8MP or PS- l2 /24 -SCP1 STROBE° +00 NAC° SYNCO CIRCUIT❑ - / ll -1:12) ESOC1 OUTC co rOOT 10 OUTPUTS —J ` EOLRO I Mill G • IN ID M, -m, ° 4 Ell 9 -CLAS SCI B "❑ / 0-0 ID / ,Ti- // MI U �❑ can ( \` AUDIBLE �❑ 2- CLASSO • lJ "A": 1 ,/ MINUS 20 PC' i rd STROBE° // OUT 20 / • NAC° \ CIRCUIT° Series PS- 12 /24-2P PO RETURN° or Ps- 12 /24 -BCPC Specifications and Ordering Information Surface Agency Approvals Order Wall Ceiling Strobe Grill Flush Mount Mounting g y' pp Model Code Mount Mount Candela Color Bacbox 8� kbox Options UL MEA CSFM FM BFP E50-R 0222 X X - Red 4' x 4" x 2 -1/8" E5OSB -R E,O,P,Q,R,U,Y,AA X * X X • E50 -W 0223 X X - White 4' x 4" x 2 -1/8" E5OSB -W E,O,P,Q,R,U,Y,AA X • X X • E50- 241575W -FR 0224 X - 15 (75 on Axis) Red 4' x 4" x 2 -1/8" E5OSSB -R E,Q,U,BB X X X • E50- 241575W -FW 0225 X - 15 (75 on Axis) White 4' x 4" x 2 -1/8" E50 -SSB -W E,Q,U,BB X X X • E50- 24MCW -FR 0226 X - 15/30/75/110 Red 4' x 4" x 2 -1/8" E50SSB -R E,Q,U,BB X • X X • E50- 24MCW -FW 0227 X - 15/30/75/110 White 4' x 4" x 2 -1/8" E50 -SSB -W E,Q,U,BB X • X X E50- 24MCW -MW 5219 X - 15/30/75/110 White 4' x 4" x 2 -1/8" E50 -SSB -W E,Q,U,BB X • X X * E50- 24MCWH -FR 0228 X - 135/185 Red 4' x 4" x 2 -1/8" E5OSSB -R E,Q,U,BB X X X ' E50- 24MCWH -FW 0229 X - 135 /185 White 4' x 4" x 2 -1/8" E50 -SSB -W E,Q,U,BB X X X * PENDING NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. Architects and Engineers Specifications The speaker appliances shall be Wheelock Series E50 Speakers and the speaker strobe appliances shall be Wheelock Series E50 Speaker Strobes or approved equals. The speakers shall be UL Listed under Standard 1480 for Fire Protective Service and speakers equipped with strobes shall be listed under UL Standard 1971 for Emergency Devices for the Hearing- Impaired. In addition, the strobes shall be certified to meet the requirements of FCC Part 15, Class B. All speakers shall be designed for a field selectable input of either 25 or 70 VRMS, with selectable power taps from 1/8 watt to 2 watts. All models shall have listed sound output of up to 89 dBA at 10 feet and a listed frequency response of 400 to 4000 Hz. The speaker shall incorporate a sealed back construction. All inputs shall employ terminals that accept #12 to #18 AWG wire sizes. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall be of low current design. Where Multi - Candela Speaker Strobes are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110cd or 135/185cd for wall mounting. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on -axis is required. When synchronization is required, the strobe portion of the appliance shall be compatible with the Wheelock's SM, DSM sync modules or Wheelock PS- 24-8MC Power Supply with built -in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non - synchronized flash rate. The speaker and speaker strobe appliances shall be designed for indoor flush mounting to 4" x 2 -1/8" electrical boxes without need for an extension ring or surface mounting to Wheelock's E5OSB or E5OSSB surface boxes. The speaker and speaker strobe shall incorporate a speaker mounting plate with a snap -on grille cover. The finish of the Series E50 speakers and speakers strobes shall be white or red. Member WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY S0510 E50 02/08 NJ Location FL Location VA Location 273 Branchport Ave. 7565 Commerce Ct. P: 877- 459 -7726 Long Branch, NJ 07740 Sarasota, FL 34243 F: 703 - 294 -6560 P: 800-631-2148 P: 941 -487 -2300 F: 732 - 222 -8707 F: 941 - 487 -2389 www.coopernotification.com Cooper Notification is Wheelock° ;,i 3 �: SAFEPATW wnvig ' COOPER Notification COOPER Notification POWERPATHTM NAC POWER SUPPLIES • p •3+ 43 fig • 4 • .3' •,i d+^7y 33" y K i L. • fe 5 . q • 6•,.. ,s3 PS- 24-8MC Description Features POWERPATHT"' Series PS -24 -8MC is an 8 Amp, 24VDC, filtered Approvals and regulated, supervised remote power supply /charger used for supervision and expanded power driving capability for Fire Alarm • Approvals Include: UL Standard 864 California Notification Appliance Circuits. The PS- 24-8MC may be connected State Fire Marshal (CSFM), New York City (MEA), to any 12V or 24V (FWR or DC) Fire Alarm Control Panel (FACP) by Factory Mutual (FM), Chicago (BFP) See using a Notification Appliance Circuit (NAC) ora "Dry Contact ". Primary Approvals by model in Specification and Ordering applications include NAC expansion (supports ADA requirements) and Information auxiliary power to support system accessories. This unit provides • Compliant with NFPA 72 filtered and regulated 24VDC, 8 Amp up to four (4) Class "B ", two (2) Class "A ", or two (2) Class "B" and one (1) Class "A" Notification Inputs Appliance Circuits. With the optional plug -in PS- 4CAmodule the unit • 120VAC, 50 /60Hz, 5.0 Amps Operating Power in supports (4) Class "A" Notification Appliance Circuits. Additionally, Alarm an auxiliary power output of 3.5 Amps (disconnected upon AC power • 24VDC Battery Backup Connection loss or an alarm condition) or 200 mAmps (constant) is provided, , 12V or 24V NAC Initiating Circuits (8 -33V at which can be manually reset. The PS- 24-8MC also contains a battery • Two o (2) 2) FWR or DC charger capable of charging either 7 or 12 Amp /Hour (AH) of battery 5mA) backup. • Two (2) "Dry" Contact initiating Circuits Two FACP NAC circuits or two "Dry" contact initiating circuits can be • Accepts two (2) Class "A" or two (2) Class "B" connected to the POWERPATH inputs. These inputs can then be circuit inputs directed to control supervision and power delivery to any combination • Built in battery charger for sealed lead acid or get of the four (4) outputs. type batteries Each output is rated at 3.0 Amps (Class "B ") or (Class "A ") and can be programmed to generate a steady or Code 3 Temporal Horn sound and a strobe output under alarm condition. Total load for the PS -24- 8MC NAC circuits must not exceed 8.0 Amps. The PS -24 -8MC under non -alarm condition provides independent supervision for Class "A" and Class "B" FACP NAC circuits. In the event of circuit trouble, the FACP will be notified via the POWERPATH steered input (IN1 or IN2). In addition there are two sets of trouble reporting terminals, one used forAC power loss reporting and the other for all troubles. The AC power loss reporting, on the common trouble terminals and on IN1 or IN2, can be delayed for either 30 seconds or 170 minutes. The AC power loss terminals will always report the trouble 30 seconds after loss of AC power. The PS- 24-8MC POWERPATH is UL Listed under UL Standard 864, to be used with any 24 volt Listed Regulated notification appliances. It includes the capability to synchronize Wheelock strobes and horns and to silence the horn signal when hom /strobes are operating on two wires. � ® YA 1 . 1 M EA APPROVED 151.92 -E ...Features continued on next page Outputs • NAC outputs are 24VDC, 3.0 Amps each, power limited • 8 Amps total alarm current • Capable of four (4), Class "B" circuits • Capable of two (2) Class "A" circuits • Capable of four (4) Class "A" circuits with optional PS -4CA module • Capable of one (1) Class "A" circuit and two (2) Class "B" circuits • Temporal (Code 3) or constant voltage output • Built -in Wheelock synchronization mode that can be fed to any or all of the output circuits • Input and output can be synchronized with "IN >OUT SYNC" mode (SM, DSM or 2nd PS- 24 -8MC is required) • Audible silence capability • Filtered and electronically regulated output • 3.5 Amp auxiliary power limited output with reset capability. (Removed upon AC loss or alarm. Automatic reset 30 seconds after AC power returns or the alarm condition is over) or 200 mAmps auxiliary power limited output which remains on during AC loss or an alarm condition Supervision • Compatible with 12V or 24V (FWR or DC) FACP • Signaling appliance circuits are supervised and steered to either IN1 or IN2 • 2.2K Ohm, 1 Watt (Wheelock Model #MPEOL) End of Line Resistor (EOLR) for supervision of all outputs • AC loss trouble reported over a separate set of contacts (delay of 30 seconds) • All troubles are reported over the common trouble contacts (AC loss can have a delay of 30 seconds or 170 minutes) • Automatic switchover to standby battery when AC fails • Thermal and short circuit protection with auto reset • Input and output status LED indicators • AC fail supervision • Battery presence and low battery supervision • Ground Fault Detection (60K ohms) • 4 latching LED's for NAC trouble annunciation Power • Not Battery Dependent - Full 8A even if battery is degraded • Automatic switch over to standby batteries when AC fails . • Supports sealed lead acid or gel type batteries • Fused battery protection • Thermal and short circuit protection with auto reset • Supports both 7AH or 12AH batteries in the same cabinet (Cabinet Size: 16.70" H x 12.83" W x 5" D) Normal Mode (Class B) purl -� TO NEXT APPLIANCE a trili IECr•c.. iii ii, OR EOLR TE NPORAL . iii "'PUT SELECT (2.2K OHMS) F TO NEXT APPLIANCE, A A TO EOL IN • APPLE OUT • • 4 OR EOLR oREOL RETt .(2.2K OHMS) C POWERPATH TO NEXT APPLIANCE P OUT Er • E 4 OR EOLR (2.2K OHMS) !OE TO NEXT APPLIANCE; • • our �•I•. OR EOLR (2.2K OHMS) Normal Mode (Class A) OUIJA INsOUT SYNC OUT7 TO NEXT APPLIANCE p 017 . WHEELOCN SYNC " TEMPORAL ,,.., INPUT SELECT F OR EOLR R ETI OR RETURI TO FACP 01172 A 0 C POWERPATH .P OM ina OUT, • I 7 I 1 POWERPATH Tr" Operating Modes (refer to Installation Manual): Normal Mode: Provides constant 24 VDC output upon initiation by a voltage to input IN1 or IN2 or by a contact opening on DRY1 or DRY2. The unit returns to standby mode when the input is deactivated. Wheelock Sync Mode: Provides signals for synchronization of patented Wheelock audible and strobe notification appliances. Audibles can also be silenced in this mode while the strobes continue to flash. In >Out Sync Mode: Accepts a coded signal or synchronization signal on the input to provide a coded output or synchronized output. This signal may come from a FACP, another POWERPATH or a Wheelock SM or DSM synchronization module. Caution: Do not use strobes on coded output circuits. Temporal Mode: Codes the output voltage in a code -3 temporal pattern to drive audible appliances such as horns, bells or chimes. Caution: Do not use strobes on coded output circuits. Specifications and Ordering Information Order Approvals Model Number Code Input Voltage /Current UL MEA CSFM FM BFP PS- 24 -8MC 0237 120/220 VAC @ 50/60 Hz; 5.0 amps max. X X X X * PS -0CA 1648 Four class "A" plug -in module for PS- 24-8MC X X X X • Output NAC Circuit Output Voltage /Current Four (4) Class "B" or 24 VDC @ 3 amps per Circuit X= Approved Two (2) Class "A" or 24 VDC @ 3 amps per Circuit Pending One (1) Class "A" and Two (2) Class "B" or 24 VDC @ 3 amps per Circuit (Class "A ") Four (4) Class "A" (optional PS-4CA module) 24 VDC @ 3 amps per Circuit (Class "A ") Standby Current 0.080 Amps Alarm Current 0.240 Amps Total NAC Current 8 Amps Max. Standby Alarm Output Aux Output Standby Batteries Time Total Amps /Minutes CP Mode MP Mode 24 VDC /12 AH 24 Hours 8 Amps/15 Minutes 200 mA 3.5A during (uses two (2) 12 VDC batteries in series) 60 Hours 8 Amps /15 Minutes 60 mA nonalarm Architects and Engineers Specifications The power supply shall be Wheelock POWERPATHTM' Series PS -24 -8MC, or equivalent. The unit shall be stand alone power supply intended for powering fire alarm notification appliances via its own Notification Appliance Circuit(s) (NAC). The unit shall be UL 864 Listed for power limited operation of outputs and comply with NFPA 70 (NEC), article 760. The power suppliy shall support a full 8A of notification power even if the battery is in a degraded mode and only AC power is con- nected. The power supply shall be activated by a standard Notification Appliance Circuit (NAC) from any Fire Alarm Control Panel (FACP) or a "Dry contact" opening. The units shall be 8 ampere, 24 VDC, regulated and filtered, supervised remote power supply /charger. It shall operate over the voltage range of 8 to 33 VDC or FWR. The primary application of the unit shall be able to expand fire alarm system capabilities for additional NAC circuits to support ADA requirements and to provide auxiliary power to support system accessories or functions. The power supply shall provide four Class "B ", two Class "A ", or two Class "B" and one Class "A" NAC circuit(s). Four Class "A" circuits shall be available with an optional PS-4CA module. The PS -24 -8MC unit shall supply up to 200 mA of auxiliary power that is available during both nonalarm and alarm or auxiliary power of not less than 3.5A at 24 VDC during nonalarm. The power supply shall be capable of charging batteries of up to 12 ampere hours per NFPA 72. Input activation options shall be from not less than two NAC circuits or Dry Contact closures. These inputs shall have the capability of being directed to any combination of the four NAC circuit outputs. Each NAC circuit output shall be rated at 3 amperes for Class "B" applications or 3 amperes each for Class "A ". The outputs shall be programmable to generate a steady or Temporal (Code 3) output and or a synchronized strobe or horn output. The power supply shall provide independent loop supervision for either Class "A" or Class "B" FACP NAC circuits and shall have the capability to "steer" all alarm or trouble conditions to either incoming NAC circuit. The units shall have common trouble terminals. The power supply shall be powered from a 120 VAC source with a current consumption of 5 amperes max. The unit shall incorporate short circuit protection with auto reset. The power supply shall incorporate a built in battery charger for lead acid or gel type batteries with automatic switchover to battery back up in the event of AC power failure. The charger shall incorporate fused protection for the batteries and have the ability to report low battery and /or no battery condition(s). Standby current for battery back up shall be 80 mA max. The power supply shall have the ability to latch trouble LED's so the circuit in trouble can be identified. The cabinet dimensions shall be 16.70" H x 12.83" W x 5" D. A WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING. SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS. CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLA- TION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accor- dance with Wheelock Inc. standard terms and conditions. NMI Member - WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S8900 PS- 24-8MC 02/08 NJ Location FL Location VA Location 273 Branchport Ave. 7565 Commerce Ct. P: 877- 459 -7726 Long Branch, NJ 07740 Sarasota, FL 34243 F: 703 - 294 -6560 P: 800 - 631 -2148 P: 941- 487 -2300 F: 732-222-8707 F: 941- 487 -2389 www.coopernotification.com A ir k Cooper Notification is Wheelock° (;,I 'T' SAFEPATH' _ . : ..... ....... ......... COOPER Notification COOPER Notification Series RSS and RSSP Strobes and Strobe Plates FIRE ! tR H�_. FIRE FIRE Series RSS Series RSS Series RSSWP RSS Round Description Features • The Wheelock patented Series RSS Strobe Appliances and Approvals include: UL Standard 1971, New York City (MEA), Series RSSP Strobe Plates have lower current draw while California State Fire Marshal (CSFM), Factory Mutual (FM), and maintaining outstanding performance, reliability and cost Chicago (BFP) See approvals by model in Specifications and effectiveness. These versatile appliances will satisfy virtually all Ordering Information requirements for indoor, wall or ceiling mount applications. • ADA/NFPA/UFC /ANSI compliant. Meets OSHA 29 Part Strobe options for wall mount models include 1575 or the 1910.165 Wheelock Patented MCW multi - candela strobe with field • Wall mount Multi - Candela models are available with Field selectable candela settings of 15/30/75/110cd or the high Selectable Candela Settings of 15/30/ 75/110cd or 135/185cd. intensity MCWH strobe with field selectable 135/185cd. Single Candela models are available in 1575cd Ceiling mount models include the patented MCC multi-candela • Ceiling mount Multi- Candela models are ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable available with field selectable candela settings of 15/30/75/95cd 115/177cd. or 115/177cd. (Round or Square) All models may be synchronized using the Wheelock SM, • Strobes produce 1 flash per second over the regulated voltage DSM Sync Modules, Wheelock Power Supplies or other range manufacturers panels incorporating the Wheelock Patented 12 and 24 VDC models with wide UL "Regulated Voltage" us- Sync Protocol. Synchronized strobes can eliminate possible ing filtered (DC) or unfiltered VRMS input voltage restrictions on the number of strobes in the field of view. Wheelock's synchronized strobes offer an easy way to comply • Synchronize using the Wheelock sync modules or panels with with ADA recommendations concerning photosensitive epilepsy built -in Wheelock Patented Sync Protocol as well as meeting the requirements of NFPA 72. • Fast installation with IN /OUT screw terminals using #12 to #18 The Wheelock Series RSS Strobes employ a Patented Integral AWG wire Strobe Mounting Plate that can be mounted to a single gang, double gang, 4" square, 100mm European backboxes or the SHBB surface backbox. If the flush backbox has side or top space between it and the finished wall, the NATP (Notification For Weatherproof Series RSS See Datatsheet S9004 Appliance Trimplate) may be used. It provides an additional .65" of trim for the Appliance. An attractive cover plate is provided for a clean, finished appearance on all models. The Series RSSP Multi- Candela Strobe Plates are a cost effective way to retrofit required wall strobe appliances to bells, horns, chimes, multitones or speakers and easily mounts to standard 4" backboxes or for surface mount use with the Wheelock SBL2 surface backbox. ,7,,fr.:111 4-6) 4140o. A l _ MEA r APPROVED S5391 151 -92-E 7125-0785:141 - - - - - - • - 7300 - 0785:154 NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION ANDIOR . OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU ANDIOR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range ". Note that NFPA -72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 °F to 120 °F (0 °C to 49 °C) and maximum humidity of 93% (± 2 %). • Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology "Listed Voltage Range ". Table 1: Average RMS Current* RSS /RSSP - Wall Mount Ceiling Mount RSS /RSSP 241575W 24MCW 24MCWH 24MCC 24MCCH 24VDC Models - 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd UL max' 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420 RSS /RSSP RSS /RSSP Wall Mount 24VDC 24VDC * RMS current ratings are per UL average RMS method. UL max current M odels 121575W rating is the maximum RMS current within the listed voltage range (16 -33v for 24v units). For strobes the UL max current is usually at the minimum 12 vdc 0.152 listed voltage (16v for 24v units). For audibles the max current is usually at UL max* 0.255 the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. Table. 2: Audibles /Speakers for RSSP Strobe Plate Product Series Multitone Appliances AMT, MT Wiring Diagrams # SERIES RSS /RSSP APPLIANCE Horns AH, NH, HS Motor Bells MB- G6 /G10 FROM + + TO NEXT PRECEDING _ _ APPLIANCE Speakers ET- 1010/1080, E70, ET70 APPLIANCE, SYNC OR EOLR Chimes CH70 MODULE, POWER pi pi SUPPLY OR FACP ie • SERIES RSS /RSSP APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS "A" NAC CIRCUIT SERIES RSS /RSSP APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM MODULES DSM DSM #1 STROBE + 0 Sync ®® NAC CIRCUIT SYNC 0 Strobe NAC Or. F OUT G . IN 1 Ir® ® ® mow � / DSM #2 q ,' Nus Strobe NAC Cir.' , S e + O + AUDIBL MINUS I DSM #3 IN 2 P W�eit . $y+C ®® T r • N 2 2 Strobe NAC Cir. `y CIRCUIT RETURN DSM Interconnecting wiring shown. Maximum of twenty (20) STROBE/PLATE ASSEMBLY AUDIBLE & VISIBLE APPLIANCE OPERATE IN UNISON SERIES RSS /RSSP APPLIANCE SYNCHRONIZED WITH SM MODULE SINGLE CLASS "B" NAC CIRCUIT TO NEXT SM FROM APPLIANCE PRECEDING - OR EOLR F I STROBE APPLIANCE, SYNC I A S tr NAC ' 9 PROBE MO OR FACP ''�' ' /`1 I SUPPLY C Circuit STROBE AUDIBLE Q � *Audible P ZEudR {(� Audible STROBE /PLATE ASSEMBLY SERIES RSS /RSSP APPLIANCES SYNCHRONIZED AUDIBLE & VISIBLE APPLIANCE OPERATE INDEPENDENTLY WITH PS- 12/24 -8CP or PS- 12/24 -8MP Series PS- 12/24 -8MP FROM + + PRECEDING TO NEXT APPLIANCE APPLIANCE OR _ - FACP OR EOLR OUTPUTS 11141 EOLR 11 1 FROM T - — 1 r — — — — — 1 - 4 T TO 4 - CLASS B• PRECEDING 11 STROBE OR • y STROBE, SYNC - — I 1 r EOLR OR 411 MODULE. POWER 1 SUPPLY OR FACP 2 - CLASS AS El . Hi STROBE APPLIANCE " For detail using SM or DSM Sync Module refer to Data Series PS- 12/24 -8MP Ia Sheet S3000 or Installation Instructions P83123 for SM , and P83177 for DSM. For wiring information on the power supplies refer PS- 24 -8MC. Specifications and Ordering Information ! Square Agency Approvals Model Order Wall Ceiling Non- Strobe 24 12 Color Color Mounting Options*** or Code Mount Mount Sync Candela VDC VDC RED WHITE Round UL MEA CSFM FM BFP RSS - 24MCW - 940 X - X 15/30/75/110 X - X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS - 24MCW -FW 9401 X - X 15/30/75/110 X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS- 241575W -FR 7471 X - X 15 (75 on Axis) X - X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS- 241575W -FW 7788 X - X 15 (75 on Axis) X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS- 121575W -FR 7476 X - X 15 (75 on Axis) - X X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS- 121575W -FW 7468 X - X 15 (75 on Axis) - X - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS - 24MCC -FW 3158 - X X 15/30/75/95 X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X • RSS - 24MCC -FR 3157 - X X 15/30/75/95 X - X - B,D,E,F,G,H,J,N,O,R,X Square X X X X • RSS - 24MCCR -FW 3160 - X X 15/30/75/95 X - - X B,D,E,F,G,H,J,N,O,R,X Round X X X X • RSS-24MCCH-FW 3461 - X X 115/177 X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X • RSS- 24MCCHR -FW 3463 - X X 115/177 X - - X B,D,E,F,G,H,J,N,O,R,X Round X X X X • RSS- 24MCWH -FR 3465 X X 135/185 X X B,D,E,F,G,H,J,N,O,R,X Square X X X X • RSS- 24MCWH -FW 3464 X X 135/185 X X B,D,E,F,G,H,J,N,O,R,X Square X X X X • RSSP- 2475W -FR" 9013 X - X 180@ 77 °F W X X X - B,D,E,F,G,H,J,N,O,R,X Square X X X X • 75@ -31°F RSSP- 2475W -F 3034 X - X 180© 77 °F W W * X X - X B,D,E,F,G,H,J,N,O,R,X Square X X X X ` 75@ -31 °F RSSP- 121575W -FR 7798 X - X 15 (75 on Axis) - X X - D,E,Z Square X X X X X RSSP - 24MCW -FR 9402 X - X 15/30/75/110 X - X - D,E,Z Square X X X X X RSSP- 241575W -FR 7793 X - X 15 (75 on Axis) - X - D,E,Z Square X X X X X `PENDING All models sync with Wheelock SM, DSM or PS- 12/24 -8CP or PS- 12/24 -8MP. # Models are available in either Red or White. Call Customer Service for Order Code & Delivery. — For Weatherproof Series RSS Strobe specifications see data sheet S9004. ***Refer to data sheet S7000 for mounting options: - - - - -- Architects and Engineers Specifications The visual notification appliances shall be Wheelock Series RSS Strobe Appliances or approved equals. The Series RSS shall meet and be listed for UL Standard 1971 (Emergency Devices for the Hearing- Impaired) for Indoor Fire Protection Service. The strobe shall be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. The strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). When Strobe Plates are to be installed, they shall be the Wheelock Series RSSP Strobe Plate and shall have the same electronic circuitry as the Wheelock Series RSS. The Series RSS Strobe shall be of low current design. Where Multi - Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110cd or 135/185cd for wall mount and 15/30/75/95cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compatible with Wheelock's SM, DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built -in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain dosed), the strobe shall revert to a non - synchronized flash rate. The strobes shall be designed for indoor surface of flush mounting. The Series RSS Strobe Appliances shall incorporate a Patented, Integral Strobe Mounting Plate that shall allow mounting to single - gang, double -gang, 4 -inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided. An attaching cover plate shall be provided to give the Appliance and attractive appearance. The Appliance shall not have any mounting holes or screw heads visible when the installation is completed. The Series RSSP Multi - Candela or single candela Strobe Plate shall mount to either a standard 4 inch square backbox for flush mounting, or the Wheelock SBL2 backbox for surface mounting. All notification appliances shall be backward compatible. NOTE' Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock. Inc. standard terms and conditions. NEM Member WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA SO410 RSS /RSSP 02/08 NJ Location FL Location VA Location 273 Branchport Ave. • 7565 Commerce Ct. P: 877- 459 -7726 Long Branch, NJ 07740 Sarasota, FL 34243 F: 703 - 294 -6560 P: 800- 631 -2148 P: 941- 487 -2300 F: 732-222-8707 F: 941-487-2389 - www.coopernotification.com - Cooper Notification is Wheelock° I I:I) SAFEPATH' wAVg- - COOPER Notification