Loading...
Correspondence City of Tigard, Oregon ® 13125 SW Hall Blvd. O Tigard, OR 97223 t a March 26, 2008 4 .. ©o b £y / ° Afauvato cif y sn RE: RAcacs TrGARDp Proiect Information Building Permit: BUP2008 -00081 Construction Type: 2 -B Address: 9619 SW Washington Sq. Occupancy Type: M /S -1 Area: 19,328 Sq. Ft. Stories: 2 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code. Sign Required: Provide signage on racks that state "NO STORAGE ABOVE 12 FEET ALLOWED" Fire Extinguishers: Provide 2 -A rated fire extinguishers as required per table 906.3 (1) of OFC the extinguisher shall be located so that no usable space has a distance greater than 75 feet to the extinguishers. OFC 906.3 Clearance: The clearance between the sprinkler deflector and the top of storage shall • be 18 in. or greater. NFPA 13 8.5.6.1 Loads Posted: The racks shall display in one or more conspicuous locations a permanent plaque not less than 50 square inches in area, showing the maximum permissible unit load in clear legible print. OSSC 1603 When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Ede Dan Nelson Senior Plans Examiner (503) 718 -2436 dann @tigard- or.gov Phone: 503.639.4171 ® Fax: 503.684.7297 0 www.tigard- or.gov o TTY Relay: 503.684.2772