RE: ELECTRICAL PLANS REVIEW
Dear Mr. Gajic:
Project Information
Permit: ELC 2003 -00500
Tenant: Apple Computer
r Address] 9530 SW Washington Square Suite H 10
This plans review is based on the 2002 edition of the National Electrical Code (NEC).
The plans received on August 13, 2003 have been reviewed and are not approved as submitted. The
following items shall be revised (revisions clouded) on the plans and addressed in a response letter.
Two complete sets of the revised plans and the response letter shall be submitted to this office for
review and approval prior to issuance of the electrical permit. Please note: Loose pages are not
acceptable.
1. Provide the available fault current at panels "H ", "E" and `B"
2. Provide the documentation from the manufacturer for the Series -rated overcurrent devices.
3. Provide a lighting energy budget. The information and forms are on the Net at
www.energy.state.or.us. Go to Building Codes and click on Non Residential Code.
4. Amend the Electrical Responsibility Schedule to show that all electrical equipment is to be
installed by the Electrical Contractor per Oregon Electrical Safety Law Chapter 479.
5. Provide show window outlets per Article 210 -62
6. Correct all code references to reflect the 2002 NEC.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
Mr. Gajic
August 14, 2003
Page 2
If I can be of any additional assistance, please feel free to contact me at (503) 718 -2446.