Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 • December 7, 2006 T =I�GA�RD oFJtii ;�Sts`Ga Western Design Group Karen Huset 4612 NE Minnehaha St Vancouver, WA 98661 RE: FOREVER 21 - REVIEW Project Information Building Permit BUP2006 -00503 Construction Type: II -B Tenant Name: Forever 21 Occupancy Type: M Address: 9601 SW Washington Sq Occupant Load: 579 Area: 18,329 sq ft Stories: 2 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition and 2004 Oregon Fire Code (OFC) as amended by TVF&R. The submitted plans are approved subject to the following conditions. 1. Special inspection is required for concrete, welding, bolting, welded studs, embed plates, bolts in concrete, structural steel fabrication and erection, adhesive and expansion anchor installation, as items listed on sheet S0.0. The special inspection agency of record shall furnish inspection reports to the Engineer of Record, VLMK Engineers, the General Contractor, and the City of Tigard, Building Division, attention Hap Watkins. All discrepancies shall be brought to the immediate attention of the general contractor for correction. The special inspector shall submit a final signed report stating whether the work requiring special inspection was, to the best of the inspector's knowledge, in conformance with the approved plans and specifications and the applicable workmanship provisions of the code. 1704, 1705, 1707, 1708 OSSC FYI The special inspections do not waive any of the inspection required by code. 2. Structural Observations is required by the engineer of record on structural steel erection. Deficiencies shall be reported in writing to the owner and to the City of Tigard, Building Division, attention Hap Watkins. FYI The structural observations do not waive any inspection required by code. 3. Live Loads Posted: The live loads for which each floor has been designed to exceed 50 psf shall be conspicuously posted by the owner in that part of each story in which they apply, using durable metal signs, and it shall be unlawful to remove or deface such notices. The occupant of the building shall be responsible for keeping the actual load below the allowable limits. 1603.3 OSSC 4. Provide 2 -A rated fire extinguisher per OFC table 906.3(1) on the first and second story area. The extinguisher shall be located so that no usable space has a distance greater than 75 feet to the extinguishers. OFC 906.3 Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 5. The main exterior door or doors are permitted to be equipped with key- operated locking devices from the egress side provided: 1. The locking device is readily distinguishable as locked, 2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. Sec. 1008.1.8.3 6. All exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. Sec. 1008.1.8 7. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Sec. 1011.1 8. Exit signs shall be illuminated at all times and shall be provided with a second source of power that will provide 1 1/2 hours of illumination in case of primary power loss. Sec. 1006.3 FYI Additional exit signs may be required by the city field inspector to clearly indicate the path of egress. 9. The means of egress shall be provided with illumination of not less than 1 foot candle at the floor level anytime the building is occupied. The means of egress illumination shall be provided with a second source of power in case of primary power loss. Sec. 1006.2 10. Accessible checkout aisles shall be on an accessible route and at least 36 inches wide. Counters in accessible checkout aisles shall be not more than 38 inches (965 mm) high and the top of the raised edge of the counter shall not exceed 40 inches (1016 mm) in height above the finished floor. Accessible checkout aisles shall be identified by the international symbol of access. Sec. 1109.19, 1109.23.3 11. Floor drains shall not be located within the clear floor space at a lavatory, water closet, urinal, or bathtub or shower. Floors shall not slope in excess of 1 unit vertical in 50 units horizontal (2 % slope). Floor drains shall comply with Section 1109.4.5 and be without abrupt changes of level. Exception: Floor drains may be located within a clear floor space at a frxtune provided the openings in the drain corer shall not exceed 1/2 inch (12.7 mm) in any direction and the drain cover shall be no more than 1 /8 inch below the level of the surrounding finished floor surface. 1109.10.1 OSSC 12. Safety glazing including but not limited to: the following locations: Each unit of glazing shall be �.l permanently identified by the manufacturer. Sec. 2406. Some of these locations are as follows: a. Glazing in ingress and means of egress doors. b. Glazing in an individual fixed or operable panel adjacent to a door where the nearest vertical edge is within a 24" arc of the door in a closed position and whose bottom edge is less than 60" above the floor or walking surface except when there is an intervening wall or other permanent barrier between the door and the glazing. 13. Deferred submittals; Deferred Items: None listed NOT PART OF THIS REVIEW: * Electrical * Fire Sprinklers /Alarm * Mechanical System * Plumbing American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC, which may not include all of the requirements of the ADA. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC Certificate of Occupancy: No building or structure shall be used or occupied until the Building Official has issued a certificate of occupancy 109.1 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter' of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respec .�..� y / e ,/ zel, Senior Plans Examiner y .. • CONS ULTING 503.222.4453 v14m 503.24 ENGINEERS G I N E E R S 8192. 8192 @vlmk.com 3933 SW Kelly Avenue • Portland • Oregon 97239.4393 www.vlmk.com RECE December 1, 2006 Val Henzel I GE L 0 5 20 06 V E D Senior Plans Examiner B UILDING CITY OF TIGARD City of Tigard DIVISION 13125 SW Hall Blvd. Tigard, OR 97223 Re: BUP2006 -00503 - Forever 21 Dear Val: The following is in response to your plan check comments dated November 7, 2006: Item #1: Provided a complete code analysis on the building space utilizing current codes see attached. Building is to be upgraded to type II -B per prior construction area increase allowance. Response: This to be answered by Forever 21. Item #2 Provide engineer design calculations with construction details showing ceiling system meets chapter 16. OSSC 106. Response: Please refer to detail 1 and 2 S4.0 for standard industry accepted details. Item #3 Provide egress path information (The construction documents shall show in sufficient detail the location, construction, size and character of all portions of the means of egress in compliance with the provisions of this code. The construction documents shall designate the number of occupants to be accommodated on every floor, and in all rooms and spaces. OSSC 106.1.2). Response: This to be answered by Forever 21. Item #4 Provide engineered design calculations with construction details on the stand alone store front system. OSSC 106, ch 15. Response: See attached sheets S3.0, S3.1, S4.0 and calculation pages FFS -1 and SFS -1. • Structural Engineering•Civil Engineering. Industrial Engineering•Planning•Studies /Evaluations•Entitlement : \Ac; ;c1206 \206434..'. \Pi;:n Check RespKn e, Dc Forever 21 - Washington Square Permit #BUP2006 -00503 December 1, 2006 Page 2of2 Item #5 Provide construction details for stairway as shown on sheet A1.0.0 - A1.01 to go with submitted engineer design calculations. OSSC 106 & ch. 16. Response: The structural drawings must not have been submitted. However, drawings S0.0, S1.0 and S1.1 are attached. Item #6 Provide engineer design calculations with construction details on walls, soffit and cove for lateral support etc. OSSC 106, ch 16. Response: Please refer to detail 1„2 and 3/S4.0 for standard industry accepted details. In addition see calculation sheet W -1. If you have any additional questions or concerns, please do not hesitate to contact me. E fv / jf / p ,•'<1 75- Richard M. Boyer, P.E., Associate N • Kt'n' , gineers v Q A ,, - - - :0 Additional Structural Calculations Drawing Sheets S0.0, S1.0, S1.1, S3.0, S3.1 and S4.0 [EXPIRES: 12 /31/20 C) j • City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 mil November 7, 2006 += ®�r Western Design Group Karen Huset 4612 NE Minnehaha St Vancouver, WA 98661 RE: FOREVER 21 — REVIEW # 1 Project Information Building Permit BUP2006 -00503 Construction Type: II -B Tenant Name: Forever 21 Occupancy Type: M Address: 9601 SW Washington Sq Occupant Load: 579 Area: 18,329 sq ft Stories: 2 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition and 2004 Oregon Fire Code as amended by TVF&R. The following information is required in order to complete the review. "Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code and relevant laws, ordinances, rules and regulations (OSS 106.). *Cross section(s) and details. Show all framing -member sizes and spacing such as floor beams, headers, joists, sub -floor, wall construction, roof construction. More than one cross section may be required to clearly portray construction." 1. Provide a complete code analysis on the building space utilizing current codes see attached. Building is to be upgraded to type II -B per prior construction area increase allowance. 2. Provide engineer design calculations with construction details showing ceiling system meets chapter 16. OSSC 106 3. Provide egress path information(The construction documents shall show in sufficient detail the location, construction, size and character of all portions of the means of egress in compliance with the provisions of this code. The construction documents shall designate the number of occupants to be accommodated on every floor, and in all rooms and spaces. OSSC 106.1.2) 4. Provide engineered design calculations with construction details on the stand alone store front system. OSSC 106, ch 16 5. Provide construction details for stairway as shown on sheet A1.0.0 — A1.0.1 to go with submitted engineer design calculations. OSSC 106 & ch.16 Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard - or.gov • TTY Relay: 503.684.2772 • 6. Provide engineer design calculations with construction details on walls, soffit and cove for lateral support etc. OSSC 106, ch 16 NOT PART OF THIS REVIEW: *Mechanical *Pluming *Fire sprinkler *Electrical *Fire alarm *Racks * Awnings Deferred submittals such as Truss Joist Shop Drawings, TJI floor joist, Acoustical ceiling suspension system, Fire stopping, Intercom system, Specialty retaining walls, etc, will be charged a deferred submittal fee based on the valuation of the portion of the work being deferred. The minimum fee shall be $200.00. This fee is in addition to the project plan review fee based on the total project value. OAR 918- 050 -0150 "Documents for deferred submittal items shall be submitted to the registered design professional in responsible charge who shall review them and forward them to the building official with a notation indicating that the deferred submittal documents have been reviewed and been found to be in general conformance to the design of the building. The deferred submittal items shall not be installed until the design and submittal documents have been approved by the building offidal Oregon Structural Specialty Code Section 106.3.4.2" Please provide an item by item response. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Val Henzel, Senior Plans Examiner