COMMENTS: Bob this is from Kramer Gehlen Associates. We are using exiting opening in roof.
Thank You
Art Schacher ` At'
170 :39W L62L178920Sc01 6L8TT6920S MO&I :WOad 80:TT 00 82 -d3S
y '
September 26, 2000�_I I111
CITY OF TIGARD
Arrow Mechanical OREGON
10330 SW Tualatin Road
Tualatin, OR. 97062
RE: The Sharper Image MEC #2000 -00373
9585 SW Washington Square
Dear Applicant:
Your plans have been zeviewed for compIian with State Code; the following items require your
attention.
l . Provide Engineering for loads imposed and lateral force. OSSC, Section 1632.
2. Provide a gas piping schematic.
3. Provide Oregon Non - Residential Energy Code Forms 4a through 4j.
If you have questions, please call me at 639 -4171 X392.
Sincerely,
04LZ 7des
R bert Poskin, 030
Senior Plans Examiner
raK ,'cJ 72.9
!,;
SEP 2 t.7 20G0
13125 SW Hall Blvd.. Tigard. OR 97223 (503) 639 -4171 TDD (503) 684 -2772 • -- -
TO:3Sdd L62Lf8920S :01 6LBTT6920S MONelb:WOAld LO: TT 00 82 -d3S -
SEP -28 -00 09:03 FROM- WESTERN CONSTRUCTION SERVICES INC, 1- 380 -894 -7818 T -660 P 03/04 F -024
„ & ASSOCIATES. INC.
400 Columol9 St
Consulttng Eng,neere Suite 240
Structural /Civil
KRAMER Vancouver, WA
98660 -3117
GEHLEN
360 r 693 -1621
so3 / 289.2661
Fax
September 25, 2000 ASSOCIATES 3so
asvi sss -lsrx
Mr. Ron Edwards
Western Construction Company
4612 N. E. Minnehaha
Vancouver, WA 98665
RE: Sharper Image, Located at Washington Square In Beaverton, Oregon
KGA Project No. 00 - 296
Dear Ron:
On September 21, 2000, I met with Bill Frenzel of Western Construction Company at the project
site. He identified where they wanted to cut a 2' -0" diameter opening in an existing concrete
masonry wall. The existing concrete masonry wall was currently acting as a spandrel that was
approximately 20' tall above the existing opening. The spandrel had been reinforced with external
metal added to the bottom and sides of the concrete masonry.
The new opening was to be located very near a column that was providing support for the concrete
masonry spandrel. It was Intended to be approximately 5'-0" above the bottom of the spandrel.
Structurally, this new opening should be acceptable, as the shear of the concrete masonry and the
bending capabilities of the concrete masonry will only be affected in a very minor way.
The second Issue we reviewed was the locations of additional mechanical equipment on the roof.
There was a 1,200 lb. make up air unit that was intended to be added to the roof. Initially, we
discussed locating it near an existing column; however, the Mall Manager Indicated he wanted to
re -use the existing curbs on the roof and utilize short, over -the -roof duct runs to existing openings
that were approximately 4' -0" from the existing curbs,
The existing curbs appeared to have supported a condenser previously, as they were two isolated
curbs. There was an adjacent location where two similar existing curbs were supporting a new
mechanical unit. The mechanical unit would be required to span across from one curb to the other.
I would additionally recommend that there be four (4) %" x 4" lag bolts used to anchor the contact
points of the new mechanical equipment to the existing curbs. I have Included our calculation
indicating that the mechanical equipment should not overload the existing roof.
In addition, it appears as though the original condenser was removed and, more than likely,
weighed as much or more than the new, proposed make up air unit. Therefore, with the above -
described anchorage the new unit should be able to utilize the existing curbs.
I trust the above information is satisfactory for your needs. If you have any questions, please call
our office.
Sincerely,
Rick E. Jones, , .
Kramer Gehlen & Associates, Inc. AntikiCAN c�atAn�
pY .
20 :39dd L62Lt'8920S :01 6L8TT6920S MOZINd:WOdd 80 :TT 00 82 -d3S
SEP -29 •00 09:04 FROM- WESTERN CONSTRUCTION SERVICES INC, 1- 360 - 994 •1916 T -669 P.04/04 F -024
t K
ic•x/ s r
_ �NC. f oOF ST-mac ru IcE
X[5T /N
Mt�C1+ w7' (Z- c)O LD /JONST = Goa*
D a r ri o N ,9- c., 1"7 . (v o O (3 o /4-) 4 SUo 1_*
a _ ¢ s o c i (e)/( ) - = ¢o p.) f
ECk Ps 4-0/c = /c.e0 p f
EX/srI P2)4- Gvin(6S /Nb) CAT S re-GO
C. G = 3 S p s -F L t , I I C I I S / v c -F )4 /) /€/(
rZ lY E C;2 ' to • . S / nv C 6.6/60%-c IS S i• 7,4 -4-L
ra Ili / es 4 / a iv i Q t - 7 tf C.( A/ /
✓C / -'oC? D Nor OciNc re e,0 )46 T/ E'X/sr/A C
d -OO ST)2 u c It E . T I-I E x is T" / /1/416 C ,z,es r3
d Al a we fc x/ Si Jot s~"
MEW
A
PrfOrECT r 4
I I r l ` V P Ec r - , t�, , z p ,Z v 1 liN AG t -- 14.44- SC..2 S r/ N (i 2 OC F
I Al CLIENT /r+
S. � 1 CO I 1 - ICE
KRAMER CONSULTIN 0 6NGINEERe- .$TRJCTURAI,/JIVIL DATE DESipN
GEHLEN 40ot,aumola 3901113-1691 9 / ZS /Z—V.
s,,.IB 240 V eneeur er, 103 / X9661 !(
WA
Mu GOT No. SWEET
R4
ASSOCIATES $0660 -31i7 MO/ 898.7572
20 :391Jd L62Lb8920S :01 6L8TT6920S MaNd :Wald 80 :TT 00 82 -d3S
September 26, 2000
CITY OF TIGAR�
Arrow Mechanical OREGON
10330 SW Tualatin Road
Tualatin, OR. 97062
RE: The Sharper Image MEC #2000 -00373
9585 SW Washington Square
Dear Applicant:
Your plans have been reviewed for compliance with State Code; the following items require your
attention.
. Provide ineerin for loads imposed and lateral force. OSSC, Section 1632.
Engineering P
2. Provide a gas piping schematic.
3. Provide Oregon Non - Residential Energy Code Forms 4a through 4j.
If you have questions, please call me at 639 -4171 X392.