Loading...
Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 January 28, 2008 q • • • • RE: TENANT IMPROVEMENT T I GARD Project Information Building Permit: BUP2008 -00014 Construction Type: 2 -B Address: 9567 SW Washington Sq. Occupancy Type: M Area: 1482 Sq. Ft. Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code. Please respond to conditions below. 1) Please provide engineered design for the grid ceiling supports, including seismic struts, taking into consideration the approximate 17 -20 ft. of interstitial space between the ceiling tile and the roof. Please include all calculations for engineered designs with all submittals. OSSC106.1 2) Construction requirements for suspended ceiling systems are found in the Oregon Building Codes Division website under Statewide Code Interpretations dated 4/20/2007. (see enclosed) 3) Provide calculations and construction details (including seismic bracing details for non full height partitions) for all walls. Note: The roof structure is approximately 30' above the finished floor. OSSC 106.1 4) Please provide calculations and construction details for the soffits and storefront construction. Every structure, and portion thereof, including non structural components that are permanently attached to structures and their supports and attachments, shall be designed and constructed to resist the effects of earthquake motions in accordance with ASCE 7 as modified by Section 1613.7. The seismic design category for a structure is permitted to be determined in accordance with Section 1613 or ASCE 7. OSSC 1613.1 When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfu , Dan Nelson Senior Plans Examiner (503) 718 -2436 dann@tigard -or.gov Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 City of Tigard, Oregon o 13125 SW Hall Blvd. ® Tigard, OR 97223 , "} March 7, 2008 _ 7 ., w:. RE: TENANT IMPROVEMENT 4* s �_ TIGti Di Project Information Building Permit: BUP2008 -00014 Construction Type: 2 -B Address: 9567 SW Washington Sq. Occupancy Type: M Area: 1482 Sq. Ft. Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code. Provide the following items prior to issuance of this permit. 1) All improvements made to the building shall be inspected prior to covering. 2) Make approved set of plans available for all inspections. 3) A total of 25% of the cost of the project shall go towards removing architectural barriers (accessibility). FIRE LIFE AND SAFETY / GENERAL The main exterior door or doors are permitted to be equipped with key - operated locking devices from the egress side provided: 1. The locking device is readily distinguishable as locked, 2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. (Sec. 1008.1.8.3) All exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. (Sec. 1008.1.8) Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. (Sec. 1011.1) Exit signs shall be illuminated at all times and shall be provided with a second source of power that will provide 1 1 /2 hours of illumination in case of primary power loss. (Sec. 1006.3) FYI - Additional exit signs may be required by the city field inspector to clearly indicate the path of egress. The means of egress shall be provided with illumination of not less than 1 foot candle at the floor level anytime the building is occupied. The means of egress illumination, when two exits are required, shall be provided with a second source of power in case of primary power loss. (Sec. 1006.2) Portable fire extinguishers shall be installed in new and existing Group A, B, E, F, H, I, M, R -1, R -2, R-4, and S occupancies. (OFC Sec. 906) Phone: 503.639.4171 o Fax: 503.684.7297 ® www.tigard- or.gov o TTY Relay: 503.684.2772 rr American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and inspects the structure only for compliance with Chapter 11 of the OSSC, which may not include all of the requirements of the ADA. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. (106.3.1 OSSC) Certificate of Occupancy: No building or structure shall be used or occupied until the Building Official has issued a certificate of occupancy (109.1 OSSC) Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. espectfully, N an Nelson Senior Plans Examiner (503) 718 -2436 dann @tigard- or.gov