Correspondence ^
rjk
October 11, 2005
CITY OF TIGARD
OREGON
Commercial Permits, Inc.
Brigitte Arms
2620 63`I St
Fennville, MI 49408
RE: REGIS - REVIEW
Project Information
Building Permit: BUP2005 -00479 Construction Type: II-B
Tenant Name: Regis Occupancy Type: B
Address: 9510 SW Washington Sq Occupant Load: 50
Area: 1,506 sq ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
edition; and 2003 International Fire Code as amended by TVF &R The following information is
required in order to complete the review.
1. The main exterior door or doors are permitted to be equipped with key - operated locking
devices from the egress side provided:
1. The locking device is readily distinguishable as locked,
2. A readily visible durable sign is posted on the egress side on or adjacent to the door
stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.
The sign shall be in letters 1 inch (25 mm) high on a contrasting background.
2. All exit doors shall be openable from the inside without the use of a key or any special
knowledge or effort. 1008.1.8 OSSC
3. The means of egress shall be provided with illumination of not less than 1 foot candle at the
floor level anytime the building is occupied. The means of egress illumination shall be
provided with a second source of power in case of primary power loss. 1006.2 OSSC
4. Safety glazing including but not limited to: the following locations: Each unit of glazing shall
be permanently identified by the manufacturer. 2406 OSSC. Some of these locations are as
follows:
a. Glazing in ingress and means of egress doors.
b. Glazing in an individual fixed or operable panel adjacent to a door where the nearest
vertical edge is within a 24" arc of the door in a closed position and whose bottom
edge is less than 60" above the floor or walking surface except when there is an
intervening wall or other permanent barrier between the door and the glazing.
5. Accessible checkout aisles shall be on an accessible route and at least 36 inches wide.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
Counters in accessible checkout aisles shall be not more than 38 inches (965 mm) high and
the top of the raised edge of the counter shall not exceed 40 inches (1016 mm) in height
above the finished floor. Accessible checkout aisles shall be identified by the international
symbol of access. OSSC section 1109.19, 1109.23.3
6. Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings, etc, will
be charged a deferred submittal fee based on the valuation of the portion of the work being
deferred. The minimum fee shall be $200.00. Deferred Items: None listed
NOT PART OF THIS REVIEW:
* Electrical * Mechanical System * Plumbing
* Fire Sprinklers * Fire Alarms
7. American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the
structure only for compliance with Chapter 11 of the OSSC, which may not include all of the
requirements of the ADA.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.3.1 OSSC
Certificate of Occupancy: No building or structure shall be used or occupied until the Building
Official has issued a certificate of occupancy 110.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new buildings
in such a position as to be plainly visible and legible from the street or road fronting the property.
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
Respectful ,
Val Henzel
Senior Plans Examiner
' •10/11/2005 08:37 FAX 952 918 4602 REGIS CORPORATION fl 002/005
09/30/2805 10:30 5036243681 TIGARD BUILDING DEPT PAGE 01/01
4 710 4(.4,04,66, leol
•
September 30, 2005 CITY OF TIGARD
OREGON
Commercial Permits, Inc.
•
Brigitte Arms
2620 63 St
Fennville, MI 49408
RE: REGIS - REVIEW
Projectinfoun4i111
Building Permit: BUP2005 - 00479 Constriction Type: II -
Tenant Name: ...., Regis ........ Occupancy Type: M
Address_ 9459 SW Washington Sq Occupant Load: 51
Area: 1,506 sq @ Stories:
The plan review was performed under the State of Oregon Structural Specialty Code (OS SC) 2004
edition; and 2003 International Pire Code as amended by TVI: &R. The following information is
required in order to complete the review.
PRELIMINARY REVIEW
1. provide cover sheet for this set of plans_
2. Provide framing details showing all construction details at being done on interior walls
and at front entry.
NOT FART OF TEES REVIEW:
* Electrical * The Sprinklers
" Fire Alarms " Mechanical System
* Plumbing
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal, 'The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
al
Senior Plans Examiner
503.7e 2 430 ,
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684-2772