Loading...
Specifications 4 0,,O 01 'oo ,5 tqco Fire & Building Products SECE Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 JUN 19 2007 cir Ql ' IR R ARD Series RFII — 5.6 K- factor BUPI DIVISIO DING "Royal Flush II" Pendent Concealed Sprinklers Quick & Standard Response, Standard Coverage - - -- General Cap. The Protective Cap i temporarily removed for installation, and then it can be replaced to help protect the Oft Description sprinkler while the ceiling is being in- / stalled or finished. The tip of the Pro- _ . The Series RFII Quick Response tective Cap can also be used to mark _ _ (3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas- _ - _ mm bulb), 5.6 K- Factor, "Royal Flush ter board, ceiling tiles, etc. by gently II" Concealed Pendent Sprinklers are pushing the ceiling product against the f ..„- = °^�° --„:: decorative sprinklers featuring a flat Protective Cap. When the ceiling in- cover plate designed to conceal the stallation is complete the Protective sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate tecturally sensitive areas such as hotel Assembly installed. lobbies, office buildings, churches, As an option, the Series RFII Standard and restaurants. Response (5 mm bulb) "Royal Flush II" Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be sembly that conceals the sprinkler op- fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175 erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM. The separable two -piece design of the intended for sensitive areas where it is Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical blies allows installation of the sprin- through the cover plate from the area klers and pressure testing of the fire above the ceiling. Data protection system prior to installation WARNINGS of a suspended ceiling or application The Series RFII Concealed Pendent Approvals for Series RFII of the finish coating to a fixed ceiling. Sprinklers described herein must be U and C -UL Listed. FM Approved. They also permit removal of sus- i nstalled and maintained in compli- NYC under MEA 353-01-E. LPCB Ref. pended ceiling panels for access to p " building service equipment without ante with this document, as well as No. 094a/09 for TY3551 & 094a/10 for having to first shut down the fire pro- with the applicable standards of the TY3531) Approved. hav system and remove sprinklers. National Fire Protection Association, The approvals apply only to the serv- raig in addition to the standards of any ice conditions indicated in the Design Also, the separable two-piece design f the the Sprinkler wo p other authorities having jurisdiction. Criteria section and maximum pres- inch (12,7 mm) okverprovides e e for ign for 1 2 Failure to do so may impair the per- sure ratings indicated in the formance of these devices. Model/Sprinkler Identification Num- to reduce the accuracy to which the res The owner is onsible for maintain- bers section. length of fixed pipe drops to the sprin- p klers must be cut. ing their fire protection system and de- Approvals for Air & Dust Seal vices in proper operating condition. Part #10908100 The Series RFII Sprinklers are The installing contractor or sprinkler U L and C -UL Li for use with the shipped with a Disposable Protective manufacturer should be contacted RFII (TY3551 & TY3504) Standard Re- with any questions. sponse Concealed Sprinkler. IMPORTANT Temperature Ratings Always refer to Technical Data Model /Sprinkler 155F/68C Sprinkler - 135F/57C Plate Sheet TFP700 for the `INSTALLER 200F/93C Sprinkler - 165F/74C Plate WARNING" that provides cautions Identification Discharge Coef i ient with respect to handling and instal- K = 5.6 GPM /psi �' (80,6 LPM /bar lation of sprinkler systems and com- Numbers Adjustment ponents. Improper handling and in- 1/2 inch (12,7 mm) stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm Finishes a sprinkler system or its compo- bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass nents and cause the sprinkler to fail UL, C -UL, FM, LPCB and NYC. Plated, or White Painted (Custom paint to operate in a fire situation or cause TY3504 (5 mm bulb) & TY3505 (3 mm matches and colors other than white it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by are available on request.) Page 1 of 4 JULY, 2004 TFP181 • • Page 2 of 4 TFP181 Physical Characteristics 1/2° NPT SEALING Frame Bronze f ASSEMBLY Support Cup . Chrome Plated Steel Guide Pins Stainless Steel FRAME Iii � Deflector Bronze f �__ CAP Compression Screw Brass i� I n d j ; Bulb Glass `• Cap Bronze or Copper SUPPORT Sealing Assembly ROLL CUP FORMED WITH �I' BULB Beryllium Nickel w/Teflon* , Cover Plate Brass THREADS — ` Retainer Brass A COMPRESSION Ejection Spring . . . . Stainless Steel , - GUIDE Patents PINS (2) \���' ���,'���� SCREW f I— ,I / =I� I ; U _S.A. 4,014,388 _ DEFLECTOR I Operation (DROPPED ■ DEF : J r 'POSITION) G i �/ When exposed to heat from a fire, the ■ SPRINKLER/SUPPORT CUP Cover Plate, which is normally sol- I ASSEMBLY dered to the Retainer at three points, falls away to expose the Sprinkler As- THREAD INTO I RETAINER sembly. At this point the Deflector sup- SUPPORT CUP O j WITH THREAD y p p UNTIL MOUNTING O ) DIMPLES ported by the Guide Pins drops down SURFACE IS to its operational position. FLUSH WITH EJECTION The glass Bulb contains a fluid that CEILING SPRING expands exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the \- �� . glass Bulb, activating the sprinkler and allowing water to flow. SOLDER COVER TABS (3) COVER PLATE/RETAINER PLATE ASSEMBLY Design FIGURE 1 Criteria SERIES RFII CONCEALED SPRINKLER ASSEMBLY The RFII (TY3551 & TY3504), 5 mm Bulb Type, Concealed Pendent Sprin- Step 1. The sprinkler must only be klers are UL and C -UL Listed as stand- Installation installed in the pendent position and and response - standard spray sprin- with the centerline of the sprinkler per - klers for use in accordance with the The Series RFII must be installed in pendicular to the mounting surface. current NFPA standard. They are FM accordance with the following instruc- Step 2. Remove the Protective Cap. Approved as standard response - tions: standard spray sprinklers for use in Step 3. With pipe thread sealant ap- accordance with the current FM Loss NOTES plied to the pipe threads, hand tighten Prevention Data Sheets. Do not install any bulb type sprinkler if the sprinkler into the sprinkler fitting. The RFII (TY3531 & TY3505) 3 mm the bulb is cracked or there is a loss of Step 4. Wrench tighten the sprinkler liquid from the bulb. With the sprinkler using only the RFII Sprinkler Wrench Bulb Type, Concealed Pendent Sprin- held horizontally, a small air bubble Ref. 3 Figure The Sprinkler klers are UL and C -UL Listed as quick should be present. The diameter of the ( g 3). p Wrench response - standard spray sprinklers air bubble is approximately 1/16 inch as w to in Figure Fgured e 3. . the Sprin kler as for use in accordance with the current (1,6 mm) for the 155 °F /68 °C and 3/32 shown NFPA standard. They are FM Ap- inch (2,4 mm) for the 200 °F /93 °C tern- Step 5. Replace the Protective Cap proved as standard response - stand- perature ratings. (Ref. Figure 4) by pushing it upwards and spray sprinklers for use in accord- until it bottoms out against the Support ante with the current FM Loss A leak tight 1/2 inch NPT sprinkler joi Cup. The Protective Cap helps prevent Prevention Data Sheets. should be obtained with a torque o 7 damage to the Deflector and Arms dur- The Series RFII Concealed Pendent to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- ing ceiling installation and /or during S rinklers are only listed and a mum of 21 ft.lbs. (28,5 Nm) of torque application of the finish coating of the p y p is to be used to install sprinklers. ceilin It ma also be used to locate proved with the Series RFII Concealed Higher levels of torque may distort the g' y the center Cover Plates having a metallic or white sprinkler inlet with consequent leak- y us hinn the clearance e u p painted finish. gently pushing the ceiling materia l uriap age or impairment of the sprinkler. against the center point of the Protec- The Series RFII must not be used in Do not attempt to compensate for in- tive Cap. applications where the air pressure sufficient adjustment in the Sprinkler above the ceiling is greater than that Assembly by under- or over - tightening NOTE below. Down drafts through the Sup- the Sprinkler /Support Cup Assembly. As long as the Protective Cap remains port Cup could delay sprinkler opera- Readjust the position of the sprinkler in place, the system is considered to tion in a fire situation. fitting to suit. be "Out of Service ". " Registered Trademark of DuPont . ,_ TFP181 Page 3 of 4 FACE OF CLEARANCE HOLE f _ CLEARANCE SPRINKLER L� DIAMETER — HOLE FITTING DIMENSION C •=a SPRINKLER 1 SUPPORT CUP � - 11 * ASSEMBLY 1 1/2" (12,7 mm) I' THREADED D ADJUSTMENT l� FACE OF CEILING, 1 i--i RETAINING RING _ - FIGURE 4 MOUNTING _ DISPOSABLE PROTECTIVE CAP SURFACE j ■ ∎ I i I I � Step 6. After the ceiling has been com II pleted with the 2 -1/2 inch (63,5 mm) �� - -• diameter clearance hole and in prepa- 7 ration for installing the Cover Plate As- I I sem tective bly, rem , and and discard verify the that Pro - the 3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE Deflector moves up and down freely. If (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER the Sprinkler has been damaged and REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY the Deflector does not move up and down freely, replace the entire Sprin- COVER PLATE COVER PLATE kler assembly. Do not attempt to mod- - PROFILEDEPTH DIAMETER — ify or repair a damaged sprinkler. DIMENSION B DIMENSION A Step 7. When installing an Air and Dust Seal, refer to Figure 5, otherwise proceed to Step 8. To attach the Air and A: 3 -1/4" (82,6 mm) C: 2 -3/8" to 2 -5/8" (60,3 to 66,7 mm) Dust Seal, verify the angle of the out - B: 3/16" (4,8 mm) D: 1 -3/4" to 2 -1/4" (44,5 to 57,2 mm) side edge of the seal is oriented ac- cording to Figure 5. Start the edge of FIGURE the Retainer in the grooved slot of the SERIES RFII CONCEALED SPRINKLER Air and Dust Seal and continue around INSTALLATION DIMENSIONS the retainer until the entire Air and Dust Seal is engaged. NOTE The Air and Dust Seal is only to be installed on the periphery of the Re- if, = i', FRAME ;l =t; tainer. ARM Sri r: Step 8. Screw on the Cover Plate /Re- • { tainer Assembly until the Retainer - l (� - I - � � Figure 2 (or Air and Dust Seal - Figure i SUPPORT j 5) contacts with the ceiling. Do not i i CUP 1 I - I ; continue to screw on the Cover i i i c Plate /Retainer Assembly such that it IT M ' L i ' lifts a ceiling panel out of its normal ,,,, position. If the Cover Plate /Retainer MU � Assembly cannot be engaged with the O Support Cup or the Cover Plate /Re- 7/8" (23 mm) tainer Assembly cannot be engaged SQUARE sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. ALIGN � �, Ca ARROWS WITH \ C \ re and FRAME 1' 41 1$ M ®py ,yea al Maintenance ACCEPTS . - The Series RFII must be maintained � 0 1/2" SOCKET - and serviced in accordance with the DRIVE following instructions: NOTES FIGURE 3 Absence of the Cover Plate Assembly RFII SPRINKLER WRENCH may delay sprinkler operation in a fire situation. Page 4 of 4 TFP181 When properly installed, there is a SUPPORT SPRINKLER FACE OF ORIENT nominal 3/32 inch (2,4 mm) air gap CUP CEILING SEAL between the lip of the Cover Plate and • BEVEL AS the ceiling, as shown in Figure 2. This COVER � , SHOWN air gap is necessary for proper opera- yl` PLATE All tion of the sprinkler. If the ceiling is to �) RETAINER M.' be repainted after the installation o f tIllf lk ASSEMBLY '-' . : the Sprinkler, care must be exercised i∎ • to ensure that the new paint does NOT I; seal off any of the air gap. `/` I / - a ! /� -w CLEAN .� ROOM Factory painted Cover Plates MUST ' m 1 ∎1_ — 6.1!_ LIP OF COVER NOT be repainted. They should be re- -- — SEAL placed, if necessary, by factory RETAINER PLATE painted units. - - - - - -- ----- - - - - -- FIGURE 5 Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504) the Enclosure. Separation may result. Before closinga fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT main control valve for maintenance local requirements and /or national SHALL TYCO FIRE PRODUCTS' LI- work on the fire protection system that codes. ABILITY EXCEED AN AMOUNT it controls, permission to shut down the EQUAL TO THE SALES PRICE. affected fire protection system must be THE FOREGOING WARRANTY IS obtained from the proper authorities Li MADE IN LIEU OF ANY AND ALL. and all personnel who may be affected OTHER WARRANTIES EXPRESS OR by this action must be notified. warranty IMPLIED. INCLUDING WARRANTIES Sprinklers that are found to be leaking OF MERCHANTABILITY AND FIT - or exhibiting visible signs of corrosion Products manufactured by Tyco Fire NESS FOR A PARTICULAR PUR- must be replaced. Products are warranted solely to the POSE. Automatic sprinklers must never be original Buyer for ten (10) years ma otherwise against defects in material and work - altered painted, plated, leaving ted ted, coated s or o ever b factory. Mode manship when paid for and properly Ordering ed sprinklers leaving oth. d. installed and maintained under normal i klr must be replaced. use and service. This warranty will ex- Procedure Sprinklers or rr not operated, should be replaced that have ve been exposed of combustion, but pire ten (10) years from date of ship - od ment by Tyco Fire Products. No war- When placing an order, indicate the full ha if they cannot be completely ranty is given for products or product name. Contact your local dis- by wiping ca the spr om lattbe ly eleaced a cloth or components manufactured by compa- tributor for availability. by brushing it with a soft bristle brush. Hies not affiliated by ownership with Sprinkler Assembly: Tyco Fire Products or for products and Care must e t x e to avoid dam- components which have been subject rating) s) (specify temperature Pen - age sprinklers during, t o misuse, improper installation, corro- dent Sprinkler, Seri and after installation. Sprinklers dam- sion, or which have not been installed, s P/N (specify). aged by dropping, striking, wrench maintained, modified or repaired in ac- applicable Standards of 155F/68C 2 -sac twist/slippage, or the like, must be re- cordance with a placed. Also, replace any sprinkler that PP TY35 51-790-1-155 51-790-1-200 P P Y P the National Fire Protection Associa- TY3504 51- 796 -1 -155 51 -796-1-200 has a cracked bulb or that has lost tion, and /or the standards of any other TY3531 51- 792 -1 -155 51 -792 -1 -200 liquid from its bulb. (Ref. Installation Authorities Having Jurisdiction. Mate - TY3505 51- 797 -1 -155 51 -797 -1 -200 Section). rials found by Tyco Fire Products to be If a sprinkler must be removed, do not defective shall be either repaired or Separately Plate: reinstall it or a replacement without replaced, at Tyco Fire Products' sole Specify: (specify temperature rating) reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate If a Cover Plate Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify). dislodged during service, replace it im- assume for it, any other obligation in mediately. connection with the sale of products or 135F/57C(a) 165F/74C'(b) parts of products. Tyco Fire Products Brass 56- 792 -1 -135 56- 792 -1 -165 P P Y Bright Brass 56- 792 -2 -135 56- 792 -2 -165 The owner is responsible for the in- shall not be responsible for sprinkler Chrome 56- 792 -9 -135 56 -792 -9 -165 spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome - --- -- their fire protection system and de- incomplete information supplied by White 56 56792 - 792 8 -3 -135 135 5656792 - 792 8 -3 -165 165 P Y P pp Y White (RAL9010)' 56- 792 -3 -135 56- 792 -3 -165 vices in compliance with this docu- Buyer or Buyer's representatives. Bright White 56- 792 -4 -135 56- 792 -4 -165 ment, as well as with the applicable IN NO EVENT SHALL TYCO FIRE Off W hite 56- 792 -5 -135 56- 792 -5 -165 standards of the National Fire Protec- PRODUCTS BE LIABLE, IN CON- Clack 56- 792 -6 -135 56- 792 -6 -165 Custom 56- 792 -X -135 56- 762 -x -165 tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR addition to the standards of any other UNDER ANY OTHER LEGAL THE (a) For use with 155F/68C sprinklers. jurisdiction. The in- (b) For use with 200F/93C sales sprinklers. ly authorities having 1 ORY, FOR INCIDENTAL, INDIRECT, Eastern Hemisphere sales only stalling contractor or sprinkler manu- SPECIAL OR CONSEQUENTIAL facturer should be contacted relative to DAMAGES, INCLUDING BUT NOT Sprinkler Wrench: any questions. LIMITED TO LABOR CHARGES, RE- Specify: RFII Sprinkler Wrench, It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56-000-1-075. sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal: tested, and maintained by a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal, P/N 56 -908 -1 -001. TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 , , tqCD Fire & Building Products Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series TY -FRB - 28, 4.2, 5.6, and 8.0 K- factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General mospheres. Although corrosion resis- tant coated sprinklers have passed the "` ''''' standard corrosion tests of the appli- Description cable approval agencies, the testing is >�,: not representative of all possible cor- • The Series TY -FRB, 2.8, 4.2, 5.6, and rosive atmospheres. Consequently, it 8.0 K- factor, Upright and Pendent is recommended that the end user be r i Sprinklers described in this data sheet consulted with respect to the suitability I ) -, 1 ! are quick response - standard cover- of these coatings for any given corro- 4'1 age, decorative 3 mm glass bulb type sive environment. The effects of ambi- :i! • spray sprinklers designed for use in ent temperature, concentration of -""' light or ordinary hazard, commercial chemicals, and gas /chemical velocity, . - - = occupancies such as banks, hotels, should be considered, as a minimum, `" ° shopping malls, etc. along with the corrosive nature of the , The recessed version of the Series chemical to which the sprinklers will be TY -FRB Pendent Sprinkler, where ap- exposed. plicable, is intended for use in areas An intermediate level versions of the with a finished ceiling. It uses either a Series TY -FRB Pendent Sprinklers are 1- two -piece Style 10 (1/2 inch NPT) or detailed in Technical Data Sheet , `� Style 40 (3/4 inch NPT) Recessed Es- TFP356, and Sprinkler Guards are de- ( 4 t cutcheon with 1/2 inch (12,7 mm) of tailed in Technical Data Sheet TFP780 i recessed adjustment or up to 3/4 inch /, (19,1 mm) of total adjustment from the WARNINGS 4 flush pendent position, or a two -piece The Series TY -FRB Sprinklers de- Style 20 (1/2 inch NPT) or Style 30 (3/4 scribed herein must be installed and '' inch NPT) Recessed Escutcheon with maintained in compliance with this ,."'; 1/4 inch (6,4 mm) of recessed adjust- document, as well as with the applica- ment or up to 1/2 inch (12,7 mm) of ble standards of the National Fire Pro- TY3231 - Pendent 5.6K, 1/2 "NPT total adjustment from the flush pen- tection Association, in addition to the TY4131 - Upright 8.0K, 3/4 "NPT dent position. The adjustment provided standards of any other authorities hav TY4231 - Pendent 8.0K, 3/4 "NPT by the Recessed Escutcheon reduces ing jurisdiction. Failure to do so may the accuracy to which the fixed pipe impair the performance of these de- T drops to the sprinklers must be cut. vices. ■ echnical Corrosion resistant coatings, where The owner is responsible for maintain- Data applicable, are utilized to extend the ing their fire protection system and de- life of copper alloy sprinklers beyond vices in proper operating condition. that which would otherwise be ob- The installing contractor or sprinkler Approvals tamed when exposed to corrosive at- manufacturer should be contacted UL and C -UL Listed. with any questions. FM, LPCB, and NYC Approved. (Refer to Table A for complete approval IMPORTANT information including corrosion resis- Always refer to Technical Data tant status.) Sheet TFP700 for the "INSTALLER Model /Sprinkler Maximum Working Pressure WARNING" that provides cautions with respect to handling and instal- Identification 175 psi (12,1 bar) lation of sprinkler systems and com- Discharge Coefficient ponents. Improper handling and in- Numbers K = 2.8 GPM /psi (40,3 LPM /barli stallation can permanently damage K = 4.2 GPM /psi (60,5 LPM /barli a sprinkler system or its compo- TY1131 - Upright 2.8K, 1/2 "NPT K = 5.6 GPM /psi (80,6 LPM /bar / nents and cause the sprinkler to fail TY1231 - Pendent 2.8K, 1/2"NPT K = 8.0 GPM /psi (115,2 LPM /bar to operate in a fire situation or cause TY2131 - Upright 4.2K, 1/2 "NPT Temperature Ratings it to operate prematurely. TY2231 - Pendent 4.2K, 1/2"NPT Refer to Table A and B TY3131 - Upright 5.6K, 1/2"NPT Page 1 of 8 JULY, 2004 TFP171 Page 2 of 8 TFP171 ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING ** NOMINAL RECESSED * SURFACE 1/2 MAKE -IN ESCUTCHEON SSU 1 NPT DEFLECTOR W 7/16" r 5 i 1 2 1/4" 1 ITM-1 � (11,1 mm) I 4 (57,2 mm) f � � �� I N I 2 i MAKE IN 1- 9/16" I gr .04. 2 3/16 "IN 3 (39,7 mm) WRENCH (55,6 mm) WS FLATS � 1 1 1 Ndj trim SSP DEFLECTOR * - 2 -7/8" (73,0 mm) DIA. 1/2" NPT } PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 1 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING ** NOMINAL RECESSED SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR 1! _ 7/16" ' 5 2- 3/16" ,� } =1 — I (11,1 mm) I (55,6 mm) 1�� �� NA i 4 f MAKE NOMI -IN L 1-1/2" I 1I V$ i1 , � � 1 2- 3/16" 9 i co 2 (38,1 mm) WRENCH 1 (55,6 mm) ■ FLATS = 3 I SSP DEFLECTOR * - 2 -7/8" (73,0 mm) DIA. 1/2" NPT 1 PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 2 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT LC Finishes Bulb Glass Sprinkler: Refer to Table A and B Compression Screw Bronze Operation i° Recessed Escutcheon: White Coated, Deflector Copper /Bronze Chrome Plated, or Brass Plated Bushing (K =2.8) Bronze The glass Bulb contains a fluid which E expands when exposed to heat. When N a) Physical Characteristics the rated temperature is reached the '1 Frame Bronze fluid expands sufficiently to shatter the ¢ Button Brass /Copper glass Bulb, allowing the sprinkler to a activate and water to flow. a Sealing Assembly Beryllium Nickel w/Teflont ° TFP171 Page 3 of 8 ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING ** NOMINAL RECESSED SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR 6 i .....-- 7/16" !te• 5 2- 3/16" } am, mm) I (55,6 mm) � �� �A I NOMINAL 4 ` MAKE IN II ' i 1 -1/2" I frill■Mr / TO 2 (38,1 mm) �� I j 2- 3/16" D � WRENCH F LATS (55,6 mm) 0 V t 3 - � 1 SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. 1/2" NPT ** PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 3 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40 PLATE SEATING * * NOMINAL RECESSED SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR t _------- 6 11._ 1/2.. f 5 2- 5/16" ' row (12,7 mm) � (58,7 mm) ill � - I NOMINAL li 4 1 ` MAKE -IN 1- 9/16" t — y " i � 2 I 1I Iii r (57,2 mm) 9 (39,7 mm) WRENCH ,6 1 --- ° - ---.. - -- ° -- -• FLATS Y tt 3 fig 1 SSP DEFLECTOR * 2 -7/8" (73,0 mm) DIA. —� 3/4" NPT ** t PENDENT - RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 4 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT Listing is based on the requirements of Design NFPA 13, and FM Approval is based Installation Criteria on the requirements of FM's Loss Pre vention Data Sheets ). Only the Style The Series TY -FRB Sprinklers must be 10, 20, 30, or 40 Recessed Escutch- installed in accordance with the follow - The Series TY -FRB Pendent and Up- eon, as applicable, is to be used for ing instructions: right Sprinklers are intended for fire recessed pendent installations. protection systems designed in ac- NOTES cordance with the standard installation Do not install any bulb type sprinkler if rules recognized by the applicable the bulb is cracked or there is a loss of Listing or Approval agency (e.g., UL liquid from the bulb. With the sprinkler • Page 4 of 8 TFP171 SPRINKLER FINISH (See Note 7) inch NPT sprinkler joint should be ob- K TYPE tained with a torque of 10 to 20 ft.lbs. YPE TEMP. BULB NATURAL CHROME WHITE'*' LIQUID BRASS PLATED POLYESTER (13,4 to 26,8 Nm). A maximum to be of 30 ft.lbs. (40, 7 Nm) ) of of i torque is to be used 135 °F /57 °C Orange to install sprinklers with 3/4 NPT con - PENDENT nections. Higher levels of torque may 155 °F /68 °C Red distort the sprinkler inlet and cause (TY1231) 1, 2, 3, 5 leakage or impairment of the sprinkler. and 175 °F /79 °C Yellow UPRIGHT Do not attempt to make -up for insuffi- 200 °F /93 °C Green cient adjustment in the escutcheon 2.8 (TY1131) 286 °F /141 °C Blue plate by under- or over - tightening the 1/2" sprinkler. Readjust the position of the NPT 135 °F /57 °C Orange sprinkler fitting to suit. RECESSED 155 °F /68 °C Red PENDENT The Series TY -FRB Pendent and Up- (TY1231)* 175 °F /79 °C Yellow right Sprinklers must be installed in Figure 5 accordance with the following instruc- g ure 200 °F /93 °C Green 1, 2, 5 tions. 135 °F /57 °C Orange Step 1. Pendent sprinklers are to be RECESSED Red installed in the pendent position, and PENDENT upright sprinklers are to be installed in (TY1231) ** 175 °F /79 °C Yellow the upright position. Figure 6 200 °F /93 °C Green Step 2. With pipe thread sealant ap- 135 °F /57 °C Orange plied to the pipe threads, hand tighten PENDENT the sprinkler into the sprinkler fitting. (TY2231) 155 °F /68 °C Red Step 3. Tighten the sprinkler into the and 175 °F /79 °C Yellow sprinkler fitting using only the W -Type UPRIGHT 200 °F /93 °C Green 6 Sprinkler Wrench (Ref. Figure 13). 42 (TY2131) With reference to Figures 1, 2, 3, and 286 °F1141 °C Blue 2 4, the W -Type 6 Sprinkler Wrench is to 1/2" be applied to the sprinkler wrench NPT 135 °F /57 °C Orange RECESSED flats. PENDENT 155 °F /68 °C Red (TY2231)* 175F/79°C Yellow The Series TY -FRB Recessed Pen - Figure 7 200 °F /93 °C Green dent Sprinklers must be installed in accordance with the following instruc- 135°F/57°C Orange tions. RECESSED 155 °F /68 °C Red Step A. After installing the Style 10. PENDENT 20, 30, or 40 Mounting Plate, as appli- (TY2231)** 175 °F /79 °C Yellow cable, over the sprinkler threads and Figure 8 200 °F /93 °C Green with pipe thread sealant applied to the pipe threads, hand tighten the sprin- NOTES: kler into the sprinkler fitting. 1 Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. Step B. Tighten the sprinkler into the 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response sprinkler fitting using only the W - Type Sprinklers. 7 Recessed Sprinkler Wrench (Ref. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin klers. Figure 14). With reference to Figure 1, 5. Approved by the City of New York under MEA 354 -01 -E. 2, 3, and 4, the W - Type 7 Recessed 7 Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- Sprinkler Wrench is to be applied to klers are UL and C -UL Listed as Corrosion Resistant Sprinklers. the sprinkler wrench flats. Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Step C. After the ceiling has been in- Recessed Escutcheon, as applicable. stalled or the finish coat has been ap- Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment plied, slide on the Style 10, 20, 30, or Recessed Escutcheon, as applicable. 40 Closure over the Series TY -FRB — Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available Sprinkler and push the Closure over TABLE A the Mounting Plate until its flange LABORATORY LISTINGS AND APPROVALS comes in contact with the ceiling. 2.8 AND 4.2 K- FACTOR SPRINKLERS held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint should be present. The diameter of the should be obtained with a torque of 7 air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- (1,6 mm) for the 135 °F /57 °C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque inch (2,4 mm) for the 286 °F /141 °C may be used to install sprinklers with temperature ratings. 1/2 NPT connections. A leak tight 3/4 TFP171 Page 5 of 8 SPRINKLER FINISH (See Note 8) K TYPE TEMP. BULB NATURAL CHROME WHITE "' LEAD LIQUID BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 5:`-' (TY3131) 286 °F /141 °C Blue 1/2" NPT 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 4, 5 N/A (TY3231)' 175 °F /79 °C Yellow Figure 9 200 °F /93 °C Green 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A (TY3231)** 175 °F /79 °C Yellow Figure 10 200 °F /93 °C Green 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY4231) 1, 2, 5 and 175F/79°C Yellow 1, 2, 3, 4, 5, 6, 7 UPRIGHT 200 °F /93 °C Green 8.0 (TY4131) 286 °F /141 °C Blue 3/4" NPT 135 °F /57 °C Green RECESSED 155 °F /68 °C Orange PENDENT 1, 2, 4, 5 N/A (TY4231)* 175 °F /79 °C Red Figure 11 200 °F /93 °C Yellow 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 N/A (TY4231)•° 175 °F /79 °C Yellow Figure 12 200 °F /93 °C Green NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as -Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428 - 3377). 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a106) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion Resistant Sprinklers • Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. • Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. "' Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS 5.6 AND 8.0 K- FACTOR SPRINKLERS Page 6 of 8 TFP171 2 -7/8" DIA. - 2 -7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8° (73,0 mm) 1/2" (12,7 mm) (15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2 -1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8" •• ' (3,2 mm) N ______,_ .411 (3,2 mm) I J . '.uI 0 _ f \ � \I � MOUNTING 4111P MOUNTING SURFACE . SURFACE i7rr��. ui /��h CLOSURE SERIES 1- 5/16" (33,3 mm) CLOSURE SERIES 1 -5 /16" (33,3 mm) TY -FRB 13/16" (20,6 mm) TY -FRB 1 -1/16" (27,0 mm) FIGURE 5 FIGURE 6 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO- PIECE_1 /2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA. 2 -7/8" DIA. 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) (73,0 mm) 1/2 ±1/8° 1/2" (12,7 mm) (15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) 57,2 mm SPRICNKOLER ( mm) MOUNTING FACE OF (57,2 mm) MOUNTING PLATE SPRINKLER PLATE FITTING FITTING 1 /8" 1/8" •., (3,2 mm) •� ( mm) i --._- .-iiiiii �- IN , � _ f \ AM:4 w \ � MOUNTING I �/ MOUNTING . ■ SURFACE .- CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm) TY -FRB 3/4" (19,1 mm) TY -FRB 1" (25,4 mm) FIGURE 7 FIGURE 8 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT �s and used to cover a clearance hole, may and after installation. Sprinklers dam- and delay the time to sprinkler operation in aged by dropping, striking, wrench M • a fire situation. twist/slippage, or the like, must be re- aintenance that are found to be leaking has a crackedpbulb or has lost The Series TY -FRB Sprinklers must be or exhibiting visible signs of corrosion liquid from its bulb. (Ref. Installation maintained and serviced in accord- must be replaced. Section). ance with the following instructions: Automatic sprinklers must never be Frequent visual inspections are rec- NOTES painted, plated, coated or otherwise ommended to be initially performed for altered after leaving the factory. Modi- corrosion resistant coated sprinklers, Before closing a fire protection system fied sprinklers must be replaced. p main control valve for maintenance Sprinklers that have been exposed to after the installation has been com- work on the fire protection system that corrosive products of combustion, but pleted, to verify the integrity of the cor- it controls, permission to shutdown the have not operated, should be replaced rosion resistant coating. Thereafter, affected fire protection system must be if they cannot be completely cleaned annual inspections per NFPA 25 obtained from the proper authorities by wiping the sprinkler with a cloth or should suffice; however, instead of in- and all personnel who may be affected by brushing it with a soft bristle brush. specting from the floor level, a random by this action must be notified. sampling of close -up visual inspec- Care must be exercised to avoid dam- tions should be made, so as to better Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi- TFP171 Page 7 of 8 2 -7/8° DIA. - 2 -718' DIA 5/811/4" ( mm) 3/4° (19 1 mm) (73,0 mm) 1/2±1/8° 1/2' (12,7 mm) (15,9±6,4 mm) 2 -1/4' DIA 1/4' (6,4 mm) (12,7±3,2 mm) 1/4° (6,4 mm) 2 -1/4° DIA y FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8 1/8' NM �411 ( mm) i ����� % /L (3,2 m Milli 'Or I ;i jt \ f �,,, MOUNTING IIIP MOUNTING SURFACE SURFACE = = -r i R�r- , CLOSURE SERIES 1 -1/4' (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm) TY -FRB 3/4 (19,1 mm) TY -FRB 1° (25,4 mm) FIGURE 9 FIGURE 10 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT 2 -7/8' DIA 2 -7/8' DIA 5/8±1/4' (73,0 mm) 3/4' (19,1 mm) 1/2 ±1/8' (73,0 mm) 1/2" (12,7 mm) (15,9±6,4 mm) 2 -1/4' DIA. 1/4° (6,4 mm) (12,7 ±3,2 mm) F 2 -1/4' DIA 1/4° (6,4 mm) FACE OF (57,2 mm) MOUNTING (57,2 mm) FACE OF MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8° 1/8 " (3,2 mm) ■II (3 mm) filE111 Pr f \ AMMKAI Or i ' MOUNTING MOUNTING �:• SURFACE II v CLOSURE SERIES 1 -5/16' (33,3 mm) CLOSURE SERIES 1 -5/16' (33,3 mm) TY -FRB 13/16 (20,6 mm) TY -FRB 1 -1/16' (27,0 mm) FIGURE 11 FIGURE 12 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT tion and the long term integrity of the corrosion resistant coating, as it may WRENCH e be affected by the corrosive conditions ' RECESS present. WRENCH RECESS f* The owner is responsible for the in- (END "A" USED FOR i spection, testing, and maintenance of 1/2 NPT MODELS) n their fire protection system and de- � vices in compliance with this docu- S ' IIIJJJ ment, as well as with the applicable .....i. standards of the National Fire Protec- WRENCH RECESS tion Association (e.g., NFPA 25 , in (END "B" USED FOR PUSH WRENCH g . 3 /4" NPT MODELS) IN TO ENSURE addition to the standards of any other ENGAGEMENT authorities having jurisdiction. The in- WITH SPRINKLER stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA facturer should be contacted relative to W -TYPE 6 SPRINKLER any questions. WRENCH It is recommended that automatic FIGURE 14 sprinkler systems be inspected, local requirements and /or national W-TYPE RECESSED tested, and maintained by a qualified codes. SPRINKLER WRENCH Inspection Service in accordance with Page 8 of 8 TFP171 P/N 57 - XXX - X - XXX I I TEMPERATURE MODEUSIN RATING SPRINKLER 330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135 °F /57 °C 331 2.8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C 340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C 341 4.2K PENDENT (1/2 "NPT) TY2231 3 WHITE (RAL9010)' 200 200 °F /93 °C 370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C 371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED 390 8 OK UPRIGHT (3/4 "NPT) TY4131 391 8.0K PENDENT (3/4 "NPT) TY4231 ' Eastern Hemisphere sales only. TABLE C PART NUMBER SELECTION SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS ORY, FOR INCIDENTAL, INDIRECT, Recessed - Escutcheon: Limited SPECIAL OR CONSEQUENTIAL Specify: Style (specify) Recessed Es- DAMAGES, INCLUDING BUT NOT cutcheon with (specify finish), P/N Warranty LIMITED TO LABOR CHARGES, RE- (specify). GARDLESS OF WHETHER TYCO Products manufactured by Tyco Fire FIRE PRODUCTS WAS INFORMED 1/2" (15 mm) Products are warranted solely to the ABOUT THE POSSIBILITY OF SUCH Style 10 original Buyer for ten (10) years DAMAGES, AND IN NO EVENT Chrome Plated .... ... . P/N 56- 701 -9 -010 against defects in material and work- SHALL TYCO FIRE PRODUCTS' LI- White Coated P/N 56- 701 -4 -010 manship when paid for and properly ABILITY EXCEED AN AMOUNT Brss P '..... ... P/N 56-701-3-010 installed and maintained under normal EQUAL TO THE SALES PRICE. Braass Pllated ated P/N 56 701 -2 -010 use and service. This - warranty -will ex- THE FOREGOING WARRANTY IS 1/2" (15 mm) pire ten (10) years from date of ship- Style 20 ment by Tyco Fire Products. No war- MADE IN LIEU OF ANY AND AL L. Chrome Plated P/N 56- 705 -9 -010 ranty is given for products or OTHER WARRANTIES EXPRESS OR White Coated P/N 56- 705 -4 -010 components manufactured by compa IMPLIED. INCLUDING WARRANTIES White RAL9010' . ..... P/N 56- 705 -3 -010 Hies not affiliated by ownership with OF MERCHANTABILITY AND FIT- Brass Plated . P/N 56- 705 -2 -010 Tyco Fire Products or for products and NESS FOR A PARTICULAR PUR 3/4" (20 mm) components which have been subject POSE Style 30 to misuse, improper installation, corro- Chrome Plated . P/N 56- 705 -9 -011 sion, or which have not been installed, White Coated P/N 56- 705 -4 -011 maintained, modified or repaired in ac- White Plated 0' P/N 56- 705 -3 -011 cordance with applicable Standards of � d�� ®n� Brass Plated P/N 56- 705 -2 -011 the National Fire Protection Associa- Procedure 3/4" (20 mm) tion, and /or the standards of any other Style 40 Authorities Having Jurisdiction. Mate- Oontatabygtafs Local distributor for avail Chrome Plated P/N 56- 700 -9 -010 rials found by Tyco Fire Products to be abi1 ,indicate the White Coated P/N 56- 700 -4 -010 defective shall be either repaired or ful product White RAL9010' .. P/N 56- 700 -3 -010 replaced, at Tyco Fire Products' sole name. Refer to Brass Plated P/N 56- 700 -2 -010 option. Tyco Fire Products neither as- the complete List for o p y complete listing 'Eastern Hemisphere sales only sumes, nor authorizes any person to of Part Numbers assume for it, any other obligation in Sprinkler Wrench: connection with the sale of products or Sprinkler Assemblies with NPT Specify: W -Type 6 Sprinkler Wrench, parts of products. Tyco Fire Products Thread Connections: P/N 56- 000 -6 -387. shall not be responsible for sprinkler Specify: (Specify Model /SIN), Quick system design errors or inaccurate or Response, (specify K- factor), (specify Specify: W-Type 7 Sprinkler Wrench, incomplete information supplied by temperature rating), Series TY -FRB P/N 56- 850 -4 -001. Buyer or Buyer's representatives. (specify Pendent or Upright) Sprinkler IN NO EVENT SHALL TYCO FIRE with (specify type of finish or coating), PRODUCTS BE LIABLE, IN CON P/N (specify from Table C). TRACT, TORT, STRICT LIABILITY OR UNDER ANY OTHER LEGAL THE- TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 tLICD /Ffre & Building Products Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series DS -1 — 5.6 K- factor Dry Type Sprinklers Quick Response, Standard Coverage General standards of any other authorities hay- ing jurisdiction. Failure to do so may A. s impair the performance of these de- I Description vices. , :-.- The Series DS -1, 5.6 K- factor, Quick The owner is responsible for maintain- q i Response, Standard Coverage, Dry ng their fire protection system and d Type Sprinklers are decorative 3 mm vices in proper operating condition. " glass bulb automatic sprinklers de The installing contractor or sprinkle I signed for the following typical uses: manufacturer should be contacted g gyp with any questions. t n • where pendent sprinklers are re- quired on dry pipe systems that The Series DS -1 Dry Type Sprinklers r are exposed to freezing tempera must only be installed in fittings that t ii I meet the requirements of the Desi n ry tures (e.g. sprinkler drops from un- q g I heated portions of buildings) Criteria section : • where sprinklers and /or a portion i of the connecting piping may be Model /Sprinkler I ._-, - exposed to freezing temperatures ■ (e.g. sprinkler drops from wet sys- Identification tems into freezers, sprinkler �/ sprigs from wet systems into un- Numbers heated attics, or horizontal piping extensions through a wall to pro- TY3235 - (Pendent) ' ' tect an unheated area of a build- TY3135 - (Upright)., 1; ing) TY3335 - (Horizontal Sidewall) • where sprinklers are used on sys - tems that are seasonably drained Technical to avoid freezing (e.g. vacation re- sort areas) Data WARNINGS Approvals The Series DS -1 Dry Type Sprinklers UL and C -UL Listed. Physical Characteristics described herein must be installed and FM and NYC Approved. Inlet Copper maintained in compliance with this (Refer to Table A) Plug Copper document, as well as with the applica- Yoke Stainless Steel ble standards of the National Fire Pro- Maximum Working Pressure Casing . . Galvanized Carbon Steel tection Association, in addition to the 175 psi (12,1 bar) Insert Bronze Inlet Thread Connection Bulb Seat Stainless Steel 1 inch NPT (Standard Order) Bulb Glass IMPORTANT ISO 7 -R1 Compression Screw Bronze Deflector Bronze Always refer to Technical Data Discharge Coefficient Frame Bronze Sheet TFP700 for the `INSTALLER K = 5.6 GPM /psi Guide Tube Stainless Steel WARNING" that provides cautions (80,6 LPM /barli Water Tube Stainless Steel with respect to handling and instal- Spring Stainless Steel latronof sprinkler systems and com Temperature Rating p g onents. Im ro er handlin and in Refer to Table A Sealing Assembly p p p g Beryllium Nickel w/Teflon' stallation can permanently damage Finishes Escutcheon Carbon Steel a sprinkler system or its compo- Sprinkler: Natural Brass, Chrome "Registered Trademark of DuPont nents and cause the sprinkler to fail Plated, White Polyester to operate in a fire situation or cause Escutcheon: White Coated or Chrome Patents it to operate prematurely. Plated U.S.A. Patent No. 5,188,185 Page 1 of 8 APRIL, 2004 TFP510 • Page 2 of 8 TFP51O SPRINKLER FINISH TY3235 Pendent TY3235 Pendent TY3335 Hor. Sidewall w/ Standard w/ Std. Escutcheon with top of Recessed Escutcheon (Ref. Fig. 5) Deflector - to-Ceiling (Ref. Fig. 3) w/ Deep Escutcheon distance of w/ Wide Flange (Ref. Fig. 6) 4 to 12 inches Recessed Escutcheon w/o Escutcheon (100 to 300 mm) (Ref. Fig. 4) (Ref. Fig. 7) w/ Std. Escutcheon (Ref. Fig. 9) TY3135 Upright w/ Deep Escutcheon w/o Escutcheon (Ref. Fig. 10) (Ref. Fig. 8) w/o Escutcheon (Ref. Fig. 11) Temperature Bulb Natural Chrome White Natural Chrome White Natural Chrome White Rating Color Code Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester 135 °F /57 °C Orange 1, 2, 3, 4 1. 2, 4 1, 2, 3, 4 1, 2, 4 1', 2', 3 ", 4 1', 2', 4 155 °F /68 °C Red 1,2,3,4 1, 2,4 1,2,3,4 1,2,4 1',2',3 ",4 1',2 ",4 175 °F /79 °C Yellow 1, 2, 3, 4 1, 2, 4 1, 2, 3, 4 1, 2, 4 1 *, 2', 3 ", 4 1', 2*, 4 200 °F /93 °C Green 1, 2, 3, 4 1, 2, 4 1, 2, 3, 4 1, 2, 4 1*, 2*, 3 ", 4 1*, 2 *, 4 286 °F /141 °C Blue N/A ' 1, 2, 3, 4 1, 2, 4 1 2', 3'', 4 1*, 2', 4 Notes: 1. Listed by Underwriters Laboratories, Inc (Maximum order length of 48 inches). 2. Listed by Underwriters Laboratories for use in Canada. (Maximum order length of 48 inches). 3. Approved by Factory Mutual Research Corporation (Maximum order - length of 48 inches) 4. Approved by the City of New York under MEA 352 -01 -E. ' Light and Ordinary Hazard Occupancies Only. " Light Hazard Occupancies Only. N/A - Not Available. TABLE A SERIES DS -1, QUICK RESPONSE - STANDARD COVERAGE, DRY TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVALS WRENCH PLUG WITH ,i� INLET RECESS GASKETED SPRIN ' PLATE SEAL j i 1 6ii Y OKE r ------1- 1 , �� SPRING �._ 1 4 �� , 7 1 1 _. -- CASING @ � = � '; WATER - PUSH WRENCH IN TO TUBE i q ENSURE ENGAGEMENT WITH 1 INSE S PRINKLER WRENCHING AREA GUIDE III 0 FIGURE2 TUBE � 'IN - ! 11 /' W-TYPE 7 SPRINKLER WRENCH 1 / SEAT FRAME l A I � + l ! � = - 3 mm BULB VENT HOLE III kill0 - COMPRESSION SCREW DEFLECTOR FIGURE 1 SERIES DS -1 QUICK RESPONSE DRY TYPE SPRINKLER ASSEMBLY • TFP510 Page 3 of 8 SPRINKLER FITTING SPRINKLER FITTING SPRINKLER FITTING (REFER TO DESIGN (REFER TO DESIGN (REFER TO DESIGN Z_ CRITERIA SECTION -- - - -, CRITERIA SECTION) - - - 2 r - i CRITERIA SECTION) ) J FACE OF FACE OF L1 -. FACE OF \ L-�'> SPRINKLER _ SPRINKLER L__[I SPRINKLER L FITTING - FITTING FITTING ORDER LENGTHS. ORDER LENGTHS. ORDER LENGTHS 3 -1/2" to 48" 3 -1/2" to 48" 2 -1/2° to 48" 1 -3/4" DIA. (88,9 to 1219,2 mm) (88,9 to 1219,2 mm) (63,5 to 1219,2 mm) (44,5 mm) IN 1/4° (6,4 mm) 2 -1/4" DIA. IN 1/4" (6,4 mm) 3" DIA IN 1/4" (6,4 mm) INCREMENTS _(57.2 mm) , INCREMENTS (76,2 mm) INCREMENTS FACE OF I FACE O ;� � � y; � . CEILING , CEILING I - :!J F ' I . I _ !:- FACE OF ■ ' • � CEILING , I 2 -7/8" DIA. 3 -5/8" DIA 3" DIA 1 -3/8" ± " 1/8" 2 -3/16" ± 1 /8" (76 mm) 1 (34,9 ± 3,2 mm) (73,0 mm) (34,9 ± 3,2 mm) (92,1 mm) (55,6 t 3,2 mm) - FIGURE 3 FIGURE 4 FIGURE 5 TY3235 PENDENT TY3235 PENDENT TY3235 PENDENT w/ STANDARD RECESSED w/ WIDE FLANGE RECESSED w/ STANDARD ESCUTCHEON ESCUTCHEON ESCUTCHEON SPRINKLER FITTING SPRINKLER FITTING t i (REFER TO DESIGN (REFER TO DESIGN TOP OF CRITERIA SECTION) - - - ti r-- CRITERIA SECTION) --1 r--• DEFLECTOR �. ( -- FACE OF - FACE OF -1 SPRINKLER ~ I SPRINKLER L_I� J I 41 FITTING _ FITTING ORDER LENGTHS' - 5" to 48" - (127,0 to 1219,2 mm) ORDER LENGTHS: j _3 -1/2" DIA. 1 IN 1/4" (6,4 mm) 1/2" to 46" ' (88,9 mm) ORDER LENGTHS: INCREMENTS (12,7 to 1168,4 mm) 2 -1/2" DIA. 5" to 48" IN 1/4" (6,4 mm) (63,5 mm) (127,0 to 1219.2 mm) FACE OF INCREMENTS I I- - - - - -I IN 1/4" (6,4 mm) SPRINKLER ' I INCREMENTS FITTING r _ FACE OF __; - _, CEILING -- MINIMUM F 4 -1/4" ± 1/8" . 1 -3/4° (44,5 mm) I, ` - (108,0 ±3,2 mm) DEFLECTOR i TO CEILING SPRINKLER FITTING DESIGN (REFER , CRITERIA TO SECTION) FIGURE 6 FIGURE 7 FIGURE 8 TY3235 PENDENT TY3235 PENDENT TY3135 UPRIGHT w/ DEEP ESCUTCHEON w/o ESCUTCHEON w/o ESCUTCHEON • Page4of8 TFP51O ORDER LENGTHS- Operation 2 -1/2" to 48" (63,5 to 1219,2 mm) IN 1/4" (6,4 mm) INCREMENTS 4 " :1/8" (101,6±3.2mm) When the Series DS -1 is in service, FACE OF FACE OF 1 -3/4" DIA water is prevented from entering the _ __ — SPRINKLER MOUNTING — (44,5 mm) assembly by the Plug & Belleville Seal- __�__; FITTING SURFACE ,, Ing Assembly (Ref. Figure 1) in the � � !! Inlet of the Sprinkler. The glass Bulb I' ���1� =-Ji 36",2 contains a fluid that expands when ex- II (76.2 mm) posed to heat. When the rated tern- 3.5° 1 perature is reached, the fluid expands -- , SPRINKLER FITTING `\ sufficiently to shatter the glass Bulb, '— '---; (REFER TO DESIGN CENTERLINE 5/16" and the Bulb Seat is released. The CRITERIA SECTION) OF WATERWAY (7,9 mm) compressed Spring is then able to ex- FIGURE 9 pand and push the Water Tube as well TY3335 HORIZONTAL SIDEWALL w/ STANDARD ESCUTCHEON as the Guide Tube outward. This action simultaneously pulls inward on the Yoke, withdrawing the Plug & Belleville ORDER LENGTHS FACE OF Seal from the Inlet allowing the sprin- 1/2" to 45 -3/4" (12,7 to 1162.1 mm) MOUNTING kler to activate and flow water. IN 1/4" (6,4 mm) INCREMENTS SURFACE I /7.7' , 4-13/16° ± 1/8° (122,2±3.2 mm) FACE OF 2 -1/2" DIA. - SPRINKLER (63,5 mm) Design it ±_-_-_'._ FITTING 6 ', j i IL--- 3 1/2° DIA Criteria r — I- / ■ (88,9 aim) The Series DS -1 Sprinklers are in- IF-- / 3 s° tended for use in fire sprinkler systems SPRINKLER FITTING q designed in accordance with the ' -= --' (REFER TO DESIGN CENTERLINE 5/16" standard installation rules recognized CRITERIA SECTION) OF WATERWAY (7,9mm) by the applicable Listing or Approval FIGURE 10 agency (e.g., UL Listing is based on TY3335 HORIZONTAL SIDEWALL w/ DEEP ESCUTCHEON NFPA 13 requirements). The Series DS -1 Dry Type Sprinkler is ORDER LENGTHS, to be installed in the 1 inch NPT outlet 5" to 48" (127,0 to 1219,2 mm) - or run of malleable or ductile iron IN 1/4" (6,4 mm) INCREMENTS MINIMUM threaded tee fittings that meet the di- 2-1/4" (57,2 mm) mensional requirements of ANSI FACE OF DEFLECTOR TO B16.3 (Class 150) or cast iron — SPRINKLER MOUNTING threaded tee fittings that meet the di- 1_ FITTING SURFACE mensional requirements of ANSI B16.4 (Class 125) with the end sprin- 1���j�� -----r kler fitting on a branch line to be r, / plugged as shown in Figures 3 - 11. T' / 3s° 5/16" When installing 1 inch NPT Series SPRINKLER FITTING (7,9 mm) DS -1 Dry Type Sprinklers on a dry pipe -' (REFER TO DESIGN CENTERLINE sprinkler system, only use the side CRITERIA SECTION) OF WATERWAY outlet of maximum 2 -1/2 inch size re- FIGURE 11 ducing tee's. TY3335 HORIZONTAL SIDEWALL w/o ESCUTCHEON For wet pipe sprinkler systems, the Series DS -1 Dry Type Sprinklers may also be installed in the 1 inch NPT outlet of a Central Figure 730 Me- chanical Tee or the following Tyco Fire Products CPVC fittings: (P /N 80145) 1" x 1" NPT Female Adapter or (P /N 80249) 1" x 1" x 1" NPT Sprinkler Head Adapter Tee. NOTE Do not install the Series DS -1 into any other type fitting without first consult- ing the Technical Services Depart- ment. Failure to use the appropriate fitting may result in: failure of the sprin- kler to properly operate due to forma- tion of ice over the inlet Plug or binding of the inlet Plug; or, insufficient en- TFP51 O Page 5 of 8 gagement of the inlet pipe threads with Deep Escutcheon, hold the outer consequent leakage. installation piece in contact with the mounting sur- Branch, cross, and feedmain piping The Series DS 1 Dry Type Sprinklers face (ceiling), and then rotate the inner connected to Dry Sprinklers and sub- y yp p piece approximately 1/4 turn with re- must be installed in accordance with spect to the outer piece, to hold the ject to freezing temperatures must be the following instructions: Deep Escutcheon firmly together. pitched for drainage in accordance with the minimum requirements of the NOTES National Fire Protection Association The Series DS -1 must only be installed Care and for dry pipe sprinkler systems. in fittings that meet the requirements When Dry Sprinklers are to be used in of the Design Criteria section. Maintenance wet areas ubject to temperatures e protecting Refer to the Design Criteria section for The Series DS -1 Dry Type Sprinklers other important requirements re must be maintained and serviced in (e.g., sprinkler drops into freezers), ing piping design and sealing of the consideration must be given to the ap- c space around the Sprinkler accordance with the following instruc- propriate length of the sprinkler that tions: will prevent freezing of the water in the Casing. connecting pipes due to conduction. Do not install any bulb type sprinkler if NOTES When the temperature surrounding the bulb is cracked or there is a loss of Absence of the outer piece of an es- the wet pipe sprinkler system is main- liquid from the bulb. With the sprinkler cutcheon, which is used to cover a tained at a minimum temperature of held horizontally, a small air bubble clearance hole, may delay the time to 40 °F /4 °C, the following are the mini- should be present. The diameter of the sprinkler operation in a fire situation. mum recommended lengths between air bubble is approximately 1/16 inch Before closing a fire protection system the face of the sprinkler fitting and the (1,6 mm) for the 135 °F /57 °C rating to main control valve for maintenance outside surface of the protected area 1/8 inch (3,2 mm) for the 286 °F /141 °C work on the fire protection system that (i.e., length exposed to minimum am- rating. it controls, permission to shut down bient of 40 °F /4 °C): A leak tight 1 inch NPT sprinkler joint the affected fire protection systems • 12 inches (300 mm) when the tern- should be obtained with a torque of 20 must be obtained from the proper perature within the protected area to 30 ft.lbs. (26,8 to 40,2 Nm). Higher authorities and all personnel who may is - 20 °F / -29 °C levels of torque may distort the sprin- be affected by this action must be no- • 18 inches (450 mm) when the tern- kler inlet with consequent leakage or titled. impairment of the sprinkler. A Vent Hole is provided in the Bulb perature within the protected area p is - 40 °F / -40 °C Do not attempt to compensate for in- Seat (Ref. Figure 1) to indicate if the inches (600 mm) when the tern- sufficient adjustment in an Escutcheon Dry Sprinkler is remaining dry. Evi- • 24 the protected area Plate by under- or over - tightening the dence of leakage from the Vent Hole perature is r within (600 °C Sprinkler. Readjust the position of the is an indication that there may be sprinkler fitting to suit. weepage past the Inlet seal and that For protected area temperatures be- S tep 1. Pendent sprinklers must be the sprinkler needs to be removed for tween those given above, the minimum determining the cause of leakage (e.g. installed only in the pendent position, recommended length from the face of and upright sprinklers must be in- an improper insfallation or an ice plug) . t fitting to the outside of the pro- stalled only in the upright position. The T fire protection system control tected area may be determined by in- deflector of a pendent or upright sprin- valve must be closed and the system terpolating between the 'indicated val- kler is to be parallel to the ceiling. drained before removing the sprinkler. ues. Sprinklers that are found to be leaking Horizontal sidewall sprinklers are to be or exhibiting visible signs of corrosion NOTE installed in the horizontal position with must be replaced. When Dry Sprinklers penetrate a cell- their centerline of waterway perpen- ing or wall into an area subject to freez- dicular to the back wall and parallel to Automatic sprinklers must never be ing, the clearance space around the the ceiling. The word 'TOP" on the De- painted, plated, coated, or otherwise Sprinkler Casing must be completely flector is to face towards the ceiling. altered after leaving the factory. Modi- sealed in order to prevent the leakage Step 2. With pipe thread sealant ap fied sprinklers must be replaced. of moist air into the freezing area plied to the inlet threads, hand tighten Sprinklers that have been exposed to which might result in the formation of the sprinkler into the sprinkler fitting. corrosive products of combustion, but condensate around the Frame, Deflec- have not operated, should be corn- tor, Bulb Seat, or Bulb. Failure to pre- Step 3. Wrench tighten the sprinkler by pletely cleaned by wiping the sprinkler vent the formation of condensate could wrenching on the Casing with a pipe with a cloth or by brushing it with a soft result in the build -up of ice around the wrench whenever the casing is readily bristle brush. releasing components. This could re- accessible. Otherwise, use a W -Type 7 Care must be exercised to avoid dam - sult an inadvertent operation of the Sprinkler Wrench (Ref. Figure 2). The age - before, during, and after instal - sprinkler or impaired operation due to wrench recess of the W -Type 7 is to be lation. Sprinklers damaged by drop - reduced thermal sensitivity. applied to the sprinkler wrench flats ping, striking, wrench twist/slippage, (Ref. Figure 2). or the like, must be replaced. Also, Step 4. After the ceiling /wall has been replace any sprinkler that has a installed /finished, slide on the outer cracked bulb or that has lost liquid from piece of the Escutcheon until it comes its bulb (Ref. Installation Section). in contact with the ceiling /wall. Do not The owner is responsible for the in- lift the ceiling panel out of its normal spection, testing, and maintenance of position. their fire protection system and de- in the case of the outer piece of the vices in compliance with this docu- Page 6 of S 9 TF510 ment, as well as with the applicable MADE IN LIEU OF ANY AND ALL standards of the National Fire Protec- OTHER WARRANTIES EXPRESS OR tion Association (e.g., NFPA 25), in IMPLIED. INCLUDING WARRANTIES addition to the standards of any other OF MERCHANTABILITY AND FIT - authorities having jurisdiction. The in- NESS FOR A PARTICULAR PUR- stalling contractor or sprinkler manu- POSE. facturer should be contacted relative to any questions. It is recommended that automatic Ordering sprinkler systems be inspected, tested, and maintained by a qualified Procedure Inspection Service in accordance with local requirements and /or national Contact your local distributor for avail - codes. ability, and please specify the follow- ing: Limited 1 . Sprinkler. Warranty • Model /SIN. • Quick Response, Standard Cover - Products manufactured by Tyco Fire age, Dry Type Sprinkler Products are warranted solely to the • Deflector Style. original Buyer for ten (10) years against defects in material and work- • 5.6 K- factor. manship when paid for and properly • Order Length. installed and maintained under normal use and service. This warranty will ex- Dry Type Sprinklers are furnished pire ten (10) years from date of ship- based upon Order_Length as ment by Tyco Fire Products. No war- measured per Figure 3 through ranty is given for products or 11, as applicable. After the meas- components manufactured by compa- urement is taken, round it to the nies not affiliated by ownership with nearest 1/4 inch increment. Tyco Fire Products or for products and components which have been subject • Inlet Connection (1 Inch NPT or to misuse, improper installation, corro- ISO 7 -R1). sion, or which have not been installed, • Temperature Rating. maintained, modified or repaired in ac- cordance with applicable Standards of • Sprinkler Finish. the National Fire Protection Associa- • Escutcheon Style and Finish, as tion, and /or the standards of any other applicable. Authorities Having Jurisdiction. Mate- rials found by Tyco Fire Products to be • Part Number from Table B. (Part defective shall be either repaired or numbers are for 1 inch NPT stand - replaced, at Tyco Fire Products' sole and order sprinklers. Orders for all option. Tyco Fire Products neither as- other sprinkler assemblies must sumes, nor authorizes any person to be accompanied by a complete assume for it, any other obligation in description.) connection with the sale of products or 2. W- Type Sprinkler Wrench. parts of products. Tyco Fire Products shall not be responsible for sprinkler Refer to the Price List for complete system design errors or inaccurate or listing of Part Numbers. incomplete information supplied by Buyer or Buyer's representatives. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE, IN CON- TRACT, TORT, STRICT LIABILITY OR UNDER ANY OTHER LEGAL THE- ORY, FOR INCIDENTAL, INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LABOR CHARGES, RE- GARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT SHALL TYCO FIRE PRODUCTS' LI- ABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE. THE FOREGOING WARRANTY IS TFP51 O Page 7 of 8 P/N 60 - XXX - X - XXX I J ORDER LENGTH (1) (EXAMPLES) 055 5.50" SPRINKLER ESCUTCHEON MODEUSIN FINISH FINISH (2) 082 8.25" 36 Pendent w/ Standard TY3235 1 NATURAL BRASS WHITE 180 18 00" Escutcheon (1" NPT) (Fig. 5) 4 WHITE POLYESTER WHITE 187 18.75" 33 Pendent w/ Deep TY3235 Escutcheon (1" NPT) (Fig. 6) 9 CHROME PLATED CHROME PLATED 372 37.25" 37 Pendent w/ Std. Recessed TY3235 0 CHROME PLATED WHITE 480 48.00" Escutcheon (1" NPT) (Fig 3) 3 WHITE (RAL9010)" WHITE (RAL9010)" 32 Pendent w/o Escutcheon TY3235 - - Escutcheon (1" NPT) (Fig. 7) TEMPERATURE 34 Sidewall w/ Standard TY3335 I RATING (3) Escutcheon (1" NPT) (Fig. 9) 0 135F/57C 43 Sidewall w/ Deep TY3335 Escutcheon (1" NPT) (Fig. 10) 1 155F/68C 44 Sidewall w/o TY3335 2 175F/79C Escutcheon (1" NPT) (Fig. 11) 3 200F/93C 4 286F/141C 38 Upright w/o Escutcheon TY3135 (1" NPT) (Fig.8) NOTES (1). Dry Type Sprinklers are furnished based upon "Order Length" as measured per Figures 3 through 11, as applicable, and for each individual sprinkler where it is to be installed. After the meas- urement is taken, round it to the nearest 1/4 inch increment. (2). Escutcheon Finish applies to sprinklers provided with escutcheons. (3). The 286F/141C temperature rating applies to non - recessed sprinkler assemblies. • Eastern Hemisphere sales only. TABLE B PART NUMBER SELECTION SERIES DS -1, QUICK RESPONSE, STANDARD COVERAGE, DRY TYPE SPRINKLERS (Use Prefix "I" for ISO 7 -R1 Connection, e.g., 1-60-361-1-180) 4 Page 8 of 8 TF510 TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 [Page Too Large for OCR Processing]