Specifications 4
0,,O 01 'oo ,5
tqco Fire & Building
Products SECE
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 JUN 19 2007
cir Ql ' IR R ARD
Series RFII — 5.6 K- factor BUPI DIVISIO
DING "Royal Flush II" Pendent Concealed Sprinklers
Quick & Standard Response, Standard Coverage - - --
General Cap. The Protective Cap i temporarily
removed for installation, and then it
can be replaced to help protect the Oft
Description sprinkler while the ceiling is being in- /
stalled or finished. The tip of the Pro- _ .
The Series RFII Quick Response tective Cap can also be used to mark _ _
(3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas- _ - _
mm bulb), 5.6 K- Factor, "Royal Flush ter board, ceiling tiles, etc. by gently
II" Concealed Pendent Sprinklers are pushing the ceiling product against the f ..„- = °^�° --„::
decorative sprinklers featuring a flat Protective Cap. When the ceiling in-
cover plate designed to conceal the stallation is complete the Protective
sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate
tecturally sensitive areas such as hotel Assembly installed.
lobbies, office buildings, churches, As an option, the Series RFII Standard
and restaurants. Response (5 mm bulb) "Royal Flush II"
Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be
sembly that conceals the sprinkler op- fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175
erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM.
The separable two -piece design of the intended for sensitive areas where it is
Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical
blies allows installation of the sprin- through the cover plate from the area
klers and pressure testing of the fire above the ceiling. Data
protection system prior to installation WARNINGS
of a suspended ceiling or application The Series RFII Concealed Pendent Approvals for Series RFII
of the finish coating to a fixed ceiling. Sprinklers described herein must be U and C -UL Listed. FM Approved.
They also permit removal of sus- i nstalled and maintained in compli- NYC under MEA 353-01-E. LPCB Ref.
pended ceiling panels for access to p "
building service equipment without ante with this document, as well as No. 094a/09 for TY3551 & 094a/10 for
having to first shut down the fire pro- with the applicable standards of the TY3531) Approved.
hav system and remove sprinklers. National Fire Protection Association, The approvals apply only to the serv-
raig in addition to the standards of any ice conditions indicated in the Design
Also, the separable two-piece design f the the Sprinkler wo p other authorities having jurisdiction. Criteria section and maximum pres-
inch (12,7 mm) okverprovides e e for ign for 1 2 Failure to do so may impair the per- sure ratings indicated in the
formance of these devices. Model/Sprinkler Identification Num-
to reduce the accuracy to which the res The owner is onsible for maintain- bers section.
length of fixed pipe drops to the sprin- p
klers must be cut. ing their fire protection system and de- Approvals for Air & Dust Seal
vices in proper operating condition. Part #10908100
The Series RFII Sprinklers are The installing contractor or sprinkler U L and C -UL Li for use with the
shipped with a Disposable Protective manufacturer should be contacted
RFII (TY3551 & TY3504) Standard Re-
with any questions. sponse Concealed Sprinkler.
IMPORTANT Temperature Ratings
Always refer to Technical Data Model /Sprinkler 155F/68C Sprinkler - 135F/57C Plate
Sheet TFP700 for the `INSTALLER 200F/93C Sprinkler - 165F/74C Plate
WARNING" that provides cautions Identification Discharge Coef i ient
with respect to handling and instal- K = 5.6 GPM /psi �' (80,6 LPM /bar
lation of sprinkler systems and com- Numbers Adjustment
ponents. Improper handling and in- 1/2 inch (12,7 mm)
stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm Finishes
a sprinkler system or its compo- bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass
nents and cause the sprinkler to fail UL, C -UL, FM, LPCB and NYC. Plated, or White Painted (Custom paint
to operate in a fire situation or cause TY3504 (5 mm bulb) & TY3505 (3 mm matches and colors other than white
it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by
are available on request.)
Page 1 of 4 JULY, 2004 TFP181
•
•
Page 2 of 4 TFP181
Physical Characteristics 1/2° NPT SEALING
Frame Bronze f ASSEMBLY
Support Cup . Chrome Plated Steel
Guide Pins Stainless Steel FRAME Iii �
Deflector Bronze
f �__
CAP
Compression Screw Brass i� I n d j ;
Bulb Glass `•
Cap Bronze or Copper SUPPORT
Sealing Assembly
ROLL CUP FORMED WITH �I' BULB
Beryllium Nickel w/Teflon*
,
Cover Plate Brass THREADS — `
Retainer Brass A COMPRESSION
Ejection Spring . . . . Stainless Steel ,
- GUIDE
Patents PINS (2) \���' ���,'���� SCREW
f I— ,I / =I� I ;
U _S.A. 4,014,388 _ DEFLECTOR
I Operation (DROPPED
■ DEF : J r 'POSITION)
G i �/
When exposed to heat from a fire, the ■ SPRINKLER/SUPPORT CUP
Cover Plate, which is normally sol- I ASSEMBLY
dered to the Retainer at three points,
falls away to expose the Sprinkler As- THREAD INTO I RETAINER
sembly. At this point the Deflector sup- SUPPORT CUP O j WITH THREAD
y p p UNTIL MOUNTING O ) DIMPLES
ported by the Guide Pins drops down SURFACE IS
to its operational position. FLUSH WITH EJECTION
The glass Bulb contains a fluid that CEILING SPRING
expands exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the \- �� .
glass Bulb, activating the sprinkler and
allowing water to flow. SOLDER COVER
TABS (3) COVER PLATE/RETAINER PLATE
ASSEMBLY
Design FIGURE 1
Criteria SERIES RFII CONCEALED SPRINKLER
ASSEMBLY
The RFII (TY3551 & TY3504), 5 mm
Bulb Type, Concealed Pendent Sprin- Step 1. The sprinkler must only be
klers are UL and C -UL Listed as stand- Installation installed in the pendent position and
and response - standard spray sprin- with the centerline of the sprinkler per -
klers for use in accordance with the The Series RFII must be installed in pendicular to the mounting surface.
current NFPA standard. They are FM accordance with the following instruc- Step 2. Remove the Protective Cap.
Approved as standard response - tions:
standard spray sprinklers for use in Step 3. With pipe thread sealant ap-
accordance with the current FM Loss NOTES plied to the pipe threads, hand tighten
Prevention Data Sheets. Do not install any bulb type sprinkler if the sprinkler into the sprinkler fitting.
The RFII (TY3531 & TY3505) 3 mm the bulb is cracked or there is a loss of Step 4. Wrench tighten the sprinkler
liquid from the bulb. With the sprinkler using only the RFII Sprinkler Wrench
Bulb Type, Concealed Pendent Sprin- held horizontally, a small air bubble Ref. 3 Figure The Sprinkler
klers are UL and C -UL Listed as quick should be present. The diameter of the ( g 3). p
Wrench
response - standard spray sprinklers air bubble is approximately 1/16 inch as w to in Figure Fgured e 3. . the Sprin
kler as
for use in accordance with the current (1,6 mm) for the 155 °F /68 °C and 3/32 shown
NFPA standard. They are FM Ap- inch (2,4 mm) for the 200 °F /93 °C tern- Step 5. Replace the Protective Cap
proved as standard response - stand- perature ratings. (Ref. Figure 4) by pushing it upwards
and spray sprinklers for use in accord- until it bottoms out against the Support
ante with the current FM Loss A leak tight 1/2 inch NPT sprinkler joi Cup. The Protective Cap helps prevent
Prevention Data Sheets. should be obtained with a torque o 7 damage to the Deflector and Arms dur-
The Series RFII Concealed Pendent to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- ing ceiling installation and /or during
S rinklers are only listed and a mum of 21 ft.lbs. (28,5 Nm) of torque application of the finish coating of the
p y p is to be used to install sprinklers. ceilin It ma also be used to locate
proved with the Series RFII Concealed Higher levels of torque may distort the g' y
the center
Cover Plates having a metallic or white sprinkler inlet with consequent leak- y us hinn the clearance e u p
painted finish. gently pushing the ceiling materia l uriap
age or impairment of the sprinkler. against the center point of the Protec-
The Series RFII must not be used in Do not attempt to compensate for in- tive Cap.
applications where the air pressure sufficient adjustment in the Sprinkler
above the ceiling is greater than that Assembly by under- or over - tightening NOTE
below. Down drafts through the Sup- the Sprinkler /Support Cup Assembly. As long as the Protective Cap remains
port Cup could delay sprinkler opera- Readjust the position of the sprinkler in place, the system is considered to
tion in a fire situation. fitting to suit. be "Out of Service ".
" Registered Trademark of DuPont
. ,_
TFP181 Page 3 of 4
FACE OF CLEARANCE HOLE f _ CLEARANCE
SPRINKLER L� DIAMETER — HOLE
FITTING DIMENSION C
•=a
SPRINKLER 1
SUPPORT CUP � - 11 *
ASSEMBLY 1
1/2" (12,7 mm) I'
THREADED
D ADJUSTMENT l�
FACE OF CEILING, 1 i--i
RETAINING RING _ - FIGURE 4
MOUNTING _ DISPOSABLE PROTECTIVE CAP
SURFACE j ■ ∎ I i
I I � Step 6. After the ceiling has been com II pleted with the 2 -1/2 inch (63,5 mm)
�� - -• diameter clearance hole and in prepa-
7 ration for installing the Cover Plate As-
I I sem tective bly, rem , and and discard verify the that Pro -
the
3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE Deflector moves up and down freely. If
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER the Sprinkler has been damaged and
REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY the Deflector does not move up and
down freely, replace the entire Sprin-
COVER PLATE COVER PLATE kler assembly. Do not attempt to mod-
- PROFILEDEPTH DIAMETER — ify or repair a damaged sprinkler.
DIMENSION B DIMENSION A Step 7. When installing an Air and
Dust Seal, refer to Figure 5, otherwise
proceed to Step 8. To attach the Air and
A: 3 -1/4" (82,6 mm) C: 2 -3/8" to 2 -5/8" (60,3 to 66,7 mm) Dust Seal, verify the angle of the out -
B: 3/16" (4,8 mm) D: 1 -3/4" to 2 -1/4" (44,5 to 57,2 mm) side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
FIGURE the Retainer in the grooved slot of the
SERIES RFII CONCEALED SPRINKLER Air and Dust Seal and continue around
INSTALLATION DIMENSIONS the retainer until the entire Air and
Dust Seal is engaged.
NOTE
The Air and Dust Seal is only to be
installed on the periphery of the Re-
if, = i', FRAME ;l =t; tainer.
ARM Sri r: Step 8. Screw on the Cover Plate /Re-
• { tainer Assembly until the Retainer -
l (� - I - � � Figure 2 (or Air and Dust Seal - Figure
i SUPPORT j 5) contacts with the ceiling. Do not
i i CUP 1 I - I ; continue to screw on the Cover
i i i c Plate /Retainer Assembly such that it
IT
M ' L i ' lifts a ceiling panel out of its normal
,,,, position. If the Cover Plate /Retainer
MU � Assembly cannot be engaged with the
O Support Cup or the Cover Plate /Re-
7/8" (23 mm) tainer Assembly cannot be engaged
SQUARE sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
ALIGN � �, Ca
ARROWS WITH \ C
\ re and
FRAME 1'
41 1$ M ®py ,yea
al Maintenance
ACCEPTS . - The Series RFII must be maintained
�
0 1/2" SOCKET - and serviced in accordance with the
DRIVE following instructions:
NOTES
FIGURE 3 Absence of the Cover Plate Assembly
RFII SPRINKLER WRENCH may delay sprinkler operation in a fire
situation.
Page 4 of 4 TFP181
When properly installed, there is a SUPPORT SPRINKLER FACE OF ORIENT
nominal 3/32 inch (2,4 mm) air gap CUP CEILING SEAL
between the lip of the Cover Plate and • BEVEL AS
the ceiling, as shown in Figure 2. This COVER � , SHOWN
air gap is necessary for proper opera- yl` PLATE All
tion of the sprinkler. If the ceiling is to �) RETAINER M.' be repainted after the installation o f tIllf lk ASSEMBLY '-' . : the Sprinkler, care must be exercised i∎ • to ensure that the new paint does NOT I; seal off any of the air gap. `/` I / - a ! /� -w CLEAN
.� ROOM
Factory painted Cover Plates MUST
'
m 1 ∎1_ — 6.1!_ LIP OF COVER
NOT be repainted. They should be re-
-- — SEAL
placed, if necessary, by factory RETAINER PLATE
painted units. - - - - - -- ----- - - - - -- FIGURE 5
Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504)
the Enclosure. Separation may result.
Before closinga fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT
main control valve for maintenance local requirements and /or national SHALL TYCO FIRE PRODUCTS' LI-
work on the fire protection system that codes. ABILITY EXCEED AN AMOUNT
it controls, permission to shut down the EQUAL TO THE SALES PRICE.
affected fire protection system must be THE FOREGOING WARRANTY IS
obtained from the proper authorities Li MADE IN LIEU OF ANY AND ALL.
and all personnel who may be affected OTHER WARRANTIES EXPRESS OR
by this action must be notified. warranty IMPLIED. INCLUDING WARRANTIES
Sprinklers that are found to be leaking OF MERCHANTABILITY AND FIT -
or exhibiting visible signs of corrosion Products manufactured by Tyco Fire NESS FOR A PARTICULAR PUR-
must be replaced. Products are warranted solely to the POSE.
Automatic sprinklers must never be original Buyer for ten (10) years
ma otherwise against defects in material and work -
altered painted, plated,
leaving ted ted, coated s or o ever b factory. Mode manship when paid for and properly Ordering
ed sprinklers leaving oth. d. installed and maintained under normal
i klr must be replaced. use and service. This warranty will ex- Procedure
Sprinklers or rr not operated, should be replaced that have ve been exposed of combustion, but pire ten (10) years from date of ship -
od ment by Tyco Fire Products. No war- When placing an order, indicate the full
ha
if they cannot be completely ranty is given for products or product name. Contact your local dis-
by wiping ca the spr om lattbe ly eleaced a cloth or components manufactured by compa- tributor for availability.
by brushing it with a soft bristle brush. Hies not affiliated by ownership with Sprinkler Assembly:
Tyco Fire Products or for products and
Care must e t x e to avoid dam- components which have been subject rating) s) (specify temperature
Pen -
age sprinklers during, t o misuse, improper installation, corro- dent Sprinkler, Seri
and after installation. Sprinklers dam- sion, or which have not been installed, s P/N (specify).
aged by dropping, striking, wrench maintained, modified or repaired in ac-
applicable Standards of
155F/68C 2 -sac
twist/slippage, or the like, must be re- cordance with a
placed. Also, replace any sprinkler that PP TY35 51-790-1-155 51-790-1-200
P P Y P the National Fire Protection Associa- TY3504 51- 796 -1 -155 51 -796-1-200
has a cracked bulb or that has lost tion, and /or the standards of any other TY3531 51- 792 -1 -155 51 -792 -1 -200
liquid from its bulb. (Ref. Installation Authorities Having Jurisdiction. Mate - TY3505 51- 797 -1 -155 51 -797 -1 -200
Section). rials found by Tyco Fire Products to be
If a sprinkler must be removed, do not defective shall be either repaired or Separately Plate:
reinstall it or a replacement without replaced, at Tyco Fire Products' sole Specify: (specify temperature rating)
reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate
If a Cover Plate Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify).
dislodged during service, replace it im- assume for it, any other obligation in
mediately. connection with the sale of products or 135F/57C(a) 165F/74C'(b)
parts of products. Tyco Fire Products Brass 56- 792 -1 -135 56- 792 -1 -165
P P Y Bright Brass 56- 792 -2 -135 56- 792 -2 -165
The owner is responsible for the in- shall not be responsible for sprinkler Chrome 56- 792 -9 -135 56 -792 -9 -165
spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome - --- --
their fire protection system and de- incomplete information supplied by White 56 56792
- 792 8
-3 -135 135 5656792
- 792 8
-3 -165 165
P Y P pp Y White (RAL9010)' 56- 792 -3 -135 56- 792 -3 -165
vices in compliance with this docu- Buyer or Buyer's representatives. Bright White 56- 792 -4 -135 56- 792 -4 -165
ment, as well as with the applicable IN NO EVENT SHALL TYCO FIRE Off W hite 56- 792 -5 -135 56- 792 -5 -165
standards of the National Fire Protec- PRODUCTS BE LIABLE, IN CON- Clack 56- 792 -6 -135 56- 792 -6 -165
Custom 56- 792 -X -135 56- 762 -x -165
tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR
addition to the standards of any other UNDER ANY OTHER LEGAL THE (a) For use with 155F/68C sprinklers.
jurisdiction. The in- (b) For use with 200F/93C
sales sprinklers. ly
authorities having 1 ORY, FOR INCIDENTAL, INDIRECT, Eastern Hemisphere sales only
stalling contractor or sprinkler manu- SPECIAL OR CONSEQUENTIAL
facturer should be contacted relative to DAMAGES, INCLUDING BUT NOT Sprinkler Wrench:
any questions. LIMITED TO LABOR CHARGES, RE- Specify: RFII Sprinkler Wrench,
It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56-000-1-075.
sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal:
tested, and maintained by a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal,
P/N 56 -908 -1 -001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
, ,
tqCD Fire & Building
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series TY -FRB - 28, 4.2, 5.6, and 8.0 K- factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General mospheres. Although corrosion resis-
tant coated sprinklers have passed the "` '''''
standard corrosion tests of the appli-
Description cable approval agencies, the testing is >�,:
not representative of all possible cor- •
The Series TY -FRB, 2.8, 4.2, 5.6, and rosive atmospheres. Consequently, it
8.0 K- factor, Upright and Pendent is recommended that the end user be r i
Sprinklers described in this data sheet consulted with respect to the suitability I ) -, 1 !
are quick response - standard cover- of these coatings for any given corro- 4'1
age, decorative 3 mm glass bulb type sive environment. The effects of ambi- :i! •
spray sprinklers designed for use in ent temperature, concentration of -""'
light or ordinary hazard, commercial chemicals, and gas /chemical velocity, . - - =
occupancies such as banks, hotels, should be considered, as a minimum, `" °
shopping malls, etc. along with the corrosive nature of the ,
The recessed version of the Series chemical to which the sprinklers will be
TY -FRB Pendent Sprinkler, where ap- exposed.
plicable, is intended for use in areas An intermediate level versions of the
with a finished ceiling. It uses either a Series TY -FRB Pendent Sprinklers are 1-
two -piece Style 10 (1/2 inch NPT) or detailed in Technical Data Sheet , `�
Style 40 (3/4 inch NPT) Recessed Es- TFP356, and Sprinkler Guards are de- ( 4 t
cutcheon with 1/2 inch (12,7 mm) of tailed in Technical Data Sheet TFP780 i
recessed adjustment or up to 3/4 inch /,
(19,1 mm) of total adjustment from the WARNINGS 4
flush pendent position, or a two -piece The Series TY -FRB Sprinklers de-
Style 20 (1/2 inch NPT) or Style 30 (3/4 scribed herein must be installed and ''
inch NPT) Recessed Escutcheon with maintained in compliance with this ,."';
1/4 inch (6,4 mm) of recessed adjust- document, as well as with the applica-
ment or up to 1/2 inch (12,7 mm) of ble standards of the National Fire Pro- TY3231 - Pendent 5.6K, 1/2 "NPT
total adjustment from the flush pen- tection Association, in addition to the TY4131 - Upright 8.0K, 3/4 "NPT
dent position. The adjustment provided standards of any other authorities hav TY4231 - Pendent 8.0K, 3/4 "NPT
by the Recessed Escutcheon reduces ing jurisdiction. Failure to do so may
the accuracy to which the fixed pipe impair the performance of these de- T
drops to the sprinklers must be cut. vices. ■ echnical
Corrosion resistant coatings, where The owner is responsible for maintain- Data
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition.
that which would otherwise be ob- The installing contractor or sprinkler Approvals
tamed when exposed to corrosive at- manufacturer should be contacted UL and C -UL Listed.
with any questions. FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
IMPORTANT information including corrosion resis-
Always refer to Technical Data tant status.)
Sheet TFP700 for the "INSTALLER Model /Sprinkler Maximum Working Pressure
WARNING" that provides cautions
with respect to handling and instal- Identification 175 psi (12,1 bar)
lation of sprinkler systems and com- Discharge Coefficient
ponents. Improper handling and in- Numbers K = 2.8 GPM /psi (40,3 LPM /barli
stallation can permanently damage K = 4.2 GPM /psi (60,5 LPM /barli
a sprinkler system or its compo- TY1131 - Upright 2.8K, 1/2 "NPT K = 5.6 GPM /psi (80,6 LPM /bar /
nents and cause the sprinkler to fail TY1231 - Pendent 2.8K, 1/2"NPT K = 8.0 GPM /psi (115,2 LPM /bar
to operate in a fire situation or cause TY2131 - Upright 4.2K, 1/2 "NPT Temperature Ratings
it to operate prematurely. TY2231 - Pendent 4.2K, 1/2"NPT Refer to Table A and B
TY3131 - Upright 5.6K, 1/2"NPT
Page 1 of 8 JULY, 2004 TFP171
Page 2 of 8 TFP171
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING ** NOMINAL RECESSED *
SURFACE 1/2 MAKE -IN ESCUTCHEON SSU
1 NPT DEFLECTOR
W 7/16" r 5
i
1
2 1/4"
1 ITM-1 � (11,1 mm) I 4
(57,2 mm) f � � �� I N I
2
i MAKE IN 1- 9/16" I
gr .04. 2 3/16 "IN
3
(39,7 mm) WRENCH (55,6 mm) WS FLATS � 1
1 1 Ndj
trim SSP DEFLECTOR * - 2 -7/8" (73,0 mm) DIA. 1/2" NPT }
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING ** NOMINAL RECESSED
SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR
1!
_ 7/16" ' 5
2- 3/16" ,� } =1 — I (11,1 mm) I
(55,6 mm) 1�� �� NA i 4
f MAKE NOMI -IN L
1-1/2" I 1I V$ i1 , � � 1 2- 3/16" 9 i co 2
(38,1 mm) WRENCH 1 (55,6 mm)
■ FLATS = 3
I SSP DEFLECTOR * - 2 -7/8" (73,0 mm) DIA. 1/2" NPT 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K- FACTOR, 1/2 INCH NPT
LC
Finishes Bulb Glass
Sprinkler: Refer to Table A and B Compression Screw Bronze Operation i°
Recessed Escutcheon: White Coated, Deflector Copper /Bronze
Chrome Plated, or Brass Plated Bushing (K =2.8) Bronze The glass Bulb contains a fluid which E
expands when exposed to heat. When N a)
Physical Characteristics the rated temperature is reached the '1
Frame Bronze fluid expands sufficiently to shatter the ¢
Button Brass /Copper glass Bulb, allowing the sprinkler to a
activate and water to flow. a
Sealing Assembly
Beryllium Nickel w/Teflont °
TFP171 Page 3 of 8
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING ** NOMINAL RECESSED
SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR
6
i .....--
7/16" !te• 5
2- 3/16" }
am, mm) I
(55,6 mm) � �� �A I NOMINAL 4
` MAKE IN II ' i
1 -1/2" I frill■Mr
/ TO 2
(38,1 mm) �� I j 2- 3/16" D �
WRENCH F LATS (55,6 mm) 0 V t 3
- � 1
SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. 1/2" NPT **
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw * * Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40
PLATE SEATING * * NOMINAL RECESSED
SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR
t _-------
6
11._ 1/2..
f 5
2- 5/16" ' row (12,7 mm) � (58,7 mm) ill � - I NOMINAL
li 4
1 ` MAKE -IN 1- 9/16" t — y " i � 2
I 1I Iii r
(57,2 mm) 9
(39,7 mm) WRENCH ,6
1 --- ° - ---.. - -- ° -- -• FLATS Y tt 3
fig
1
SSP DEFLECTOR * 2 -7/8" (73,0 mm) DIA. —� 3/4" NPT ** t
PENDENT - RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
Listing is based on the requirements of
Design NFPA 13, and FM Approval is based Installation
Criteria on the requirements of FM's Loss Pre
vention Data Sheets ). Only the Style The Series TY -FRB Sprinklers must be
10, 20, 30, or 40 Recessed Escutch- installed in accordance with the follow -
The Series TY -FRB Pendent and Up- eon, as applicable, is to be used for ing instructions:
right Sprinklers are intended for fire recessed pendent installations.
protection systems designed in ac- NOTES
cordance with the standard installation Do not install any bulb type sprinkler if
rules recognized by the applicable the bulb is cracked or there is a loss of
Listing or Approval agency (e.g., UL liquid from the bulb. With the sprinkler
•
Page 4 of 8 TFP171
SPRINKLER FINISH (See Note 7) inch NPT sprinkler joint should be ob-
K
TYPE tained with a torque of 10 to 20 ft.lbs.
YPE TEMP. BULB NATURAL CHROME WHITE'*'
LIQUID BRASS PLATED POLYESTER (13,4 to 26,8 Nm). A maximum to be of 30
ft.lbs. (40, 7 Nm) ) of of i
torque is to be used
135 °F /57 °C Orange to install sprinklers with 3/4 NPT con -
PENDENT nections. Higher levels of torque may
155 °F /68 °C Red distort the sprinkler inlet and cause
(TY1231) 1, 2, 3, 5 leakage or impairment of the sprinkler.
and 175 °F /79 °C Yellow
UPRIGHT Do not attempt to make -up for insuffi-
200 °F /93 °C Green cient adjustment in the escutcheon
2.8 (TY1131) 286 °F /141 °C Blue plate by under- or over - tightening the
1/2" sprinkler. Readjust the position of the
NPT 135 °F /57 °C Orange sprinkler fitting to suit.
RECESSED 155 °F /68 °C Red
PENDENT The Series TY -FRB Pendent and Up-
(TY1231)* 175 °F /79 °C Yellow right Sprinklers must be installed in
Figure 5 accordance with the following instruc-
g ure 200 °F /93 °C Green 1, 2, 5 tions.
135 °F /57 °C Orange Step 1. Pendent sprinklers are to be
RECESSED Red installed in the pendent position, and
PENDENT upright sprinklers are to be installed in
(TY1231) ** 175 °F /79 °C Yellow the upright position.
Figure 6 200 °F /93 °C Green Step 2. With pipe thread sealant ap-
135 °F /57 °C Orange plied to the pipe threads, hand tighten
PENDENT the sprinkler into the sprinkler fitting.
(TY2231) 155 °F /68 °C Red Step 3. Tighten the sprinkler into the
and 175 °F /79 °C Yellow sprinkler fitting using only the W -Type
UPRIGHT 200 °F /93 °C Green 6 Sprinkler Wrench (Ref. Figure 13).
42 (TY2131) With reference to Figures 1, 2, 3, and
286 °F1141 °C Blue 2 4, the W -Type 6 Sprinkler Wrench is to
1/2" be applied to the sprinkler wrench
NPT 135 °F /57 °C Orange
RECESSED flats.
PENDENT 155 °F /68 °C Red
(TY2231)* 175F/79°C Yellow The Series TY -FRB Recessed Pen -
Figure 7 200 °F /93 °C Green dent Sprinklers must be installed in
accordance with the following instruc-
135°F/57°C Orange tions.
RECESSED 155 °F /68 °C Red Step A. After installing the Style 10.
PENDENT 20, 30, or 40 Mounting Plate, as appli-
(TY2231)** 175 °F /79 °C Yellow cable, over the sprinkler threads and
Figure 8 200 °F /93 °C Green with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
NOTES: kler into the sprinkler fitting.
1 Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. Step B. Tighten the sprinkler into the
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response sprinkler fitting using only the W - Type
Sprinklers. 7 Recessed Sprinkler Wrench (Ref.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin
klers. Figure 14). With reference to Figure 1,
5. Approved by the City of New York under MEA 354 -01 -E. 2, 3, and 4, the W - Type 7 Recessed
7 Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin- Sprinkler Wrench is to be applied to
klers are UL and C -UL Listed as Corrosion Resistant Sprinklers. the sprinkler wrench flats.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Step C. After the ceiling has been in-
Recessed Escutcheon, as applicable. stalled or the finish coat has been ap-
Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment plied, slide on the Style 10, 20, 30, or
Recessed Escutcheon, as applicable. 40 Closure over the Series TY -FRB
— Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available Sprinkler and push the Closure over
TABLE A the Mounting Plate until its flange
LABORATORY LISTINGS AND APPROVALS comes in contact with the ceiling.
2.8 AND 4.2 K- FACTOR SPRINKLERS
held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint
should be present. The diameter of the should be obtained with a torque of 7
air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
(1,6 mm) for the 135 °F /57 °C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque
inch (2,4 mm) for the 286 °F /141 °C may be used to install sprinklers with
temperature ratings. 1/2 NPT connections. A leak tight 3/4
TFP171 Page 5 of 8
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL CHROME WHITE "' LEAD
LIQUID BRASS PLATED POLYESTER COATED
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5
and 175 °F /79 °C Yellow
UPRIGHT 200 °F /93 °C Green
5:`-' (TY3131)
286 °F /141 °C Blue
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 4, 5 N/A
(TY3231)' 175 °F /79 °C Yellow
Figure 9 200 °F /93 °C Green
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A
(TY3231)** 175 °F /79 °C Yellow
Figure 10 200 °F /93 °C Green
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY4231) 1, 2, 5
and 175F/79°C Yellow 1, 2, 3, 4, 5, 6, 7
UPRIGHT 200 °F /93 °C Green
8.0 (TY4131)
286 °F /141 °C Blue
3/4"
NPT 135 °F /57 °C Green
RECESSED 155 °F /68 °C Orange
PENDENT 1, 2, 4, 5 N/A
(TY4231)* 175 °F /79 °C Red
Figure 11 200 °F /93 °C Yellow
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4231)•° 175 °F /79 °C Yellow
Figure 12 200 °F /93 °C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as -Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428 - 3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a106) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers
• Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
• Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
"' Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K- FACTOR SPRINKLERS
Page 6 of 8 TFP171
2 -7/8" DIA. - 2 -7/8" DIA.
5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8° (73,0 mm) 1/2" (12,7 mm)
(15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm)
2 -1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm)
MOUNTING
SPRINKLER
PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
•• ' (3,2 mm) N ______,_ .411 (3,2 mm)
I
J . '.uI 0 _ f \ � \I �
MOUNTING 4111P MOUNTING SURFACE .
SURFACE i7rr��. ui /��h
CLOSURE SERIES 1- 5/16" (33,3 mm) CLOSURE SERIES 1 -5 /16" (33,3 mm)
TY -FRB 13/16" (20,6 mm) TY -FRB 1 -1/16" (27,0 mm)
FIGURE 5 FIGURE 6
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO- PIECE_1 /2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT
2 -7/8" DIA. 2 -7/8" DIA.
5/8±1/4" (73,0 mm) 3/4" (19,1 mm) (73,0 mm)
1/2 ±1/8° 1/2" (12,7 mm)
(15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm)
57,2 mm
SPRICNKOLER ( mm) MOUNTING FACE OF (57,2 mm) MOUNTING
PLATE SPRINKLER PLATE
FITTING FITTING
1 /8" 1/8"
•., (3,2 mm) •� ( mm)
i --._- .-iiiiii
�- IN , � _ f \ AM:4 w
\ � MOUNTING I �/
MOUNTING . ■
SURFACE .-
CLOSURE SERIES 1 -1/4" (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm)
TY -FRB 3/4" (19,1 mm) TY -FRB 1" (25,4 mm)
FIGURE 7 FIGURE 8
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT
�s
and used to cover a clearance hole, may and after installation. Sprinklers dam- and delay the time to sprinkler operation in aged by dropping, striking, wrench
M • a fire situation. twist/slippage, or the like, must be re-
aintenance that are found to be leaking has a crackedpbulb or has lost
The Series TY -FRB Sprinklers must be or exhibiting visible signs of corrosion liquid from its bulb. (Ref. Installation
maintained and serviced in accord- must be replaced. Section).
ance with the following instructions: Automatic sprinklers must never be Frequent visual inspections are rec-
NOTES painted, plated, coated or otherwise ommended to be initially performed for
altered after leaving the factory. Modi- corrosion resistant coated sprinklers,
Before closing a fire protection system fied sprinklers must be replaced. p
main control valve for maintenance Sprinklers that have been exposed to after the installation has been com-
work on the fire protection system that corrosive products of combustion, but pleted, to verify the integrity of the cor-
it controls, permission to shutdown the have not operated, should be replaced rosion resistant coating. Thereafter,
affected fire protection system must be if they cannot be completely cleaned annual inspections per NFPA 25
obtained from the proper authorities by wiping the sprinkler with a cloth or should suffice; however, instead of in-
and all personnel who may be affected by brushing it with a soft bristle brush. specting from the floor level, a random
by this action must be notified. sampling of close -up visual inspec-
Care must be exercised to avoid dam- tions should be made, so as to better
Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi-
TFP171 Page 7 of 8
2 -7/8° DIA. - 2 -718' DIA
5/811/4" ( mm) 3/4° (19 1 mm) (73,0 mm)
1/2±1/8° 1/2' (12,7 mm)
(15,9±6,4 mm) 2 -1/4' DIA 1/4' (6,4 mm) (12,7±3,2 mm) 1/4° (6,4 mm)
2 -1/4° DIA y
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm)
MOUNTING
SPRINKLER
PLATE SPRINKLER PLATE
FITTING FITTING
1/8 1/8' NM
�411 ( mm) i ����� % /L (3,2 m
Milli 'Or
I ;i jt \ f
�,,, MOUNTING
IIIP
MOUNTING SURFACE
SURFACE = = -r i R�r- ,
CLOSURE SERIES 1 -1/4' (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm)
TY -FRB 3/4 (19,1 mm) TY -FRB 1° (25,4 mm)
FIGURE 9 FIGURE 10
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT
2 -7/8' DIA 2 -7/8' DIA
5/8±1/4' (73,0 mm) 3/4' (19,1 mm) 1/2 ±1/8' (73,0 mm) 1/2" (12,7 mm)
(15,9±6,4 mm) 2 -1/4' DIA. 1/4° (6,4 mm) (12,7 ±3,2 mm) F 2 -1/4' DIA 1/4° (6,4 mm)
FACE OF (57,2 mm) MOUNTING (57,2 mm)
FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8° 1/8
" (3,2 mm) ■II (3 mm)
filE111 Pr
f \ AMMKAI Or i '
MOUNTING
MOUNTING �:• SURFACE II v
CLOSURE SERIES 1 -5/16' (33,3 mm) CLOSURE SERIES 1 -5/16' (33,3 mm)
TY -FRB 13/16 (20,6 mm) TY -FRB 1 -1/16' (27,0 mm)
FIGURE 11 FIGURE 12
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may WRENCH
e
be affected by the corrosive conditions ' RECESS
present.
WRENCH RECESS f*
The owner is responsible for the in- (END "A" USED FOR i
spection, testing, and maintenance of 1/2 NPT MODELS) n
their fire protection system and de- �
vices in compliance with this docu- S ' IIIJJJ
ment, as well as with the applicable .....i.
standards of the National Fire Protec- WRENCH RECESS
tion Association (e.g., NFPA 25 , in (END "B" USED FOR PUSH WRENCH
g . 3 /4" NPT MODELS) IN TO ENSURE
addition to the standards of any other ENGAGEMENT
authorities having jurisdiction. The in- WITH SPRINKLER
stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA
facturer should be contacted relative to W -TYPE 6 SPRINKLER
any questions. WRENCH
It is recommended that automatic FIGURE 14
sprinkler systems be inspected, local requirements and /or national W-TYPE RECESSED
tested, and maintained by a qualified codes. SPRINKLER WRENCH
Inspection Service in accordance with
Page 8 of 8 TFP171
P/N 57 - XXX - X - XXX
I I
TEMPERATURE
MODEUSIN RATING
SPRINKLER
330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135 °F /57 °C
331 2.8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C
340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C
341 4.2K PENDENT (1/2 "NPT) TY2231 3 WHITE (RAL9010)' 200 200 °F /93 °C
370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C
371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED
390 8 OK UPRIGHT (3/4 "NPT) TY4131
391 8.0K PENDENT (3/4 "NPT) TY4231 ' Eastern Hemisphere sales only.
TABLE C
PART NUMBER SELECTION
SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS
ORY, FOR INCIDENTAL, INDIRECT, Recessed - Escutcheon:
Limited SPECIAL OR CONSEQUENTIAL Specify: Style (specify) Recessed Es-
DAMAGES, INCLUDING BUT NOT cutcheon with (specify finish), P/N
Warranty LIMITED TO LABOR CHARGES, RE- (specify).
GARDLESS OF WHETHER TYCO
Products manufactured by Tyco Fire FIRE PRODUCTS WAS INFORMED 1/2" (15 mm)
Products are warranted solely to the ABOUT THE POSSIBILITY OF SUCH Style 10
original Buyer for ten (10) years DAMAGES, AND IN NO EVENT Chrome Plated .... ... . P/N 56- 701 -9 -010
against defects in material and work- SHALL TYCO FIRE PRODUCTS' LI- White Coated P/N 56- 701 -4 -010
manship when paid for and properly ABILITY EXCEED AN AMOUNT Brss P '..... ... P/N 56-701-3-010
installed and maintained under normal EQUAL TO THE SALES PRICE. Braass Pllated ated P/N 56 701 -2 -010
use and service. This - warranty -will ex- THE FOREGOING WARRANTY IS 1/2" (15 mm)
pire ten (10) years from date of ship- Style 20
ment by Tyco Fire Products. No war- MADE IN LIEU OF ANY AND AL L. Chrome Plated P/N 56- 705 -9 -010
ranty is given for products or OTHER WARRANTIES EXPRESS OR White Coated P/N 56- 705 -4 -010
components manufactured by compa IMPLIED. INCLUDING WARRANTIES White RAL9010' . ..... P/N 56- 705 -3 -010
Hies not affiliated by ownership with OF MERCHANTABILITY AND FIT- Brass Plated . P/N 56- 705 -2 -010
Tyco Fire Products or for products and NESS FOR A PARTICULAR PUR 3/4" (20 mm)
components which have been subject POSE Style 30
to misuse, improper installation, corro- Chrome Plated . P/N 56- 705 -9 -011
sion, or which have not been installed, White Coated P/N 56- 705 -4 -011
maintained, modified or repaired in ac- White Plated 0' P/N 56- 705 -3 -011
cordance with applicable Standards of � d�� ®n� Brass Plated P/N 56- 705 -2 -011
the National Fire Protection Associa- Procedure 3/4" (20 mm)
tion, and /or the standards of any other Style 40
Authorities Having Jurisdiction. Mate- Oontatabygtafs Local distributor for avail Chrome Plated P/N 56- 700 -9 -010
rials found by Tyco Fire Products to be abi1 ,indicate the White Coated P/N 56- 700 -4 -010
defective shall be either repaired or ful product White RAL9010' .. P/N 56- 700 -3 -010
replaced, at Tyco Fire Products' sole name. Refer to Brass Plated P/N 56- 700 -2 -010
option. Tyco Fire Products neither as- the complete List for
o
p y complete listing 'Eastern Hemisphere sales only
sumes, nor authorizes any person to of Part Numbers
assume for it, any other obligation in Sprinkler Wrench:
connection with the sale of products or Sprinkler Assemblies with NPT Specify: W -Type 6 Sprinkler Wrench,
parts of products. Tyco Fire Products Thread Connections: P/N 56- 000 -6 -387.
shall not be responsible for sprinkler Specify: (Specify Model /SIN), Quick
system design errors or inaccurate or Response, (specify K- factor), (specify Specify: W-Type 7 Sprinkler Wrench,
incomplete information supplied by temperature rating), Series TY -FRB P/N 56- 850 -4 -001.
Buyer or Buyer's representatives. (specify Pendent or Upright) Sprinkler
IN NO EVENT SHALL TYCO FIRE with (specify type of finish or coating),
PRODUCTS BE LIABLE, IN CON P/N (specify from Table C).
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
tLICD /Ffre & Building
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series DS -1 — 5.6 K- factor
Dry Type Sprinklers
Quick Response, Standard Coverage
General standards of any other authorities hay-
ing jurisdiction. Failure to do so may A. s
impair the performance of these de- I
Description vices. , :-.-
The Series DS -1, 5.6 K- factor, Quick The owner is responsible for maintain- q
i
Response, Standard Coverage, Dry ng their fire protection system and d
Type Sprinklers are decorative 3 mm vices in proper operating condition. "
glass bulb automatic sprinklers de The installing contractor or sprinkle I
signed for the following typical uses: manufacturer should be contacted
g gyp with any questions. t n
• where pendent sprinklers are re-
quired on dry pipe systems that The Series DS -1 Dry Type Sprinklers r
are exposed to freezing tempera must only be installed in fittings that t ii I
meet the
requirements of the Desi n ry
tures (e.g. sprinkler drops from un- q g I
heated portions of buildings) Criteria section :
• where sprinklers and /or a portion i
of the connecting piping may be Model /Sprinkler
I ._-, -
exposed to freezing temperatures ■
(e.g. sprinkler drops from wet sys- Identification
tems into freezers, sprinkler �/
sprigs from wet systems into un- Numbers
heated attics, or horizontal piping
extensions through a wall to pro- TY3235 - (Pendent) ' '
tect an unheated area of a build- TY3135 - (Upright)., 1;
ing) TY3335 - (Horizontal Sidewall)
• where sprinklers are used on sys -
tems that are seasonably drained Technical
to avoid freezing (e.g. vacation re-
sort areas) Data
WARNINGS Approvals
The Series DS -1 Dry Type Sprinklers UL and C -UL Listed. Physical Characteristics
described herein must be installed and FM and NYC Approved. Inlet Copper
maintained in compliance with this (Refer to Table A) Plug Copper
document, as well as with the applica- Yoke Stainless Steel
ble standards of the National Fire Pro- Maximum Working Pressure Casing . . Galvanized Carbon Steel
tection Association, in addition to the 175 psi (12,1 bar) Insert Bronze
Inlet Thread Connection Bulb Seat Stainless Steel
1 inch NPT (Standard Order) Bulb Glass
IMPORTANT ISO 7 -R1 Compression Screw Bronze
Deflector Bronze
Always refer to Technical Data Discharge Coefficient Frame Bronze
Sheet TFP700 for the `INSTALLER K = 5.6 GPM /psi Guide Tube Stainless Steel
WARNING" that provides cautions (80,6 LPM /barli Water Tube Stainless Steel
with respect to handling and instal- Spring Stainless Steel
latronof sprinkler systems and com Temperature Rating p g
onents. Im ro er handlin and in Refer to Table A Sealing Assembly
p p p g Beryllium Nickel w/Teflon'
stallation can permanently damage Finishes Escutcheon Carbon Steel
a sprinkler system or its compo- Sprinkler: Natural Brass, Chrome "Registered Trademark of DuPont
nents and cause the sprinkler to fail Plated, White Polyester
to operate in a fire situation or cause Escutcheon: White Coated or Chrome Patents
it to operate prematurely. Plated U.S.A. Patent No. 5,188,185
Page 1 of 8 APRIL, 2004 TFP510
•
Page 2 of 8 TFP51O
SPRINKLER FINISH
TY3235 Pendent TY3235 Pendent TY3335 Hor. Sidewall
w/ Standard w/ Std. Escutcheon with top of
Recessed Escutcheon (Ref. Fig. 5) Deflector - to-Ceiling
(Ref. Fig. 3) w/ Deep Escutcheon distance of
w/ Wide Flange (Ref. Fig. 6) 4 to 12 inches
Recessed Escutcheon w/o Escutcheon (100 to 300 mm)
(Ref. Fig. 4) (Ref. Fig. 7) w/ Std. Escutcheon
(Ref. Fig. 9)
TY3135 Upright w/ Deep Escutcheon
w/o Escutcheon (Ref. Fig. 10)
(Ref. Fig. 8) w/o Escutcheon
(Ref. Fig. 11)
Temperature Bulb Natural Chrome White Natural Chrome White Natural Chrome White
Rating Color Code Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester
135 °F /57 °C Orange 1, 2, 3, 4 1. 2, 4 1, 2, 3, 4 1, 2, 4 1', 2', 3 ", 4 1', 2', 4
155 °F /68 °C Red 1,2,3,4 1, 2,4 1,2,3,4 1,2,4 1',2',3 ",4 1',2 ",4
175 °F /79 °C Yellow 1, 2, 3, 4 1, 2, 4 1, 2, 3, 4 1, 2, 4 1 *, 2', 3 ", 4 1', 2*, 4
200 °F /93 °C Green 1, 2, 3, 4 1, 2, 4 1, 2, 3, 4 1, 2, 4 1*, 2*, 3 ", 4 1*, 2 *, 4
286 °F /141 °C Blue N/A ' 1, 2, 3, 4 1, 2, 4 1 2', 3'', 4 1*, 2', 4
Notes:
1. Listed by Underwriters Laboratories, Inc (Maximum order length of 48 inches).
2. Listed by Underwriters Laboratories for use in Canada. (Maximum order length of 48 inches).
3. Approved by Factory Mutual Research Corporation (Maximum order - length of 48 inches)
4. Approved by the City of New York under MEA 352 -01 -E.
' Light and Ordinary Hazard Occupancies Only.
" Light Hazard Occupancies Only.
N/A - Not Available.
TABLE A
SERIES DS -1, QUICK RESPONSE - STANDARD COVERAGE, DRY TYPE SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
WRENCH
PLUG WITH ,i� INLET RECESS
GASKETED SPRIN '
PLATE SEAL j i 1
6ii Y OKE r ------1- 1 , ��
SPRING �._ 1 4 �� , 7 1
1 _. -- CASING
@ � = � ';
WATER - PUSH WRENCH IN TO
TUBE i q ENSURE ENGAGEMENT WITH
1
INSE S PRINKLER WRENCHING AREA
GUIDE III 0 FIGURE2
TUBE � 'IN - ! 11 /' W-TYPE 7 SPRINKLER WRENCH
1 / SEAT
FRAME l A I � +
l ! � = - 3 mm
BULB
VENT HOLE III
kill0 - COMPRESSION SCREW
DEFLECTOR
FIGURE 1
SERIES DS -1 QUICK RESPONSE
DRY TYPE SPRINKLER ASSEMBLY
•
TFP510 Page 3 of 8
SPRINKLER FITTING SPRINKLER FITTING SPRINKLER FITTING
(REFER TO DESIGN (REFER TO DESIGN (REFER TO DESIGN
Z_ CRITERIA SECTION -- - - -,
CRITERIA SECTION) - - - 2 r - i CRITERIA SECTION) ) J
FACE OF FACE OF L1 -. FACE OF \ L-�'>
SPRINKLER _ SPRINKLER L__[I SPRINKLER L
FITTING - FITTING FITTING
ORDER LENGTHS. ORDER LENGTHS. ORDER LENGTHS
3 -1/2" to 48" 3 -1/2" to 48" 2 -1/2° to 48" 1 -3/4" DIA.
(88,9 to 1219,2 mm) (88,9 to 1219,2 mm) (63,5 to 1219,2 mm) (44,5 mm)
IN 1/4° (6,4 mm) 2 -1/4" DIA. IN 1/4" (6,4 mm) 3" DIA IN 1/4" (6,4 mm)
INCREMENTS _(57.2 mm) , INCREMENTS (76,2 mm) INCREMENTS
FACE OF I FACE O ;� � � y; �
.
CEILING , CEILING I -
:!J F ' I . I _ !:- FACE OF
■ ' • � CEILING
,
I 2 -7/8" DIA. 3 -5/8" DIA 3" DIA
1 -3/8" ± " 1/8" 2 -3/16" ± 1 /8" (76 mm) 1
(34,9 ± 3,2 mm) (73,0 mm) (34,9 ± 3,2 mm) (92,1 mm) (55,6 t 3,2 mm) -
FIGURE 3 FIGURE 4 FIGURE 5
TY3235 PENDENT TY3235 PENDENT TY3235 PENDENT
w/ STANDARD RECESSED w/ WIDE FLANGE RECESSED w/ STANDARD
ESCUTCHEON ESCUTCHEON ESCUTCHEON
SPRINKLER FITTING SPRINKLER FITTING t i
(REFER TO DESIGN (REFER TO DESIGN TOP OF
CRITERIA SECTION) - - - ti r-- CRITERIA SECTION) --1 r--• DEFLECTOR
�. ( --
FACE OF - FACE OF -1
SPRINKLER ~ I SPRINKLER
L_I� J I 41
FITTING _ FITTING ORDER LENGTHS'
- 5" to 48"
- (127,0 to 1219,2 mm)
ORDER LENGTHS: j _3 -1/2" DIA. 1 IN 1/4" (6,4 mm)
1/2" to 46" ' (88,9 mm) ORDER LENGTHS: INCREMENTS
(12,7 to 1168,4 mm) 2 -1/2" DIA. 5" to 48"
IN 1/4" (6,4 mm) (63,5 mm) (127,0 to 1219.2 mm) FACE OF
INCREMENTS I I- - - - - -I IN 1/4" (6,4 mm) SPRINKLER
' I INCREMENTS FITTING
r _
FACE OF __; - _,
CEILING --
MINIMUM F
4 -1/4" ± 1/8" . 1 -3/4° (44,5 mm) I, ` -
(108,0 ±3,2 mm) DEFLECTOR i
TO CEILING SPRINKLER FITTING DESIGN
(REFER , CRITERIA TO SECTION)
FIGURE 6 FIGURE 7 FIGURE 8
TY3235 PENDENT TY3235 PENDENT TY3135 UPRIGHT
w/ DEEP ESCUTCHEON w/o ESCUTCHEON w/o ESCUTCHEON
•
Page4of8 TFP51O
ORDER LENGTHS- Operation
2 -1/2" to 48" (63,5 to 1219,2 mm)
IN 1/4" (6,4 mm) INCREMENTS 4 " :1/8"
(101,6±3.2mm) When the Series DS -1 is in service,
FACE OF FACE OF 1 -3/4" DIA water is prevented from entering the
_ __ — SPRINKLER MOUNTING — (44,5 mm) assembly by the Plug & Belleville Seal-
__�__; FITTING SURFACE ,, Ing Assembly (Ref. Figure 1) in the
� � !! Inlet of the Sprinkler. The glass Bulb
I' ���1� =-Ji 36",2 contains a fluid that expands when ex-
II (76.2 mm) posed to heat. When the rated tern-
3.5° 1 perature is reached, the fluid expands
-- , SPRINKLER FITTING `\ sufficiently to shatter the glass Bulb,
'— '---; (REFER TO DESIGN CENTERLINE 5/16" and the Bulb Seat is released. The
CRITERIA SECTION) OF WATERWAY (7,9 mm) compressed Spring is then able to ex-
FIGURE 9 pand and push the Water Tube as well
TY3335 HORIZONTAL SIDEWALL w/ STANDARD ESCUTCHEON as the Guide Tube outward. This action
simultaneously pulls inward on the
Yoke, withdrawing the Plug & Belleville
ORDER LENGTHS FACE OF Seal from the Inlet allowing the sprin-
1/2" to 45 -3/4" (12,7 to 1162.1 mm) MOUNTING kler to activate and flow water.
IN 1/4" (6,4 mm) INCREMENTS SURFACE
I
/7.7' , 4-13/16° ± 1/8°
(122,2±3.2 mm)
FACE OF 2 -1/2" DIA.
- SPRINKLER (63,5 mm) Design
it ±_-_-_'._ FITTING 6
',
j i IL--- 3 1/2° DIA Criteria
r
— I- / ■ (88,9 aim) The Series DS -1 Sprinklers are in-
IF-- / 3 s° tended for use in fire sprinkler systems
SPRINKLER FITTING q designed in accordance with the
' -= --' (REFER TO DESIGN CENTERLINE 5/16" standard installation rules recognized
CRITERIA SECTION) OF WATERWAY (7,9mm) by the applicable Listing or Approval
FIGURE 10 agency (e.g., UL Listing is based on
TY3335 HORIZONTAL SIDEWALL w/ DEEP ESCUTCHEON NFPA 13 requirements).
The Series DS -1 Dry Type Sprinkler is
ORDER LENGTHS, to be installed in the 1 inch NPT outlet
5" to 48" (127,0 to 1219,2 mm) - or run of malleable or ductile iron
IN 1/4" (6,4 mm) INCREMENTS MINIMUM threaded tee fittings that meet the di-
2-1/4" (57,2 mm) mensional requirements of ANSI
FACE OF DEFLECTOR TO B16.3 (Class 150) or cast iron
— SPRINKLER MOUNTING threaded tee fittings that meet the di-
1_ FITTING SURFACE mensional requirements of ANSI
B16.4 (Class 125) with the end sprin-
1���j�� -----r kler fitting on a branch line to be
r, / plugged as shown in Figures 3 - 11.
T' / 3s° 5/16" When installing 1 inch NPT Series
SPRINKLER FITTING (7,9 mm) DS -1 Dry Type Sprinklers on a dry pipe
-' (REFER TO DESIGN CENTERLINE sprinkler system, only use the side
CRITERIA SECTION) OF WATERWAY outlet of maximum 2 -1/2 inch size re-
FIGURE 11 ducing tee's.
TY3335 HORIZONTAL SIDEWALL w/o ESCUTCHEON For wet pipe sprinkler systems, the
Series DS -1 Dry Type Sprinklers may
also be installed in the 1 inch NPT
outlet of a Central Figure 730 Me-
chanical Tee or the following Tyco Fire
Products CPVC fittings: (P /N 80145)
1" x 1" NPT Female Adapter or (P /N
80249) 1" x 1" x 1" NPT Sprinkler Head
Adapter Tee.
NOTE
Do not install the Series DS -1 into any
other type fitting without first consult-
ing the Technical Services Depart-
ment. Failure to use the appropriate
fitting may result in: failure of the sprin-
kler to properly operate due to forma-
tion of ice over the inlet Plug or binding
of the inlet Plug; or, insufficient en-
TFP51 O Page 5 of 8
gagement of the inlet pipe threads with Deep Escutcheon, hold the outer
consequent leakage. installation piece in contact with the mounting sur-
Branch, cross, and feedmain piping The Series DS 1 Dry Type Sprinklers face (ceiling), and then rotate the inner
connected to Dry Sprinklers and sub- y yp p piece approximately 1/4 turn with re-
must be installed in accordance with spect to the outer piece, to hold the
ject to freezing temperatures must be the following instructions: Deep Escutcheon firmly together.
pitched for drainage in accordance
with the minimum requirements of the NOTES
National Fire Protection Association The Series DS -1 must only be installed Care and
for dry pipe sprinkler systems. in fittings that meet the requirements
When Dry Sprinklers are to be used in of the Design Criteria section. Maintenance
wet areas ubject to temperatures e protecting Refer to the Design Criteria section for The Series DS -1 Dry Type Sprinklers
other important requirements re must be maintained and serviced in
(e.g., sprinkler drops into freezers), ing piping design and sealing of the
consideration must be given to the ap- c space around the Sprinkler accordance with the following instruc-
propriate length of the sprinkler that tions:
will prevent freezing of the water in the Casing.
connecting pipes due to conduction. Do not install any bulb type sprinkler if NOTES
When the temperature surrounding the bulb is cracked or there is a loss of Absence of the outer piece of an es-
the wet pipe sprinkler system is main- liquid from the bulb. With the sprinkler cutcheon, which is used to cover a
tained at a minimum temperature of held horizontally, a small air bubble clearance hole, may delay the time to
40 °F /4 °C, the following are the mini- should be present. The diameter of the sprinkler operation in a fire situation.
mum recommended lengths between air bubble is approximately 1/16 inch Before closing a fire protection system
the face of the sprinkler fitting and the (1,6 mm) for the 135 °F /57 °C rating to main control valve for maintenance
outside surface of the protected area 1/8 inch (3,2 mm) for the 286 °F /141 °C work on the fire protection system that
(i.e., length exposed to minimum am- rating. it controls, permission to shut down
bient of 40 °F /4 °C): A leak tight 1 inch NPT sprinkler joint the affected fire protection systems
• 12 inches (300 mm) when the tern- should be obtained with a torque of 20 must be obtained from the proper
perature within the protected area to 30 ft.lbs. (26,8 to 40,2 Nm). Higher authorities and all personnel who may
is - 20 °F / -29 °C levels of torque may distort the sprin- be affected by this action must be no-
• 18 inches (450 mm) when the tern- kler inlet with consequent leakage or titled.
impairment of the sprinkler. A Vent Hole is provided in the Bulb
perature within the protected area p
is - 40 °F / -40 °C Do not attempt to compensate for in- Seat (Ref. Figure 1) to indicate if the
inches (600 mm) when the tern- sufficient adjustment in an Escutcheon Dry Sprinkler is remaining dry. Evi-
• 24 the protected area Plate by under- or over - tightening the dence of leakage from the Vent Hole
perature
is r within (600 °C Sprinkler. Readjust the position of the is an indication that there may be
sprinkler fitting to suit. weepage past the Inlet seal and that
For protected area temperatures be- S tep 1. Pendent sprinklers must be the sprinkler needs to be removed for
tween those given above, the minimum determining the cause of leakage (e.g.
installed only in the pendent position,
recommended length from the face of and upright sprinklers must be in- an improper insfallation or an ice plug) .
t fitting to the outside of the pro- stalled only in the upright position. The T fire protection system control
tected area may be determined by in- deflector of a pendent or upright sprin- valve must be closed and the system
terpolating between the 'indicated val- kler is to be parallel to the ceiling. drained before removing the sprinkler.
ues. Sprinklers that are found to be leaking
Horizontal sidewall sprinklers are to be or exhibiting visible signs of corrosion
NOTE installed in the horizontal position with must be replaced.
When Dry Sprinklers penetrate a cell- their centerline of waterway perpen-
ing or wall into an area subject to freez- dicular to the back wall and parallel to Automatic sprinklers must never be
ing, the clearance space around the the ceiling. The word 'TOP" on the De- painted, plated, coated, or otherwise
Sprinkler Casing must be completely flector is to face towards the ceiling. altered after leaving the factory. Modi-
sealed in order to prevent the leakage Step 2. With pipe thread sealant ap fied sprinklers must be replaced.
of moist air into the freezing area plied to the inlet threads, hand tighten Sprinklers that have been exposed to
which might result in the formation of the sprinkler into the sprinkler fitting. corrosive products of combustion, but
condensate around the Frame, Deflec- have not operated, should be corn-
tor, Bulb Seat, or Bulb. Failure to pre- Step 3. Wrench tighten the sprinkler by pletely cleaned by wiping the sprinkler
vent the formation of condensate could wrenching on the Casing with a pipe with a cloth or by brushing it with a soft
result in the build -up of ice around the wrench whenever the casing is readily bristle brush.
releasing components. This could re- accessible. Otherwise, use a W -Type 7 Care must be exercised to avoid dam -
sult an inadvertent operation of the Sprinkler Wrench (Ref. Figure 2). The age - before, during, and after instal -
sprinkler or impaired operation due to wrench recess of the W -Type 7 is to be lation. Sprinklers damaged by drop -
reduced thermal sensitivity. applied to the sprinkler wrench flats ping, striking, wrench twist/slippage,
(Ref. Figure 2). or the like, must be replaced. Also,
Step 4. After the ceiling /wall has been replace any sprinkler that has a
installed /finished, slide on the outer cracked bulb or that has lost liquid from
piece of the Escutcheon until it comes its bulb (Ref. Installation Section).
in contact with the ceiling /wall. Do not The owner is responsible for the in-
lift the ceiling panel out of its normal spection, testing, and maintenance of
position. their fire protection system and de-
in the case of the outer piece of the vices in compliance with this docu-
Page 6 of S
9 TF510
ment, as well as with the applicable MADE IN LIEU OF ANY AND ALL
standards of the National Fire Protec- OTHER WARRANTIES EXPRESS OR
tion Association (e.g., NFPA 25), in IMPLIED. INCLUDING WARRANTIES
addition to the standards of any other OF MERCHANTABILITY AND FIT -
authorities having jurisdiction. The in- NESS FOR A PARTICULAR PUR-
stalling contractor or sprinkler manu- POSE.
facturer should be contacted relative to
any questions.
It is recommended that automatic Ordering
sprinkler systems be inspected,
tested, and maintained by a qualified Procedure
Inspection Service in accordance with
local requirements and /or national Contact your local distributor for avail -
codes. ability, and please specify the follow-
ing:
Limited 1 . Sprinkler.
Warranty • Model /SIN.
• Quick Response, Standard Cover -
Products manufactured by Tyco Fire age, Dry Type Sprinkler
Products are warranted solely to the • Deflector Style.
original Buyer for ten (10) years
against defects in material and work- • 5.6 K- factor.
manship when paid for and properly • Order Length.
installed and maintained under normal
use and service. This warranty will ex- Dry Type Sprinklers are furnished
pire ten (10) years from date of ship- based upon Order_Length as
ment by Tyco Fire Products. No war- measured per Figure 3 through
ranty is given for products or 11, as applicable. After the meas-
components manufactured by compa- urement is taken, round it to the
nies not affiliated by ownership with nearest 1/4 inch increment.
Tyco Fire Products or for products and
components which have been subject • Inlet Connection (1 Inch NPT or
to misuse, improper installation, corro- ISO 7 -R1).
sion, or which have not been installed, • Temperature Rating.
maintained, modified or repaired in ac-
cordance with applicable Standards of • Sprinkler Finish.
the National Fire Protection Associa- • Escutcheon Style and Finish, as
tion, and /or the standards of any other applicable.
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be • Part Number from Table B. (Part
defective shall be either repaired or numbers are for 1 inch NPT stand -
replaced, at Tyco Fire Products' sole and order sprinklers. Orders for all
option. Tyco Fire Products neither as- other sprinkler assemblies must
sumes, nor authorizes any person to be accompanied by a complete
assume for it, any other obligation in description.)
connection with the sale of products or 2. W- Type Sprinkler Wrench.
parts of products. Tyco Fire Products
shall not be responsible for sprinkler Refer to the Price List for complete
system design errors or inaccurate or listing of Part Numbers.
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
TFP51 O Page 7 of 8
P/N 60 - XXX - X - XXX
I J ORDER
LENGTH (1)
(EXAMPLES)
055 5.50"
SPRINKLER ESCUTCHEON
MODEUSIN FINISH FINISH (2) 082 8.25"
36 Pendent w/ Standard TY3235 1 NATURAL BRASS WHITE 180 18 00"
Escutcheon (1" NPT) (Fig. 5)
4 WHITE POLYESTER WHITE 187 18.75"
33 Pendent w/ Deep TY3235
Escutcheon (1" NPT) (Fig. 6) 9 CHROME PLATED CHROME PLATED 372 37.25"
37 Pendent w/ Std. Recessed TY3235 0 CHROME PLATED WHITE 480 48.00"
Escutcheon (1" NPT) (Fig 3)
3 WHITE (RAL9010)" WHITE (RAL9010)"
32 Pendent w/o Escutcheon TY3235 - -
Escutcheon (1" NPT) (Fig. 7)
TEMPERATURE
34 Sidewall w/ Standard TY3335 I RATING (3)
Escutcheon (1" NPT) (Fig. 9)
0 135F/57C
43 Sidewall w/ Deep TY3335
Escutcheon (1" NPT) (Fig. 10) 1 155F/68C
44 Sidewall w/o TY3335 2 175F/79C
Escutcheon (1" NPT) (Fig. 11)
3 200F/93C
4 286F/141C
38 Upright w/o Escutcheon TY3135
(1" NPT) (Fig.8)
NOTES
(1). Dry Type Sprinklers are furnished based upon "Order Length"
as measured per Figures 3 through 11, as applicable, and for
each individual sprinkler where it is to be installed. After the meas-
urement is taken, round it to the nearest 1/4 inch increment.
(2). Escutcheon Finish applies to sprinklers provided with
escutcheons.
(3). The 286F/141C temperature rating applies to
non - recessed sprinkler assemblies.
• Eastern Hemisphere sales only.
TABLE B
PART NUMBER SELECTION
SERIES DS -1, QUICK RESPONSE, STANDARD COVERAGE, DRY TYPE SPRINKLERS
(Use Prefix "I" for ISO 7 -R1 Connection, e.g., 1-60-361-1-180)
4
Page 8 of 8 TF510
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446