Correspondence 7z//e,a 4c/064A 5,, i<G,(
P RETAIL PERMIT SERVICES, INC. •
S A National, Permit Service Company
April 3, 2000
ROBERT POSIrIN
City of Tigard
BUILDING DEPARTMENT
503- 639 -4171
RE: AFTERTHOUGHTS (REVISIONS)
Washington Square Mall
PROJECT #BUP 2000 -00Q59
PC #2 -50C
Robert,
Per your review, enclosed are 2 REVISED SETS, a copy of YOUR
COMMENTS and a RESPONSE LETTER; from the Architect.
Please RECHECK and APPROVE, so we can obtain a Building Permit.
If you have any - questions or:problems, please call, me at 800- 556 -8641.
Thank you.
Kent Fahey
3019 Hollinwell Drive • Katy, Texas'77450 • Tel: (281) 579 -2226 • Fax: (281) 579 -2227
February 25, 2000 l '" „ , d �
Kent Fahey CITY OF TIGA
3019 Hollinhill Drive
Katy, Texas 77450 OREG
• RE: Macerich Corporation PC# 2 -50C
gq/40 — 94-51 SW Washington Square BUP# 2000 -00059
Dear Sir:
Your plans for the proposed tenant improvement have been reviewed the following items require your
attention.
Energy Code
Submit Oregon Non - Residential Energy Code Forms 5 (a) through 5 (c).
Structural
Provide structural details and calculations for new the storefront.
Accessibility.
Provide an accessible cashier counter detail. OSSC, Section 1108.4.7.2 and 1109.23.2.
Fire Life Safety
1. Washington Square Mall was designed and approved under alternate methods of design and
construction. All spaces require two exits regardless of occupant load. Both exits must enter an approved
rated corridor. The exit at door #2 enters a storage area, this is not allowed under OSSC, Section 1004.2.3.
In order to comply a rated corridor complete with "S" label rated doors will be required. Door # 2 shall
also have a twenty- minute rating with an "S" label door. Doors entering the storage area shall also be
rated with the "S" label door.
2. Provide an illuminated exit directional area eight feet beyond the egress opening at door #2.
- 4 Electrical, mechanical, plumbing and sprinkler permits are deferred submittals. Your contractor will most
likely apply for these permits.
If you have questions, please call me at (503) 639 -4416.
Sincerely,
R ert Poskin, CBO
Senior Plans Examiner
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
•
` 4-c- yaoro — °a-° s
Y .7yka 1 C)C A. • R.,/
R t RETAIL PERMIT SERVICES INC.
P A National Permit Service Company
February 22, 2000
City of Tigard
Building Department
Attn: Bob Poskin
13125 S.W. Hall Hlvd.
Tigard, OR 97223
503- 639 -4171
Re: Afterthoughts
Washington Square
Dear Bob:
Please have the enclosed plans reviewed for a Building Permit. The
Contractor, when selected, will be in to pay for and pick up the permit.
Should you have any questions, please call me at 1- 800 - 556 -8641. Thank
you for your help.
Sincerely,
Kent Fahey
Enc.: 3 Sets /Application/Check
3019 Hollinwell Drive • Katy, Texas 77450 • Tel: (281) 579 -2226 • Fax: (281) 579 -2227
PROJECT INFORMATION SHEET
Project: (REMODEL) Owner:
Afterthoughts Claire's
Washington Square 3 S.W. 129 Ave.
9585 S.W. Washington Sq. Rd. Pembroke Pines, FL 33027
Space #K8 Stan Combs
Tigard, OR 97223 954- 433 -3435
Contractor:
Out to Bid -- Will pick up and pay for Building Permit at a later date. Contractor will
Have all necessary licenses. We are to submit plans, so permit will be ready when
Project is awarded.
Use Group: Mercantile Size: 2,570 sq. ft.
Construction Type: 2 -C (1 Hr) Value: $50,000
Occupant Load: 74 No. of Employees: 2 -3
Subdivision: Washington Square Start Date: 4/1/00
Scope of Work: (INTERIOR ALTERATION)
Tenant improvement of existing retail lease space. No Structural work is involved.
No Food Handling involved. Standard upgrade.
Applicant: Architect:
Retail Permit Services Mikael Kane
3019 Hollinwell Drive 421 Cattell Avenue
Katy, TX 77450 Collingswood, NJ 08108
800 -556 -8641 201- 848 -9060
Kent Fahey
February 25, 2000 i q�� �l
Kent Fahey CITY OF TIG ARD
3019 Hollinhill Drive
Katy, Texas 77450 OREGON
RE: Macerich Corporation PC# 2 -50C
9451 SW Washington Square BUP# 2000 -00059
Dear Sir:
Your plans for the proposed tenant improvement have been reviewed the following items require your
attention.
Energy Code
Submit Oregon Non - Residential Energy Code Forms 5 (a) through 5 (c).
Structural
Provide structural details and calculations for new the storefront.
Accessibility
Provide an accessible cashier counter detail. OSSC, Section 1108.4.7.2 and 1109.23.2.
Fire Life Safety
1. Washington Square Mall was'designed and approved under alternate methods of design and
construction. All spaces require two exits regardless of occupant load. Both exits must enter an approved
rated corridor. The exit at door #2 enters a storage area, this is not allowed under OSSC, Section 1004.2.3.
In order to comply a rated corridor complete with "S" label rated doors will be required. Door # 2 shall
also have a twenty- minute rating with an "S" label door. Doors entering the storage area shall also be
rated with the "S" label door.
2. Provide an illuminated exit directional area eight feet beyond the egress opening at door #2.
Electrical, mechanical, plumbing and sprinkler permits are deferred submittals. Your contractor will most
likely apply for these permits.
If you have questions, please call me at (503) 639 -4416.
Sincerely,
d0 /l�rt+
R ert Poskin, CBO
Senior Plans Examiner
13125 SW Hall Blvd., Tigard, OR 97223 639 -4171 TDD (503) 684 -2772
Mikael T. Kane, Architect
Design, Planning and Construction Administration Consultant
March 29, 2000
City of Tigard ' 1
BUILDING DEPARTMENT
13125 SW Hall Blvd. '
Tigard, OR 97223
Attn: Robert Poskin
RE: Afterthoughts
Washington Square
PC# 2 -50C
B U P # 2000 -00059
Dear Sir:
The following is in response to your review dated February 25th:
Energy Code
Attached are the Oregon Non - Residential Energy Code Forms 5(a)
through 5(c).
Structural
Attached are the structural details and calculations for the new storefront.
Accessibility
Refer to Sheet A302 for the accessible cashier counter detail. OSSC,
Section 1108.4.7.2 and 1109.23.2.
Fire Life Safety
1. Refer to Sheet A101 for the addition of the egress rated corridor with
"S" label rated doors.
2. Refer to Sheet A102 for the illuminated exit directional area.
Re; pe t Ily,
/11
Mikael T ane, AIA, NCARB
• Registered in The Forty -Eight States •
421 Cattell Avenue • Collingswood, NJ 08107 • (215) 638 -6663 • (215) 638 -6760
Form 5a Project Name: w,Q � A, ,r� I SQ . Page: b
LIGHTING - GENERAL
1. Interior Exceptions (Section 1316.1)
❑ No Interior Lighting. The building plans do not call for new or altered interior lighting. Skip to
Item 4, Exterior Building Lighting — General, below.
Exceptions ❑ Exception. The building or part of the building qualifies for an exception from code lighting
Discussion or requirements. The applicable code exception is Section , Exception(s)
qualifying excep- Portions of the building that qualify: •
lions on page 5 -7 — - –
2. Local Shut -off Controls (Section 1316.1.2.1,1)
❑ Complies. At least one local shut -off lighting control for every 2,000 square feet of lighted floor
area and for all spaces enclosed by walls or ceiling height partitions. This control(s) is detailed in
Exceptions the building plans on drawing number --- - --
Discussion or itit Exception. The building or part of the building qualifies for an exception. The applicable code
Qualifying excep- exception is Section 1316.1.2.1,1, Exception if . Portions of the building that qualify: Ail
lions on page 5 -8.
3. Office Controls (Section 1316.1.2.1,2)
Not an Office Occupancy over 2,000 square feet.
❑ Complies. All interior lighting systems are equipped with a separate automatic control to shut off
Exceptions the lighting and local override switching. These control(s) are detailed in the building plans on
drawing number
Discussion qualifying exc ❑ Exception. The building or part of the building qualifies for an exception. The a licable code
qualifying excep- P 9 P 9 q P PP
lions on page 5 -9 exception is Section 1316.1.2.1,2, Exception . Portions of the building that qualify:
Definition
EXTERIOR 4. Exterior Building Lighting - General
BUILDING No Exterior Building Lighting. Skip the rest of this form.
LIGHTING is
lighting g directed to ❑ Complies. Complete items 5 and 6 below.
illuminate the INEMENZOSSIENCEB
exterior of the
building and 5. Exterior Building Lighting Controls (Section 1316.1.2.2)
adjacent walkways ❑ Complies. The building plans require that all exterior building lighting is equipped with automatic
and loading areas controls described in Sec. 1316.1.2.2. These controls are detailed in the building plans on
with or without drawing number •
canopies.
❑ Exception. The exterior building lighting is intended for 24 -hour continuous use.
6. Exterior Building Lighting Power (Section 1316.2.2)_
❑ Complies. The plans do not call for incandescent lamps greater than 10 Watts for use in exterior
building lighting.
❑ Exception. The building plans indicate luminaires with incandescent lamps greater than 10
Watts, but they are 5 percent or less of the total installed exterior lamps. Total number of exterior
lights . Total number of exterior incandescent lights
(12/99)
Forms & Worksheets 5