Correspondence A si gio t o 1 / ; ,
June 15, 2004
CITY OF TIGARD
ri OREGON
Wyatt Fire Protection
9095 SW Burnham
Tigard, OR 97223
RE: MODIFICATION TO FIRE SPRINKLER SYSTEM
Project Information
Building Permit: BUP2004 -00258 Construction Type: VN
Tenant Name: Journey's Occupancy Type: M
Address: 9426 SW Washington Sq Rd Occupant Load: 39
Area: 1817 Sq Ft Stories: 2
Hazard: Ordinary, Group 2
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The submitted plans are approved subject to the following.
1. A supply of spare sprinklers (never less than 6) shall be maintained on the premises
so that any sprinklers that have operated or been damaged in any way can be
promptly replaced. These sprinklers shall correspond to the types and temperature
ratings of the sprinklers in the property. Standard 9 -1, section 2 -2.7.1 OSSC
2. A special sprinkler wrench shall be provided and kept in the cabinet along with the
spare sprinklers to be used in the removal and installation of sprinklers. Standard 9 -1,
section 2 -2.7.2 OSSC
3. A minimum of 18 inches shall be maintained between top of storage and ceiling
sprinkler deflectors. Standard 9 -1, section 4 -4.1.6 OSSC
4. Sidewall sprinkler deflectors shall be located not more than 6 inches or less than 4
inches from walls and ceilings. Standard 9 -1, section 4- 4.2.3.3 OSSC
5. Clearances shall be provided around all piping extending through walls, floors,
platforms and foundations. Minimum clearance for pipe sizes 1 inch through 3 '/2
inches shall be not less than 1 inch. Standard 9 -1, section 4- 5.4.3.4
f' Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
PP PP P � g Y g PP P
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772