Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
October 19, 2007 UI
•
RE: FIRE ALARM SYSTEM t j ' '
Project Information
Building Permit: BUP2007 -00522 Construction Type: 2 -B
Tenant Name: Dick's Sporting Goods Occupancy Type: M
Address: 9402 SW Washington Square Required: Yes
The plan review was performed under the State of Oregon Structural Specialty Code
(OSSC), 2007 edition the Oregon Fire Code 2007 edition and 2002 edition of NFPA 72.
The submitted plans are approved subject to the following.
General Requirements
A separate low- voltage electrical permit is required for installation and inspection of
alarm wiring.
A completed inspection and testing form is required at the time of final inspection
containing the information as outlined in NFPA section 10.6.2.3.
TESTING — NFPA 72 Chapter 10, OFC 901.2.1, 901.5, 903.5
1. Upon completion of the installation, a satisfactory test of the entire system shall be
made in the presence of the building inspector. All functions of the system or alteration
shall be tested.
2. A record of completion in accordance with NFPD 72 verifying that the system has
been installed in accordance with the approved plans and specifications shall be
provided.
3. The permittee shall provide written certification to the Fire Chief that the system has
been installed in accordance with the approved plans and specifications. A copy of the
completed form shall be maintained on the premises and made available to the Fire
Chief.
VISUAL ALARMS — NFPA 72 - 5.14.5, 7.5.4, OSSC chapter 9 & 11
4. When required; Visual alarms shall be located not less than 80 inches and not more
than 96 inches above floor level. When a low ceiling exists, the visual alarm shall be
mounted within the dimensions stated above and at least 6 inches below the ceiling. No
place in a room shall be more than 50 feet from a visual signal. In corridors spacing
• between devices shall be no more than 100 Ft. and no more than 15 Ft. from the end.
MANUAL ALARM - 1109.2.3.5, 1109.2.3.6 OSSC
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
5. Manual Fire Alarm activation devices when installed shall be mounted in the following
reach ranges:
• Forward Reach -15 inches to 48 inches above the floor.
• Side Reach — 9 inches to 54 inches above the floor.
ALARM SIGNALS — OFC 903.4
6. Alarm, supervisory and trouble signals shall be distinctly different and shall be
automatically transmitted to an approved central station, remote supervising station or
proprietary supervising station as defined in NFPA 72 or, when approved by the fire
code official, shall sound an audible signal at a constantly attended location.
7. Duct smoke detectors shall be connected to the building's fire alarm control panel
when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a
visible and audible supervisory signal at a constantly attended location. Duct smoke
detectors shall not be used as a substitute for required open -area detection.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp,
shall be maintained on the jobsite. The plans shall be available to the Building Division
inspectors throughout all phases of construction. 106.3.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.
Respectfully,
Dan Nelson,
Senior Plans Examiner
1 PO
n7-6o5,2,_
Fire Alarm Submittal WED
OCT 9 / III /
CITYOF rIGA D
BUVLO1NGDIUISIO"
Prepared for
Dick's Sporting Goods
Washington Square Mall
Tigard, OR
Submitted By
ADT Tyco Fire & Security
2815 Sw 153Rd Dr
Beaverton, OR 97006
(503) 469 -7100
Prepared By
ADT Tyco Fire & Security
National Accounts Group
120 West Park Drive
Birmingham, AL 35211
Billy Sanders
Phone (205)- 940 -7348
FAX (205) - 942 -4943
NICET SET 101167
09/20/07 �.<<G��N Ky Ro ssi
G IBBENS DRAKE SCOTT, INC d • r
9 E. 63rd STREET, SUITE 100 - .�
RAYTOWNM MISSOURI 64133
>, ✓ CREGGN ? Zl 0
1. 1, -7 9 3 7 ` •
ENGINEERING Oh. LEE
S '
X o g
7w
Fire Marshal Inquiry Sheet
Customer Dick's Sporting Goods 342 Fire Planner Billy Sanders
Date Called
c
o AHJ's Name
s7.
co
E Phone #
51 NFPA 72 Eg NEC ❑ ADA / Handicapped
Dept name ❑ Life Safety 101 ❑ BOCA Fire & Building ❑ UBC /UFC /UMC
a1 Address ❑ Southern Building ❑ South Florida ❑ Standard Flre & Bldg.
j City,St Zip ❑ International ❑ Other
Is combination Panel Acceptable 10 Yes O Separate Panel 0 Addressable
tn
E' Are there requirements for Class "A" O No 0 Both 0 Initiating 0 Indicating
a)
E Smoke Detector Requirements O None 0 At Panel 0 Full Smoke 0 Selected areas
CD
'E Pull Station Requirements 10 None 0 At Panel 0 All Exits 43 -48" AFF 0 Front Door
Q
LL
Annunciator Type I O None 0 LCD 0 LED 0 Special Requirement I
Annunciator / Keypad Location I O Front Door 0 Attended Location 0 SprInkler Riser 0 Special Requirement I
` Monitoring of Duct Detectors I O None 0 Supervisory 0 Alarm
0
' Mounting location I O Return duct only 0 Supply Duct Only 0 Supply and Return I
O Remote Test Switches I O None 0 Below HVAC Unit 0 At Fire Panel
LI Duct Detectors Powered By JO HVAC Unit 0 By Fire Panel
CI
HVAC Shutdown Control I O None 0 Unit Only 0 All Units Ducts only 0 All Units Any Alarm
Elevator Recall I O None 0 Passanger Only N O Freight only 0 All Elevators
C Notification Required I O None
O 0 Full Notification 0 One Inside
co Horn Strobes or Voice Evacuation I O Horn Strobes 0 Voice Evacuation
r, Horn Strobe Required Outside I O None
0 Sprinkler Connectior 0 Front of Bldg.
O
Z Can Horn Strobes Be Ceiling Mounted I ® No 0 Ceiling Mount is OK
Type of Monitoring I ® Remote Station 0 Central Station 0 Direct Connect I
O
• E Other Requirements I ❑ Kelton ❑Reverse Polarity ❑ UL Certificate Required I
0
Monitoring Location I O Aurora 0 Other Specify ADT
c Is a separate permit required JO No 0 Yes Cost
I E Can Work Begin Before Permit Is Issued I O No 0 Yes
Cl. Is Knox Box Required I ® No 0 Yes Order from Fire Dept and Locate per Fire Dept Instructions.
I
Submittals Required O No 0 Yes
0
E Number Of Sets 2
xi Turn around time Days Weeks
CO I . Stamp Required O No 0 Engineers 0 California C - 10 0 NICET
c
ar
E
E
o
0
System Outline
Location
Dick's Sporting Goods 342
Washington Square Mall
Tigard, OR
II. Codes
A. 2002 NFPA 72 Chapters 1 -10 as Applicable(Remote Station)
B. 2002 NEC Articles 250, 725, 760
C. Local, City, State
III. Control
A. 1 Unimode 2000DLS Fire Alarm Control
B. 2 AL1002UL -ADA -J ADA Power Booster 10A @24VDC
IV. Fire Alarm Initiating Devices
A. 9 BG -12LX Manual Pull Station Addressable
B. 11 SD355 Smoke Detector Photo
C. 2 Water Flow Connection Only, Provided by Others
D. 2 Tamper Switch Connection Only, Provided by Others
E. 10 Duct Detector Connection Only, Provided by Others
F. 6 H355R Heat Detector Rate of Rise
V. Fire Alarm Indicating Devices
A. 1 LCD -80F Annunciator LCD
B. 51 PC2W -115 Ceiling Horn strobe white 24VDC 115CD
C. 21 PC2W -75 Ceiling Horn strobe white 24VDC 75CD
D. 1 P2W -75 Wall Horn strobe white 24VDC 75CD
E. 14 P2W -30 Wall Horn strobe white 24VDC 30CD
F. 1 SW -75 Wall Strobe white 24VDC 75CD
G. 16 SW -30 Wall Strobe white 24VDC 30CD
H. 2 P2W -110 Wall Horn strobe white 24VDC 110CD
VI. Zones
All devices are addressable with there own adddress
1 -159 detector addresses
1 -159 module addresses
SLC Loop is style 4
VII. Wiring
All Circuits and Wiring Shall be "Power Limited"
SLC Circuits Shall be 16/2 Sheilded U.L. FPLP Cable
Initiating Zones Shall be 18/2 or 18/4 U.L. FPLP Cable
Indicating Circuits Shall be 14/2 U.L. FPLP Cable
System Ground Shall be 14 THWN Green Conductor
Under Ground and Outside Wire shall be 14 THWN in Approved Raceway
VIII. Listings
A. All Equipment Shall Be U.L. Listed and Compatible
IX. Power Supply
A. Primary - 110 VAC Dedicated 20 Amp Circuit
B. Secondary - 12 Amp Hour Battery
X. Alarm Supervision
A. Human
B. Remote Station Installing Branch /Contractor
ADT Fire & Security ADT Tyco Fire & Security
14200 E Exposition Blvd. 2815 Sw 153Rd Dr
Aurora, CO 80012 Beaverton, OR 97006
(503) 469-7100
S994 -183 UUFX