Permit •/
CITY OF TIGARD BUILDING PERMIT
, A
PERMIT #: BUP2005 -00614
'ilk DEVELOPMENT SERVICES DATE ISSUED: 12/14/2005
' --- 13125 SW Hall Blvd Tigard, OR 97223 503 - 639 -4171
1 PARCEL: 1S12600-00300
SITE ADDRESS: 09377 SW WASHINGTON SQUARE RD ZONING: C -G
SUBDIVISION: WASHINGTON SQUARE LOT: JURISDICTION: TIG
Project Description: T.I. (11,090 sq ft)
' REISSUE: FLOOR AREAS EXTERIOR WALL CONSTRUCTION
CLASS OF WORK: ALT FIRST: sf N: S: E: W:
TYPE OF USE: COM SECOND: sf PROJECT OPENINGS?
TYPE OF CONST: 2N : sf N: S: E: W:
OCCUPANCY GRP: M TOTAL AREA: 0 sf ROOF CONST: FIRE RET?
OCCUPANCY LOAD: 234 BASEMENT: sf AREA SEP. RATED:
STOR: 2 HT: ft GARAGE: sf • OCCU SEP. RATED:
BSMT ?: MEZZ ?: Y REQD SETBACKS REQUIRED
FLOOR LOAD: psf LEFT: ft RGHT: ft FIR SPKL: Y SMOK DET:Y
DWELLING UNITS: FRNT: ft REAR: ft FIR ALRM : Y HNDICP ACC:Y
BEDRMS: BATHS: IMP SURFACE: PRO CORR: PARKING:
VALUE: $ 350,000.00
Owner: Contractor:
WASHINGTON SQUARE LLC ROYAL SEAL CONSTRUCTION
BY THE MACERICH COMPANY 124 MCMAKIN, RD
9585 WASHINGTON SQUARE RD BARTONVILLE TX 76226
TIGARD, OR 97223,
Phone: Contact #: PRI 817 - 491 -6400 ..
•
FEES Reg #: LIC 78744
Description Date Amount REQUIRED ITEMS AND REPORTS
[BUPPLN] PIn Rv 11/23/200: $1,114.30 Bolts in concrete.
[FLS] FLS Pin Rv 11/23/200`. ' $685.72 High- strength bolts
[BUILD] Permit Fee 12/14/200° $1,714.30 Structural welding
[TAX] 8% State Surchari 12/14/200: $137.14 Fire - proofing
Special- inspection (see pla
Total $3,651.46
This permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes
and all other applicable law. All work will be done in accordance with approved plans. This permit will expire if work is
not started within 180 days of issuance, or if work is suspended for more than 180 days. ATTENTION: • son law
requires you to follow the rules adopted by the Oregon Utility Notification Center. Those rules are set • in OAR
952 - 001 -0010 through OAR 952 - 001 -0100. You may obtain a copy of these rules or direct que do - o OUNC by
calling 503 - 246 -6699 or 1- 800 -332 -2344.
' Issued By: Permittee Signature:
Call 503 -639 -4175 by 7:00 a.m. for an inspection that business day.
This permit card shall be kept in a conspicuous place on the job site until completion of the project.
Approved plans are required on the job site at the time of each inspection.
73 ?7 tjJc,4b s
A ,0.
Building Permit Applications e r �, & � FOROFFICE USE ONLY � City of Tigard DatReceived e/B – I J om Permit No' '�� • -ro /t/
13125 SW Hall Blvd., Tigard, OR 97223 ICI Plan Review / Phone' 503 639 4171 Fax: 503.598 1960 / d U ulr I � Dat& _ lg'1' Other Permit
Inspection Line' 503 639.4175 � 6 '?1 1 0 Date Ready :y luris 0 See Attached Checklist for
Internet www ci tigard or us VI I i n - i IUARD Notified/Method 4,Z. - 42, "S 4" )( Supplemental Information
BUILDING onnsitrl 3 (N-& ( A/ Cz•ec
TYPE OF WORK REQUIRED DATA: 1- AND 2- FAMILY DWELLING
® New construction ❑ Demolition i Permit fees* are based on the value of the work performed.
Indicate the value (rounded to the nearest dollar) of all
❑ Addition/alteration/replacement ❑ Other: equipment, materials, labor, overhead, and the profit for the
CATEGORY OF CONSTRUCTION work indicated on this application.
❑ I- and 2- family dwelling ® Commercial /industrial Valuation: $
❑ Accessory building ❑ Multi- family Number of bedrooms:
❑ Master builder ❑ Other: Number of bathrooms:
957 / JOB SITE INFORMATION AND LOCATION Total number of floors:
Job site addressy90 Washington Square Rd. New dwelling area: square feet
City /State /ZIP: Tigard, Oregon 97223 Garage /carport area: square feet
Suite/bldg. /apt. no.: S -07 Project name: Abercrombie & Fitch #972 Covered porch area: square feet
Cross street/directions to job site: Washington Square Mall Deck area: square feet
Other structure area: square feet
REQUIRED DATA: COMMERCIAL -USE CHECKLIST
Subdivision: Lot no.: Permit fees* are based on the value of the work performed.
fax map /parcel no.: Indicate the value (rounded to the nearest dollar) of all
' equipment, materials, labor, overhead, and the profit for the
DESCRIPTION OF WORK work indicated on this application.
Tenant Build Out. First and partial second floor. Valuation: $$350,000.00
Existing building area: 11,090 square feet
New building area: 11,090 square feet
❑ PROPERTY OWNER ® TENANT Number of stories: 2 •
Name: Abercrombie & Fitch - Store Planning Type of construction: 213' .
Address: 6301 Fitch Path Occupancy groups:
City /State /ZIP: New Albany, Ohio 43054 Existing: Merchantile
Phone: (614)283 -6541 Fax: (614)283 -8541 New: Merchantile
❑ APPLICANT ® CONTACT PERSON
NOTICE
Business name: Feinknopf Macioce Schappa Architects Inc. (EMS Architects) All contractors and subcontractors are required to be
Contact name: George Pack licensed with the Oregon Construction Contractors Board
under ORS 701 and may be required to be licensed in the
Address: 1020 Dennison Ave Suite 300 jurisdiction in which work is being performed. If the
City/State/ZIP: Columbus, Ohio 43201 applicant is exempt from licensing, the following reasons
apply:
Phone: (614) 297 -1020 Fax: : (614) 291-1020
E -mail: gpack] @fmsarchitects.com
CONTRACTOR
Business name: TBD' 7 � , 0\ j \ C. e �s — BUILDING PERMIT FEES*
Address: ! \\,... 1,, , P''. - 7.... (J .._-
Please refer to fee schedule.
City /State /ZIP: - �'‘ \ \ ,� Tx - 7 6 ��6
Fees due upon application $0.00
Phone N r Y7 I - p er/0) Fax: )
CCB lie.: Amount received _ __
; Date received:
Authorized signature: / This permit application expires if a permit is not obtained
within 180 days after it has been accepted as complete.
Print name: George Pack Date: 10 -21 -05 * Fee methodology set by Trt- County Building In \lustry
Service Board
i. \Budding \Pcrmas \BUP- PcrmitAppdor 1 2/03 440.46t3T(I1 /02/COM/WEB)
4
bC P.3605- 00 644
!f Form 5a Project Name: Abercrombie & Fitch #972 Page: 1
LIGHTING - GENERAL
1. Interior Exceptions (Section 1313.1)
❑ No Interior Lighting. The building plans and specifications do not call for new or altered interior lighting.
Skip to item 5, Exterior building Lighting - General, below.
Exceptions ❑ Exceptions. 1. The building or part of the building qualifies for an exception from code lighting
Discussion of qualifying requirements. Applicable code exception is number:
exceptions in instructions
section. 2. Lighting equipment that qualifies for an exception - in addition to general lighting and is separately
controlled. Applicable code exception is number:
Areas of the building and equipment that qualify for any exceptions:
Plans/ Specs
Show compliance by including a
drawing sheet, detail number,
and /or specification section and
subparagraph. 2. Local Shut -off controls (Section 1313.3.1.1)
p Complies. At least one local shut -off lighting control for every 2,000 square feet of
lighted floor area and for all spaces enclosed by walls or ceiling height partitions.
This control(s) is detailed in the building plans on drawing number: E2.1 and E2.2
RECEIVED Exception. The building or part of the building qualifies for an exception.
L� Applicable code exception is Section 1313.3.1.1, Exception: 4
NOV 1 NOO5 Portions of the building that qualify: Sales Area
CITY OF TIGARD
BUILDING DNISION 3. Automatic Shutoff Controls (Section 1313.3.1.2)
❑ Not Applicable. Office floor area is not over 2,000 square feet of contiguous office floor area or
permitted space is not over 5,000 square feet. No offices less than 300 square feet, meeting
or conference rooms, or school classrooms.
El Complies. All interior lighting systems are equipped with a separate automatic control to shut off lighting
during unoccupied periods. Offices less than 300 square feet, meeting and conference rooms, and school
classrooms shall be equipped with occupancy sensors that comply with Section 1313.3.1.2.1.
Compliance details in plans /specs: E2.1 and E2.2
El Exception. The building or part of the building qualifies for an exception. The
applicable code exception is Section 1313.3.1,2, Exception: 3 and 7
Portions of the building that qualify: Sales Area and Mechanical /Electrical Rooms
4. Daylighting Controls (1313.3.1.3)
o No classrooms or atriums with skylights or window to wall ratio greater than 50 %.
❑ Complies. All classrooms and atriums with window to wall ratio,greater than 50% and /or skylights are
equipped with automatic daylight sensing controls, as required by Section 1313.3.1.3.1 and Section
1313.3.1.3.2. The daylight sensors specified comply with Section' 1313.3.1.3.3.
Compliance details in plans /specs:
Exterior Build 5. Exterior Lighting (Section 1313.5)
ing Lighting O Complies. The plans do not call for use of incandescent or mercury vapor lamps for use on building exterior.
is lighting directed to illuminate ❑ Exception. The building plans indicate luminaires with incandescent or mercury vapor lamps, but are
the exterior of the building and specified for use in or around swimming pools, water features, or other locations subject to requirements
adjacent walkways and. of Article 680 of the 2002 National Electrical Code.
loading areas with or without
canopies.
Clock Switches 6. Exterior and Canopy Lighting Controls (Section 1313.3.2)
shall be astronomic (seasonal 0 Complies. The building plans and specifications include photoelectric and /or clock switches on all exterior
correcting) type with separate lighting systems which are designed and programmed to extinguish lights when daylight is present, as
programs for each day of the required by Section 1313.3.2.
week and shall store energy to
maintain timekeeping during
power outages. 7 Interior Connected Lighting Power (Section 1313.4)
YES IComplies. The interior lighting power does not exceed the interior power allowance established
in either the Tenant Space Method (Form 5b) or the Space -by -Space Method (Form 5c).
V C
V.17 Tenant Space Method (Form 5b) r. Space -by -Space Method (Form 5c)
� s
5-1
Compliance with OSSC, effective 01/01/05
Ir
Form 5c Project Name: Abercrombie & Fitch #972 Page: 2
INTERIOR LIGHTING POWER - Space -by -Space Method
Lighting 1: Total interior Lighting Power Budget from Worksheet 5b -1 (Sum of Column (I)) 17,455
Power Budget
2: Total length' of track lighting (ft) 317
Track Lighting
Power 3. Line 2 multiplied by 37.5 Watts /ft 11,888
4 Total amperage of circuit breaker(s) serving track lighting (amps) 65
5. Voltage of circuit breaker serving track lighting (volts) 120
6. Maximum wattage of track lighting (multiply line 4 by line 5) 7,800
7. Track Lighting Power (lesser value of line 3 or line 6) 7,800
8. Total Interior Lighting Power from Worksheet 5b-1 (Sum of Column (m)) + 9,
Building's 9. Total Adjusted Lighting Power (line 7 + line 8) _ 17,146
Lighting Power
10. Does design meet budget? Line 9 must be no greater than line 1. YES
5-3
Compliance with OSSC, effective 01/01/05
Work: Project Name: Abercrombie & Fitch #972 Page: 3
LIGHTING SCHEDULE
(a) (b) (c) (d) (e) (f)
Lum Luminaire Is Luminaire
ID Luminaire Lamp Ballasts Power From
Type Description No. Description No. Description (watts) Table 5c
H User Defined J 1 -23 watt lamp- Compact Fluorescent J 1 23 watt lamp 1 Self Ballasted 23 NO
L 12 Volt Tungsten Halogen Lamps 1 -35 watt lamp - EPS -38W J 1 35 watt lamp 1 Electronic Power Supply 38 YES
P 12 Volt Tungsten Halogen Lamps J 1 -35 watt lamp- EPS -38W J 1 35 watt lamp 1 Electronic Power Supply 38 YES
R 112 Volt Tungsten Halogen Lamps 1 -35 watt lamp- EPS -38W
A 1 35 watt lamp 1 Electronic Power Supply 38 YES
u I Fluorescent T8 -4 foot A 1- F32T8/30ES -ELECT NO -29W — I 1 F32T8/30ES 1 Electronic Normal Output. IS 29 YES
✓ I Track Lighting A Track Lighting J — _ — — 37.5 YES
x 12 Volt Tungsten Halogen Lamps 1 -35 watt lamp- EPS -38W ■ 1 35 watt lamp 1 Electronic Power Supply 38 YES
z I Track Lighting Track Lighting _ — — — — 37.5 YES
•
J
J
A A
J
. _
J
J
J
J
1 -I
Final- 2005- 0689_Energy_Oregon- V2.3.xls
Y'
Worksheet 5b-1 Project Name: Abercrombie 8 Fitch #972 Page: 4
INTERIOR LIGHTING POWER
Space -by -Space Method Only
Skip to column (f) if using the Tenant Space Method
(a) (b) (c) (d) (e) Lure ID (9) (h) (I) 9) (k)
from Quantity of
Room ID (do Space Type Space Lighting Power Worksheet Luminaires (or Luminaire Lighting Room
not leave any Area (Table 13-H) Type Budget 5a Column lineal R for track Power Exempt Power Total Ltg
blanks) (f( (enter space type only once per room) LPD (b) x (d) (a) lighting) (Watts) Fixtures (g) x (h) Power
Each room Sales Area 7667 Retell - Other Merchandise Sales Area 2 15,334 H :J 135 23 ❑ 3,105 19,175
must be Sales Area — — L :) 27 38 ❑ 1,026 —
identified. Sales Area — — P -1 12 38 ❑ 456 —
Desnabe R - - 8 38 ❑ 304
luminaires for each Sales Area — — —
individual room in Sales Area — — U 4 29 ❑ 116 —
plans _ V - 301 38 ❑ 11,288
Sales Area — — —
Sales Area — — X 60 38 ❑ 2,280 —
Sales Area — — Z 16 38 ❑ 600 —
For track lighting Comdor 340 Comdor/Transition 0 5 170 U �} 10 29 ❑ 290 493
enter lineal feet in Stairwell 200 Stairs -active 0 6 120 U J 6 29 ❑ 174 174
column column (g)
Comdor 355 Comdor/Transition 0.5 178 U J 7 29 ❑ 203 493
Column (k), enter Restrooms 145 Resirooms 0 9 131 U J 2 29 ❑ 58 58
sum of column (j) Office 150 Office - enclosed 1 1 165 U "1 2 29 ❑ 5e 58
for each room only Stockroom 1478 Active Storage 0 8 1,182 U .J 42 29 ❑ 1,218 1,218
once et first entry
for the room See Electnc room 117 Elecmcal/Mechanical 1.5 178 U J 2 29 ❑ 58 58
example In — — _I - - _
instructions
J ❑
— — J - ❑ - —
— — J - ❑ - —
— — J - ❑ - — -
- — T1 - ❑ - —
— — J - ❑ - —
. — — ,. - ❑ - -
- — 71 - ❑ - —
— — 71 - ❑ - — ,
— — J - ❑ - —
— — 7.1 - ❑ - -
- — .71 - ❑ - -
- — 71 - ❑ - —
— — .71 - ❑ - -
- — 11 - ❑ - -
- — J - ❑ - —
— — J - ❑ - - _
- - - ❑ - -
- - zi - ❑ - -
- - J - ❑ - -
- - ..,.1 - ❑ - -
- - J - ❑ - -
- - J - ❑ - -
- - J - ❑ - -
- - zi - ❑ - -
- - -,1 - ❑ - -
- - -1 - ❑ - -
10,452 Worksheet 5b-1 Total Budget 17,455 Wksht 5b-1 Total Lighting Power (excluding exempt/track fixtures) 9,346
Other Pages Total Number of Additional Worksheet bb f 0
List the additional
worksheets nece-
ssary to catalog all -
luminaires in (I) (m) (n)
building Lighting Power Budget. Space Proposed Buiding Lighting
by-Space only (Total of Power (Total of column (k), Area Sqft (not required
Worksheet Number column (e)) excluding exempt/track) for Tenant Method)
5b-1 17,455 9,346 10,452
5b-2
5b-3
Sum of additional 5b worksheets
�e {^ Total Budget (of all worksheets) 17,455 9,346 10,452
{ { { d '
\Ad» •,y
5-5
Compliance with OSSC, effective 01/01/05
' L
• u'aoo - cb /
•
Form 2a Project Name: A b e/rC- 'COM V 1 e fr f i G/ Page:
SUMMARY
Project 1. Project Name 4 b 4r c » ivl b P. g Ft
2. Project Address VaA (1 iPt tar S t
3. City/Town - r —" 1 a 6 h c. orgy 5. County I
4. Building, Gross Area (ft2) 6. No. of Floors I O.
7. Construction Site Elevation Above 2,000 ft? ❑ YES 0 N
Attached Chapter Type ID Description Attach
Forms and Building Envelope Form 3a Building Envelope - General ❑
3b Prescriptive Path - All Climate Zones ❑
Worksheets * CodeComp Report for Simplified Trade -off ❑
* In lieu of 3b * Floppy disc with .occ CodeComp file ❑
Check boxes to Worksheet 3a Wall U- factor U
indicate attached 3b Roof U- factor El
forms and 3c Floor U- factor ❑
worksheets 3d Window /Skylight Schedule ❑
Systems Form 4a Systems - General Q
4b Complex Systems ❑
Worksheet 4a Unitary Air Conditioners - Air Cooled C
4b Unitary Air Cond. - Water & Evap Cooled ❑
AECE 1VED 4c Unitary Heat Pump - Air Cooled ❑
4d Unitary Heat Pump - Water Cooled ❑
NOV 1 4 2005 4e Packaged Terminal A.C. - Air Cooled ❑i
4f Packaged Terminal Heat Pump - Air Cooled ❑ .
CITY OF TIGARD 4g Water Chilling Pkgs - Water & Air Cooled 1
BUILDING DIVISION 4h Heat Rejection Equipment ❑
4i Boiler - Gas -Fired and Oil -Fired ❑
4j Furnace & Unit Heaters - Gas and Oil -Fired ❑
4k Simultaneous Heating and Cooling ❑
41 Air Transport Energy ❑
4m Natural Ventilation ❑
Lighting Form 5a Lighting - General U
5b Interior Lighting Power - Tenant Method ❑
5c Int. Ltng. Power - Space -by -Space Method ❑
Worksheet 5a Lighting Schedule LI
5b Interior Lighting Power ❑
Applicant 7. Name 10. Telephone
8. Company 11. Date
9. Signature
Attached No. of Pages Description of Documentation
Document- 6 via cant/Errs
ation
•
t,ompnanue wan u'.., enecuve u 110 uuo
Form 4a Project Name: 4-174-cCrem b 2 2 i; /ah Page:
SYSTEMS - GENERAL
Applicability Plans/ Specs
Discussion of qualifying Show compliance by including a drawing sheet, detail number,
exceptions on page 4 -25 specification section and subparagraph
1. Applicablity (Section 1317)
Is this form required?
❑ Form Required. Complete form if a new HVAC system is being installed, or components of an
existing HVAC system are being replaced (I.e., equipment, controls, ductwork, and insulation.)
0 Exception. The building or part of the building qualifies for an exception from HVAC code
requirements. Applicable code exception is Section 1317.1. Portions of the building that
qualify:
Area: Exception ❑ - CI - ❑ -3
Area: Exception ❑ - ❑ -2 ❑ -3
Area: Exception ❑ - CI -2 ❑ -3
O Form Not Required. This project does not contain work required to comply with code.
2 Simple or Complex Systems (Section 1317.9 or 1317.10)
I� Simple System. Building contains only Simple HVAC System(s). Complete this form (4a) and
equipment efficiency worksheets as required. Form 4b is not required.
❑ Complex System. Project includes a Complex System. Complete this form (4a), form 4b and
equipment efficiency worksheets as required.
3. Equipment Performance (Section 1317.5)
❑ No New HVAC Equipment. The building plans do not call for new electrical HVAC equipment,
combustion heating equipment, or heat - operated cooling equipment.
Complies. All new HVAC equipment have efficiencies not less than those required by code.
TV following equipment efficienn9y worksheets are attached:
�a 0 -4b ❑ -4c ❑ -4c ❑ -4e ❑ -4f 3N -4g O -4h O -41 O -4
4. Duct Insulation and Sealing (Sections 1317.7 & 1317.8)
O No Ducts. The building plans and specifications do not call for new HVAC ducts or plenums.
L(Complies. The plans and specifications call for all air - handling ducts and plenums to be
insulated and sealed as reauired by Sections 1317.7 &1317.8.
5. Distribution Transformers (Section 1316.1)
❑ No Distribution Transformers. The plans /specs do not call for new distribution transformers.
❑ Complies. All new distribution transformers comply with efficiency, testing, and labeling
requirements of Section 1316.1.1.
❑ Exception. The project qualifies for an exception per Section 1316.1.1, Exceptiion:
❑ -1 ❑ -2 0 -3 ❑-4 ❑ -5 0 -6 ❑ -7 0 -8 0 -9 0 -100 -1 0- 120 -12 ❑ -14
Attach relevant documentation for appropriate exception. The plans /specs show compliance in the
`, following locations:
5
4 -1 April 2005
Compliance with OSSC, effective 01/01/05
Form 4a Project Name: A b d w e qr File (i Page:
SYSTEMS - GENERAL
6. HVAC Controls (Section 1317.4)
/ 6.1 System Thermostat /Zone Controls (Section 1317.4.1)
® Complies. All new HVAC systems include at least one temperature control device responding to
temperatures within the zones.
❑ Exception. HVAC system qualifies for an exception from zone control requirements.
The applicable code exception is Section 1317.4.2, Exception 0-1 0-2
Portions of the building that qualify:
The plans /specs show compliance in the following locations:
6.2 Off - hour Controls - Auto Setback or Shutdown (Section 1317.4.3)
A, Complies. Systems must have at least one of the following features:
l Control Setback Complies. Each system is equipped with automatic control capable of reducing
energy through control setback during periods of non -use or alternate use of spaces served.
gi Equipment Shutdown Complies. Each system is equipped with controls capable of reducing
energy use through automatic shutdown during periods of non -use or alternate use of spaces.
HVAC systems with equipment shutdown are equipped with at least one of the following:
NI Programmable controls (1317.4.3.1 (1))
❑ Occupant sensor (1317.4.3.1 (2))
O Interlocked to a security system (1317.4.3.1 (3))
❑ Manually activated timers with 2 -hour operation max (1317.4.3.1 (4))
❑ Exception. The building qualifies for an exception to the requirement for automatic setback or
shutdown controls. The applicable code exception is Section 1317.4.3
Exception 0-1 0-2
The plans /specs show compliance in the following locations:
6.3 Control Capabilities (Sec. 1317.4.2.1)
gr Complies. Zone thermostats are capable of being set to the temperatures described in Sec.
1317.4.2.1. Where used to control both heating and cooling, zone controls shall be capable of
providing a temperature range or deadband of at least 5 degrees F within which the supply of
heating and cooling energy to the zone is shut off or reduced to a minimum.
❑ Exception. The building qualifies for an exception to the deadband requirements.
The applicable code exception is Section 1317.4.2.1 Exception 0-1 0-2
Portions of the building that qualify:
The plans /specs show compliance in the following locations:
6.4 Optimum Start Controls (Section 1317.4.3.2)
❑ Complies. Separate HVAC systems have controls capable of varying start-up time of system to
ii just meet temperature set point at time of occupancy.
Exception. HVAC systems have a design supply air capacity not exceeding 10,000 cfm.
The plans /specs show compliance in the following locations:
ANu -x,1,3
6.5 Heat Pump Controls (Section 1317.4.4)
❑ No Heat Pump. The plans /specs do not call for a new heat pump
❑ Complies. All new heat pumps equipped with supplementary heaters are controlled to minimize
the use of supplemental heat as defined in Section 1317.4.4.
'te The plans /specs show compliance in the following locations:
4 -2 April 2005
Compliance with OSSC, effective 01/01/05
Form 4a Project Name: 41742 -c-C rp b i c s' J I 1 C Page:
SYSTEMS - GENERAL
7. Economizer Cooling (Section 1317.3)
❑ No Cooling. The building plans do not call for a new fan system with mechanical cooling.
Sid Complies. Each new fan system has an air economizer capable of modulating outside -air and
return -air dampers to provide up to 100 percent of the design supply air as outside air.
❑ Exception At least one new fan system qualifies for an exception. The applicable code exception
is Section 1317.3, Exception ❑ - ❑ - ❑ -3 ❑ -4 ❑ - ❑ -
If Exception 3 is selected complete the following:
(a) Total cooling capacity of exempt units (Btu /hr)
(b) Total installed building cooling capacity (Btu /hr)
❑ Complies. Sum of exempt units rated at less than 54,000 Btu /hr is <240,000 Btu /hr or a/b
< 0.10 (10% of total building cooling capacity).
Unit Identifier of exempt units:
The plans /specs show compliance in the following locations:
8. Economizer Pressure Relief & Integration (Section 1317.3.1 and 1317.3.2)
0/No Economizers Required. Project does not contain a new fan system requiring economizers.
Nif Overpressurization Complies. The drawings specifically identify a pressure relief mechanism for
each fan system that will relieve the extra air introduced by the economizer.
NO Integration Complies. Economizer is capable of providing partial cooling even when additional
mechanical cooling is required to meet the remainder of the cooling toad.
❑ Exception. The applicable exception is Section 1317.3.2, Exception ❑ - ❑ -2
The plans /specs show compliance in the following locations:
9i Hot Gas Bypass (Section 1317.5)
p No Hot Gas Bypass
❑ Complies. See allowable amount of hot gas bypass as a percentage of total cooling capacity in
table below.
Unit ID Rated Cooling Capacity Hot Gas Bypass Capacity
:, ....'
(---
Allowable Hot Gas Bypass
Rated Cooling Capacity Max Hot Gas Bypass
50%
<240,000 Btu /hr
°b >240,000 Btu /hr 25%
❑ Exception. Unitary packaged system with cooling capacity no greater than 90,000 Btu /h
4 -3 April 2005
-
Compliance with OSSC, effective 01/01/05
Form 4a Project Name: 4'b &t`C, rorA bl e If f 1 f -iA , Page:
SYSTEMS - GENERAL
10. Shutoff Dampers (1317.4.3.3)
❑,Plot Required. Shutoff dampers are not required on this project.
Complies. Each outdoor air supply & exhaust system shall be equipped with motorized dampers.
❑ Exception. The building qualifies for an exception to the motorized damper requirement. The
applicable code exception is Section 1317.4.3.3 Exception ❑ - I=1-2 ❑ -3 ❑ -4 ❑ -5 ❑ -6
The plans /specs show compliance in the following locations:
/h x,
,10.1. Shutoff Damper Controls (Section 1317.4.3.3.1)
Complies. Outdoor air supply and exhaust systems shall be provided dampersthat automatically
shut when systems or spaces served are not in use or during building warm -up, cooldown, or
setback.
❑ Complies. Stair and shaft vents are capable of being automatically closed during normal building
operation and interlocked to open as required by fire and smoke detection systems.
The plans /specs show compliance in the following locations:
10.2. Motorized Damper Leakage (1317.4.3.3.2)
N Complies. Motorized outdoor air supply and exhaust air dampers have a maximum leakage rate
of 4 cfm /ft2 at 1.0 in w.g. when tested in accordance with AMCA Standard 500 -1998.
❑ Exception. Packaged HVAC equipment may have maximum leakage rate of 20 cfm /ft at 1.0 in
w.g. when tested in accordance with AMCA Standard 500 -1998.
The plans /specs show compliance in the following locations:
11. Piping Insulation (Section 1314)
❑ No New Piping. The building plans and specifications do not call for new piping serving a
/heating or cooling system or part of a circulating service water heating system.
IV Complies. All new piping serving a heating or cooling system or part of a circulating service
water heating system complies with the requirements of the Code, Section 1314.1.
❑ Exception. New piping qualifies for exception: Section 1314.1, Exception ❑ -1 ❑ -2
12. Occupancy Ventilation
® Complies. Mechanical ventilation systems provide the required amount of ventilation is indicated
in plans /specifications as specified in Chapter 4 of the Oregon Mechanical Specialty Code.
❑ Complies. Natural ventilation systems provide required amount of ventilation as certified by a reg-
istered architect or engineer as specified by Section1203.4.1, Exception. Attach worksheet 4m.
The plans /specs show compliance in
the following locations:
The plans /specs show compliance
( - on the following pages:
4 -4 April 2005
Compliance with OSSC, effective 01/01/05
Form 4a Project Name: 4 DP/'(', M PI t £ r1 � C � Page:
SYSTEMS - GENERAL
13. High Occupancy Ventilation (Section 1317.2.2)
❑ Complies. HVAC systems with ventilation air capacities of 1,500 CFM or greater that serve areas
having an average occupant load of 20 square feet per person or less from Table 1004.1.2 have a
means to automatically reduce outside air intake.
Identify applicable systems:
Plans /specs indicate where equipment (i.e. carbon dioxide sensor) and sequence is specified:
❑ Exception. HVAC systems are equipped with an energy recovery device with at least 50%
/ recovery effectiveness.
l�J No High Occupancy Systems. Project does not contain an HVAC system as described above.
1f. Exhaust Air Heat Recovery (Section 1318.3)
❑ Not Regulated. HVAC system does not have: 1) design supply air cap. of >10,000 cfm, and 2)
min. outside air supply >70 %, and 3) at least 1 exhaust fan rated at 75% of min outside air supply.
❑ Complies. Heat recovery system increases outside air temperature by 20 °F (Climte Zone 1) or
30 °F (Zone 2) and has provision to provide bypass during air economizer mode.
❑ Exception. An HVAC system qualifies for an exception to this requirement. Applicable exception
from Section 1318.3 Exception ❑ -t 0-2 0-3 0-4 0-5 0-6 0-7
The plans /specs show compliance in the following .
locations:
Large Volume Fan System's (Section 1318.4.2.4)
ilil Not Regulated. The building plans or specifications do not call for fan systems over 15,000 CFM
that serve a single zone and function for the purpose of temperature control.
❑ Complies. Fan systems are equipped with variable frequency drive or two speed motor to reduce
airflow as required by Section 1318.4.2.3.
The plans /specs show compliance in the following
locations:
14. Variable Speed Drives (Section 1317.10.3.1)
Not Regulated. The building plans or specifications do not call for fan and pump motors 10
horsepower and greater that serve variable -flow air or liquid systems.
❑ Complies. All fan and pump motors 10 hp and greater which serve variable -flow air or liquid
systems are controlled by a variable -speed drive.
❑ Exception. The building qualifies for an exception to the variable -speed drive requirement.
Portions of the building that qualify:
Applicable code exception is Section 1317.10.3.1, Exception
The plans /specs show compliance in the following
locations:
17. Service Water Heating (Sec. 1315)
❑ No New Water Heating. The building plans and specifications do not call for new water heaters,
j hot water storage tanks or service hot water distribution systems.
Complies. All new water heaters, hot water storage tanks or service hot water distribution
systems comply with the requirements of the Section 1315.
❑ Exception. The applicable code exception is Section: Exception:
.cr . Portions of the building that qualify:
The plans /specs show compliance in the following locations:
4 -5 April 2005
Compliance with OSSC, effective 01/01/05
Form 4a Project Name: [a 1,4-re. to r.DI c g 1.-
, / Page:
SYSTEMS - GENERAL
1. Swimming Pools, Spas and Hot Tubs (Section 1315.5)
V No New Pools. The building plans and specifications do not call for new, swimming pools, spas
or hot tubs.
❑ On /Off Controls Complies. Spa and hot tub heaters are equipped with a readily accessible
ON /OFF switch as required by Section 1315.5.1.
❑ Ventilation Controls Complies. Pool ventilation system is controlled based on humidity.
❑ Cover Complies. All heated pools, hot tubs and spas are equipped with a cover.
❑ Heat Recovery Complies. Pools, Spas, and hot tubs, over 200 ft utilize recovered heat as
required by Section 1315.5.3.
❑ Exception. Heat recovery is not necessary as pool is heated by renewable energy or
waste heat recovery sources capable of providing at least 70 percent of the heating
energy required over an operating season.
�
. Fume Hoods (Section 1317.2.1.)
No Fume Hoods. The building plans do not call for fume hood systems that have a total exhaust
rate greater than 15,000 cfm.
❑ Complies. Fume hood systems have at least one of the following features:
❑ Variable air volume hood exhaust and room supply systems capable of reducing exhaust
and makeup air volume to 50% or less of design values.
❑ Direct makeup (auxiliary) air supply equal to at least 75% of the exhaust rate, heated no
warmer than 2° F below room set point, cooled no cooler than 3° F above room set point,
no humidification added, and no simultaneous heating and cooling used for
dehumidification control.
❑ Heat recovery systems to precondition makeup air from fume hood exhaust in accordance
with 1318.3 - Exhaust Air Energy Recovery, without using any exception.
The plans /specs show compliance in the following locations:
29. Parking Garage Ventilation (Section 1317.2.3)
NO No Enclosed Garages. The building plans and specifications do not call for enclosed Group S -2
parking garages with a ventilation exhaust rate greater than 30,000 CFM.
❑ Complies. The plans and specifications call for carbon monoxide sensing devices as required by
Section 1317.2.3.
❑ Exception. Open parking garages.
2 Kitchen Hoods (Section 1317.11)
Not Regulated. The plans /specs do not call for any new kitchen hoods with exhaust capacity
greater than 5,000 cfm each.
❑ Complies. All new kitchen hoods with a total exhaust capacity greater than 5,000 cfm have at
least 50 percent of the required makeup air; (a) unheated or heated to no more than 60 °F; and (b)
uncooled or evaporatively cooled.
g - '''' 7. The plans/specs show compliance in the following locations:
:��; P P P � 9
2p . Outside Heating Systems (Section 1317.12)
No Outside Heating Systems. The plans /specs do not call for new permanently installed heating
systems outside the building.
❑ Complies. All new permanently installed outside heating systems are radiant gas fired systems
controlled by an occupancy sensor or timer switch as required by Section 1317.12.
4 -6 April 2005
Compliance with OSSC, effective 01/01/05
•
Abode n%1 Pa
Worksheet 4g Project Name: . � � �j TC � Page:
g
WATER CHILLING PKGS. - WATER & AIR COOLED
Equipment (a) (b) (c) (d) (e) (f)
Discussion of equipment Proposed
ratings and equipment Cooling Steady Proposed Compliance
definitions on page 4 - 19. Capacity State Part Load Schedule
Equip. ID Model Designation (Btu /hr) COP IPLV (A - I)
AH 0 -I AA 08F CIO,AGD�f.z 1 1.65 C
*fUl -2 L ?C AA Cg F I »,coo 't. Z 4.65 C
ii fWl -3 1 -PC AA01P 15;XO 4 1.1 1 1.65" c.
Required Indicate source of information
Document- ARI Unitary Directory, Section AC, page:
ation
ARI Applied Products directory, Section ULE, Page'
I Product data (Attach data furnished by the equipment supplier, I e , "cut sheets ")
Code Minimum Rating
Required Com Schedule Equipment Type Cooling Capacity (Tons) COP IPLV
q A Air Cooled, With Condenser, Electrically All Capacities 2.80 2 80
Efficiencies Operated
B Air Cooled, Without Condenser, All Capacities 3.10 3.10
This schedule of equip Electrically Operated
ment efficiencies was
reformatted from code, C Water Cooled, Electrically Operated All Capacities 4 20 4 65
Table 13 -0. Positive Displacement (Reciprocating)
Water Cooled, Electrically Operated, < 150 tons 4 45 4 50
D Positive Displacement (Rotary, Screw and >150, <300 tons 4 90 4 95
Scroll) >300 tons 5 50 5.60
< 150 tons 5.00 5 00
E Water Cooled, Electncally Operated, >150, <300 tons 5.50 5.50
Centnfugal >300 tons 6.10 6.10
F Air Cooled Absorption, Single Effect All Capacities 0 60 --
o G Water Cooled Absorption, Single Effect All Capacities 0 70 --
f l
H Absorption Double Effect, Indirect Fired All Capacities 1 00 1 05
409
I Absorption Double Effect, Direct Fired All Capacities 1.00 1 00
4 - 17
Compliance with OSSC, effective 01/01/05
I
Transmittal / Facsimile ' 3 �'i 9 a) 5 - eQ Co IV
F E I N K N O P T IIIMIIE M A C I O C E S C H A P P A Architects, Inc. CEI` G
I C
RE �/
Date 18- Jan -06 Project # 05227
JAN 1 9 2006
To City of Tigard Project A &F #972 Washington G.'►Y OF TIGARD
Buiding Department Tigard, OR BUILDING D )1,i)'
13125 SW Hall Blvd. It J�
�° ,� " � V j)
Tigard, OR 97223 Fax
lf 59
y ` /
T elephone #
ATTN: Val Henzel \
c o, Ns ,
No. of Pages .-
From George Pack 6 SP (e, t ,
Delivered By :-.-.:' Fax 41, Mail A (�
C' In Person C..) Courier ,I ��`� '/
�( It jr
.,, '
� �
J k,
For Your ' :� C. 4 11 1 0 Use ' Review & Enclosed Drawings C'-' -% Product Literature ��
C.% Record C_.% Distribution C. Specifications C...% Copy of Letter
• Approval Information , - - .% Shop Drawings C• Computer Disc
` ..= Samples (.. Other
Copies Date or No. Description
2 1/18/2006 Architectural S &S sets
Storefront sheets only
Message !Val,
Please find the attached (2) sets of "Signed and Sealed" Architectural
!Construction documents for the Abercrombie & Fitch Store #972 at the
!Washington Square Mall. These are the "storfront sheets" only, for you approval.
i
Please feel free to contact me if you have any questions or are in need of any
€additional information.
E
Thank you,
George
Copy
1020 Dennison Avenue, Suite 300, Columbus, Ohio 43201 telephone (6141297 -1020 fax (614) 291 -1020
Consulting Engineers
THORSON BAKER & Associates, Inc. 3030 West Streetsboro Road (330) 659 -¢688 phone
Richfield, Ohio 44286 (330) 649 -6675 fox
RECEIVED
mi
!JAN 3 0 2006
TRANSMITTAL CITY OF TIG
BUILDING DIVISION
Date January 27, 2006 Project No: 2005 -0689
To: City of Tigard Oregon Project: Abercrombie & Fitch
13125 SW Hall Blvd. Project Site: Tigard, Oregon
Tigard, OR 97223 Sent Via: Overnight X UPS
Attention: Val Henzal Delivery E -mail
From: Patty Fellenstein Mail Fax
No of sheets f cover
Copies Type Drawing No Description
1 30x42 S1.0, S1.1, S1.2, S2.2, S2.3 Structural drawings for rear wall, stamped & signed
Bond
1 8 x 11 - Structural Calculations for rear wall, stamped & signed
These are transmitted as checked below:
For Approval As Requested X For Your Use X For Review & Comment
Remarks:
Distribution: TBA, Laurie Borchert
Mitchell Gruesen @ A &F (Fax: 614 - 283 -8541)
George Pack @ FMS (Fax:614- 291 -1020)
Robert Peraza @ A &F (Fax:614- 283 -8819)
Mike Sheneman @ Royal Seal (1 copy for record)
Structural • Mechanical • Electrical • Civil • Landscape Architecture
x 1200512005- 06891DocumentslTransmNals12005 -0689 TRO9 doc
•
Site Address: cm-7-7 &,0 Lo (. / ,
4 '0 Building Division
Transmittal Letter
City of Tigard
TO: eL-0 DATE RECEIVED: DEPT: BUILDING DIVISION RECEIVED
JAN 1 9 2006
FROM: 0\,e-
CITY OF TIGARD
BUILDING DIVISION
COMPANY:
PHONE NO.: e).
RE: JLLp 0 — CO I q (7.
(Case
atIOL
number, site address, etc.)
(Project name or subdivision name and lot number)
ATTACHED ARE THE FOLLOWING ITEMS:
I Copies: I Description: I Copies: I Description:
Additional set(s) of plans. Revisions:
Cross section(s) and details. Wall bracing and/or lateral analysis.
Floor /roof framing. Basement and retaining walls.
Beam calculations. Engineer's calculations.
x Other (explain):
REMARKS:
FOR OFFICE USE ONLY
Routed to Permit Technician: Date: Initials:
Fees Due: 1 ❑ Yes I ❑ No Fee Description: Amount Due:
Special
Instructions:
Reprint Permit (per PE): ❑ Yes I ❑ No ❑ Done
Applicant Notified: Date: Initials:
I: Buildin \Forms\LetterTransmittal.doc 01/17/06
4
`'' :,';:tilkIO TIGARD
•
z-s�'BUILDING DIVISION PERMIT #: BUP200;}00614
13125 SWi45II Blvd., Tigard, OR 97223 DATE ISSUED: 12/140005
Phone: (503) 639 -Wli i3 %b& Ate-
Inspection Requests (24 Hrs�i) ?(503) 639 -4175 s' ''I .. [k) E' 1<
m6igaee
INSPECTION WORKSHEET FOR DATE? 12/29/2005 TIME: 7 :00AM PAGE: 50
011 i Aaae
0
SITE ADDRESS: 09377 SW WASHINGTON SQUARE RIP i A is 13f' CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: F° TYPE OF USE:
PROJECT NAME: AI3ERCROMBIE & FITCH ¢9D i a &Anfr
DESCRIPTION: T.I. (11,090 sq ft) r°
ra i aaal.le
OWNER: WASHINGTON SQUARE LLG, PHONE #: 4 _
CONTRACTOR: ROYAL. SEAL CONSTRUCTION PHONE #: 017491 i43t4 e
Eo
filniU
Inspection Request Scheduled For: Date: 12/2.9/2005 Pour Time:
Code # Inspection Description Confirm # Contact # Message
275 Framing 024111 -01 503-519-9132 N
Corrections /Comments /Instructions:
k
. _� �
AIM 1
Airill
w w
❑ PASS ARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL ❑ CALL FOR INSPECTION ❑ ADDITIINAL FEES ASSESSED
Inspector: WI Date: goi Phone #: (503) 718-
CITY OF TIGARD
BUILDING DIVISION PERMIT #: BUP700fr0 614
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 12/14/20W)
Phone: (503) 639 -4171
Inspection Requests (24 Hrs.): (503) 639 -4175
INSPECTION WORKSHEET FOR DATE: 5/10/2006 TIME: 7:02AM PAGE: 71
SITE ADDRESS: 09377 SW WASHING ION SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: AF3ERCROMBlE & 1=1 i CH
DESCRIPTION: T.1. (11,090 q ft)
OWNER: WASHINGTON SQUARE LLC, PHONE #:
CONTRACTOR: ROYAL SEAL CONSTRUCTION PHONE #: 817- 491 -( >100
Inspection Request Scheduled For: Date: 5/10 /2006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
::99 Final inspection 029585-01 912-24D-6896 N
Corrections /Comments /Instructions:
461
•
1 ❑ PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL C L FOR I SPECTION ❑ ADDITION FE. S ASSESSED
ei
' 1r ', ,, /
Inspector: Date. 1 40 'hone #: (503) 718-b4k—ZO
•
CITY OF TIGARD
BUILDING DIVISION PERMIT #: 13UP2005. 0€14
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 12/14/2005
Phone: (503) 639 -4171 Ak
Inspection Requests (24 Hrs.): (503) 639 -4175 ti.:
INSPECTION WORKSHEET FOR DATE: 5/2/2006 TIME: 7:01AM PAGE: 68
SITE ADDRESS: 93" S WASHINGTON G
0.., !7 � lNlriA.�l IIN STUN SQUAF RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: ADE :RCROMIBIE & FITCH
DESCRIPTION: T.I. (11,090 sq ft)
OWNER: WASHINGTON SQUARE LLC, PHONE #:
CONTRACTOR: ROYAL SLAL CONSTRUCTION PHONE #: 817 - 49 1 - 0:100
Inspection Request Scheduled For: Date: 502006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
299 Final iii pection 029062"01 972249 -6096 N
Corrections /Comments /Instructions:
t
rijaailgir411L110.4 mom
— 1 � t St C am 60PrsS
\ OTrysEK--- tSa)ES
•
❑ PAS ❑ PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
FAIL _ ❑ CALL FOR INSPECTION ❑ ADDITIONAL FEES ASSESSED
Inspector: Date: 54- 0A, Phone #: (503) 711747 �
CITY-Of TIGARD �� f
BUILDING DIVISION (6 PERMIT 246 SF'- 0o (o i V 13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED:
Phone: (503) 639 -4171 �,I�I
Inspection Requests (24 Hrs.): (503) 639 -4175 ":_..
INSPECTION WORKSHEET FOR DATE: TIME: PAGE:
SITE ADDRESS: q 377 50 CLASS OF WORK:
SUBDIVISION: LOT #: TYPE OF USE:
PROJECT NAME:
DESCRIPTION: ib Tesp..e6c. __ -
OWNER: ��' PHO #:
CONTRACTOR: ��T, G PH E #: S, 5 / ? y
Inspection Request Scheduled For: Date: Pour
Code # Inspection Description Confirm # Contact # Message (----,----
Corrections /Comments /Instructions:
4 G'7 A s 0,42_ Fi,
F r tOrVik.-7-312S*-7-#-C--
I a
ld?iltft&M)3/12
_ . ...._th---
E i PASS PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL NI CAL FOR INSPECTION ❑ ADDITIONAL FE S ASSESSED
&IA Si
Inspector: MK Date: 1 ° Phone #: (503) 718-
I
CITY OF TIGARD 6-6
BUILDING DIVISION PERMIT #:2--06.6 0°6' 1 13125 SW Hall Blvd., Tigard, OR 97223 D ATE ISSUED:
Phone: (503) 639 -4171
Inspection Requests (24 Hrs.): (503) 639 -4175 s I I ..
INSPECTION WORKSHEET FOR DATE: TIME: PAGE:
DDRES qS 1 .1 59.1 Utz Pr CLASS OF WORK:
SUBDIVISION: LOT #: TYPE OF USE:
PROJECT NAME:
DESCRIPTION: ) P-
OWNER: PHONE #: 1
CONTRACTOR: PHONE #:
Inspection Request Scheduled For: Date: 3 - a Li -O Pour Time:
Code # Inspection Description Confirm # Contact # Message
7 g D --- - w _ 5 - 9/3
Corrections /Comments /Instructions:
_ c.a.i
-d4 L
/AIMEE ■ / ,-
_v
ASS ❑ PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL ❑ CALL FOR INSPECTION ❑ ADDITIONAL FEES . SSESSED
1 I
Inspector:
0'4 Date: . 11� ' e #: (503) 718- /'
CITY (0 TIGARD 6-
BUILDING DIVISION PERMIT #: a0dS —006/4f
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED:
Phone: (503) 639 -4171
Inspection Requests (24 Hrs.): (503) 639-4175 sA I �..
INSPECTION WORKSHEET FOR DATE: TIME: PAGE:
SITE ADDRESS: Gj37 SW & J /T-'Q CLASS OF WORK:
SUBDIVISION: LOT #: TYPE OF USE:
PROJECT NAME: 1
DESCRIPTION: /� ` g gtE.-
OWNER: PHONE #:
CONTRACTOR: PHONE #:
Inspection Request Scheduled For: Date: 3 -2- Z -- D r° Pour Time: C - F ; H ---1/ '
Code # Inspection Description Confirm # Contact # Message
7 5— 28 c ,ri - 1 3D–
r ectionn C�rnmen
it _�i�t t`. a r .� 4'
A l i
arMilliW31111i■ a %
■l.fir r - I - w -AIIV
---- ' ---V: Unkt r PAT O 543te__
, J
Ali
- .
I r. , Iii
U
-�- w
❑ PASS PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL ❑ CALL FOR I SPECTION ❑ ADDIT NAL FEES ASSESSED
k Inspector: I AI & 1 Date: dG Phone #: (503) 718 - ' ,0-.J
•
CITY CYF TIGARD
BUILDING DIVISION PERMIT #:ZQ S- 06) 6 i V.
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED:
Phone: (503) 639 -4171 A
I nspection Requests (24 Hrs.): (503) 639 -4175 �'I I ..
INSPECTION WORKSHEET FOR DATE: `3 /2 6 TIME: PAGE:
SITE ADDRESS: 'r 1 1 4Jq J CQ. CLASS OF WORK:
SUBDIVISION: LOT #: TYPE OF USE:
PROJECT NAME:
DESCRIPTION: A A o pavg. Fle_
OWNER: PHONE #:
CONTRACTOR: _T--S Some_ PHONE #: '.----/ _ q )3 Z
Inspection Request Scheduled For: Date: Pour Time:
Code # Inspection Description Confirm # Contact # Message
S
'Z� T - 6 r- a ( C
Corrections /Comments /Instructions:
I /
�" )
I . . �� Y. ! ,-- �. --- ), J•- J l C� ri p 5.-
) L t•
�i 1 -ii i U 6-- ( � _:t - om � ��F C L
9:- ' ------'
❑ PASS PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL ❑ CALL FOR INSPECTION ❑ ADDITIONAL EES ASSESSED
Inspector: / l Date: ( 1 Phone #: (503) 718 ZA2
CITV ..1 TIGARD 6
BUILDING DIVISION PERMIT #: aeK) j p0 ( Cf
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED:
Phone: (503) 639 -4171 /aor�►
Inspection Requests (24 Hrs.): (503) 639 -4175
INSPECTION WORKSHEET FOR DATE: TIME: PAGE:
SITE ADDRESS: q3 1 , F� s � � S CLASS OF WORK:
- 5IISUIVISI N: LOT #: TYPE OF USE:
PROJECT NAME:
DESCRIPTION: U
OWNER: PHONE #:
CONTRACTOR: PHONE #:
Inspection Request Scheduled For: Date: 3 - t' 3 - D (P Pour Time:
Code # Inspection Description Confirm # Contact # Message
Corrections/Comments/Instructions:
t " 51 fog -
4110'
•
❑ PASS E ARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL MI CALL FO INSPECTION ❑ ADDITI ,NAL FEES ASSESSED
l■ Vi
401 •
Inspector: _ Date: hone #: (503) 718- A_Zt
CITY 'OP TIGARD
BUILDING DIVISION PERMIT #: 311P100:00E14
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 12/11i/2006
Phone: (503) 639 -4171 1111
Inspection Requests (24 Hrs.): (503) 639 -4175 �• "_
INSPECTION WORKSHEET FOR DATE: /01/2006 TIME: 7:02AM PAGE: 08
SITE ADDRESS: 09377 SW WASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: AF3ERCROMBIE & FITCIi
DESCRIPTION: r I. (11,090 sq ft)
OWNER: WASHINGTON SQUARE LLC, PHONE #:
CONTRACTOR: ROYAL SEAL CONSTRUCTION PHONE #: 817 - 491 -CA00
Inspection Request Scheduled For: Date: 2/21/2006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
235 L)iyw.all nailing 027199 - 01 503 N
Corrections /Comments /Instructions:
_.- : VA-Cil
- (9_3( --(---- be bJ
7,-- rE0-60____ ang-P-WP-ak-IPOG--
❑ PASS ARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL ❑ CALL F. • INSPECTION ❑ ADDITIO L FE S ASSESSED
Inspector: was ik Date: `( 6aDhone #: (503) 718 -2
CITY Op TIGARD .
Il BUILDING DIVISION PERMIT #: i3UP2005-0oc 14
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 12/141/200S
Phone: (503) 639 -4171 l
Inspection Requests (24 Hrs.): (503) 639 -4175 67 1 I ..
INSPECTION WORKSHEET FOR DATE: 2/ 14/7006 TIME: 2:22PM PAGE 2
SITE ADDRESS: 09377 W WASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: At3ERCROMBIE & Fl TCH
DESCRIPTION: T I. (11,090 sq ft)
OWNER: WASHINGTON SQUARE LLC, PHONE #:
CONTRACTOR: ROYAL SEAL CONSTRUCTION (ION PHONE #: 817-491-6400 i
Inspection Request Scheduled For: Date: 2/140006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
775 Framing 026877-01 503 -510 0132 N
Corrections /Comments /Instructions:
/ 2 i(Th ''( 49 . l Car-g-1,1)4 . . 'Fr /06,./.
MP li 4 A A
MIL ‘ ■ . c ( 0 0 , '
•
.,r ► .air ► ► .. : AV =
IV _,_____
❑ PASS PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL • CALL FOR INSPECTION ❑ ADDITIO AL F ES ASSESSED
Inspector: diii Date: / ` ` 6 Phone #: 503 71 � , r (503)
CITY OF TIGARD .
BUILDING DIVISION PERMIT #: f3vp2005 00614
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 1W14/7005
Phone: (503) 639 -4171 i�
Inspection Requests (24 Hrs.): (503) 639 -4175 s' IL.
INSPECTION WORKSHEET FOR DATE: 2/10/2006 TIME: 7 :Ot4A4v1 PAGE: 20
SITE ADDRESS: 093/7 SW WA SHINGTON SQUARES RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: ABERCROMBIE & FITCH
DESCRIPTION: T.I. (11,090 :.q ft)
OWNER: WASHINGTON SQI.JARE I.LC, PHONE #:
CONTRACTOR: ROYA1 SLAL CONSTRUCTION PHONE #: 817
Inspection Request Scheduled For: Date: 2110 /2006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
24f Firewall 026683 -01 503 - 519.9132 N
Corrections /Comments /Instructions:
/ 1
i in i - 1-- - , , viv
a ii • NI -F-(
S7 X1
�-
❑ PASS PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL r CALL FOR INSPECTION ❑ ADDITI NA FEES ASSESSED
Inspector: Ant Date: 10 0 1 0 Phone #: (503) 718 -
_∎
CITY - OF TIGARD .
BUILDING DIVISION PERMIT #: 13UP70M- 0Q614
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 12/140006
Phone: (503) 639 - 4171 .. 11
Inspection Requests (24 Hrs.): (503) 639 -4175 _. _-_- I �..
INSPECTION WORKSHEET FOR DATE: 1/20/2006 TIME: 7:00AM PAGE: 76
SITE ADDRESS: 09377 SW WASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: AI3FRCROMBIF & FITCH
DESCRIPTION: TA. (11,090 cq ft)
OWNER: WASHINGTON SQUARE LLC, PHONE #:
CONTRACTOR: ROYAL SEAL CONSTRUCTION PHONE #: B17- 491 -6400
Inspection Request Scheduled For: Date: 1/20/2006 Pour Time:
Code # Inspection Description Confirm # Contact # Message
276 Framing 025382 -01 503- 513.9132 N
Corrections /Comments /Instructions:
L
t
s p4
..... I K15Vk-c-c . 6 - rs ,ks 6
V -
❑ PASS PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL Ini CAL FOR I PECTION ❑ ADDITI NAL F \ 1Phone ES ASSESSED
Inspector: Date: #: 503 718 - p D te. ( )
CITY' Of TIGARD . - {
BUILDING DIVISION I PERMIT #: BUPA/06 13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 12/14/2006
Phone: (503) 639 -4171
Inspection Requests (24 Hrs.): (503) 639 -4175 i-
INSPECTION WORKSHEET FOR DATE: 1/9/2008 TIME: 7:01AM PAGE: 68
SITE ADDRESS: 09377 SW WASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: AI3ERCROMBIE & FITCH
DESCRIPTION: T.I. (11,030 sq ft)
OWNER: WASHINGTON SQUARE L.I.C, PHONE #:
CONTRACTOR: ROYAL SEAL CONSTRUCTION PHONE #: t317 €191 - M00
Inspection Request Scheduled For: Date: 1/9/2008 Pour Time' 9 :00
Code # Inspection Description , Confirm # Contact # Me-. -age e ia
270 F2eii►futcing steel (rebar) 024531 -01 t3 Y „
( 2 2 0) S l c..10 el e eZ--4
orrections /Comments /I tructions: t4-2-nr
.PASS ❑ PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL ❑ CALL FOR INSPECTION ❑ ADDITIONAL FEES ASSESSED ,
1 &' ( °I/1' 16 /6 & 7>i42-Y‘
Inspector: Date: / Phone #: (503) 718 -
CITY Of TIGARD -
. A .• ,
BUILDING DIVISION PERMIT #: BUPN)0E 00614
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: /2114/2006
Phone: (503) 639 -4171 1
Inspection Requests (24 Hrs.): (503) 639 -4175 ° 'I ..
INSPECTION WORKSHEET FOR DATE: 1/4/2006 TIME: 6:59Ata1 PAGE: 4
SITE ADDRESS: 09377 SW WASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: ABERCROMBIE & FITCH
DESCRIPTION: T.I. (11,090 sq ft.)
OWNER: WASHINGTON SQUARE L.LC, PHONE #:
CONTRACTOR: ROYAL SEAL CONSTRUCTION PHONE #: 817-491-6400
Inspection Request Scheduled For: Date: 114/2006 Pour Time:
r
Code # Inspection Description Confirm # Contact # Message
275 Fran 024361 -01 603 -519 -9132 N
Corrections /Comments/ Instructions:
Wk 1-61-0"- ipm,„ (R k !'/' d4,';/11 6U/ ' ) !>!/d
7 d
pK,,,;I (iit pi i f ,Q,/t,/ l # 7 5 I,witti A)
`l7ift* � Gt -a true( -
•
60 tu m/i/7/ o, kAtylwevi, II r ate. a---(1
54 r r // vat ' Gz'1'4 -
❑ PASS I■ PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL CALL F! R INSPECTION ❑ ADDITIONAL FEES ASSESSED
r
Inspector: Date: l --- Phone #: (503) 718 -