Correspondence 6411
July 25, 2005
CITY OF TIGARD
OREGON
Janie & Jack
Sara Nielsen
1120E 80 St. #211
Bloomington, MN 55420
RE: JANIE & JACK - REVIEW
Project Information
Building Permit: BUP2005 -00320 Construction Type: II-B
Tenant Name: Janie & Jack Occupancy Type: M
Address: 9368 SW Washington Sq. Occupant Load: 31
• Area: 1,188 sq ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
edition; and 2003 International Fire Code as amended by TVF &R. The submitted plans are
approved subject to the following conditions.
1. The main exterior door or doors are permitted to be equipped with key - operated locking
devices from the egress side provided:
1. The locking device is readily distinguishable as locked,
2. A readily visible durable sign is posted on the egress side on or adjacent to the door
stating: THIS DOOR 0 REMAIN UNLOCKED WHENBUILDING IS OCCUPIED. The
sign shall be in letters 1 inch (25 mm) high on a contrasting background,
3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to
be used, provided that the door leaf having the automatic flush bolts has no doorknob or
surface- mounted hardware. 1008.1.8.3 OSSC
2. Exits and exit access doors shall be marked by an approved exit sign readily visible from any
direction of egress travel. Access to exits shall be marked by readily visible exit signs in
cases where the exit or the path of egress travel is not immediately visible to the occupants.
Exit sign placement shall be such that no point in an exit access corridor is more than 100
feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit
sign. 1011.1 OSSC
4. All exit doors shall be openable from the inside without the use of a key or any special
knowledge or effort. 1008.1.8 OSSC
5. Exit signs shall be illuminated at all times and shall be provided with a second source of
power that will provide 1 'h hours of illumination in case of primary power loss. 1006.3
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
OSSC FYI Additional exit signs may be required by the city field inspector to clearly
indicate the path of egress.
6. The means of egress shall be provided with illumination of not less than 1 foot candle at the
floor level anytime the building is occupied. The means of egress illumination shall be
provided with a second source of power in case of primary power loss. 1006.2 OSSC
7. Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings, etc,
will be charged a deferred submittal fee based on the valuation of the portion of the work
being deferred. The minimum fee shall be $200.00. Deferred Items:
a. None Listed
8. Safety glazing including but not limited to: the following locations: Each unit of glazing
shall be permanently identified by the manufacturer. 2406 OSSC. Some of these locations
are as follows:
a. Glazing in ingress and means of egress doors.
b. Glazing in an individual fixed or operable panel adjacent to a door where the nearest
vertical edge is within a 24" arc of the door in a closed position and whose bottom
edge is less than 60" above the floor or walking surface except when there is an
intervening wall or other permanent barrier between the door and the glazing.
9. American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the
structure only for compliance with Chapter 11 of the OSSC, which may not include all of the
requirements of the ADA.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.3:1 OSSC
Certificate of Occupancy: No building or structure shall be used or occupied until the Building
Official has issued a certificate of occupancy 110.1 OSSC
• Premises Identification: Approved numbers or addresses shall be provided for all new buildings
in such a position as to be plainly visible and legible from the street or road fronting the property.
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
Res ect
al Henzel,
Senior Plans Examiner
Fire and Life Safety Inspection Checklist for Rated Assemblies
❑ Exterior Walls— 704 - Rated - inside 1 2 3 4 Rated — exterior 1 2 3 4 Parapet Y N Openings protected Y N
❑ Fire Wall — 705 ❑ Party wall Y N (503.2) - Parapet Y N Openings protected Y N
705.5 Horizontal continuity. Fire walls shall be continuous from exterior wall to exterior wall and shall extend at least 18 inches
(457 mm) beyond the exterior surface of exterior walls. "See Code book for exceptions"
705.6 Vertical continuity. Fire walls shall extend from the foundation to a termination point at least 30 inches (762 nun) above
both adjacent roofs. "See Code book for exceptions"
❑ Fire Barriers - 706 - Rated 1 2 3 4 Openings protected Y N
706.4 Continuity of fire barrier walls. Fire barrier walls shall extend from the top of the floor /ceiling assembly below to
the underside of the floor or roof slab or deck above and shall be securely attached thereto. These walls shall be continuous
through concealed spaces such as the space above a suspended ceiling.
❑ Shaft Enclosures — 707 - Rated 1 2 3 4 Openings protected Y N
707.5 Continuity. Shaft enclosure walls shall extend from the top of the floor /ceiling assembly below to the underside of the
floor or roof slab or deck above and shall be securely attached thereto. These walls shall be continuous through concealed spaces` '',
such as the space above a suspended ceiling. The supporting construction shall be protected to afford the required fire; resistance
rating of the element supported. Hollow vertical spaces within the shaft enclosure construction wall shall be fire - stopped of every
floor level.
tlit Fire Partitions - 708 - Rate42 3 4 Openings protected N
708.4 Continuity. Fire partitions shall extend from the top of the floor assembly below to the underside the floor`
or roof slab or deck above or to the fire- resistance-rated floor /ceiling or roof/ceiling assembly above,i aiid,sball be
securely attached thereto. If the partitions are not continuous to the deck, and where constructed of combustible'
construction, the space between the ceiling and the deck above shall be fire- blocked or draft- stopped in accordance
with Sections 717.2.1 and 717.3.1 at the partition line. ` `,s'
1:1 Smoke Barriers — 709 - Rated 1 2 3 4 Openings protected Y N � ` cv ,
709.4 Continuity. Smoke barriers shall form an effective membrane continuous fromoutside'wall to outside wall and from floor
slab to floor or roof deck above, including continuity through concealed spaces, svch as those found above suspended ceilings, and
interstitial structural and mechanical spaces. The supporting construction shall be p "ratected to afford the required fire - resistance
rating of the wall or floor supported in buildings of other than Type LIB, HI13 or VB construction.
❑ Smoke Partition — 710 - Rated 1 2 3 4 Openings protected `Ya.N
710.4 Continuity. Smoke partitions shall extend from the floor t to the underside of the floor or roof deck above or to the
underside of the ceiling above where the ceiling membrane is constructed to limit the transfer of smoke.
❑ Horizontal Assemblies — 711 - Rated 1 2 3 4 :�O penings protected Y N
711.4 Continuity. Assemblies shall be continuous without openings, penetrations or joints except as permitted by this section and
Sections 707.2, 712.4 and 713. Skylights and other penetrations through a fire- resistance-rated roof deck are permitted to be
unprotected, provided that the structural integrity of the fire- esistance-rated roof construction is maintained.
Membrane Penetrations — 712
• Er Through Penetrations — 712
El Fire Resistive Joint System — 713
{
El Fire Resistive Rating of Structural Members — 714
• ❑ Opening Protective — 715
['Ducts & Air Transfer Openings — 716 - 716.4 Access and identification. Fire and smoke dampers shall be provided
with an approved means of access, large enough to permit inspection and maintenance of the damper and its operating parts.
..Access points shall be permanently identified on the exterior by a label having letters not less than 0.5inch (12.7 mm) in height
reading: SMOKE DAMPER or FIRE DAMPER.
❑ Thickness of Protective Coverings — 720 -Table 720.1(1)
❑ Safety Glazing — 2406
❑ Other -
•