Loading...
Correspondence January 20, 2006 CITY OF TIGARD Oregon Electric Group OREGON Loth Martin 1010 SE 11 Portland, OR 97214 RE: FIRE ALARM SYSTEM Project Information Building Permit: BUP2006 -00042 Construction Type: II - Tenant Name: Abercrombie & Fitch #972 Occupancy Type: M Address: 9377 SW Washington Sq. Occupant Load) 234 Area: 11,090 sq ft Stories: 2 Hazard: Ordinary Group II Sprinklers; Yes • The plan review was performed under the State of Oregon Sttructural Specialty Code (OSSC) 2004 edition; Oregon Fire Code 2004 edition and NFPA 72'.`The submitted plans are approved subject to the following. General requirements A key box for building access may be r juu Please contact the local Fire Marshal's Office for an order form and instructions regarding iinstallation and placement. (OFC 506) 1. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence of the building ofc a l and fire code official. All functions of the system or alteration shall be tested. 901.5 ' OSSC and NFPA 72 2. Before requesting-final approval of the installation, the installing contractor shall furnish a written statement to the fire code official that the subject fire protection system has been installed in accordance with approved plans and has been tested in accordance with the manufacturer's specifications and the appropriate installation standard. Any deviations from the design standards shall be noted and copies of the approvals for such deviations • shall be attached to the written statement. 901.2.1 OFC 3. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and connections shall be mechanically protected. The circuit disconnecting means shall be accessible only to authorized personnel and shall be clearly and permanently marked FIRE ALARM CIRCUIT CONTROL. NFPA 72 4.4.1.4, 907.5 OFC 4. The emergency voice/alarm communication system shall be designed and installed in accordance with NFPA 72. 907.2.12.2.3 OFC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 5. All power supplies shall be installed in conformity with NFPA 70. NFPA 72, 4.4.1.2 6. All primary and secondary power supplies shall be monitored for the presence of voltage at the point of connection to the system. Failure of either supply shall result in a trouble signal in accordance with 4.4.3.5. The trouble signal also shall be visually and audibly indicated at the protected premises. NFPA 72, 4.4.7.3 7. Visual alarm signal appliances shall be integrated pp egrated into the building or facility alarm system. At a minimum, visual signal appliances shall be provided in buildings and " facilities in each of the following areas: 1109.14 OSSC \■ ��j • restrooms and any other general usage areas • e • meeting rooms • classrooms • hallways, lobbies, and any other area for common use. / `Y 8. Visual alarms shall be located not less ess than 80 inches and not more than 96 inches above floor level. When a low ceiling exists, the visual alarm shall be mounted within the dimensions stated above and at least 6 inches below the g' 1109.14 OSSC, NFPA 72, 7.5.4 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 0S C Premises Identification: Approved numbers or'addresses shall be provided for all new buildings in such a position as to be plainly visible and leible from the street or road fronting the property. <, \ When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfu Hemel, Senior Plans Examiner 03/15/2006 11:03 FAX 614 291 1020 F M S ARCHITECTS INC. Ij002 lay A V I ItD A. Y LI S E Architects March 15, 2006 RECEIVED MAR 1 5 2006 City of Tigard Building Department CITY OF TIGARD 13125 SW Hall Blvd. BUILDING DIVISION Tigard, OR 97223 ATTN. Val Henze! Re: 05 -117 Abercrombie & Fitch #972 / Washington Square Mall g371 s"SW Washington Sq. Road Space #S11 Tigard, OR 97223 Val, This letter is written to inform the building department that the stairwell located at the rear of space #S1 1 will not be a fire rated stairwell as originally designed and planned. Below is a list of code references as described by City of Tigard Building Inspector Dan Nelson to verify compliance with egress and safety requirements. Governing codes: 2003 IBC and 2005 OSSC • Table 1016.1: No rated corridors MOCC with sprinklers. L • Table 1013.3: Common path of travel when 2 exits are provided 1/� • Table 1014.1: MOCC only 1 exit required for less than 50 occupancy or 7S • Table 1015.1: MOCC travel distance of 196 ft. with sprinklers. 111 ego y 0,1r ,a r-e-7 1 /I pUbik v� boa Please feel free to contact my office and speak to George Pack if you have any questions regarding the nature of this letter or its' contents. , /a0 0 , 4 .1 -nk yo David A You IA Ih''0 U,:ruu<. : \.cnu,:, S : :Oh ..olumblig ;'hl Icicphonc (6l•).'i! -t ■:. t; I i I :I•'1:.1I 10';c