Loading...
Correspondence . October 6, 2005 `^ IY� J�I� I \ CITY OF TIGARD OREGON Fisher Development Inc. Jon Taber 506 SW 6 Ave. #403 Portland, OR 97204 • RE: RACK STORAGE @ WILLIAMS- SONOMA Project Information Building Permit: BUP2005 -00506 Construction Type: II B Tenant Name: Williams- Sonoma on S Occupancy Type: S1 Address: 9367 SW Washington q Occupant Load: NA The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and 2003 Oregon Fire Code (OFC) as amended by TVF &R. The submitted plans are approved subject to the following conditions. 1. Provide three 2 -A rated fire extinguisher on the second story area and one on lower story area. The extinguisher shall be located so that no usable space has a distance greater than 75 feet to the extinguishers. OFC 906.3 2. The clearance between the deflector and the top of storage shall be 18 in. or greater. NFPA 13 8.5.6.1 3. The racks shall display in one or more conspicuous locations a permanent plaque not less than 50 square inches in area, showing the maximum permissible unit load in clear - legible print. OSSC 1603 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectful Val Henzel, Senior Plans Examiner 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772