Correspondence rA ikpu R OAN
August 30, 2005
CITY OF TIGARD
OREGON
OCCHIALI DA SOLE
TIM SCHENK
1120E 80 ST. SUITE 211
BLOOMINGTON, MN 55420
RE: OCCHIALI DA SOLE - TI REVIEW
Project Information
Building Permit: BUP2005 -00377 Construction Type: II-B
Tenant Name: OCCHIALI DA SOLE Occupancy Type: M
Address: 9364 SW Washington Sq. Occupant Load: 20
Area: 609 sq ft Stories:
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
edition; and 2003 International Fire Code as amended by TVF &R The submitted plans are
approved subject to the following conditions.
1. Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings, etc, will
be charged a deferred submittal fee based on the valuation of the portion of the work being
deferred. The minimum fee shall be $200.00. Deferred Items:
A. Egress /Access Door System — Shall be submitted for review and approval prior to
installing door system.
2.NOT PART OF THIS REVIEW:
• Fire Sprinklers
• Mechanical System
• Plumbing
• Electrical
3. Accessible checkout aisles shall be on an accessible route and at least 36 inches wide.
Counters in accessible checkout aisles shall be not more than 38 inches (965 mm) high and
the top of the raised edge of the counter shall not exceed 40 inches (1016 mm) in height
above the finished floor. Accessible checkout aisles shall be identified by the international
symbol of access. OSSC section 1109.19, 1109.23.3
•
4. The main exit shall be provided with signage indicating "THIS DOOR MUST REMAIN
UNLOCKED DURING BUSINESS HOURS" Section 1008.1.8 OSSC
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
5. Exits and exit access doors shall be marked by an approved exit sign readily visible from
any direction of egress travel. Access to exits shall be marked by readily visible exit
signs in cases where the exit or the path of egress travel is not immediately visible to the
occupants. 1011.1 OSSC
6. American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
only for compliance with Chapter 11 of the OSSC, which may not include all of the
requirements of the ADA.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.3.1 OSSC
Certificate of Occupancy: No building or structure shall be used or occupied until the Building
Official has issued a certificate of occupancy 110.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new buildings
in such a position as to be plainly visible and legible from the street or road fronting the property.
•
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
Resp 11
al Hemel,
Senior Plans Examiner
•
N
s�
{
hodilla
I /1 1 , 116 ,1 1
September 27, 2005 -
CITY OF TIGARD
OREGON
OCCHIALI DA SOLE
TIM SCHENK
1120E 80 ST. SUITE 211
BLOOMINGTON, MN 55420
RE: OCCHIALI DA SOLE- DEFERRED SUBMITTAL ITEM REVIEW
Project Information
Building Permit: BUP2005-00377 Construction Type: II-B
Tenant Name: OCCHIALI DA SOLE Occupancy Type: M
Address: 9364 SW Washington Sq. Occupant Load: 20
Area: 609 sq ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
edition; and 2003 International Fire Code as amended by TVF &R. The submitted plans are
approved subject to the following conditions. Please add to approved plans on site.
Horizontal sliding or vertical security grilles or doors that are a part of a required means of
egress shall conform to the following:
1. They shall remain in the full open position during the period of occupancy by the
general public.
2. Doors or grilles shall not be brought to the closed position when there are more than 10
persons occupying spaces served by a single exit or 50 persons occupying spaces served
by more than one exit.
3. The doors or grilles shall be openable from within without the use of any special
knowledge or effort where the space is occupied.
4. Where two or more exits are required, not more than one -half of the exits shall be
permitted to include either a horizontal sliding or vertical rolling grille or doors.
Premises Identification: Approved numbers or addresses shall be provided for all new buildings
in such a position as to be plainly visible and legible from the street or road fronting the property.
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
Respect , /I jj,
fr
Val Henze', Senior Plans Examiner
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772