FIRE ALARM SUBMITTAL
Washington Square
Williams Sonoma
Siemens Job Number
258070
Siemens Project Manager
Chuck Neely
Siemens Project Engineer
Ron Pulioff
Date Submitted
September 12, 2005
Proprietary document for approval only
SIEMENS
Siemens Building Technologies, Inc.
3025 S.W. Corbett Ave
Portland, OR 97201
Phone: (503) 234 -9995
Fax: (503) 234 -8030
Table of Contents SIEMENS
BILL OF MATERIAL &
COMPONENT SPECIFICATIONS
FUNCTIONAL MATRIX
BATTERY CALCULATIONS
VOLTAGE DROP CALCULATIONS
BILL OF MATERIALS SIEMENS
Washington Square
•
Williams Sonoma
258070 Fire Alarm System
Item Part # Qty Mfg Description
1 FP -11 21 Siemens Fire Print Intelligent Detector
2 DB -11 18 Siemens Detector Base Standard
3 AD -11XPR 3 Siemens Duct Detector Housing
4 STA -10 3 Siemens Sample Tube 6' 3" - 9' 9"
5 TRI -D 1 Siemens Dual Input Module
6 E50- 24MCW -FW 6 Wheelock Speaker /strobe, Multi- candela, White
7 RSS- 24MCW -FW 2 Wheelock Strobe, Multi- candela, White
PROPRIETARY DOCUMENT FOR APPROVAL ONLY 1 9/13/2005
SIEMENS Fire Safety
FP -11 FirePrintTM Detector
Intelligent Fire Detector for MXL, MXL -IQ, and MXLV Control Panels
ENGINEER AND ARCHITECT SPECIFICATIONS
• Most Sophisticated "Detector Intelligence" available today
• Multi- Criteria fire detection for the price of a
photoelectric detector
• FirePrintTM Technology to discriminate between deceptive
phenomena and an actual fire
• Easily programmed to match specific hazard profiles from the
control panel
• Pre -Alarm reporting based on fire profile selected.;;
• Remote sensitivity measurement capability
• System logic activation based on any of three inputs from
detector (smoke, heat or neural network),
• Field cleanable chamber with replaceable chamber
parts available` -�
• Multi -color detector status LED 'f
• Two-wire operation
• Compatible with Model DPU or FPI -32 field
programmer /tester
• Supports EnviroLINK software based automatic
environmental compensation
• Backward compatible with older MXL systems
(Rev. 2 and above)
• Optional fully programmable relay base , audible base, and
duct housing
• ( 12) UL Listed, ULC Listed, CSFM, FM, NYMEA
Approved
Introduction
The FP -11 Intelligent Fire Detector provides the life need for cumbersome, unreliable mechanical program-
safety industry with the most highly evolved detection ming methods and reduces installation and service
system available today. The FP -11 utilizes advanced costs by electronically programming and testing the
detection technology that allows the detector to detector prior to installation.
distinguish nonthreatening deceptive phenomena, such
as cigarette smoke, from actual fire hazards, while The FP -11 fire detector is compatible with the MXL
optimizing detection for the area in which it is in- family of control panels including the MXL, MXL-IQ,
stalled. No other detection system available today and MXLV.
offers a higher level of protection or nuisance The FP -11 detector is Underwriters Laboratories and
alarm immunity. The FP -11 uses state -of- the -art Underwriters Laboratories of Canada Listed.
microprocessor circuitry with error check, detector
self- diagnostics and supervision programs.
Description
The FP 11 intelligent fire detector is compatible with The FP -11 is a plug -in, two-wire, multi- sensor detector
the Siemens Building Technologies, Fire Safety Divi with both photoelectric and thermal inputs and is
sion, Model DPU or FPI -32 field programmer /tester, compatible with the MXL family of control panel
which is a compact, portable, menu - driven accessory systems. Each detector consists of a dust resistant,
for electronically programming and testing detectors, field cleanable photo chamber, a solid state
easily and reliably. The DPU or FPI -32 eliminates the
CATALOG NUMBER 6175
non - mechanical thermal sensor, microprocessor based evaluating this information with sophisticated
electronics with a low- profile plastic cover and base. mathematical formulas, or algorithms, comparing this
The FP -11 utilizes state -of- the -art ASIC and surface input to characteristics of both threatening fires and
mount technology for maximum reliability. Every FP -11 deceptive phenomena that would "fool" any ordinary
fire detector is shipped with a protective dust cover. detector. This technology was developed over years of
research and reviewing the results of over 20 years of
The FP -11 fire detector utilizes an infrared light fire test data in one of the world's most advanced fire
emitting diode ( IRLED), and light sensing photodiode. research centers. The results of this research are the
Under normal conditions, light transmitted by the LED mathematical models that form the algorithms used in
is directed away from the photodiode and scattered FirePrint. No other fire detector has this level of
through the smoke chamber in a controlled pattern. intelligence or this amount of research and develop -
The smoke chamber is designed to manage light ment supporting it's design.
dissipation and extraneous reflections from dust
particles or other non -smoke airborne contaminants in The microprocessor's software can identify and
such a way as to maintain stable, consistent detector disregard false input caused by radio frequency (RFI)
operation. When smoke enters the detector chamber, and electromagnetic (EMI) interference, and validates
light emitted from the IRLED is scattered by the all trouble conditions before annunciating or reporting
smoke particles and is received by the photodiode. to the control panel. The FP -11 detector's microproces-
The sor uses an integral EEPROM to store the detector's
he FP 11 also utilizes a modern, accurate, shock-
resistant thermistor to sense temperature changes. address and other critical operating parameters which
include the assigned program values for alarm and
The "on- board" FirePrint technology allows the trouble thresholds. Communications within the
detector to gather smoke and thermal data, and to detector itself and between the FP -11 and the control
analyze this information in the detector's "neural panel, or with the FPI -32 field programmer /tester, are
network" By comparing data received with the supervised and safeguarded against disruption by
common characteristics of fires, or fire fingerprints, reliable, microprocessor based error checking routines.
the FP -11 can compare these "Fire Prints" to those of Additionally, the microprocessor supervises all
deceptive phenomena that cause other detectors to EEPROM memory locations and provides a high
alarm. The advanced FirePrint technology allows the degree of EEPROM failure fault tolerance.
FP -11 to accurately determine a true fire hazard from
a nonthreatening deceptive phenomena WITHOUT In MXL(V) applications, the FP -11 determines its
needing to use alarm delaying verification and confir- operating status to be normal, in alarm, or in trouble
mation techniques, which can increase the probability depending on the difference between the alarm
of losses due to fire. threshold values stored in the detector's memory and
the detector's latest analog measurement. The
The FP 11 provides the highest level of detector
intelligence available today with a detector /control detector then communicates changes in its status to
the control panel.
panel link that allows the user to program the detector
for the specific hazard profile Detectors are optimized In addition, the MXL(V) control panel will sample the
by selecting one of the following applications: value of the FP -11's analog signal over a period of time
in order to determine if those values indicate exces-
• Office /Retail sive buildup in the photo chamber; if so, the MXL(V)
• Lobby will indicate that the particular detector requires
• Computer Room maintenance.
• Dormitory
• Healthcare The FP -11 is listed as a self- testing device. The FP -11's
• Parking Garage visible light emitting diode (LED) flashes green every
• Utility/Transformer Room 4 seconds to indicate it is communicating with the
• Hostile Environment control panel and that it has passed its internal self-
• Precious Storage test. Should the detector sense a fault or failure within
• Air Duct its systems, the LED will flash amber and the detector
• Warehouse /Light Manufacturing will transmit that information to the control panel.
A quick visual inspection is sufficient to indicate the
The software does the rest; no guessing on detector condition of the detector at any time. If more detailed
sensitivities or alarm verification; the control panel information is required, a printed report can be
programs the FP -11 detector for the protected area provided from the MXL panel indicating the status
without hassle and without confirmation delays. and settings assigned to each individual detector.
Once optimized for the hazards in the protected area,
the FP -11 provides the best detection you can buy. When the FP -11 moves to the alarm mode, it will flash
Should the operator or installer forget to program the amber and transmit that information to the control
detector, the FP -11 will revert to a default setting that panel. When the MXL(V) confirms the detectors
allows it to operate as a standard photoelectric or condition, the panel will instruct the FP -11 to flash red
photothermal detector. and to continue flashing until the system is reset at
The FP -11's FirePrint technology monitors input from the control panel. At that same time, any user defined
both the photo chamber and the thermal sensor,
system alarm functions programmed into the system All FP -11 detectors are approved for operation within
are activated. Each FP -11 detector can operate one the UL specified temperature range of 32 to 100
remote alarm indicator, one auxiliary relay, or one degrees F (0 to 38 degrees C).
audible base.
Detector sensitivity, calibration, and identification are Application Data
dynamically supervised by the control panel. Detector Installation of the FP -11 series of fire detectors
• sensitivity and pre -alarm levels are a function of the requires a two -wire circuit of 18 AWG (minimum)
application chosen at the control panel and are thermoplastic fixture wire enclosed in conduit, or 18
controlled by the panel. If an alternate, non - FirePrint AWG limited energy, shielded cable without conduit,
mode is selected, then the sensitivity can be changed if permitted by local codes. Field wiring should
from the control panel. conform to local and National Electric Codes and the
The DPU or FPI -32 Program/Test accessory is used to control panel wiring specifications.
program and verify the detector's address. The "T- tapping" is permitted only for Style 4 (Class B)
technician selects the accessory's program mode to wiring.
enter the desired address. The DPU or FPI -32 auto-
matically sets and verifies the address and tests the FP -11 fire detectors can be applied within the maxi -
detector. It also allows the user to change the device mum 30 foot center spacing (900 sq. ft. areas) as
ID from that of an FP -11 to an older detector ID such as referenced in NFPA 72. This applications guideline is
an ILP -1, ILPT -1, ILP -2, ID -60P or ID -60PT to allow for based on ideal conditions, specifically, smooth ceiling
easy replacement of older detectors without the need surfaces, minimal air movement, and no physical
of reprogramming the control panel. obstructions between potential fire sources and the
detector. Do not mount detectors in close proximity
The FPI -32 operates on AC power or rechargeable to ventilation or heating and air conditioning outlets.
batteries, providing flexibility and convenience in Exposed joints or beamed ceilings may also affect safe
programming and testing equipment almost anywhere. spacing limitations for detectors. Should questions
When in the test mode, the DPU or FPI -32 will perform arise regarding detector placement, observe NFPA
a series of diagnostic tests without altering the 72 guidelines.
address or other stored data, allowing technicians to
determine if the detector is operating properly. Good fire protection system engineering and common
sense dictate how and when fire detectors are
The FP -11 fire detector may be installed on the same installed and used. Contact your local Siemens
initiating circuit with IL or ID series detectors (Photo- Building Technologies, Fire Safety Division authorized
electric, thermal, or ionization), MSI series manual sales outlet whenever you need assistance applying
stations, TRI series interfaces, ICP output control FirePrint in unusual applications. Be sure to follow
devices, or CZM series of addressable, conventional NFPA guidelines, UL/ULC approved installation
zone modules. instructions, which are included with every detector,
All FP -11 detectors can be cleaned in the field, when and local codes as for all fire protection equipment.
required, by simply removing the detector cover and
- unsnapping the photo chamber. There is also the Dimensions
option of cleaning the interior of the detector with a
clean, soft cloth or brush, or replacing the labyrinth and 6" Diameter Base
• bug screen included in the detector maintenance kit,
model DMK -11.
The FP -11 uses the low profile surface mounting base,
model DB -11. This base mounts on a 4 -inch octagon,
• 1 -1 3 111 !
square, or a single gang electrical box. The base 2 3"
utilizes screw clamp contacts for electrical connections Overall
and self- wiping contacts for increased reliability. The
base can be used with the optional LK -11 detector = ��'► 1
locking kit which contains 50 detector locks and an � In y � / �
installation tool, to prevent unauthorized removal of
the detector head. The DB -11 base has integral decora-
tive plugs to cover the outer mounting screw holes.
The FP -11 is electrically compatible with existing MXL
detector accessories including relays, remote lamps,
duct housings, and audible bases. With duct housings,
a base adapter and new detector housing cover are
required (order AD -11 UK upgrade kit). To use existing
DB -3S base or audible base, the FP -11 requires a DB-
ADPT base adapter.
Technical Specifications
Current Requirements: Normal 750 pa Alarm 750 pa
Operating Temperature: +32 °F (0 °C) to 100 °F (38 °C)
per UL 268/268A
Humidity: 0 -93% Relative Humidity
Non - Condensing
Ordering Information
Part
Model Description Number
FP -11 Addressable FirePrint Fire Detector 500- 095112
DB -11 Detector Mounting Base for Series 11 500- 094151
DB -11E Detector Base (Small) 500- 094151E
AD-11P Air Duct Housing for Series 11 500- 095656
AD -11XPR Air Duct Housing w /Relay for Series 11 500 - 096062
Intelligent Detector
ADBX -11 Audible Base 500- 096181
DB -X11 RS Relay Base for Series 11 Intelligent Detectors 500- 096125
RLI -1 Remote (red) alarm indicator- 4" octagon box mount 500- 390673
RLI -2 Remote (red) alarm indicator- single gang box mount 500 - 390674
LK -11 Base Locking Kit for Series 11 detectors 500 - 695350
DMK -11 Series 11 Maint Kit (replacement labyrinth and bug 500- 695338
bug screen)
AD -11 UK Air Duct Housing Cover /Adapter Kit 500 - 695967
DB -ADPT Base Adapter to DB -3S Base 500- 094187
In Canada Order:
FP -11C Addressable FirePrint Fire Detector (ULC) 500- 095112C
DB -11C Detector Mounting Base for Series 11 (ULC) 500- 095687
AD -11 PC Air Duct Housing (ULC) 500- 095984
DB -X11 RSC Relay Base for Series 11 Intelligent Detectors (ULC) 500- 096125C
ADBX -11C Audible Base for Series 11 Intelligent Detector (ULC) 500- 096181C
- I I
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 6/03 Brampton, Ontario
Siemens Building Technologies Tel: (973) 593 -2600 10M Canada L6T 5E4
g g FAX: (973) 593 -6670 SFS -IG Tel: (905) 799 -9937 June 2003
Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799 -9858 supersedes sheet dated 7ro2
SIEMENS Fire Safety
Air Duct Housings-Series 11
ENGINEER AND ARCHITECT SPECIFICATIONS
remx
• For Series 11 Detectors
• Relay Models Available
• Self contained Model available with
"On - Board" Power Supply m
• Alarm LED Visible from Front
• Clear Housing Cover for Quick
Identification of DetectorType
�
• ® Listed, ULC Listed "� T
CSFM, FM, NYMEA Approved •
b -
introduction Description
The Siemens Fire Safety air duct detector housings are The Siemens Fire Safety air duct housing is uniquely
designed to be used with the PE -11 and FP -11 detec- designed to use the photoelectric detector.
tors. Designed for installation directly to heating,
ventilating and air conditioning duct systems, they Sensitivity of PE -11 detectors can be checked by
comply with National Fire Protection Association viewing the LED or an RSAW -11 or RSAC -11 multicolor
Standard No. 90A. When equipped with photoelectric remote lamp. A green flash indicates the detector has
detectors, these units will signal the presence of passed its self test. Amber indicates a trouble condi
hazardous quantities of products of combustion or tion, and red indicates an alarm state.
smoke being carried through the duct system. Air duct FP -11 sensitivity may be viewed from the multi -color
detectors are not intended to be substituted for open LED on the detector or preferably may be printed
area detection. by command on an optional printer from the MXL
Air duct housings can be equipped with optional control panel.
relays. These relays are utilized to operate any The detector unit employs a cross - sectional sampling
supplementary equipment when smoke or parficles principle of operation. Inlet sampling tubes are avail -
of combustion are detected. able in four lengths (see table on reverse side). Outlet
Note: Most control equipment guarantee only one sampling tubes are one common length. A continuous
detector per zone when the detector operated relay cross-sectional sample of air moving through the duct
function is critical. The connection of a remote lamp is taken. This averages the effects of laminar flow,
and a remote relay per detector is allowed with PXL or stratification or skin effect phenomena occurring in the
System 3n" only, other conventional systems may use duct that could prevent combustion product or smoke
either a remote lamp or a relay. (especially in large ducts) from reaching a spot type
detector.
With the MXL series of control panels, up to 60
detectors per circuit having relays may be used. In addition, the unique design of the sampling chambe
insures uniform sensitivity in air velocities, ranging
The connection of a remote lamp or a remote relay
s allowed for each detector but not both, from a low of 300 feet per minute to as high as 4000
feet per minute.
Air duct housings (see Ordering Information) are
Underwriters Laboratories, Inc. listed.
CATALOG NUMBER 6178
Replaces Catalog Sheet Number 6177 0
The inlet sampling tube length is determined by the Dimensions
width of the air duct being protected. The inlet tube 7W 4 -
nearest to but greater than the duct width should be 19 cm ' 10.2cm
used (see table). The inlet tube can then be trimmed at H 010 3 i4 i t 4
the job site to the exact width of the duct. The outlet
sampling tube for all ducts, irrespective of width, has ��=
a fixed length of approximately 3 inches (75 cm) and is ���. Il I, '''N ReturnTube
supplied with the duct housing.
-
Duct Width Sampling Tube Model No.
I 2 Gasket
9" to 1'9" (21 cm to 51 cm) STA-2
1'9" to 3'3" (51 cm to 97.5 cm) STA-3 � 13 {e cm o �s� °Pwr "be
0 o t 3'3" to 6'3" (95.5 cm to 187.5 cm) STA -6 _� 33.2 � F,,,,,.........
6'3 "to9'9 "1187.5cmto292.5cm) STA -10
Greater than 9'9" (292.5 cm) Consult Siemens Fire Safety Duct
0 Electraai Connection
Hole for ii'
When the use of a remote relay is required, order Conduit (Both Sldesl
model AD -11 PR for conventional systems; AD-11XPR
for MXL systems. ,
SamplingTube SelectionTable
Shipping Weight
Maintenance of the detector is easily accomplished by Model Description Lb. Kg.
the removal of the Series 11 duct housing sampling
AD 11P Series and air duct dhousingwithcoverforthe
chamber cover. The detector, which plugs into the
PE -11 and FP -11 detectors 5 2.25
housing, is easily removed for cleaning by a trained AD -11 PR Series 11 air duct housing with cover for the
technician. PE -11 photoelectric detector and equipped
with remote relay 5 2.25
All that is necessary for the installation of the air duct AD -11XPR Series 11 air duct housing with civer for the
detector is the cutting of three small holes for the FP -11 detector equipped with remote relay 5 2.25 ,
sampling tube installation (template included) and the SA -11P Series 11 air duct housing with power supply
drilling of four holes for mounting the air duct housing. for self- contained unit operation for Pe -11
The unit is then easily mounted in place and connec- photoelectric detector 7 3.15
tion made to the existing wires or terminals if optional AD -11UK Upgrade kit for using PE -11 or FP -11 detector
accessories are utilized. in a series 3 duct housing 1 .45
STA -2 Sampling Tube, for ducts 9' to 1'9" 1 .45
When using the PE -11 or FP -11 detector in an AD -3l or STA -3 Sampling Tube, for ducts 1'9" to 3'3" 2 .9
AD -3ILP duct detector housing you must use the STA -6 Sampling Tube, for ducts 3'3' to 6'3" 4 1.8
AD -11 UK upgrade kit consisting of a detector base STA -10 SamplingTube, for ducts 6'3" to 9'9 ". Sampling
adapter and a new duct housing cover. Any Series 3 Tubes greater than 9'9 ", consult Siemens
accessories such as remote lamps on relays will also Fire Safety 6 3.7
have to be updated to PE -11 accessories. The FP -11 is RLC 11 Remote Alarm Lamp, ceiling mounted for PE 11 .5 .22
electrically compatible with Series 3 MXL accessories. RLW -11 Remote Alarm Lamp, wall mounted for PE -11 .5 .22
RSAC -11 RemoteTri -color LED, ceiling mounted for PE -11 .5 .22
RSAW -11 RemoteTri -color LED, wall mounted for PE -11 .5 .22 -
PE-11 Conventional Photelectric Detector 1 .45
FP -11 Intelligent FirePrintt"' Detector 1 .45
Model Description Part Number
RLI -1 Remote (red) alarm indicator -
4" octagon box mount 500 - 390673
RLI -2 Remote (red) alarm indicator -
single gang box mount 500- 390674
Note: Minimum hardware required is one Air Duct Housing Assembly, one Sampling Tube and one Detector.
NOTICE: The use of other than Siemens Fire Safety detectors and bases with Siemens Fire Safety equipment will be considered a misapplication of
Siemens Fire Safety equipment and as such voids all warranties either expressed or implied in regard to loss, damage, liabilities and /or service problems
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 4/02 Brampton, Ontario
Siemens Building Technologies Tel: 1973) 593 -2600 10M Canada L6T 5E4
g g IeS FAX: (973) 593 -6670 SFS -IG Tel: (905) 799 -9937 April 2002
Fire Safety Website: www.cerbpyro. corn Printed in U.S.A. FAX: (905) 799-9858 Supersedes iheet dated 6A1
SIEMENS Fire Safety
TRI Series
Intelligent Initiating Devices Interface Modules
for MXL Fire Detection Panels TRI- S,TRI- D,TRI -R
ENGINEER AND ARCHITECT SPECIFICATIONS
• Interfaces and Supervises Normally Open Contacts
• Integral SPDT Relay (up to 4 amps) on TRI -R Model
• Dual Input on TRI -D Model
• Multi -color L.E.D. indicates status (green, amber, red)
• Easy front access to programming port and
wiring terminals
• Mounts in 4 inch square 2 deep box, or double ? ,
gang box
• Dynamic Supervision �
��,�
DIcONN
• Comes with 5x5 inch faceplate DEVIC EADD RESS EEORE PRO T NG
• Two wire operation PE ER �pPg., INSTR
ARE POWER LIMIT e, 5
• Model DPU or FPI -32 Programs and Verifies
Device's Address and Tests Device's functionality si _ -
0
• Electronic Address Programming is Easy
and Dependable
• 0 UL Listed, ULC Listed
CFSM, FM, NYMEA Approved
Introduction module reports the contact's status to the control
The TRI Series Intelligent interface modules are panel. The TRI -S model can only monitor and report the
designed to provide the means of interfacing direct status of the contact, while the TRI -R incorporates an
shorting devices to the MXL system's ALD loop addressable Form C relay. The TRI -R relay and contact
circuit. device input are controlled at the same address. For
the MXL system, the relay and input contact can be
The TRI Series Intelligent interface modules provide controlled as a separate function. The relay is typically
the market's most advanced method of address used where control or shunting of external equipment
programming and supervision, combined with sophis- is required.
ticated control panel communication. Each TRI Series
interface module incorporates a microcomputer chip. The TRI -D is a dual input module and is designed to
The TRI Series microcomputer chip technology and its supervise and monitor two sets of dry contacts. This
sophisticated bi- directional communication capabilities interface module requires two address settings. The
with the control panel, achieve the state of an "Intelli- TRI -D is ideal for monitoring a waterflow switch and its
gent Device." respective valve tamper switch.
The TRI has a multi -color Light Emitting Diode that
Description flashes green when operating normally, amber if unit
The TRI Series Intelligent interface modules are avail-
able in three models. The TRI -S and TRI -R are designed
to monitor a normally open dry contact. The interface
CATALOG NUMBER 6179
is in trouble condition, and red to indicate a change of Mounting Data
state. The TRI -D flashes twice, once for each address, Addressable interface Model TRI S, TRI D, TRI -R
the TRI -R red L.E.D. indicates a change of state in mounts directly into a 4 inch square 21/4 deep box
the relay.
or a double gang box (user supplied). A 5 inch square
The device's microcomputer chip has the capacity of off -white faceplate is included with each TRI.
storing, in memory, identification information as well
as important operating status information. MOUNTING SLOTS _
FOR 4 INCH
Siemens Building Technologies, Fire Safety Division SWITCHBOX
innovative technology allows all TRI Series intelligent
interface modules to be programmed by using the
model DPU or FPI -32 Programmer/Tester. The Pro- . / 0 0
grammer/Tester is a compact, portable, menu driven
accessory that makes programming and testing an ( =_] TRI- S / -D / -R
interface device faster, easier and more dependable I I 10 0 MODULE
p
than previous methods. [_'7 .,, 0
The DPU or FPI -32 eliminates the need for mechanical - 1 _ MOUNTING rei addressing mechanisms, such as program jumpers, HOLES FOR
DIP switches or rotary dials, because the Programmer/ lij SWITCHPLATE
Tester electronically sets the TRI interface's address
into the interface's microcomputer chip nonvolatile 0
memory. Vibration, corrosion and other conditions that
deteriorate mechanical addressing mechanisms are no
longer a cause for concern.
MOUNTING SLOTS
The TRI Series is fitted with screw terminals for FOR DOUBLEGANG
connection to an addressable circuit. SWITCHBOX
The TRI Series is fully compatible on the same MXL Figure A
circuit with all intelligent FF IL and ID -60 Series Mounting the TRI- S / -R / -D
detectors, MSI Series addressable manual stations
or any other addressable intelligent modules, such
as the CZM or ICP. Electrical Ratings
All TRI Series intelligent interface modules are Current Draw (Active or Standby): 1.5mA
UL listed.
TRI-R
Environmental operating conditions for all TRI Series Relay R 1 25s
R
modules are 32 °F ( °C) to 120 °F (49 °C) with a relative Ressi stive: 4A, 1 VAC
4A, 3 VDC
0
humidity of not greater than 93% non - condensating.
Inductive: 3.5A, 120 VAC (0.6P.F.) .
Ordering Information 3.0A, 30 VDC (0.6P.F.)
2.0A, 120 VAC (0.4P.F.)
Shipping Wt. 2.OA, 120 VAC (0.35P.F.)
Model Description Lb. Kg. 2.OA, 30 VDC (0.35P.F.)
TRI -S Single Input 7 oz. 2
TRI -R Single Input w/Relay 7 oz. 2
TRI -D Dual Input 7 oz. 2
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 7/03 Brampton, Ontario
Siemens Building Technologies Tel: (973) 593 -2600 5M Canada L6T 5E4
g g FAX: (9731 593 -6670 SFS-IG Tel: (905) 799 -9937 July 2003
Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: (905) 799 -9858 Supersedes sheet dated 1/03
wheelock INC. Series E50 Speakers &
Helping People Take Actions"' Speaker Strobes
Description:
Series E50 Speakers & Speaker Strobes are designed for high
efficiency sound output with field selectable input voltage
(25/70 VRMS) and field selectable taps from 1/8 to 2 watts.
They are also designed to provide a sleek, aesthetic
appearance for emergency voice /alarm communication I ';
systems.
Strobe Options:
Single Candela Wall: 1575 cd N
Multi Candela Field Selectable Wall: 15/30/75/110 cd E
•
or 135/185 cd
Features: Series E50 Series E50
• Mountto 4" square x 2-1 /8" deep backboxw•Ith no extension Speaker Strobe Speaker
ring required
• High efficiency design for maximum output at minimum
wattage across a listed frequency range of400 to 4000 Hz
• Strobes may be synchronized with Wheelock SM, DSM
Sync Modules or PS- 12/24 -8CP and PS- 12/24 -8MP Power
Supplies with built -in sync protocol
Specification and Ordering Information Note: Available October 2004
Order Wall Ceiling Strobe Grill Flush Mount Surface Agency Approvals
Model Code Mount Mount Candela Color Backbox Mount Mounting Options
Backbox UL MEA CSFM FM BFP
E50-W 0223 X X - White 4' x 4" x 2 -1/8" E5OSB -W E,O,P,Q,R,U,Y,AA * * * * *
E50- 241575W -FW 0225 X - 15 (75 on Axis) White 4' x 4" x 2 -118" E50-SSB-W E,Q,U,BB * * * * *
E50- 24MCW -FW 0227 X - 15/30/75/110 White 4' x 4" x 2 -1/8" E50 -SSB -W E,Q,U,BB * * * * *
E50- 24MCWH -FW 0229 X - 135/185 White 4' x 4" x 2 -1/8" E50 -SSB -W E,Q,U,BB * * * * *
#See mounting options
pull out guide in the last
section of this binder.
Average RMS Current X = Approved
= Pending
E50 E50 Strobe Current - Wall Mount
Speaker 241575W 24MCW 24MCWH * RMS current ratings are per UL average RMS method. UL max
Strobes - current rating is the maximum RMS current within the listed
1575cd 15cd 30cd 75cd 110cd 135cd 185cd voltage range (16 -33v for 24v units). For strobes the UL max
current is usually at the minimum listed voltage (16v for 24v
24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 units). For audibles the max current is usually at the maximum
listed voltage (33v for 24v units). For unfiltered FWR ratings,
UL max* 0.090 0.060 0.092 i 0.165 0.220 0.300 .0420 see installation instructions.
08/04
''0 .•00 631 2148 •www 2 -
wheeJoCk INC. Series RSS Strobes &
Helping People Take Actions"" Series RSSP Strobe
Description: Plate Appliances
Wheelock Series RSS Strobes provide a wide range of intensities
and mounting options for wall or ceiling applications.
Series RSSP Single & Multi- Candela Strobe Plates are designed
for retrofitting existing audible notification appliances to strobe II
applications.
• FIRE
Strobe Options:
Single Candela: 1575 cd (wall), 75 cd (weatherproof) -z1
Multi Candela Field Selectable Wall: 15/30/75/110 cd or 135/185 cd
Ceiling: 1 5/30/75/95 cd or 115/177 cd FIRE FIRE
Features: -
• Patented Universal Mounting Plate Series RSS F tR
• Low current draw to reduce power consumption and wiring costs
• Strobes produce 1 flash per second over the regulated voltage range Series RSSP
• Synchronize with Wheelock's SN\ DSM Sync Modules or PS- 12/24 -8CP
and PS- 12/24 -8MP Power Supplies with built -in sync protocol
Specification and Ordering Information
Model Model Agency Approvals I
Order Wall Ceiling Strobe 24 12 Square or
Model Number Code Mount Mount Candela VDC VDC Color Color Mounting Options# Round
Red White UL MEA CSFM FM BFP
;RSS 24MCW FR 9400 X 15/30/75/110 X - X B D E FG;H Squa .
RSS - 24MCW - FW 9401 X - 15: 3C 75,n0 X - X B,D,E,F,G,H,J,N,O,P,R,X Square X X X X X
RSS- 241'575W -FR 7471 X '15(75onAxis) X - X ' - --'''''.'" P,R, q ,3 X -
RSS- 241575W -F';^, 778E X - ' X - - X B. D, E. F,OH,J.N,O.P.R.X Square X X X X X
r.. 75WFR: 7476 X -. 15(75on B
Axis) - X X - DE,FaHJNOP,R,X ,,Sq,, - ,t,, - M "-.44
RSS 121575W - FW 7468 X - 15 (75 on Axis) - 0 - ',: B,D,E,FAH,J,N,O,P,R,X Square X X X X X
,RSS 24MCC - FW 3158 - X 15130/75/95 X - - X B,D E,F,G,H,J,N,O,P,R,X Square X X X X *
RSS - 24MCCR - FW 3'59 - X 15/3C/75/95 X - X B,D,E,F,G,H,J,N,O,P,R,X Round X X X X *
RSS 24MCCR - FW 3461 - X 115/177 X - - X B,D,EF,OHJ,N,O,P,R,X Square X X X * *
RSS 24MCCHR - FW 3453 X '15!177 0 - X B,D,E,F,CGH,J,N,O,P,R,X Round X X r: *
RSS- 24MCWH -FR 3465 X 135/185 X X B,D E,F,OH,J,N,O,P,R,X Square X X X * *
RSSWP -2 5W -FR 9, ^,13 X 8 ,F X x BD _E_F,OHJ.N C P,R X Square X X X *
_ 180 @ 77 °F
RSSWP- 2475W -FW 3034 X - 75 @ -3 "F X - X T (Outdoor) Square X X X X
m ?
RSSP -12' e7J -'r F. - 79E X - 5 ; nexs x X __ _c..ae r X X X --
c
SP7241y ,, 9402 X - 15.3075/110 X - X E Z Square X X X ':: A da
RSSP- 241575W -FR __ t. - -, on .1x s x 5 Z o..:uar X X X X
9482 0 135/185 X X B,D,E,F,G,HJ,N * .O,P,R,X Square X X X =
#See mounting options pull out guide in the last section of this binder.
Average RMS Current X = Approved "= Pending
RSS/RSSP RSS/RSSP - Wall Mount RSS - Ceiling Mount
24VDC 241575W 24MCW 24MCWH 24MCC 1 24MCCH
Models -
1575cd 15cd 30cd 75cd ' 110cd 135cd 185cd 15cd 30cd 75cd 95cd i 115cd 177cd
24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270
UL max* 0.090 0.060 i 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420
RSSIRSSP RSSIRSSP
*RMS current ratings are per UL average RMS method. UL max current rating is the maximum
24VDC Wall Mount RMS current within the listed voltage range (16 -33v for 24v units). For strobes the UL max
Models 121575W current is usually at the minimum listed voltage (16v for 24v units). For audibles the max
current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR
12 vdc 0.152 ratings, see installation instructions.
UL max" i 0.255
- 08/04
273 Bran Avenue • Long Branch. NJ 07740' • (800 831-1 - wMV.wheelockinc'co 1 -
SIEMENS Fire Safety
Air Duct Housings-Series 11
ENGINEER AND ARCHITECT SPECIFICATIONS
• For Series 11 Detectors ----
• Relay Models Available
•
• Self contained Model available with
On - Board" Power Supply •
• Alarm LED Visible from Front
• Clear Housing Cover for Quick's'
Identification of DetectorType
•
ao uP
• Listed, ULC Listed
W CSFM, FM, NYMEA Approved Q�:::;� -_�__ /
" •%
introduction Description
The Siemens Fire Safety air duct detector housings are The Siemens Fire Safety air duct housing is uniquely
designed to be used with the PE -11 and FP -11 detec- designed to use the photoelectric detector.
tors. Designed for installation directly to heating,
ventilating and air conditioning duct systems, they Sensitivity of PE -11 detectors can be checked by
comply with National Fire Protection Association viewing the LED or an RSAW -11 or RSAC -11 multicolor
Standard No. 90A. When equipped with photoelectric remote lamp. A green flash indicates the detector has
detectors, these units will signal the presence of passed its self test. Amber indicates a trouble condi-
hazardous quantities of products of combustion or tion, and red indicates an alarm state.
smoke being carried through the duct system. Air duct FP -11 sensitivity may be viewed from the multi -color
detectors are not intended to be substituted for open LED on the detector or preferably may be printed
area detection. by command on an optional printer from the MXL
Air duct housings can be equipped with optional control panel.
relays. These relays are utilized to operate any The detector unit employs a cross - sectional sampling
supplementary equipment when smoke or particles principle of operation. Inlet sampling tubes are avail -
of combustion are detected. able in four lengths (see table on reverse side). Outlet
Note: Most control equipment guarantee only one sampling tubes are one common length. A continuous
detector per zone when the detector operated relay cross-sectional sample of air moving through the duct
function is critical. The connection of a remote lamp is taken. This averages the effects of laminar flow,
and a remote relay per detector is allowed with PXL or stratification or skin effect phenomena occurring in the
System 3TM' only, other conventional systems may use duct that could prevent combustion product or smoke
either a remote lamp or a relay. (especially in large ducts) from reaching a spot type
detector.
With the MXL series of control panels, up to 60
detectors per circuit having relays may be used. In addition, the unique design of the sampling chambe
insures uniform sensitivity in air velocities, ranging
The connection of a remote lamp or a remote relay
s allowed for each detector but not both. from a low of 300 feet per minute to as high as 4000
feet per minute.
Air duct housings (see Ordering Information) are
Underwriters Laboratories, Inc. listed.
CATALOG NUMBER 6178
Replaces Catalog Sheet Number 6177
The inlet sampling tube length is determined by the Dimensions
width of the air duct being protected. The inlet tube 7 . 4 .
nearest to but greater than the duct width should be 19 cm - X 10.2 cm
used (see table). The inlet tube can then be trimmed at x,i4i3;
the job site to the exact width of the duct. The outlet
sampling tube for all ducts, irrespective of width, has r_ •.— , _
a fixed length of approximately 3 inches (75 cm) and is .J. ' \ Return Tube
supplied with the duct housing.
it
h Gpsker "
Duct Width Sampling Tube Model No.
9" to 1'9' (21 cm to 51 cm) STA -2 •
Ali 1
c
1'9"to3'3 (51 cm to 97.5 cm) STA-3 �a.2 `
3'3'to 6'3' (95.5 cm to 187.5 cm) STA -6 `� _ --, Supply Tube
6'3' to 9'9" (187.5 cm to 292.5 cm) STA -10
Greater than 9'9' (292.5 cm) Consult Siemens Fire Safety Duct
0 Electrical Connector
Hole for ii'
When the use of a remote relay is required, order Conduit (Both Sides)
model AD -11 PR for conventional systems; AD-11XPR
for MXL systems.
SamplingTube SelectionTable
Shipping Weight
Maintenance of the detector is easily accomplished by Model Description Lb. Kg.
the removal of the Series 11 duct housing sampling
AD 11P Series and air 11 detectors to with cover for the
chamber cover. The detector, which plugs into the
PE -11 and FP -11 detectors 5 2.25
housing, is easily removed for cleaning by a trained AD -11PR Series 11 air duct housing with cover for the
technician. PE -11 photoelectric detector and equipped
with remote relay 5 2.25
All that is necessary for the installation of the air duct AD -11XPR Series 11 air duct housing with civer for the
detector is the cutting of three small holes for the FP -11 detector equipped with remote relay 5 2.25
sampling tube installation (template included) and the SA -11P Series 11 air duct housing with power supply
drilling of four holes for mounting the air duct housing. for self-contained unit operation for Pe -11
The unit is then easily mounted in place and connec- photoelectric detector 7 3.15
tion made to the existing wires or terminals if optional AD -11UK Upgrade kit for using PE -11 or FP -11 detector
accessories are utilized. in a series 3 duct housing 1 45
STA -2 Sampling Tube, for ducts 9" to 1'9" 1 .45
When using the PE -11 or FP -11 detector in an AD -31 or STA -3 Sampling Tube, for ducts 1'9" to 3'3" 2 .9
AD -3ILP duct detector housing you must use the STA -6 Sampling Tube, for ducts 3'3" to 6'3" 4 1.8
AD -11 UK upgrade kit consisting of a detector base STA -10 Sampling Tube, for ducts 6'3" to 9'9 ". Sampling
adapter and a new duct housing cover. Any Series 3 Tubes greater than 9'9 ", consult Siemens
accessories such as remote lamps on relays will also Fire Safety 6 3 "
have to be updated to PE -11 accessories. The FP -11 is RLC 11 Remote Alarm Lamp, ceiling mounted for PE 11 .5 .22
electrically compatible with Series 3 MXL accessories. RLW-11 Remote Alarm Lamp, wall mounted for PE 11 .5 .22
RSAC -11 RemoteTri -color LED, ceiling mounted for PE -11 .5 .22
RSAW -11 Remote Tri-color LED, wall mounted for PE -11 .5 .22 -
PE-11 Conventional Photelectric Detector 1 .45
FP -11 Intelligent FirePrintTMf Detector 1 .45
Model Description Part Number
RLI -1 Remote (red) alarm indicator -
4" octagon box mount 500 - 390673
RLI -2 Remote (red) alarm indicator -
single gang box mount 500- 390674
Note: Minimum hardware required is one Air Duct Housing Assembly, one Sampling Tube and one Detector.
NOTICE: The use of other than Siemens Fire Safety detectors and bases with Siemens Fire Safety equipment will be considered a misapplication of
Siemens Fire Safety equipment and as such voids all warranties either expressed or implied in regard to loss, damage, liabilities and/or service problems
Fire Safety Fire Safety
B Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 4/02 Brampton, Ontario
Siemens Building Technologies Tel: (973) 593-2600 10M Canada L6T 5E4
g g IeS FAX: 1973) 593 -6670 . SFS -IG Tel: (905) 799-9937 April 2002
Fire Safety Website: www.cerbpyro. corn Printed in U.S.A. FAX: (905) 799 -9858 Supersede. sheet dared 6411
SIEMENS Fire Safety
TRI Series
Intelligent Initiating Devices Interface Modules
for MXL Fire Detection Panels TRI- S,TRI- D,TRI -R
ENGINEER AND ARCHITECT SPECIFICATIONS
• Interfaces and Supervises Normally Open Contacts
• Integral SPDT Relay (up to 4 amps) on TRI -R Model
• Dual Input on TRI -D Model
• Multi -color L.E.D. indicates status (green, amber, red)
• Easy front access to programming port and
wiring terminals
• Mounts in 4 inch square 2� /a deep box, or double
gang box t,
• Dynamic Supervision �� ,
DI ECG 1
• Comes with 5x5 inch faceplate DEvic 4.E RATER
REFER TO INRESS: MIN I
• Two wire operation T RMINg2 INS
ARE P � � •2, q 7 {
• Model DPU or FPI -32 Programs and Verifies RUMI
Device's Address and Tests Device's functionality *�a z - I
• Electronic Address Programming is Easy
and Dependable
• ® UL Listed, ULC Listed
CFSM, FM, NYMEA Approved
Introduction module reports the contact's status to the control
The TRI Series Intelligent interface modules are panel. The TRI -S model can only monitor and report the
designed to provide the means of interfacing direct status of the contact, while the TRI -R incorporates an
shorting devices to the MXL system's ALD loop addressable Form C relay. The TRI -R relay and contact
circuit. device input are controlled at the same address. For
the MXL system, the relay and input contact can be
The TRI Series Intelligent interface modules provide controlled as a separate function. The relay is typically
the market's most advanced method of address used where control or shunting of external equipment
programming and supervision, combined with sophis- is required.
ticated control panel communication. Each TRI Series
interface module incorporates a microcomputer chip. The TRI -D is a dual input module and is designed to
The TRI Series microcomputer chip technology and its supervise and monitor two sets of dry contacts. This
sophisticated bi- directional communication capabilities interface module requires two address settings. The
with the control panel, achieve the state of an "Intelli- TRI -D is ideal for monitoring a waterflow switch and its
gent Device." respective valve tamper switch.
The TRI has a multi -color Light Emitting Diode that
Description flashes green when operating normally, amber if unit
The TRI Series Intelligent interface modules are avail-
able in three models. The TRI -S and TRI -R are designed
to monitor a normally open dry contact. The interface
CATALOG NUMBER 6179
is in trouble condition, and red to indicate a change of Mounting Data
state. The TRI -D flashes twice, once for each address, Addressable interface Model TRI S, TRI -D, TRI -R
the TRI R red L.E.D. indicates a change of state in mounts directly into a 4 inch square 2 deep box
the relay. or a double gang box (user supplied). A 5 inch square
The device's microcomputer chip has the capacity of off -white faceplate is included with each TRI.
storing, in memory, identification information as well
as important operating status information. MOUNTING SLOTS _
FOR 4 INCH
Siemens Building Technologies, Fire Safety Division SWITCHBOX
innovative technology allows all TRI Series intelligent
interface modules to be programmed by usiitg the
model DPU or FPI -32 Programmer/Tester. The Pro- C,
grammer/Tester is a compact, portable, menu driven
accessory that makes programming and testing an [ =_) I TRI- S / -D / -R
interface device faster, easier and more dependable (=_> �- O I MODULE
tell previous methods. [_ .,,
The DPU or FPI -32 eliminates the need for mechanical DI = MOUNTING
MI 11 r
addressing mechanisms, such as program jumpers, HOLES FOR
DIP switches or rotary dials, because the Programmer/ ib SWITCHPLATE
Tester electronically sets the TRI interface's address
into the interface's microcomputer chip nonvolatile 0
memory. Vibration, corrosion and other conditions that
deteriorate mechanical addressing mechanisms are no
longer a cause for concern.
MOUNTING SLOTS
The TRI Series is fitted with screw terminals for FOR DOUBLEGANG
connection to an addressable circuit. SWITCHBOX
The TRI Series is fully compatible on the same MXL Figure A
circuit with all intelligent FP IL and ID -60 Series Mounting the TRI- S / -R / -D
detectors, MSI Series addressable manual stations
or any other addressable intelligent modules, such
as the CZM or ICP Electrical Ratings
All TRI Series intelligent interface modules are Current Draw (Active or Standby): 1.5mA
UL listed.
Environmental operating conditions for all TRI Series es i Relay R 1 25s
R
modules are 32 °F ( °C) to 120 °F (49 °C) with a relative Resistive: 4A, 1 VAC
humidity of not greater than 93% non - condensating. 4A, 30 VDC
Inductive: 3.5A, 120 VAC (0.6P.F.) _
Ordering Information 3.0A, 30 VDC (0.6P.F.)
2.OA, 120 VAC (0.4P.F.)
Shipping Wt. 2.0A, 120 VAC (0.35PF.)
Model Description Lb. Kg. 2.OA, 30 VDC (0.35P.E)
TRI -S Single Input 7 oz. 2
TRI -R Single Input w/Relay 7 oz. 2
TRI -D Dual Input 7 oz. 2
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 7/03 Brampton, Ontario
Siemens Building Technologies Tel: (973) 593 -2600 5M Canada L6T 5E4
g g IeS FAX: (973) 593 -6670 SFS-IG Tel: 1905) 799 -9937 July 2003
Fire Safety Website: www.sbt.siemens.com /fis Printed in U.S.A. FAX: 1905) 799 -9858 supersedessneetdatedUO3
wheeloc k ,Nc, Series E50 Speakers &
Helping People Take Actions"' Speaker Strobes
Description:
Series E50 Speakers 8 Speaker Strobes are designed for high
efficiency sound output with field selectable input voltage
(25/70 VRMS) and field selectable taps from 1/8 to 2 watts.
They are also designed to provide a sleek, aesthetic
appearance for emergency voice /alarm communication
t
Strobe Options: F
Single Candela Wall: 1575 cd
Multi Candela Field Selectable Wall: 15/30/75/110 cd , E
or 135/185 cd
Features: Series E50 Series E50
• Mount to 4" square x2-1/8" deep backboxwith no extension Speaker Strobe Speaker
ring required
• High efficiency design for maximum output at minimum
wattage across a listed frequency range of400 to 4000 Hz
• Strobes may be synchronized with Wheelock's SNP, DSM
Sync Modules or PS- 12/24 -8CP and PS- 12/24 -8MP Power
Supplies with built -in sync protocol
Specification and Ordering Information Note: Available October 2004
Order Wall Ceiling Strobe Grill Flush Mount Surface Agency Approvals
Model Code Mount Mount Candela Color Backbox Mount Mounting Options
Backbox UL MEA CSFM FM BFP
E50-W 0223 X X - White 4' x 4" x 2 -118" E5OSB -W E,O,P,Q,R,U,Y,AA * * * * *
E50- 241575W -FW 0225 X - 15 (75 on Axis) White 4' x 4" x 2 -1/8" E50 -SSB -W E,Q,U,BB * * * * *
E50- 24MCW -FW 0227 X - 15/30/75/110 White 4' x 4" x 2 -1/8" E50 -SSB -W E,Q,U,BB * * * * *
E50- 24MCWH -FW 0229 X - 135/185 White 4' x 4" x 2 -1/8" E50 -SSB -W E,Q,U,BB * * * * *
#See mounting options
pull out guide in the last
section of this binder.
e RMS Current X = Approved
Average *= Pending
E50 E50 Strobe Current - Wall Mount
Speaker 241575W 24MCW 24MCWH • RMS current ratings are per UL average RMS method. UL max
current rating is the maximum RMS current within the listed
Strobes 1575cd 15cd 30cd 75cd 110cd 135cd 185cd voltage range (16 -33v for 24v units). For strobes the UL max
current is usually at the minimum listed voltage (16v for 24v
24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 units). For audibles the max current is usually at the maximum
listed voltage (33v for 24v units). For unfiltered FWR ratings,
UL max* 0.090 0.060 0.092 0.165 0.220 0.300 .0420 see installation instructions.
08/04
2 -0
wheeiOGk INC. Series RSS Strobes &
Helping People Take Action Series RSSP Strobe
Description: Plate Appliances
Wheelock Series RSS Strobes provide a wide range of intensities
and mounting options for wall or ceiling applications.
• Series RSSP Single & Multi- Candela Strobe Plates are designed
for retrofitting existing audible notification appliances to strobe ip applications. FIR E
Strobe Options:
Single Candela: 1575 cd (wall), 75 cd (weatherproofl
Multi Candela Field Selectable Wall: 15/30/75/110 cd or 135/185 cd FI
Ceiling: 15/30/75/95 cd or 115/177 cd FIR E
} li
Features:
• Patented Universal Mounting Plate Series RSS FIR E-
• Low current draw to reduce power consumption and wiring costs
• Strobes produce 1 flash per second over the regulated voltage range Series RSSP
• Synchronize with Wheelockt SN\ DSM Sync Modules or PS- 12/24 -8CP
and PS- 12/24 -8MP Power Supplies with built -in sync protocol
Specification and Ordering Information
Model Model Agency Approvals
Order Wall Ceiling Strobe 24 12 Square or
Model Number Code Mount Mount Candela VDC VDC Color Color Mounting Options# Round
Red White UL MEA CSFM FM BFP
RSS - 24MCW -FW 9401 X - 15/30/751110 X - - X BA,E,F,QH,J,N,O,P,R.X Square X X X X X
RSS- 241575W-FW 7788 X - 15 (75 on /Ws) X - - X B.D.E,F.G.H,J.N,O,P,R,X Square X X X X X
ws �
RSS- 121575W -FW 7488 X 15 (75 on Ma) - X - X BA,E FG.H,J,N O P,RX Square X x X X X
RSS 24MCC - FW 3158 X 15/30/75195 X - X B D E F GH J N O P R,X Square X X
RSS 3159 - X 15/30/75/95 X - X B 0 E FGH J N O,P-R,X Round X X X X *
RSS - 24MCCH -FW 3461 - X 115/177 X - - X B,D,E,F,G,H,J,N C P,R,X Square X X X * *
RSS- 24MCCHR -FW 34 - X '15 17- x - - X B 0 E,F,GH J N.O,P,R,X Round X , X * *
RSS- 24MCWH -FR 3465 X 135/185 X X B D E F,G,f J N O P R,X Square X X X * * ■
- »:z �ssr.. -.. :.� „:.. -: .. ° . te e. -. y_ �- � . _..v... - -_.
RSSWP 2475bro - FR X - 75 31 ° F X - X - B,D,E.F. U,N,O.P,RX Square X X X X *
RSS 3034 X - ` -- - - 1 - ""'' -
o
75 @ - 3 1 ° F
i
RSSP-121575 \A -P. - 798 X - 15 ?5 en ■xa - X X E,Z Squats X X X X X - i
RSSP - 24MCW -FR 9402 X - 15/3075/110 X - X - i
RSSP -24 75sv - '9 X 5 on Ax s x E Square X X X X X
v
P-24MCWH-FR 9482 X 135/185 X X B.D.E,F,G,H J N O P R, ' ; ? `, -
a .mow_
#See mounting options pull out guide in the last section of this binder.
Average RMS Current X = Approved *= Pending
RSS/RSSP - Wall Mount RSS - Ceiling Mount
RSSIRSSP
24VDC 241575W 24MCW 24MCWH 24MCC 24MCCH
Models
1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 1 30cd 75cd 95cd 115cd 177cd
24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270
UL max* 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420
RSS /RSSP RSSIRSSP * RMS current ratings are per UL average RMS method. UL max current rating is the maximum
24VDC Wall Mount
RMS current within the listed voltage range (16 -33v for 24v units). For strobes the UL max
Models 121575W current is usually at the minimum listed voltage (16v for 24v units). For audibles the max
current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR
12 vdc 0.152 ratings, see installation instructions.
UL max* 0.255
08/04
i� m ft F
273 BrcanchportAvenue • Long Branch, NJ 07740 • (800)G31- 2148'`• "w+niw.w oelockinc.cc 1 -7
FIRE SYSTEM FUNCTION MATRIX SIEMENS
Washington Square Revision: 0
Williams Sonoma
258070
SYSTEM RESPONSE
a)
U
Co @
Cl
_o U)
2 C -a)
( Co c
c @
D a) a) c-
co c Co o F
T @ a io
U)) v, a E Q
Co = E @ 2
a) D @ Q LL
0) a, Q a) >,
a) c
iL
c N LL > )
v a` m
v
5
= m C ,R Cr) m o a m o a a o
-J Q ° 0 2 o Z
a) 3 0 0 a) o a
o
> o a) E -9 a E D a
INITIATION DEVICE ACTIVATED L @ @ o @ o a
Q cn � Q 1— ) rn Q 1— cn
Area Smoke /Heat Detector X X X
Air Handler Duct Smoke Detector X X X _ X
Waterflow Switch X X X
Valve Tamper Switch X X
Fire System Trouble X X
PROPRIETARY DOCUMENT FOR APPROVAL ONLY 1 9/13/2005
BATTERY SIZING CALCULATIONS SIEMENS
Washington Square
. Williams Sonoma
Panel Name: FAPS -1
Battery Size: 7 amp -hr
Requirement for standby current: 24 hrs. Design Supervison Current = 1.44 amp -hr
Requirement for alarm current: 15 min. Design Alarm Current = 0.40 amp -hr
Spare Battery Capacity: 25 % Additional Capacity Current = 0.46 amp -hr
Initiating Devices Assumed In Alarm: 10 % Battery AH requirement = 2.29 amp -hr
PANEL EQUIPMENT
Standby Alarm TOTAL TOTAL
(ma) (ma) (ma) (ma)
Quantity Device Current Current Standby Current Alarm Current
1 Model PS- 12/24 -8MP 60 150 60 150
PANEL TOTALS 60 150
2 15cd STROBE 50 100
30cd STROBE 81 0
75cd STROBE 133 _ 0
110cd STROBE 161 0
15cd SPKR /STROBE 47 47
30cd SPKR /STROBE 81 0
75cd SPKR /STROBE 130 f_;tirfr 260
110cd SPKR /STROBE 171 ;ti: r t .... 1026
f ...ti ?.._ ....... 0
FIELD TOTALS 0 1433
Standby Alarm
I GRAND TOTALS (field & panel) I 60 I 1583 I
Formula: [(A + B) x C] + [(D + E) x F] x G = Minimum Amp -Hour Battery Capacity
Where:A = Internal panel standby current {amps }.
B = External device standby current {amps }.
C = Duration panel must remain operational {hours }.
E = External device alarm current {amps }.
F = Duration panel must remain in alarm after standby period ends {hours }.
G = Spare battery capacity {percentage }.
PROPRIETARY DOCUMENT FOR APPROVAL ONLY 9/13/2005
IAC CIRCUIT CALCULATIONS SIEMENS
Washington Square
Williams Sonoma
258070
w w CO - m
`o
u _ d N m a . r. 0 3
e e
J a a, c . y W L q c m C O 0 a . e H .S u Q, a s a �n w y h Y h y e o m q t= a
z a N C O� 51 e C O ` . O O ' � . 92 Y d Y Y Q m O , j O -6 ti J J y en
a U 0 y y . CX J O y ( I5 y v, CO y b co CO y h y h D 3 a U 0 0) a O ? J _.I U
v a, :a m D Q) D c;, b y v y D 1'j: D d v y O O is a C ti .- « at
o m ` d 9 op o v ry o r . b °y h °n c h ` , ° v 4 i O c o am e a O o 0
a. �, 3 &" 9_ ti ti� �w �, a �� _. w �,� r�cq a ..w o n ti > ao 0 ti r- a,
LxR Rx2 15 • 75 110 15 30 75 110 DH AUX #xI IxR 24 -VD
FAPS -4 N4 -1 150 14 0.0026 0.39 0.78 0 0 0 0 3 0 0 0.55 0.43 23.57 1.8% 18.3%
N4 -2 305 14 0 0026 0.79 1.59 2 0 0 0 1 0 2 3 0 0 1.03 1.63 22.37 6.8% 34.2%
N4 -3 Spare 0 14 0.0026 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0.00 0.00 24.00 0.0% 0.0%
N4 -4 Spare 0 14 0.0026 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0.00 0.00 24.00 0.0% 0.0% 19.7% 1.58 AMPS
2 1 2 6
Enter Power Supply Capacity 8.0 AMPS Capacity Per Output 1 3.0 AMPS
Enter Strobe Wire Size 14 Gua.e
1 5cd Strobe RSS Series 050 RSS - 24MCW -FW Multi - Candela Strobes
30cd Strobe RSS Series .081
75cd Strobe RSS Series .133
110cd Strobe RSS Series .161 @
15cd Spkr /Strobe E50 Series .072 20.4 E50- 24MCW -FW Multi - Candela Speaker /Strobe
30cd Spkr /Strobe E50 Series .094 VDC
75cd Spkr /Strobe E50 Series .153
110cd Spkr /Strobe E50 Series .183
DOORHOLDER .096 150X OR EQUIVELANT (Supplied by Others)
24VDC RISER (AMPS) .000
Enter 24VDC Riser Wire Size 14 Guage
PROPRIETARY DOCUMENT FOR APPROVAL ONLY 9/13/2006