Correspondence September 7, 2005 1 I'I
CITY OF TIGARD
OREGON
Godiva Chocolatier
Denise Buehring
111 W Washington St -Ste 450
Chicago, IL 60602
RE: GODIVA CHOCOLATIER - TI REVIEW
Project Information
Building Permit: BUP2005-00379 Construction Type: II-B
Tenant Name: Godiva Chocolatier Occupancy Type: M
Address: 9360 SW Washington Sq. Occupant Load: 28
Area: 832 sq ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
edition; and 2003 International Fire Code as amended by TVF &IZ The submitted plans are
approved subject to the following conditions.
1. Horizontal sliding security grilles shall be openable from the inside without the use of a key or
special knowledge or effort during periods that the space is occupied. The grilles shall remain
secured in the full -open position during the period of occupancy by the general public.
402.11 OSSC
2. Exits and exit access doors shall be marked by an approved exit sign readily visible from any
direction of egress travel. Access to exits shall be marked by readily visible exit signs in
cases where the exit or the path of egress travel is not immediately visible to the occupants.
Exit sign placement shall be such that no point in an exit access corridor is more than 100
feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit
sign. 1011.1 OSSC
3. All exit doors shall be operable from the inside without the use of a key or any special
knowledge or effort. 1008.1.8 OSSC
4. Exit signs shall be illuminated at all times and shall be provided with a second source of
power that will provide 1 'A hours of illumination in case of primary power loss. 1006.3
OSSC FYI Additional exit signs may be required by the city field inspector to clearly
indicate the path of egress.
5. Accessible checkout aisles shall be on an accessible route and at least 36 inches wide.
Counters in accessible checkout aisles shall be not more than 38 inches (965 mm) high and
the top of the raised edge of the counter shall not exceed 40 inches (1016 mm) in height
above the finished floor. Accessible checkout aisles shall be identified by the international
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
symbol of access. OSSC section 1109.19, 1109.23.3
6. American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the
structure only for compliance with Chapter 11 of the OSSC, which may not include all of the
requirements of the ADA.
NOT PART OF THIS REVIEW:
* Electrical * Fire Sprinklers
* Fire Alarms * Mechanical System
* Plumbing
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.3.1 OSSC
Certificate of Occupancy: No building or structure shall be used or occupied until the Building
Official has issued a certificate of occupancy 110.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new buildings
in such a position as to be plainly visible and legible from the street or road fronting the property.
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
Res f / •
al enzel,
Senior Plans Examiner
( j 1 r
August 16, 2005
• CITY OF TIGARD
OREGON
Godiva Chocolatier
Denise Buehring
111 W Washington St -Ste 450
Chicago, IL 60602
RE: GODIVA CHOCOLATIER - TI REVIEW
Project Information
Building Permit: BUP2005 -00379 Construction Type: II -B
Tenant Name: Godiva Chocolatier Occupancy Type: M
Address: 9360 SW Washington Sq. Occupant Load: 28
Area: 832 sq ft Stories: 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
edition; and 2003 International Fire Code as amended by TVF &R. The following information is
required in order to complete the review.
PRELIMINARY REVIEW
1. Provide framing connection details showing how walls and soffits are constructed.
2. Provide Oregon Energy Forms showing project meets OSSC Energy chapter 13.
Please provide an item by item response.
NOT PART OF THIS REVIEW:
* Electrical * Fire Sprinklers
* Fire Alarms * Mechanical System
* Plumbing
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
Res 4g,
` p�
Val Henzel,
Senior Plans Examiner