Correspondence August 4, 2005 4)
CITY OF TIGARD
OREGON
Western Construction Services Inc.
Pamela Deegan
4612 NE Minnehaha St.
Vancouver, WA 98661
RE: SHARPER IMAGE - REVIEW
Project Information
Building Permit: BUP2005 -00351 Construction Type: II-B
Tenant Name: Sharper Image Occupancy Type: M
Address: 9348 SW Washington Sq. Occupant Load: 118
Area: 4,603 sq ft Stories: 2 - located on 1
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004
l c, edition; and 2003 International Fire Code as amended by TVF &R. The submitted plans are
approved subject to the following conditions.
r.
, li
1. The main exterior door or doors are permitted to be equipped with key- operated locking
devices 'from the egress side provided:
1. The' locking device is distinguishable as locked,
2. A readily visible durable sign is posted on the egress side on or adjacent to the door
stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.
The sign shall be in letters 1 inch (25 mm) high on a contrasting background,
3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to
be used, provided that the door leaf having the automatic flush bolts has no doorknob or
surface- mounted hardware. 1008.1.8.3 OSSC
2. Exits and exit access doors shall be marked by an approved exit sign readily visible from any
direction of egress travel. Access to exits shall be marked by readily visible exit signs in
cases where the exit or the path of egress travel is not immediately visible to the occupants.
Exit sign placement shall be such that no point in an exit access corridor is more than 100
feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit
sign. 1011.1 OSSC
4. All exit doors shall be openable from the inside without the use of a key or any special
knowledge or effort. 1008.1.8 OSSC
5. Exit signs shall be illuminated at all times and shall be provided with a second source of
power that will provide 1 '/2 hours of illumination in case of primary power loss. 1006.3 OSSC
FYI Additional exit signs may be required by the city field inspector to clearly indicate the
path of egress.
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
6. The means of egress shall be provided with illumination of not less than 1 foot candle at the
floor level anytime the building is occupied. The means of egress illumination shall be
provided with a second source of power in case of primary power loss. 1006.2'OSSC
7. Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings, etc, will
be charged a deferred submittal fee based on the valuation of the portion of the work being
deferred. The minimum fee shall be $200.00.
8. NOT PART OF THIS REVIEW:
* Fire Sprinklers * Fire Alarms * Electrical
* Mechanical System * Plumbing
9. Safety glazing including but not limited to: the following locations: Each unit of glazing shall
be permanently identified by the manufacturer. 2406 OSSC. Some of these locations are as
follows:
a. Glazing in ingress and means of egress doors.
b. Glazing in an individual fixed or operable panel adjacent to a door where the nearest
vertical edge is within a 24" arc of the door in a closed position and whose bottom edge
is less than 60" above the floor or walking surface except when there is an intervening
wall or other permanent barrier between the door and the glazing.
10. American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
only for compliance with Chapter 11 of the OSSC, which may not include all of the
requirements of the ADA.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.3.1 OSSC
Certificate of Occupancy: No building or structure shall be used or occupied until the Building
Official has issued a certificate of occupancy 110.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new buildings in
such a position as to be plainly visible and legible from the street or road fronting the property.
When submitting revised drawings or additional information, please attach a copy of the enclosed
City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in
tracking and processing the documents.
Respect
al e e , c; "/
Senior Plans Examiner