Permit CITY OF TIGARD BUILDING PERMIT
PERMIT #: BUP2005 -00351
Ae■ DEVELOPMENT SERVICES DATE ISSUED: 8/10/2005
, All
13125 SW Hall Blvd., Tigard, OR 97223 503 - 639 -4171 PARCEL: 1S12600 -00300
SITE ADDRESS: 09348 SW WASHINGTON SQUARE RD ZONING: C -G
SUBDIVISION: WASHINGTON SQUARE LOT: JURISDICTION: TIG
Project Description: TI.
REISSUE:. FLOOR AREAS EXTERIOR WALL CONSTRUCTION
CLASS OF WORK: NEW FIRST: sf N: S: E: W:
TYPE OF USE: COM SECOND: sf PROJECT OPENINGS?
TYPE OF CONST: 2N : 4,603 sf N: S: E: W:
OCCUPANCY GRP: M TOTAL AREA: 4,603 sf ROOF CONST: FIRE RET?
OCCUPANCY LOAD: 118 BASEMENT: sf AREA SEP. RATED:
STOR: 1 HT: ft GARAGE: sf OCCU SEP. RATED:
BSMT ?: N MEZZ ?: N REQD SETBACKS REQUIRED
FLOOR LOAD: psf LEFT: ft RGHT: ft FIR SPKL: Y SMOK DET:Y
DWELLING UNITS: FRNT: ft REAR: ft FIR ALRM : Y HNDICP ACC:Y
BEDRMS: BATHS: IMP SURFACE: PRO CORR: U PARKING:
VALUE: $ 150,000.00
Owner: Contractor:
WASHINGTON SQUARE LLC WESTERN CONSTRUCTION SERVICES
BY THE MACERICH COMPANY 4612 NE MINNEHAHA ST
9585 SW WASHINGTON SQUARE RD PO BOX 5768
TIRoARDne: , OR 97223 VANCOUVER, WA 98668
Phone: 360- 699 -5317
FEES Reg #: LIC 63717
Description Date Amount REQUIRED ITEMS AND REPORTS
[BUPPLN] Pin Rv 7/26/2005 $610.55 r
[TAX] 8% State Surchari 8/10/2005 $75.14
[FLS] FLS Pin Rv 8/10/2005 $375.72
[BUILD] Permit Fee 8/10/2005 $939.30
(additional fees not listed here)
Total $3,020.71
This permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes
and all other applicable law. All work will be done in accordance with approved plans. This permit will expire if work is
not started within 180 days of issuance, or if work is suspended for more than 180 days. ATTENTION: Oregon law
requires you to follow the rules adopted by the Oregon Utility Notification Center. Those rules are set forth in OAR
952 - 001 -0010 through OAR 952 - 001 -0100. You may obtain a copy of these rules or direct questions to OUNC by
calling 503 - 246 -6699 or 1- 800 - 332 -2344.
Issued By: : Permittee Signature: ,
Call 503 - 639 -4175 by 7:00 a.m. for an inspection that business day.
This permit card shall be kept in a conspicuous place on the job site until completion of the project. •
Approved plans are required on the job site at the time of each inspection.
ca) Fg
Building Perm A pplication FOR OFFICE USE ONLY
City of Tigard REt_,E E Date/B 7_ _• 4 ,`1�2 Permit No: `'D
13125 SW Hall Blvd., Tigard, OR 97223 r�� Plan Date/B Review C �
Phone 503.639.4171 Fax 503.598 1960 �^* /qi� b y��l' Other Permit
Inspection Line. 503.639.4175 JUL 26 21;: Date Ready /By Ju ' El See Attached Checklist for
Internet: www.ci.tigard.or.us Notified/Method Supplemental Information
CITY OF TlGARD
TN! 1 09 1 . �
r� Y1
9 I, �' 3 ^, REQUIRED DATA: 1- AND 2- FAMILY DWELLING
❑ New construction ❑ Demolition Permit fees* are based on the value of the work performed.
Indicate the value (rounded to the nearest dollar) of all
® Addition/alteration/replacement ❑ Other: equipment, materials, labor, overhead, and the profit for the
CATEGORY OF CONSTRUCTION work indicated on this application.
❑ 1- and 2- family dwelling ® Commercial/industrial Valuation: $
❑ Accessory building ❑ Multi - family Number of bedrooms:
El Master builder ❑ Other: Number of bathrooms:
JOB SITE INFORMATION AND LOCATION Total number of floors:
Job site address: 9348 SW Washington Squae Rd., Sp. W14 - First Floor New dwelling area: square feet
City/State /ZIP: Tigard, OR 97223 Garage /carport area: square feet
Suite/bldg. /apt. no.: Project name: Sharper Image- Washington Sq. TI Covered porch area: square feet
Cross street/directions to job site: Deck area: square feet
Other structure area: square feet
REQUIRED DATA: COMMERCIAL -USE CHECKLIST
Subdivision: Lot no.: Permit fees* are based on the value of the work performed.
Indicate the value (rounded to the nearest dollar) of all
Tax map/parcel no.: equipment, matenals, labor, overhead, and the profit for the
DESCRIPTION OF WORK work indicated on this application.
New Store Tenant Improvement Valuation: $150,000.00
Existing building area: 4603 square feet
New building area: 4603 square feet
❑ PROPERTY OWNER ® TENANT Number of stories: 2
Name: The Sharper Image Type of construction: II -B
Address: 650 Davis Street, 2 Floor Occupancy groups: IN\ \1 CC
City/State /ZIP: San Francisco, CA 94111 Existing: M
Phone: (415)445 -6097 Fax: (415)445 -1537 New: M
® APPLICANT Z CONTACT PERSON NOTICE
Business name: Western Construction Services, Inc. All contractors and subcontractors are required to be .
Contact name: Pam Deegan licensed with the Oregon Construction Contractors Board
under ORS 701 and may be required to be licensed in the
Address: 4612 NE Minnehaha Street jurisdiction in which work is being performed. If the
City /State /ZIP: Vancouver, WA 98661 applicant is exempt from licensing, the following reasons
apply:
Phone: (360) 699 -5317 Fax: : (360) 694 -7818
E -mail: pam @westernconstruction.com
CONTRACTOR
Business name: Western Construction Services, Inc. BUILDING PERMIT FEES*
Address: 4612 NE Minnehaha Street
Please refer to fee schedule.
City/State /ZIP: Vancouver, WA 98661 Fees due upon application ?S--(o
Phone: (360) 699 -5317 Fax: (360) 694 -7818
CCB lic.: 63717 Amount received 6/o.,55
Date received: 1/ J- /Q5
Authonzed signature: This permit application expires if a permit is not obtained
within 180 days after it has been accepted as complete.
Print name: Pamela A. Deegan Date: 7/26/05 * Fee methodology set by Tri -County Building Industry
Service Board
i: \ Building\Permits\BUP- PemutAppdnc 12/03 440 -4613T(11 /02/COM/WEB)
93 Lt/n,)1, . S,. RI 0 a o 05 -
Form 4a Project Name: Sii i //14( 4 774A I Page: I
SYSTEMS - GENERAL Part 1 of 6
Applicability Plans /Specs ,1 �
d
Discussion of qualifying Show compliance by including a drawl r r ,E
exceptions on page 4-25 specification section and subparagrap . BB....�-
1. Applicablity (Section 1317)
Is this form required? JUL 2 F 2005
Form Required. Complete form if a new HVAC system is being Installed, or componentp f�n TIGARC
existing HVAC system are being replaced (i.e., equipment, controls, ductwork, and instil EE33 � ` U� j f I IVG DIVISIC N
❑ Exception. The building or part of the building qualifies for an exception from HVAC code
requirements. Applicable code exception is Section 1317.1. Portions of the building that
quality:
Area: Exception 0 -1 0 -2 0 -3
Area: Exception 0 -1 0 -2 0 -3
Area: Exception 0 -1 0 -2 ❑ -3
0 Form Not Required. This project does not contain work required to comply with code.
2. Simple or Complex Systems (Section 1317.9 or 1317.10)
'Simple System. Building contains only Simple HVAC System(s). Complete this form (4a) and
equipment efficiency worksheets as required. Form 4b is not required.
❑ Complex System. Project includes a Complex System. Complete this form (4a), form 4b and
equipment efficiency worksheets as required.
3. Equipment Performance (Section 1317.5)
❑ No New HVAC Equipment. The building plans do not call for new electrical HVAC equipment,
combustion heating equipment, or heat - operated cooling equipment.
a All new HVAC equipment have efficiencies not less than those required by code.
The following equipment efficiency worksheets are attached: ,4/4. itAddLdwa..
0 -4a 0 -4b 0 -4c 0 -4d 0 -4e 0 -4f 0 -4g 0 -4h 0 -4i ❑ -4j
4. Duct Insulation and Sealing (Sections 1317.7 & 1317.8)
0 No Ducts. The building plans' and specifications do not call for new HVAC ducts or plenums.
Compiles. The plans and specifications call for all air - handling ducts and plenums to be insulated
and sealed as required by Sections 1317.7 &1317.8.
5. Distribution Transformers (Section 1316.1)
❑ No Distribution Transformers. The plans/specs do not call for new distribution transformers.
Complies. All new distribution transformers comply with efficiency, testing, and labeling
requirements of Section 1316.1.1.
0 Exception. The project qualifies for an exception per Section 1316.1.1, Exceptlion:
•
0 -1 0-2 0 -3 0-4 0-5, 0 -6 0 -7 0 -8 0 -9 0-10 0-11 0-12 0 -13 0 -14
Attach relevant documentation for appropriate exception. The plans/specs show compliance in the
following locations:
•
4 -1 April 2005
j��j( W Compliance with OSSC, effective 01/01/06
MTZT
MI JUL 1 8 2005
BY: _ .
:, f'r
Form 4a Project Name:ISKA /2.0 774' I Page:I 2-
SYSTEMS - GENERAL Part 2 of 6
6. HVAC Controls (Section 1317.4)
6.1 System Thermostat /Zone Controls (Section 1317.4.1)
' Complles. Al! new HVAC systems Include at least one temperature control device responding to
temperatures within the zones.
❑ Exception. HVAC system qualifies for an exception from zone control requirements.
The applicable code exception Is Section 1317.4.2, Exception ❑ -1 ❑ -2
Portions of the building that qualify:
The plans /specs show compliance in the following locations:
6.2 Off - hour Controls - Auto Setback or Shutdown (Section 1317.4.3)
Complies. Systems must have at least one of the following features:
❑ Control Setback Compiles. Each system is equipped with automatic control capable of
reducing energy through control setback during periods of non -use or alternate use of spaces
$E Shutdown Complies. Each system Is equipped with controls capable of reducing
energy use through automatic shutdown during periods of non -use or alternate use of spaces.
❑ HVAC systems with equipment shutdown are equipped with at least one of the following:
N* Programmable controls (1317.4.3.1 (1))
❑ Occupant sensor (1317.4.3.1 (2))
❑ interlocked to a security system (1317.4.3.1 (3))
❑ Manually activated timers with 2 -hour operation max (1317.4.3.1 (4))
❑ Exception. The building qualifies for an exception to the requirement for automatic setback or
shutdown controls. The applicable code exception is Section 1317.4.3 Exception ❑ -1 ❑ -2
The plans /specs show compliance in the following locations:
6.3 Control Capabilities (Sec. 1317.4.2.1)
Complies. Zone thermostats are capable of being set to the temperatures described In Sec.
1317.4.2.1. Where used to control both heating and cooling, zone controls shall be capable of
providing a temperature range or deadband of at least 5 degrees F within which the supply of
heating and cooling energy to the zone is shut off or reduced to a minimum.
❑ Exception. The building qualifies for an exception to the deadband requirements.
The applicable code exception is Section 1317.4.2.1 Exception ❑ -1 ❑ -2
Portions of the building that qualify: _
The plans/specs show compliance In the following locations:
6.4 Optimum Start Controls (Section 1317.4.3.2)
❑ Complies. Separate HVAC systems have controls capable of varying start-up time of system to
just meet temperature set point at time of occupancy.
a Exception. HVAC systems have a design supply air capacity not exceeding 10,000 cfm.
The plans /specs show compliance in the following locations:
I skid -- r rr f
• 6.5 Heat Pump Controls (Section 1317.4.4)
alio Heat Pump. The plans/specs do not call for a new heat pump
❑ Complies. All new heat pumps equipped with supplementary heaters are controlled to minimize •
• the use of supplemental heat as defined In Section 1317.4.4.
The plans/specs show compliance in the following locations:
42 April 2005
Compliance wih OSSC, effective 01 ro1N5
i
Form 4a Project Name: 4.0j rt - /1"fA4n 77Q.471.47 I Page: 2
SYSTEMS - GENERAL Part 3 of 6
7. Economizer Cooling (Section 1317.3)
-❑ No Cooling. The building plans do not call for a new fan system with mechanical cooling.
❑ Compiles. Each new fan system has an air economizer capable of modulating outside -air and
return-air dampers to provide up to 100 percent of the design supply air as outside air.
Exception At least one new fan system qualifies for an exception. The applicable code exception
is Section 1317.3, Exception ❑ -1 ❑ -2 ❑ -3 ®'-4 ❑ -5 ❑ -r
If Exception 3 is selected complete the following:
(a) Total cooling capacity of exempt units ( Btu/hr) I I
(b) Total installed building cooling capacity (Btu/hr)
❑ Complies. Sum of exempt units rated at less than 54,000 Btu/hr is <240,000 or a/b
< 0.10 (10% of total building cooling capacity).
Unit Identifier of exempt units: ,
The plans/specs show compliance in the following locations:
--
Sets Sito /ion4 PVOt+- dm/ 1..49/./v4 .4
r! pcA'S, I
8. Economizer Pressure Relief & Integration (Section 1317.3.1 and 1317.3.2)
alto Economizers Required. Project does not contain a new fan system requiring economizers.
Overpressurization Complies. The drawings specifically identify a pressure relief mechanism for
each fan system that will relieve the extra air introduced by the economizer.
❑ Integration Compiles. Economizer is capable of providing partial cooling even when additional
mechanical cooling is required to meet the remainder of the cooling load.
❑ Exception. The applicable exception is Section 1317.3.2, Exception 0 -1 ❑ -2
The plans/specs show compliance in the following locations:
9. Hot Gas Bypass (Section 1317.5)
arNo Hot Gas Bypass _
❑ Complies. See allowable amount of hot gas bypass as a percentage of total cooling capacity in
table below.
Unit lD . Rated Cooling Capacity Hot Gas Bypass Capacity
Allowable Hot Gas Bypass
Rated Cooling Capacity Max Hot Gas Bypass
4240,000 Btu/hr 50%
>240,000 Btu/hr 25%
❑ Exception. Unitary packaged system with cooling capacity no greater than 90,000 Btu/h
4-3 • -
April 2005
Compliance with OSSC, effective 01/01/05
Form 4a Project Name: (S / 1t //ya tor ruov24 Page:I /
SYSTEMS - GENERAL Part 4 of 6
10. Shutoff Dampers (1317.4.3.3)
Not Required. Shutoff dampers are not required on this project.
❑ Complies. Each outdoor air supply & exhaust system shall be equipped with motorized dampers
❑ Exception. The building qualifies for an exception to the motorized damper requirement. The
applic -able code exception is Section 1317.4.3.3 Exception ❑ -1 ❑ -2 ❑ -3 ❑ -4 ❑ -5
The plans/specs show compliance in the following locations:
ONTSowi / I 4. Amovi dY fL641- 13Krcdp'4 SYJ Te%7 i AroT
10.1. Shutoff Damper Controls (Section 1317.4.3.3.1)
❑ Complies. Outdoor air supply and exhaust systems shall be provided dampers that automatically
shut when systems or spaces served are not in use or during building warm -up, cooldown, or
setback.
❑ Complies. Stair and shaft vents are capable of being automatically closed during normal building
operation and interlocked to open as required by fire and smoke detection systems.
The plans/specs show compliance in the following locations:
10.2. Motorized Damper Leakage (1317.4.3.3.2)
❑ Complies. Motorized outdoor air supply and exhaust air dampers have a maximum leakage rate
of 4 cfm/ft2 at 1.0 In w.g. when tested in accordance with AMCA Standard500 -1998.
O Exception. Packaged HVAC equipment may have maximum leakage rate of 20 cfrn/ft 1.0 in
w.g. when tested in accordance with AMCA Standard 500 -1998.
The plans/specs show compliance in the following locations: -
11. Piping Insulation Section 1314
p g ( 1314)
❑ No New Piping. The building plans and specifications do not call for new piping serving a
heating or cooling system or part of a circulating service water heating system.
omplies. All new piping serving a heating or cooling system or part of a circulating service
i � water heating system complies with the requirements of the Code, Section 1314.1.
`7',?" Exception. New piping qualifies for exception: Section 1314.1, Exception ❑ -1 ❑ -2
12. Occupancy Ventilation -
ErComplies. Mechanical ventilation systems provide the required amount of ventilation specified
in Chapter 4 of the Oregon Mechanical Specialty Code.
❑ Complies. Natural ventilation systems provide required amount of ventilation as certified by a
reg- istered architect or engineer as specified by Section1203.4.1, Exception. Attach worksheet
The plans/specs show compliance in
the following locations:
The plans/specs show compliance
on the following pages:
4-4 April 2005
Compliance with OSSC, effective 01/01/05
;;pry.
Form 4a Project Name:Ic$ J . /•a 7 I Page: -s
SYSTEMS - GENERAL Part 5 of 6
13. High Occupancy Ventilation (Section 1317.2.2)
❑ Complies. HVAC systems with ventilation air capacities of 1,500 CFM or greater that serve
areas having an average occupant load of 20 square feet per person or less from Table
1004.1.2 have a means to automatically reduce outside air Intake.
Identify applicable systems:
Plans/specs indicate where equipment (i :e. carbon dioxide sensor) and sequence is specified:
O Exception. HVAC systems are equipped with an energy recovery device with at least 50%
recovery effectiveness.
No High Occupancy Systems. Project does not contain an HVAC system as described above.
14. Exhaust Air Heat Recovery (Section 1318.3)
'Not Regulated. HVAC system does not have: 1) design supply air cap. of >10,000 cfm, and 2)
min. outside air supply >70 %, and 3) at least 1 exhaust fan rated at 75% of min outside air
O Complies. Heat recovery system increases outside air temperature by 20 4 F (Climte Zone 1) or
30 °F (Zone 2) and has provision to provide bypass during air economizer mode.
❑ Exception. An HVAC system qualifies for an exception to this requirement. Applicable
exception from Section 1318.3 Exception Q -1 Q -2 -3 4 ] -5 I] -6 ❑ -7
The plans/specs show compliance In the following
locations:
15. Large Volume Fan Systems (Section 1318.4.2.4)
arNot Regulated. The building plans or specifications do not call for fan systems over 15,000
CFM that serve a single zone and function for the purpose of temperature control.
❑ Complies. Fan systems are equipped with variable frequency drive or Iwo speed motor to
reduce airflow as required by Sectidn 1318.4.2.3.
The plans/specs show compliance in the following
locations: _
16. Variable Speed Drives (Section 1317.10.3.1)
allot Regulated. The building plans or specifications do not call for fan and pump motors 10
horsepower and greater that serve variable -flow air or liquid systems.
❑ Complies. All fan and pump motors 10 hp and greater which serve vnnable -flow air or liquid
systems are controlled by a variable -speed drive.
❑ Exception. The building qualifies for an exception to the variable -speed drive requirement.
Portions of the building that qualify:
Applicable code exception is Section 1317.10.3.1, Exception
The plans/specs show compliance in the following I
locations:
17. Service Water Heating (Sec. 1315)
O No New Water Heating. The building plans and specifications do not call for new water
heaters, hot water storage tanks or service hot water distribution systems
ErCompiles. All new water heaters, hot water storage tanks or service hot water distribution
systems comply with the requirements of the Section 1315.
❑ Exception. The applicable code exception is Section: ]Exception:
Portions of the building that qualify:
The plans/specs show compliance in the following locations:
4-5 April 2005
Compliance with OSSC, effective 01101/05
.
Form 4a Project Name: S- f/7,Q4r 7740 I Page: 6 J
SYSTEMS - GENERAL Part 6 of 6
A
18. Swimming Pools, Spas and Hot Tubs (Section 1315.51
'No New Pools. The building plans and specifications do not call for rew, swimming pools, spas or
hot tubs.
❑ On/Off Controls Compiles. Spa and hot tub heaters are equipped with a readily accessible
ON /OFF switch as required by Section 1315.5.1.
❑ Ventilation Controls Complies. Pool ventilation system is controlled based on humidity.
❑ Cover Complies. All heated pools, hot tubs and spas are equipped with a cover.
❑ Heat Recovery Complies. Pools, Spas, and hot tubs, over 200 ft utilize recovered heat as
required by Section 1315.5.3.
❑ Exception. Heat recovery is not necessary as pool is heated by renewable energy or waste
heat recovery sources capable of providing at least 70 percent of the heating energy
required over an operating season.
19. Fume Hoods (Section 1317.2.1.)
® No Fume Hoods. The building plans do not call for fume hood systerrs that have a total exhaust
rate greater than 15,000 cfm.
❑ Compiles. Fume hood systems have at least one of the following features:
❑ Variable air volume hood exhaust and room supply systems capable of reducing exhaust
and makeup air volume to 50% or less of design values.
❑ Direct makeup (auxiliary) air supply equal to at least 75% of tha exhaust rate, heated no
warmer than 2° F below room set point, cooled no cooler than 3° F above room set point,
no humidification added, and no simultaneous heating and cooling used for
dehumidification control.
❑ Heat recovery systems to precondition makeup air from fume hood exhaust in accordance
with 131 18.3 - Exhaust Air Energy Recovery, without using any exception.
The plans/specs show compliance in She following locations:
20. Parking Garage Ventilation (Section 1317.2.3)
No Enclosed Garages. The building plans and specifications do not call for enclosed Group S -2
parking garages with a ventilation exhaust rate greater than 30,000 CFM.
❑ Complies. The plans and specifications call for carbon monoxide sen:3ing devices as required by
Section 1317.2.3.
❑ Exception. Open parking garages.
21. Kitchen Hoods (Section 1317.11)
® Not Regulated. The plans/specs do not call for any new kitchen hoods with exhaust capacity
greater than 5,000 cfm each.
❑ Complies. All new kitchen hoods with a total exhaust capacity greater than 5,000 cfm have at
least 50 percent of the required makeup air; (a) unheated or heated to no more than 60 °F; and (b)
uncooled or evaporatively cooled.
The plans/specs show compliance In the following locations:
22. Outside Heating Systems (Section 1317.12)
a No Outside Heating Systems. The plans/specs do not call for new permanently installed heating
systems outside the building.
O Complies. All new permanently installed outside heating systems are radiant gas fired systems
controlled by an occupancy sensor or timer switch as required by Section 1317.12.
4-6
April 2005
Compliance with OSSC, effective 01/01/05
r s„, 5 - 0 03 5
Form 5a Project Name' The Sharper Image, Washington Square I Page"'
. r. _...
7. c. 'fie f 4; k
1. Interior Exceptions (Section 1313.1)
Exceptions ❑ No Interior Lighting. The building plans and specifications do not call for new or
Discussion or qualifying erraptinle kl altered Interior lighting. Skip to item 5, Exterior building Lighting - General, below. i �' r1 6.. 2005
hse ucdone sedan. ❑ Exceptions. 1. The building or part of the building qualifies for an exception from
code lighting requirements. Applicable code exception is number I CITY o F TI hARO
2. Lighting equipment that qualifies for an exception - in addition to general lighting and is 3UJLD NC J lVISK) I
separately controlled. Applicable code exception is number. I
Areas of the building and equipment that qualify for any exceptions:
Plans /Specs
Show e detail compliance by nu mber. exam u 2. Local Shut -off controls (Section 1313.3.1.1)
drawing N ast number.
epeolcadon eeL9On end El Compiles. At least one local shut -off lighting control for every 2,000 square feet of
lighted floor area and for all spaces enclosed by walls or ceiling height partitions.
This control(s) is detailed in the building plans on drawing number. I Sheet E4
❑ Exception. The building or part of the building qualifies for an exception.
Applicable code exception is Section 1313.3.1.1, Exception:
Portions of the building that quality:
3. Automatic Shutoff Controls (Section 1313.3.1.2)
❑ Not Applicable. Office floor area is not over 2,000 square feet of contiguous office
floor area or permitted space is not over 5,000 square feet. No offices less than 300 square feet, meeting or conference
rooms, or school classrooms.
❑ Complies. All interior lighting systems are equipped with a separate automatic
control to shut off the lighting during unoccupied periods. Offices less than 300 square feet,
• meeting and conference rooms, and school classrooms shall be equipped with
occupancy sensors that comply with Section 1313.3.1.2.1.
Compliance details in plans/specs: I I
❑ Exception. The building or part of the building qualifies for an exception The
applicable code exception is Section 1313.3.1.2, Exception: I I
Portions of the building that qualify:
4. Daylilghting Controls (1313.3.1.3)
• No classrooms or atriums with skylights or window to wall ratio greater than 50%.
❑ Complies. All classrooms and atriums with window to wail ratio greater than 50% and/or
Exterior skylights are equipped with automatic daylight sensing controls, as required by Section
Building
Lighting 1313.3.1.3.1 and Section 1313.3.1.3.2. The daylight sensors specified comply with
Lighting
°
Itgheng t erteno
Section 1313.3.1.3.3.
mnate he
IWrinses the sktenar of N.
bulking and adjacent Compliance details In plans/specs: I
walkways and laming
areas with or ratan •
Car1opIK
5. Exterior Lighting (Section 1313.5)
❑ Complies. The plans do not call for incandescent or mercury vapor lamps for use
Clock on building exterior.
Switches alwnw ❑ Exception. The building plans indicate luminaires with incandescent or mercury vapor
wvorwnac (seasonal
ng) typo wpn
separate programs Per each lamps, but they are specified for use in or around swimming pools, water features, or other
�: to =Intim 1pcations subject to the requirements of Article 680 of the 2002 National Electrical Code.
timekeeping 82m% power
MOW*
'6. Exterior and Canopy Lighting Controls (Section 1313.3.2)
❑ Complies. The building plans and specifications include photoelectric and/or clock
switches on all exterior lighting systems which are designed and programmed to
extinguish lights when daylight is present, as required by Section 1313.3.2.
�_. .
/`��•. 7. Interior Connected Lighting Power (Section. 1313.4)
Complies. The interior lighting power does not exceed the interior power allowance established
in either the Tenant Space Method (Form 5b) or the Space-by -Space Method (Form 5c).
ETenant Space Method (Form 5b) CSpace- by-Space Method (Form 5c)
3 21105
Lighting 2004 Forms Ltr890FD.xls
Worksheet 5a _ —_ - - -_ _ Project Name. The Sharper Image, Washington :g Pages I •
LIGHTING SCHEDULE , • — —
>, x
'
Luml I :. „, • , • ' ` . Luminaire Is Luminaire
Lumir aire i Lamp Ballasts
D ; ' Power From
7ypa Description No. I Description No. Description ` (watts) Table 5c
FA -1 Fluorescent T -3 s7 4' industrial strip w/ wire Guard a „ ,, 3�-
e.
• FA -2 _ __ ___. _.___..___ _ _Fluorescent T,.8• ___ __. ___ __.. _ ..._ - r - T 4' industnal strip w/ wire Guard & emeraencv haft n _ - .. . :: , ,1 C.. Q 3 v r9
FB -1 Fluorescent T-8 . -- - - 2' x 4' Grid t r o i T e r ' 1 . , - b as i t 0 Y s'5 FB-2 Fluorescent T -6 2 . x ±.i _,____ 1 - 'rtw.. i l Al tom
ti #
FB 4 Fluorescent T 8 U6 d 2 ' x G rid Troffer _i ._ F B321 ti (L , r_ �. ' C a ' C • ' . • ► ,/ j
FD -1 Compact Fluorescent recessed down light ' G � "" f ` (xW� , .. , ' ke rQ ; c.... FILM — „ p er,
FD -2I ... _.._ __...-__.._. _ ._Compact Fluorescent ............ .. .. di recessed down licht w /emeraencv battery 1 • F t ; - 4. . .. E.61: a Pf.11r+1 a
FE -1 Fluorescent T -S J B' stagger stns J ' i Cal'-r-1114-114-1k-' '
-
FE -2 _ Fluorescen:T -8 u staaaer strip =:E � III L°
�C�C
FE -3 . Fluorescent T -8 . . ae
cr _r str l t(e.C4 reek; 0. NO pe:e , 5 • C.`2_
FE-4 Fluorescent T -8 Ai ?' - tacger gtr .. �`1 r
�� �{
FE -5 _ ___ _ r , _ _ __Fluorescent T -8 . _ _. _ __ -_ _ . - __! 4' iod�slnal strip 11 �_ � 11� ^ _ - 1 _ hlb • _
FF -1 . _ _Fluorescent T-8 .. ... 3] 4 industrial stno _ t 7 _ "L. et P AJA j ' -�. j- -yes
A -1 H�al en Incenaescent z tr ho _- _-, i'"` I _ ._ �^ n • _- _ - �^, ..: ` ` - - - L
' nt oundte6r.ea-F h t �' 1 `� r. .ktq iJ 0• L. � e 1 .. ' • `� .:... .
ti..--il - ..,,_ _..._._ .,.__.,. I - - -.„.._ - .- �,Ij-._._ ± ._......- _ -.... _- - - .- ._... ,....... _ _-
_
1 ,
. - .:�
- -_
- is .
Lighting 2004 Forms L #890FD xls
1
Worksheet 5b-1 Project Name: S nnaae t al∎1 1Ot•.Stehge:L a_
INTERIOR LIGHTING POWER
- Space-by-Space Method Only
Skip to column (P if using the Tenant Space Method
Each room be Identified. must (a) (b) (c) (d) (a) Lam ID from Qua ntity of (h) 0) U) (k)
Describe Room ID (do Space Type Space Lighting Power Worksheet Luminaires (or Luminalre Lighting Room
luminaires for each not leave any Area (Table 13-H) Type Budget 5a Column lineal ft. for track Power Exempt Power Total Llg
individual room in blanks) (ft) (enter apace type only once . per room) LPD Mix (dl (a) lighting) (Watts) Fixtures (g) x (h) Power
plans. I C> 1 3, Sra �g d pi- y.O 1wc CS -f asp 37.5 Q 137
T
For track lighting I U 1 S-t ci _62 ❑ 552
enter lineal met in 1 o .1 F D -1 2 3 5 ❑ , 1 0
column column (g) `
I D 1 FO `2 1 Sv c
Column (k), enter ❑ ' I *
sum of column U) 1 D 1 1 1 1 1m ❑ 1 1 t o
cee,a room " la1 rFZ S COb ❑ L•!75
for the room. See . 1 �� 1 G ^ . ❑ 3' o
examplean t L
aletructiana. , N 1 re- V 7, 59__ ❑ 10 q
t ut F S 9-. Co 2 ❑ 114
101 FF- I 3 9-`j ❑ 1053 380
ma 193 Sock . 8R F&l L4 C.,,,•1_ ❑ a L(i y96_
01 t 2 L( C� ❑ 29R
10. 4 1 I To; ( -e .a 3? FL-1 1 loo ❑ 100 16b
I n q as 1- L C 1. w 3 - I I 32_ ❑ 32 32-.
I Or .57 11. I . S g � Fit � k- - ), l 3I_ ❑ 22_ 3'1
o
0
o
'❑
o
0
0
❑ .
o
'❑
o
0
' ❑
❑
0
' ❑
El 1 ^ rw fir.
Wrkaht 5b- Worksheet 5b-_ Total Budget H / Wahl 5b•_ Total Lighting Power (excluding exempt/track fixtures) 4 t
Total Sq Ft 1 .c. �t K1 1 1J
' Other Pages
Lot a0drtionel Total Number of Additional Worksheet 5b (''
worksheets
necessary to catalog _
a0 luminaires m
building WORKSHEET NUMBER to Proposed adding l U ldht Power (n)
Complete this section when more than one Llpndag Poser Budget Spew-0y- (Toni of column (k), excluding Area Sae. (nor requlnd for
Worksheet 3b is completed spew only goad or column e)) exernpwadr) Tenant Method)
5b-1 1 Ll 29 4 L I, 9-1$
5b-Z 1
�` ( Sum of additional 5b worksheets � `',
2
`r �� Total Budget (of all worksheob) 14 J/.q yw.7 29 914 as
. 5s
Campence with OSSC, effective 01/01105
.‘,..-,,,,,•,• _ ' . ;� ^
1� mot-' -1 \,1-
•
•
• Form 5c Project Name: 1 1ne_cLQ ile.t ck @ W at(h; t-Ve/t 11Y11 rd, Page.'
INTERIOR LIGHTING POWER - Space -by -Space ethod
Lighting Power 1. Total Interior Lighting Power Budget from Worksheet 5b -1 (Sum of Column (I)) I L�q"11
Budget AAA...III
Track Lighting
2. Total length of track lighting (ft) 2S 0
Power
3. Line 2 multiplied by 37.5 Wattstft 93'75
4. Total amperage of circuit breaker(s) serving track lighting (amps) a GO
5. Voltage of circuit breaker serving track lighting (volts) a O
6. Maximum wattage of track lighting (multiply line 4 by line 5) °1P- 00
7. Track Lighting Power (lesser value of line 3 or line 6) 9 375
Buildings 8. Total Intenor Lighting Power from Worksheet 5b-1 (Sum of Column (m)) + 1 S
Lighting Power
9 Total Adjusted Lighting Power (line 7 + line 8) _ 1 — i 16tf
10 Does design meet budget? Line 9 must be no greater than line 1 eS
•
•
ra: �
5-3
Compliance with ossC, efs0tive 01,01/05
•
:rte = ,` t_r'
CITY = TIGARD
BUILDING DIVISION PERMIT #: BUP2005.00351
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 8/10/2005
Phone: (503) 639 -4171
Inspection Requests (24 Hrs.): (503) 639 -4175
INSPECTION WORKSHEET FOR DATE: 10/27/2005 TIME: 7:16AM PAGE: 13
SITE ADDRESS: 019348 SW WASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: SHARPER IMAGE
DESCRIPTION: TI.
OWNER: WASHINGTON SQUARE LLC, PHONE #:
CONTRACTOR: WESTERN CONSTRUCTION SERVICES PHONE #: 360 -699 -5317
Inspection Request Scheduled For: Date: 10/27/2005 Pour Time:,
Code # Inspection Description Confirm # Contact # Message
287 Suspended ceiling 019542 -01 360-601-7929 N
Corrections /Comments / Instructions:
•
��'PASS ❑ PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL ❑ CALL FOR INSPECTION ❑ ADDITIONAL FEES ASSESSED
Inspector: Date: 2 7 Phone #: (503) 718-
r i �, � :•
CIT reETIGARD
BUILDING DIVISION PERMIT #: gUP2005 00351
• 13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 8/10f2005
Phone: (503) 639-4171 i ll
Inspection Requests (24 Hrs.): (503) 639 -4175
INSPECTION WORKSHEET FOR DATE: 9/29/2005 TIME: 7:08AM PAGE: 5
SITE ADDRESS: CLASS OF WORK:
09348 SW WASHINGTON SQUARE RD
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: SHARPER IMAGE
DESCRIPTION:
WASHINGTON SQUARE LLC PHONE #:
CONTRACTOR: WESTERN CONSTRUCTION SERVICES PHONE #: 360. 699 -5317
Inspection Request Scheduled For: Date: 9/ 2912005 Pour Time:
Code # Inspection 'Description Confirm # Contact # Message
•
275 Framing 016992 -01 360 -601 -7929 N
Corrections /Comments /Instructions:
_ NIP . 11
ow •
•
ASS O PARTIAL APPROVAL CANCEL El NO ACCESS
❑ FAIL n CALL FOR INSPECTION ❑ ADDITIONAL F ES ASSESSED
•
Inspector: / Date: / 63-
one #: (503) 718-
,
r �
CITY4OF TIGARD
BUILDING DIVISION PERMIT #: BUP2005-00351
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 81/0 /2005
Phone: (503) 639 -4171
Inspection Requests (24 Hrs.): (503) 639 -4175
INSPECTION WORKSHEET FOR DATE: 11/14/2006 TIME: 7:12AM PAGE: 136
SITE ADDRESS: 09348 SW WASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: SHARPER IMAGE
DESCRIPTION: TI.
OWNER: WASHINGTON SQUARE LLC, PHONE #:
CONTRACTOR: WESTERN CONSTRUCTION SERVICES PHONE #: 360 - 699.5317
Inspection Request Scheduled For: Date: 11/14/2005 Pour Time:
Code # Inspection Description Confirm # Contact # Message
299 Final inspection 021065-01 360 -601 -7930 N
Corrections /Comments /Instructions:
F:( 3 CD
iE&b tAAECI± Fc //►— •
V ss ❑ PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ CALL FOR INSPECTION ❑ ADDITIONAL FEES ASSESSED
Inspector: /► t 7 Date: ` 14 v� Phone #: 503
P ( ) 718 -
•
CITY,;& TIGARD
BUILDING DIVISION PERMIT #: BUP200S -00351
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: 8/10/2006
Phone: (503) A
•
Inspection Requests (24 Hrs.): (503) 639 - 4175' ° 'I I..
INSPECTION WORKSHEET FOR DATE: 11/16/2005 TIME: 7:02AM PAGE: 43
SITE ADDRESS: 09348 SW WASHINGTON SQUARE RD CLASS OF WORK:
SUBDIVISION: WASHINGTON SQUARE LOT #: TYPE OF USE:
PROJECT NAME: SHARPER IMAGE
DESCRIPTION: TI.
OWNER: WASHINGTON SQUARE LLC, PHONE #:
CONTRACTOR: WESTERN CONSTRUCTION SERVICES PHONE #: 360 - 699 -5317
Inspection Request Scheduled For: Date: 11/16/2005 Pour Time:
Code # Inspection Description Confirm # Contact # Message
299 Final inspection 021290 -01 360 -601 -7930 N
•
Corrections /Comments /Instructions:
ir
4 .
IV
ASS ❑ PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL • CALL FOR INSPECTION ❑ ADDITIONAL FE S ASSESSED
: t0
tkv/ Date: l f� Phone #: (503) 718-