Loading...
Specifications 1 / � , . 0 TIMNE Submittal Trane A Division of American Standard Inc. m p Prepared For: Date: September 07, 2005 I Customer P.O. m: (� Customer Project Num ber: .2-J 0,fr C A Sold To: Job Number: 0 , Job Name: White House/ Black Market - Washington Sq. - OR Trane is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 1 BCXC Blower Coil Air Handler The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval. Roger Coll Trane 6461 Topaz Court Suite 1 Fort Myers, FL 33912 -8311 Phone: (239)275 -9420 Fax: (239)275 -9775 J:UOBS151215764612109 07 05 Submittal.doc • Table Of Contents Product Summary 1 BCXC Blower Coil Air Handler (Item Al) Tag Data 3 Product Data 3 Mechanical Specifications 4 Unit Dimensions 6 Accessory 8 Field Wiring 11 Field Installed Options - Part/Order Number Summary BCXC Blower Coil Air Handler 12 • 'White House/ Black Market - Washington Sq. - OR September 07, 2005 Tag Data - BCXC Blower Coil Air Handler (Qty: 1) Item Tag(s) Qty Description Model Number Al No Tag 1 BCXC Blower Coil Air Handler BCHC090G2 "A1 GO7L2120AC001 A M200000000000 Product Data - BCXC Blower Coil Air Handler Item: Al Qty: 1 HORIZONTAL CONFIGURATION Horizontal Configuration Unit Size 90 - 7 1/2 Ton ( 26.4 KW ) 460/60/3 Foil Faced Insulation 1" Motor, drive & control box on Same Side as Coil & Drainpan Connection PVC Drainpan - Right Hand Coil & Drainpan Connections 6 Row Cooling Hydronic Coil 3 Horse Power 678 -877 RPM 60HZ / 562 -727 RPM 50HZ 2 - Stage 12.0 KW 24 Volt Magnetic Contactors Heat Int -lock Non -Fuse Disc. & Htr. Fuse Control Interface 2 -Way, 2 Position N.C. (FId) 9.0 CV, 1 1/4", 2 Position, 1 1/4" PIPE (Fld) Deluxe Piping Package (Fld) Fl n = Frrmicharl by Trann / Inclnllcrl by fllhnrc Trone Fnrrinrnunl CrrhmiHeJ Dann f 1'7 'White House! Black Market - Washington Sq. - OR September 07, 2005 Mechanical Specifications - BCXC Blower Coil Air Handler Item: Al Qty: 1 BCHC General The product line consists of a horizontal air handling unit and mixing box. Units are tested in accordance with ARI 430 -1999 and ARI 260 -2001. The unit is UL 1995 listed in U. S. and Canada and complies with NFPA 90A. Air handlers consist of a hydronic and /or DX coil, drain pan, and centrifugal fan with motor and drive mounted in a common cabinet. Drive location and coil connections are independent for the same or opposite side location. Air handlers are provided with knockouts in all four corners for installing the unit suspended from the ceiling with threaded rods. Unit and accessories are insulated with one -inch, 1'/2 lbs. /cu. ft. density fiberglass insulation. One -inch foil faced insulation is also available. Large motor access panels are provided on both sides of the unit and accessories. Casing Casings (structural components) are constructed of 18 -gauge galvanized steel, insulated with one -inch, 1 '/2 lb density fiberglass fire resistant and odorless glass fiber material to provide thermal and acoustical insulation. Fan housing sides are directly attached to the air handler top and bottom panels strengthening the entire unit assembly. Coil access panels are located on both sides of the air handler and allow easy removal of the internal coils and drain pan. Main access panels provide generous access to the fan, motor and drive from both sides of the air handler. Foil Faced Insulation The interior surface of the unit is acoustically and thermally lined with 1 inch [26 mm] 2.0 lb. /cu. ft. [32 kgs. /cu. m.], R- Value of 4.3 density glass fiber with a foil facing. The insulation is UL listed and meets NFPA -90A, UL 181, and bacteriological C665 standards. Coil # 1 Hydronic Cooling Coils Cooling coils are two, four, or six -row, chilled water. All water coils are 12 fins per inch. All water coils use highly efficient Trane Delta Flo ?, Type H aluminum fins, mechanically bonded to seamless copper tubes. All coils are specifically designed and circuited for water use. All coils are factory tested with 450 psi air under water. Maximum standard operating conditions are: 300 psig, 200 °F. Sweat type connections are standard. Electric Heat Stages Factory provided and mounted, UL recognized resistance open -wire heater with a disc -type automatic thermal primary safety device. Two stages of control. Single point power connection to the unit is provided. Optional line fuses and a door interlocking disconnect switch are available. Magnetic Contactors A 24 volt electric heater contact for use with Thermostat Control Interface. Reset Backup Protection Secondary Manual Reset Backup Protection is provided. Disconnect Switch A factory provided disconnect switch with an interlocking door on the heater control panel. Line Fuse A safety fuse located in the electric heater's line of power to prevent power surge damage to the electric heater. Fan The fans are forward curved, centrifugal blower type equipped with heavy -duty adjustable speed V -belt drives. The fan shaft is supported by heavy -duty, permanently sealed ball bearings. All fans are dynamically balanced. All air handlers have a single fan. 60 Hertz Motor A 60 Hertz, 1750 RPM motor has a plus or minus 10% voltage utilization range. The motor is open drip -proof with permanently sealed ball bearings, internal overload protection, and minimum 1.15 service factor and size 56 resilient base frames. The motor is factory installed and wired to the air handler junction box. Polymer Drain Pan The drain pan is noncorrossive and double - sloped to allow condensate drainage. The drainpan construction is polymer. Coils mount above the drain pan, not in the drain pan - thus allowing the drain pan to be fully inspected and FLD = Furnished by Trane / Installed by Others Trane Eauioment Submittal Pace 4 of 12 White House/ Black Market - Washington Sq. - OR September 07, 2005 _ cleaned. The drain pan can also be removed for cleaning. The drain pan connections are unthreaded 3 /4" schedule 40 PVC for solvent bonding. The main drain connection is at the lowest point of the drain pan. An auxiliary drain connection is provided on the same side as the main connection. Thermostat Control Interface The thermostat control interface is intended to be used with a field supplied low voltage thermostat or controller. The control box contains a line voltage to 24 volt transformer and a one, two, or three -pole fan contactor. The wires from the.fan contactor and the low voltage side of the transformer are pulled and terminated on the inside of the two -sided terminal strip. The end devices are mounted and the wires are pulled and terminated on the inside of the two -sided terminal strip. All customer connections other than power are on the outside of the two -sided terminal strips. Deluxe Piping Package - Coil #1 The deluxe piping package consists of one shutoff ball valve, one strainer, one circuit setter balancing valve, and for three -way packages, a balancing fitting on the bypass line. The maximum entering fluid temperature on the water valves is 200 deg. F. [93 deg. C.]. The stop valves are ball type, and insulation on the piping package is by others. 2 -Way, 2 Position Control Valve - Coil #1 -Valve Type 2 -way VU Series or VC Series (Honeywell) -Cv Ranges 3.5, 6.0, 8.0, 9.0 - Material Body - Forged Brass. Operating Paddle - Patented Buna -N Ball Seat "0" Ring Seals - EPDM. Stem - Brass. - Temperature Limits 200 deg. F [93 deg. C] fluid 125 deg. F [48 deg. C] ambient. - Operating Pressure 300 psi [2068 kpa] max. -Close -off Pressure 20 psi @ 3.5 Cv 60 psi @ 6.0 Cv 9 psi @ 8.0 Cv 60 psi @ 9.0 Cv 2 Position Actuator - Coil #1 -Drive Time 6 seconds @ 60 Hz. - Voltage 24 VAC 50 & 60 Hz. -Power Consumption 5 watts - Operating Ambient Temperature 34 to 125 deg. F [15 to 54 deg. C]. FLD = Fumishad by Trans. / Installed by Others Trane Eauinment Submittal Pana S of 12 ' White House/ Black Market - Washington Sq. - OR September 07, 2005 Unit Dimensions - BCXC Blower Coil Air Handler Item: Al Qty: 1 NOTE: —c- =AIR FLOW �( 46" 1 1 7/8" (22mm] HANGER ROD KNOCKOUTS 40" 3 "• (4 PLACES) FILTER ACCESS 1 ►• c 52" I " — l I 1 28 1 /8" —� I COIL I MOTOR ACCESS ACCESS I PANEL I PANEL 1 I so I 1 • Ill 7 9 1/2" • o I. LEFT VIEW L5.J WEIGHT lb BASE UNIT 174.8 TOP VIEW COIL #1 137 COIL #2 1. CONTROL BOX IS PROVIDED WITH 7/8" [22mm] KNOCKOUTS FOR FIELD WIRING. - FILTER ACCESS 8 ONTROL BOX 1 ' 1' 17 3/4 "-=• 12 1/2" " 15/8' I I I I - 1 I 1 13 1/2" f i MOTOR ACCESS COIL PANEL i ACCESS ; �— 261/8" 14" I. i PANEL 1 1/2" 1 1 i 1 I FRONT VIEW RIGHT VIEW F1 r) = Fnmichorf by Trnna / lnetallari by (")}hare Trans Frminmanf Suhmiffal Pang. R of 19 White House/ Black Market - Washington Sq. - OR September 07, 2005 Unit Dimensions - BCXC Blower Coil Air Handler Item: Al Qty: 1 NOTE DRAIN CONNECTION STUBOUTS EXTRUDE 2' [51mm] FROM SIDE OF UNIT. RIGHT HAND DRAIN CONNECTIONS /4' SCHEDULE 40 PVC PIPE CONNECTION 4' SCHEDULE 40 PVC PIPE CONNECTION AUX MAIN DRAIN DRAIN 0 0 T II i 1 8' • 10 3/4' • 12 3/4' BOTTOM REAR CORNER OF UNIT FLD = Furnished by • Trane / installed by Others Trane Eauioment Submittal Pace 7 of 12 "White House/ Black Market - Washington Sq. - OR September 07, 2005 Accessory - BCXC Blower Coil Air Handler Right hand electric heater Item: Al Qty: 1 CONTROL PANEL DOOR 7 / 8 " [22mm] CUSTOMER ELECTRICAL WEIGHT lb CONNECTION 19.2 1 1/8" AIR FLOW 13 12' 12" 1 s/ - 4 3/8 1" / 7 65/8' 1 3/8" 18• 5/8" 11 5/:• 2 1/4" ISO1 VIEW 1. CONTROL PANEL DOOR IS HINGED AT SIDE. ALLOW FOR CLEARANCE. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Pane B of 12 White House/ Black Market - Washington Sq. - OR September 07, 2005 Accessory - BCXC Blower Coil Air Handler 2 way deluxe piping package - coil #1 Item: Al Qty: 1 105/8" SUPPLY CONNECTION COIL CONNECTION BALL VALVE STRAINER • 14' - - = WATER FLOW CONTROL VALVE RETURN CONNECTION COIL CONNECTION FLOW SETTING VALVE FLD = Furnished by Trane / Installed by Others Trane Eauioment Submittal Pace 9 of 12 ' I «White House/ Black Market - Washington Sq. - OR September 07, 2005 Accessory - BCXC Blower Coil Air Handler COIL 1 = HYDRONIC, COIL 2 = NONE, RH CONNECTIONS Item: Al Qty: 1 COIL CONNECTION SIZE INCH mm RETURN 1 5/8 41 SUPPLY 15/8 41 SUPPLY le RETURN 4D 15 1/2' 121R' 7 k 12 3/44' BOTTOM REAR OF UNIT NOTE COIL CONNECTION LOCATIONS ARE TOLERANCED WITHIN +1- 2 INCHES (51 mm). FLD = Furnished by Trane Installed by Others Trane Eauinment Submittal Pane 1/) of ' White House/ Black Market - Washington Sq. - OR September 07, 2005 Field Wiring - BCXC Blower Coil Air Handler Item: Al Qty: 1 NOTES: 1. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (NEC), STATE 6 LCCAL REQUIREMENTS. 2. DASHED LINES INDICATE RECOMMENDED FIELD WIRING BY OTHERS. DASHED LINE ENCLOSURES 6/OR DASHED DEVICE OUTLINES INDICATE COMPONENTS PROVIDED BY OTHERS SOLID LINES INDICATE WIRING BY TRANE CO 460/6013 3 CONTROL WIRING CONNECTIONS ARE 6-32 SCREW TERMINALS LOCATED ON OUTSIDE OF CONTROL BOX LI tZ L3 4. LINE VOLTAGE CONNECTIONS ARE TO BE SPLICED TO I --, WIRES INSIDE OF UNIT CONTROL BOX OR TERMINATED I I I CONNECTIONS INSIDE INSIDE OF ELECTRIC HEAT CONTROL BOX ON UNITS , _ ELECTRIC HEAT CONTROL WITH ELECTRIC HEATERS BOX UNIT POWER . ® WARNING e AVERTISSEMENT 8 ADVERTENCIA WIRING HAZARDOUS VOLTAGE TENSION DANGEREUSEI NOLTAJE PELIGROSOI DREWECT AL DECRIC POSER COWER MUTES LES TENL0f0 ET KSOO,ZCre IOM.EICRGN ELECTRCA Pflug WASTE DOOD.RCCES GWRR LES SECIOHaSs ADOrACE. N .LCQL S ER ca.. ..es REHOIASr AND PCLLOwLCOC WE NO TAG RJR SOPRE LES SRDCEDUICI Ce SCA LOS PROCEDNEMTDS DE acme PROCEDURES Wine SERVCEG KRROURI.LGC ET DES ERDLaT1E3 Av.a ETOUETICO meets Of PRCCEDER AL PSSM NAT ALL LO= inure NRRVOIOA •REER NJE TOYS SERVCO ASEGURESE Cf CA 10005 A . A 100R CAPACITORS . TI KD ERS vaT U]LU10E OARS L L DES fC 124115 0M LOSC DESCARCACH E SDELUO'ORMAVAM VARI•0 E VOL OWL REFER CO.CR OARS E W CRAM IR'.ADO .00 COM ALI.NCf1uGp VARMN SPEED DTORS F0 RF CREME AMASS , Ce FO .(N }S [R A1 MECCA DE RELO CDAD RM GE Df M SLS1RlC11p 11 CREME TOLS DE LEN E SE TR.he. O dlAIC DE KLO mes P52 CAPACITOR OGENARC E MSTR.ROp TRAWAIXf POUR WKMft canny:COKS PN4 'WA! TO CO M ASWE OECMIRCER LES Rf00CATEOW • CESCM2CA DELOONONSREGL WORE SERVCRO =LSO RESULT RE PAS RESPECIERCES SCRAMS CC et EIO REALOMLO AM,ERpaaeNTE EQUIPMENT DOOR INTERLOCKING R vanlCSI semuNARr SLE u CR,L s 0 SERVS LeS�aes PERSCRRES GROUND DISCONNECT SWITCH IREMELLES UNIT CONTROL BOX FIELD SUPPLIED CONTROLLER TERMINAL BLOCK 24VAC. 15VA MAX • 1TB5-1 I —0 I I I OPEN • DAMPER ACTUATOR 1782•4 �- 0 I I CLOSE • DAMPER ACTUATOR 1782.5 0 EXHAUST F ' AN EXHAUST FAN RELAY 1785.2 0 24VAC. 2VA MAX ' IOPEN - 02 VALVE/ 1783.1 F— � ELECTRIC MEAT 1st STAGE O I CLOSE • COIL 02 VALVE/ 1783-2 ELECTRIC HEAT 2nd STAGE 0 FAN - HIGH SPEED 1783-6 O ■ FAN •LOW SPEED 17813 1785.2 24V O 0— « «« COIL 41 VLV I,� OPEN - COIL 01 VALVE 1783-4 1783-4 ON /OFF NA MAX. ! I 0 0.—< F C E—< € L I CLOSE • COIL NI VALVE 17815 1785 -1 COM O 0—( E---C (--< C - CAUTION PRECAUCION ATTENTION USE COPPER CONDUCTORS ONLY! MUTILISER OUE DES CONDUCTEURS EN CUIVRE! IUTILICE UNICAMENTE CONDUCTORES DE COBRE! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT LES BORNEO DE LLNITE NE SONT PAS CONOUES LAS TERMINALES DE LA UNIDAD NO ESTAN DISEIIADAS OTHER TYPES OF CONDUCTORS POUR RECEVOIR D'AUTRES TYPES DE CONDUCTEURS PARA ACSPTAR OTROS TIPOS DE CONDUCTORES FAILURE TO DO SO MAY CAUSE DAMAGE TO THE LUTILISATION DE TOUT AUTRE CONDUCTEUR PEUT SI N01.0 HALE, PUEDE OCASIONAR DANO AL EQUIPO EQUIPMENT. ENDOMMAGER L'EQUIPEMENT - , FLD = Fumished Trane / Installed by Others Trane Equipment Submittal - Pace 11 of 12 • White House/ Black Market - Washington Sq. - OR September 07, 2005 Field Installed Options - Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job. Product Family - BCXC Blower Coil Air Handler Item Tag(s) Qty Description Model Number Al No Tag 1 BCXC Blower Coil Air Handler BCHC090G2* Al G07L2120AC001 A M200000000000 Field Installed Option Description Part/Ordering Number 2 -Way, 2 Position N.C. 9.0 CV, 1 1/4 ", 2 Position, 1 1/4" PIPE Deluxe Piping Package • FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Pace 12 of 12 �v) Fire and Life Safety Inspection Checklist for Rated Assemblies ❑ Exterior Walls— 704 - Rated- inside 1 2 3 4 Rated — exterior 1 2 3 4 Parapet Y N Openings protected Y N ❑ Fire Wall — 705 ❑ Party wall Y N (503.2) - Parapet Y N Openings protected Y N 705.5 Horizontal continuity. Fire walls shall be continuous from exterior wall to exterior wall and shall extend at least 18 inches (457 mm) beyond the exterior surface of exterior walls. "See Code book for exceptions" 705.6 Vertical continuity. Fire walls shall extend from the foundation to a termination point at least 30 inches (762 mm) above both adjacent roofs. "See Code book for exceptions" 4 U Fire Barriers - 706 - Rated 62 3 4 Openings protected GI N 74,1/ 14-0,10() 706.4 Continuity of fire barrier walls. Fire barrier walls shall extend from the top of the floor /ceiling assembly below to the underside of the floor or roof slab or deck above and shall be securely attached thereto. These walls shall be continuous through concealed spaces such as the space above a suspended ceiling. ❑ Shaft Enclosures — 707 - Rated 1 2 3 4 Openings protected Y N 707.5 Continuity. Shaft enclosure walls shall extend from the top of the floor /ceiling assembly below to the underside of floor or roof slab or deck above and shall be securely attached thereto. These walls shall be continuous through conceal such as the space above a suspended ceiling. The supporting construction shall be protected to afford the required 1 • rating of the element supported. Hollow vertical spaces within the shaft enclosure construction wall shall be fire-sto11 .1 floor level. Ik z111450e El Fire Partitions - 708 - Rated 1 2 3 4 Openings protected Y N 708.4 Continuity. Fire partitions shall extend from the top of the floor assembly below to the undersi. ' .: the fl' or roof slab or deck above or to the fire-resistance-rated floor /ceiling or roof/ceiling assembly abov , - ' securely attached thereto. If the partitions are not continuous to the deck, and where constructed o �' �'T`'; ib construction, the space between the ceiling and the deck above shall be fire - blocked or draft .. • ped ' . ;;�,•, rdance with Sections 717.2.1 and 717.3.1 at the partition line. ❑ Smoke Barriers — 709 - Rated 1 2 3 4 Openings protected Y N r 709.4 Continuity. Smoke barriers shall form an effective membrane continuous . m `;; ., 'de - . to outside wall and from floor slab to floor or roof deck above, including continuity through concealed spaces as P'< ;, found above suspended ceilings, and interstitial structural and mechanical spaces. The supporting construction . - p ':,,, ed o afford the required fire- resistance rating of the wall or floor supported in buildings of other than Type IIB, I'' ". 'r t: co • . I 'on. El Smoke Partition — 710 - Rated 1 2 3 4 Openings pr . tected 710.4 Continuity. Smoke partitions shall extend from the floor. c'+ e underside of the floor or roof deck above or to the underside of the ceiling above where the ceiling membrane is to limit the transfer of smoke. ❑ Horizontal Assemblies — 711 - Rated 1 2 3 ';; ! „: ning - protected Y N 711.4 Continuity. Assemblies shall be continuous without ope ��:> ;.. penetrations or joints except as permitted by this section and Sections 707.2, 712.4 and 713. Skylights and other M :lions 11 ' ugh a fire- resistance-rated roof deck are permitted to be unprotected, provided that the structural inte j .f 7.”' istance-rated roof construction is maintained ❑ Membrane Penetrations — 712 ❑ Through Penetrations — 712 ❑ Fire Resistive Joint System — 7 ❑ Fire Resistive Rating of Structur embers — 714 ❑ Opening Protective — 715 ❑ Ducts & Air Transfer Openings — 716 - 716.4 Access and identification. Fire and smoke dampers shall be provided with an approved means of access, large enough to permit inspection and maintenance of the damper and its operating parts. ..Access points shall be permanently identified on the exterior by a label having letters not less than 0.5inch (12.7 mm) in height reading: SMOKE DAMPER or FIRE DAMPER ❑ Thickness of Protective Coverings — 720 -Table 720.1(1) ❑ Safety Glazing — 2406 ❑ Other -