Plans Fire and Life Safety Inspection Checklist for Rated Assemblies S .
❑ Exterior Walls— 704 - Rated - inside 1 2 3 4 Rated — exterior 1 2 3 4 Parapet Y N Openings protected Y N
❑ Fire Wall — 705 ❑ Party wall Y N (503.2) - Parapet Y N Openings protected Y N
705.5 Horizontal continuity. Fire walls shall be continuous from exterior wall to exterior wall and shall extend at least 18 inches
(457 mm) beyond the exterior surface of exterior walls. "See Code book for exceptions"
705.6 Vertical continuity. Fire walls shall extend from the foundation to a termination point at least 30 inches (762 mm) above
both adjacent roofs. "See Code book for exceptions"
❑ Fire Barriers - 706 - Rated 1 2 3 4 Openings protected Y N -
706.4 Continuity of firebarrier walls. Fire barrier walls shall extend from the top of the floor /ceiling assembly below to
the underside of the floor or roof slab or deck above and shall be securely attached thereto. These walls shall be continuous
through concealed spaces such as the space above a suspended ceiling.
❑ Shaft Enclosures — 707 - Rated 1 2 3 4 Openings protected Y N
707.5 Continuity. Shaft enclosure walls shall extend from the top of the floor /ceiling assembly below to the underside of
floor or roof slab or deck above and shall be securely attached thereto. These walls shall be continuous through conceal::
such as the space above a suspended ceiling. The supporting construction shall be protected to afford the required . ',-
rating of the element supported Hollow verticalpaces within the shaft enclosure construction wall shall be fire -stop
floor level.
Fire Partitions - 708 - Rat 2 3 4 Openngs
08.4 Continuity. Fire partitions s extend froi the top of the floor assembly below to the undersi - the fl ' .
or roof slab or deck above or to the fire- resistance-rated floor /ceiling or roof/ceiling assembly abov " • . •
securely attached thereto. If the partitions are not continuous to the deck, and where constructed o .b {
construction, the space between the ceiling and the deck above shall be fire- blocked or draft ped • rdance*
with Sections 717.2.1 and 717.3.1 at the partition line.
� P e� �
❑ Smoke Barriers — 709 - Rated 1 2 3 4 Openings protected Y N
709.4 Continuity. Smoke barriers shall f o r m an e ff e c t i v e membrane continuous . m': 'de to outside wall and from floor
slab to floor or roof deck above, including continuity through concealed spaces `:., as �': ; ; found above suspended ceilings, and
interstitial structural and mechanical spaces. The supporting construction I. - p o afford the required fire- resistance
rating of the wall or floor supported in buildings of other than Type DB, ion.
• F
❑ Smoke Partition — 710 - Rated 1 2 3 4 Openings pr i tecte
710.4 Continuity. Smoke partitions shall extend from the floor • s. e underside of the floor or roof deck above or to the
underside of the ceiling above where the ceiling membrane is > to limit the transfer of smoke.
❑ Horizontal Assemblies — 711 - Rated 1 2 3 '., ning; protected Y N
711.4 Continuity. Assemblies shall be continuous without ope penetrations or joints except as permitted by this section and
Sections 707.2, 712.4 and 713. Skylights and other . ' •_rtions 11 .ugh a fire- resistance-rated roof deck are permitted to be
unprotected, provided that the structural inte • f :. istance-rated roof construction is maintained.
kr Membrane Penetrations — 712
Vig Through Penetrations — 712
• Fire Resistive Joint System — 7
❑ Fire Resistive Rating of Structur embers — 714
,, Opening Protective — 715
Dij Ducts & Air Transfer Openings — 716 - 716.4 Access and identification. Fire and smoke dampers shall be provided
with an approved means of access, large enough to permit inspection and maintenance of the damper and its operating pails.
..Access points shall be permanently identified on the exterior by a label having letters not less than 0.5inch (12.7 mm) in height
reading: SMOKE DAMPER or FIRE DAMPER.
❑ Thickness of Protective Coverings — 720 -Table 720.1(1)
• Safety Glazing — 2406
❑ Other -