Specifications 93y ' 1 ) 6m_Ao7ao 9= ova, R E CE IVED FEB 9 2009 B N D AR) 1 VIS1 pN SIEMENS Siemens Building Technologies, Inc. 15201 NW Greenbrier Pkwy, Suite A4 Beaverton, OR 97006 Phone: (503) 207 -1900 Fax: (503) 207 -1901 Siemens Building Technologies, Inc. Fire Alarm System Contractor Electrical Contractor FIRE ALARM SUBMITTAL Washington Square Gap Kids Siemens Job Number Siemens Project Manager Sam Correll Submittal Version Date Siemens Project Engineer David Snow Issued For Permit Review 01/30/09 Proprietary document for approval only ,r. Table of Contents SIEMENS 1 BILL OF MATERIAL & COMPONENT SPECIFICATIONS 2 FUNCTIONAL MATRIX 3 BATTERY CALCULATIONS 4 VOLTAGE DROP CALCULATIONS 5 BILL OF MATERIALS SIEMENS Washington Square Gap Kids Fire Alarm System Item Part # Qty Mfg Description 1 FP -11 12 Siemens Intellegent Photoelectric Smoke Detector 2 DB -11 * 10 Siemens Detector Base for FP -11 3 AD2 -XHR 2 Siemens Air Duct Housing for FP -11 Detector 5 MSI -10B 2 Siemens Manual Pull Station, Single Action 6 ST -50` 2 Siemens Sampling Tube 3' -0 - 5' -0 7 E50 -24MCW 2 Wheelock Speaker /strobe, Multi- candela, White 8 RSS -24MCW 2 Wheelock Strobe, Multi - candela, White 9 E60 -24MCC 2 Wheelock Speaker /strobe, Multi- candela, White Ceiling Mount 10 RSS -24MCC 4 Wheelock Strobe, Multi- candela, White Ceiling Mount * No Data Sheet Available PROPRIETARY DOCUMENT FOR APPROVAL ONLY 1 1/30/2009 SIEMENS Fire Safety FP -11 FirePrintTM Detector Intelligent Fire Detector for MXL, MXL -IQ, and MXLV Control Panels ENGINEER AND ARCHITECT SPECIFICATIONS • Most Sophisticated "Detector Intelligence" available today • Multi- Criteria fire detection for the price of a photoelectric detector • FirePrintTM Technology to discriminate between deceptive phenomena and an actual fire • Easily programmed to match specific hazard profiles from the control panel • Pre -Alarm reporting based on fire profile selected • Remote sensitivity measurement capability �y v- • System logic activation based on any of three inputs from II, , detector (smoke, heat or neural network) • Field cleanable chamber with replaceable chamber w parts available , _ • Multi -color detector status LED _ • Two-wire operation • Compatible with Model DPU or FPI -32 field -r�,: �' p programmer /tester -, s, . . • Supports EnviroLINK software based automatic environmental compensation - • Backward compatible with older MXL systems (Rev 2 and above) • Optional fully programmable relay base , audible base, and duct housing • UL Listed, ULC Listed, CSFM, FM, NYMEA U)Approved Introduction The FP -11 Intelligent Fire Detector provides the life need for cumbersome, unreliable mechanical program - safety industry with the most highly evolved detection ming methods and reduces installation and service system available today. The FP -11 utilizes advanced costs by electronically programming and testing the detection technology that allows the detector to detector prior to installation. distinguish nonthreatening deceptive phenomena, such The FP 11 fire detector is compatible with the MXL as cigarette smoke, from actual fire hazards, while optimizing detection for the area in which it is in- family of control panels including the MXL, MXLIQ, stalled. No other detection system available today and MXLV. offers a higher level of protection or nuisance The FP -11 detector is Underwriters Laboratories and alarm immunity. The FP -11 uses state -of- the -art Underwriters Laboratories of Canada Listed. microprocessor circuitry with error check, detector self- diagnostics and supervision programs. Description The FP 11 intelligent fire detector is compatible with The FP -11 is a plug -in, two -wire, multi- sensor detector the Siemens Building Technologies, Fire Safety Diva kith both photoelectric and thermal inputs and is sion, Model DPU or FPI -32 field programmer /tester, which is a compact, portable, menu - driven accessory compatible with the MXL family of control panel for electronically programming and testing detectors, systems. Each detector consists of a dust resistant, easily and reliably. The DPU or FPI -32 eliminates the field cleanable photo chamber, a solid state CATALOG NUMBER 6175 non - mechanical thermal sensor, microprocessor based evaluating this information with sophisticated electronics with a low - profile plastic cover and base. mathematical formulas, or algorithms, comparing this The FP -11 utilizes state -of- the -art ASIC and surface input to characteristics of both threatening fires and mount technology for maximum reliability. Every FP -11 deceptive phenomena that would "fool" any ordinary fire detector is shipped with a protective dust cover. detector. This technology was developed over years of research and reviewing the results of over 20 years of The FP -11 fire detector utilizes an infrared light fire test data in one of the world's most advanced fire emitting diode (IRLED), and light sensing photodiode. research centers. The results of this research are the Under normal conditions, light transmitted by the LED mathematical models that form the algorithms used in is directed away from the photodiode and scattered FirePrint. No other fire detector has this level of through the smoke chamber in a controlled pattern. intelligence or this amount of research and develop - The smoke chamber is designed to manage light ment supporting it's design. dissipation and extraneous reflections from dust particles or other non -smoke airborne contaminants in The microprocessor's software can identify and such a way as to maintain stable, consistent detector disregard false input caused by radio frequency (RFI) operation When smoke enters the detector chamber, and electromagnetic (EMI) interference, and validates light emitted from the IRLED is scattered by the all trouble conditions before annunciating or reporting smoke particles and is received by the photodiode. to the control panel. The FP -11 detector's microproces- sor uses an integral EEPROM to store the detector's The FP -11 also utilizes a modern, accurate, shock- address and other critical operating parameters which resistant thermistor to sense temperature changes. include the assigned program values for alarm and The "on- board" FirePrint technology allows the trouble thresholds. Communications within the detector to gather smoke and thermal data, and to detector itself and between the FP -11 and the control analyze this information in the detector's "neural network" By comparing data received with the panel, or with the FPI -32 field programmer /tester, are supervised and safeguarded against disruption by common characteristics of fires, or fire fingerprints, reliable, microprocessor based error checking routines. the FP -11 can compare these "Fire Prints" to those of Additionally, the microprocessor supervises all deceptive phenomena that cause other detectors to EEPROM memory locations and provides a high alarm. The advanced FirePrint technology allows the degree of EEPROM failure fault tolerance. FP -11 to accurately determine a true fire hazard from a nonthreatening deceptive phenomena WITHOUT In MXL(V) applications, the FP -11 determines its needing to use alarm delaying verification and confer- operating status to be normal, in alarm, or in trouble mation techniques, which can increase the probability depending on the difference between the alarm of losses due to fire. threshold values stored in the detector's memory and The FP 11 provides the highest level of detector the detector's latest analog measurement. The detector then communicates changes in its status to intelligence available today with a detector /control the control panel. panel link that allows the user to program the detector for the specific hazard profile Detectors are optimized In addition, the MXL(V) control panel will sample the by selecting one of the following applications: value of the FP -11's analog signal over a period of time Office /Retail in order to determine if those values indicate exces- • Lobby sive buildup in the photo chamber; if so, the MXL(V) • Computer Room will indicate that the particular detector requires • maintenance. • Dormitory • Healthcare The FP -11 is listed as a self - testing device. The FP -11's • Parking Garage visible light emitting diode (LED) flashes green every • Utility/Transformer Room 4 seconds to indicate it is communicating with the • Hostile Environment control panel and that it has passed its internal self- • Precious Storage test. Should the detector sense a fault or failure within • Air Duct its systems, the LED will flash amber and the detector • Warehouse /Light Manufacturing will transmit that information to the control panel. The software does the rest; no guessing on detector A quick visual inspection is sufficient to indicate the condition of the detector at any time. If more detailed sensitivities or alarm verification; the control panel information is required, a printed report can be programs the FP -11 detector for the protected area provided from the MXL panel indicating the status without hassle and without confirmation delays. and settings assigned to each individual detector. Once optimized for the hazards in the protected area, the FP -11 provides the best detection you can buy. When the FP -11 moves to the alarm mode, it will flash Should the operator or installer forget to program the amber and transmit that information to the control detector, the FP -11 will revert to a default setting that panel. When the MXL(V) confirms the detectors allows it to operate as a standard photoelectric or condition, the panel will instruct the FP -11 to flash red photothermal detector. and to continue flashing until the system is reset at the control panel At that same time, any user defined The FP -11's FirePrint technology monitors input from both the photo chamber and the thermal sensor, system alarm functions programmed into the system All FP -11 detectors are approved for operation within are activated. Each FP -11 detector can operate one the UL specified temperature range of 32 to 100 remote alarm indicator, one auxiliary relay, or one degrees F (0 to 38 degrees C) audible base. Detector sensitivity, calibration, and identification are Application Data dynamically supervised by the control panel. Detector Installation of the FP -11 series of fire detectors sensitivity and pre -alarm levels are a function of the requires a two -wire circuit of 18 AWG (minimum) application chosen at the control panel and are thermoplastic fixture wire enclosed in conduit, or 18 controlled by the panel. If an alternate, non - FirePrint AWG limited energy, shielded cable without conduit, mode is selected, then the sensitivity can be changed if permitted by local codes. Field wiring should from the control panel. _ conform to local and National Electric Codes and the The DPU or FPI -32 Program/Test accessory is used to control panel wiring specifications. program and verify the detector's address. The "T- tapping" is permitted only for Style 4 (Class B) technician selects the accessory's program mode to wiring. enter the desired address. The DPU or FPI -32 auto- matically sets and verifies the address and tests the FP -11 fire detectors can be applied within the maxi- detector. It also allows the user to change the device mum 30 foot center spacing (900 sq. ft. areas) as ID from that of an FP -11 to an older detector ID such as referenced in NFPA 72. This applications guideline is an ILP -1, ILPT -1, ILP -2, ID -60P or ID -60PT to allow for based on ideal conditions, specifically, smooth ceiling easy replacement of older detectors without the need surfaces, minimal air movement, and no physical of reprogramming the control panel. obstructions between potential fire sources and the detector Do not mount detectors in close proximity The FPI -32 operates on AC power or rechargeable to ventilation or heating and air conditioning outlets. batteries, providing flexibility and convenience in Exposed joints or beamed ceilings may also affect safe programming and testing equipment almost anywhere spacing limitations for detectors. Should questions When in the test mode, the DPU or FPI -32 will perform arise regarding detector placement, observe NFPA a series of diagnostic tests without altering the 72 guidelines. address or other stored data, allowing technicians to determine if the detector is operating properly Good fire protection system engineering and common sense dictate how and when fire detectors are The FP -11 fire detector may be installed on the same installed and used. Contact your local Siemens initiating circuit with IL or ID series detectors (Photo- Building Technologies, Fire Safety Division authorized electric, thermal, or ionization), MSI series manual sales outlet whenever you need assistance applying stations, TRI series interfaces, ICP output control FirePrint in unusual applications. Be sure to follow devices, or CZM series of addressable, conventional NFPA guidelines, UL /ULC approved installation zone modules. instructions, which are included with every detector, All FP -11 detectors can be cleaned in the field, when and local codes as for all fire protection equipment. required, by simply removing the detector cover and unsnapping the photo chamber. There is also the Dimensions option of cleaning the interior of the detector with a clean, soft cloth or brush, or replacing the labyrinth and I 6' Diameter Base bug screen included in the detector maintenance kit, model DMK -11. _ The FP -11 uses the low profile surface mounting base, model DB -11. This base mounts on a 4 -inch octagon, square, or a single gang electrical box. The base 2 3` utilizes screw clamp contacts for electrical connections Overall Height and self- wiping contacts for increased reliability The base can be used with the optional LK -11 detector1���J�► locking kit which contains 50 detector locks and an tc /� installation tool, to prevent unauthorized removal of the detector head. The DB -11 base has integral decora- tive plugs to cover the outer mounting screw holes. The FP -11 is electrically compatible with existing MXL detector accessories including relays, remote lamps, duct housings, and audible bases. With duct housings, a base adapter and new detector housing cover are required (order AD -11 UK upgrade kit). To use existing DB -3S base or audible base, the FP -11 requires a DB- ADPT base adapter. Technical Specifications Current Requirements: Normal 750 pa Alarm 750 pa Operating Temperature: +32 °F (0 °C) to 100 °F (38 °C) per UL 268/268A Humidity• 0 -93% Relative Humidity Non - Condensing Ordering Information Part Model Description Number FP-11 Addressable FirePrint Fire Detector 500- 095112 DB -11 Detector Mounting Base for Series 11 500-094151 DB -I1E Detector Base (Small) 500. 094151E AD2 -P Air Duct Housing for use with FP -11, HFP -11, HFPO -11, 500- 649706 PE -11 AD2 -XHR Air Duct Housing for use with FR11, HFP -11, HFPO -11 500- 649708 with relay ADBX -11 Audible Base 500 - 096181 DB -X11RS Relay Base for Series 11 Intelligent Detectors 500 - 096125 RLI -1 Remote (red) alarm indicator- 4" octagon box mount 500- 390673 RLI -2 Remote (red) alarm indicator- single gang box mount 500-390674 LK -11 Base Locking Kit for Series 11 detectors 500- 695350 DMK -11 Series 11 Maint Kit (replacement labyrinth and bug 500 - 695338 bug screen) DB -ADPT Base Adapter to DB -3S Base 500 - 094187 In Canada Order - FP-11C Addressable FirePrint Fire Detector (ULC) 500- 095112C DB -11C Detector Mounting Base for Series 11 (ULC) 500-095687 AD -I1PC Air Duct Housing (ULC) 500- 095984 DB- X11RSC Relay Base for Series 11 Intelligent Detectors (ULC) 500- 096125C ADBX -11C Audible Base for Series 11 Intelligent Detector (ULC) 500- 096181C Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park NJ 07932 5/06 Brampton, Ontario Siemens Building Technologies Tel (973) 593 -2600 10M Canada L6T 5E4 g 9 IeS FAX (973) 593 -6670 SFS-IG Tel (905) 799 -9937 May2006 Fire Safety Website www sbt siemens com /f is Printed in U S A FAX (905) 799 -9858 Sucetsodes shoal dated 6/03 SIEMENS Fire Safety Air Duct Housings-AD2 Series ENGINEER AND ARCHITECT SPECIFICATIONS • For Series 11 Detectors — ._-- -= • Relay Models Available ___v ( a SIEMENS p • Design for Air Velocity Range of 100 -�= to 4000 fpm ^ n ,%no-r z ^� • Alarm LED Visible From Front • Clear Housing Cover for Quick , r Identification of DetectorType Removable =�"" With Only Four Captive Screws • ® UL Listed, CSFM Approved, ULC Listed Introduction Description The Siemens BuildingTechnologies, Fire Safety Division The Fire Safety air duct housing is uniquely designed to air duct detector housings are designed to be used with use the photoelectric detector. the 11- Series detectors. Designed for installation directly to heating, ventilating and air conditioning duct systems, Sensitivity of PE -11 detectors can be checked by viewing they comply with National Fire Protection Association the LED or an RSAW -11 or RSAC -11 multicolor remote Standard No. 90A. When equipped with photoelectric lamp. A green flash indicates the detector has passed its detectors, these units will signal the presence of hazard- self test Amber indicates a trouble condition, and red ous quantities of products of combustion or smoke being indicates an alarm state. carried through the duct system. Air duct detectors are HFP- 11,HFP0 -11 and FP -11 sensitivity may be viewed not intended to be substituted for open area detection. from the multi -color LED on the detector or preferably Air duct housings can be equipped with optional relays. may be printed by command on an optional printer from These relays are utilized to operate any supplementary the MXL control panel equipment when smoke or particles of combustion The detector unit employs a cross - sectional sampling are detected. principle of operation. Inlet sampling tubes are available in Note: Most conventional time control equipment guaran four lengths (see table on reverse side). Outlet sampling tee only one detector per zone when the detector oper tubes are one common length. A continuous cross ated relay function is critical.The connection of a remote sectional sample of air moving through the duct stratifica lamp and a remote relay per detector is allowed with tion or skin effect phenomena occurring in the duct that PXL or System 3TM only, other conventional systems could prevent combustion product or smoke (especially may use either a remote lamp or a relay. in large ducts) from reaching a spot type detector. With the MXL series of control panels, up to 60 detectors In addition, the unique design of the sampling chamber per circuit having relays may be used.The connection of a insures uniform sensitivity in air velocities, ranging from a remote lamp or a remote relay is allowed for each low of 100 feet per minute to as high as 4000 feet per detector but not both. minute. The housing comes with two' " conduit With the FireFinderXLS series of control panels, up to 252 detectors per circuit having relays may be used. The Connection of an intelligent remote lamp and a remote Relay (ILED), is also allowed. Air duct housings (see Ordering Information) are Under- writers Laboratories, Inc. listed. CATALOG NUMBER 6185 knockouts and one 1/2" conduit opening for a number of 3 Technical Data wiring entry ports. Temperature Range 32 °F (0 °C) -100 °F (38 °C) The inlet sampling tube length is determined by the Altitude Range No Altitude Limitations width of the air duct being protected.The inlet tube nearest to but greater than the duct width should be used Relative Humidity 10-85% (non -condens (see table).The inlet tube can then be trimmed at the job ing /non- freezing) site to the exact width of the duct.The outlet sampling tube for all ducts, irrespective of width, has a fixed length Air Duct Velocity Range 100 -4000 Ft/Min. of approximately 5 5 inches and is supplied with the duct housing. SamplingTube Pressure Greater than 0.01 amps Range of Differences less than 1.2 inches of When the use of a remote relay is required, order model water column AD2 -PR for conventional systems, AD2 -XHR for address Note to Architect:When building codes regulate the able systems. When required the WP -2000 weatherproof location of detectors within ventilating systems, make enclosure for Duct Housing is available. For full details, refer to installation instructions part number 315 - 049708. sure that the number and locations of detectors is in accordance with the code regulations. Sampling Tube Selection Table Order Information Duct Width Sampling Tube Model No. Model Description Part Number For duct widths 6' to 1' ST-10 AD2 -P Air Duct Housing for use with FP -11, HFP -11, 500 - 649706 For duct widths over 1' to 3' ST-25 HFPO -11, PE -11 For duct widths over 3' to 5' ST-50 AD2 -PR Air Duct Housing for use with PE -11 with relay 500 - 649707 (requires support) AD2 -XHR Air Duct Housing for use with FP -11, HFP -11, 500 - 649708 For duct widths over 5' to 10' ST-100 HFPO -11, with relay (requires support) ST-10 Sampling Tube for Ducts 6" to 1' 500 - 649710 ST-25 Sampling Tube for Ducts over 1' to 3' 500 - 649711 Maintenance of the detector is easily accomplished by ST -50 Sampling Tube for Ducts over 3' to 5' 500- 649712 the removal of the Series 11 duct housing sampling ST 100 Sampling Tube for Ducts over 5' to to' 500 -649713 chamber cover The detector, which plugs into the hous- ing, is easily removed for cleaning by a trained technician. Product Includes All that is necessary for installation of the air duct detector One Short Return (outlet)Tube is the cutting of three small holes for the sampling tube installation (template included) and the drilling of four One Stopper holes for mounting the air duct housing.The unit is then easily mounted in place and connection made to the Two #12 + 3 A" Sheet Metal Screws existing wires or terminals if optional accessories MountingTemplate are utilized. ST 50 and ST 100 require support. ST-1001s shipped Note: Detector and sampling tube to be purchased pped In separately two five foot pieces with a coupling for field assembly. Note: Minimum hardware required is one Air Duct Housing Assembly, one Sampling Tube and one Detector NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment will be considered a misapplication of Fire Safety equipment and as such voids all warranties either expressed or implied in regard to loss, damage, liabilities and /or service problems Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 9/06 Brampton. Ontario Siemens Building Technologies Tel (973) 593 -2600 EM Canada L6T 5E4 g g 16S FAX 1973) 593 -6670 SFS-IG Tel (905) 799 -9937 September2006 Fire Safety Website www sbt siemens com /f is Printed in U S A FAX. (905) 799 -9858 sopersedos sheer dated 4i06 SIEMENS Fire Safety Intellig Initiating Devices Manual Fire Alarm Boxes MSI -10B and MSI -20B Intelligent Manual Fire Alarm Boxes for MXL, IXL, and XL3 Control Panels ENGINEER AND ARCHITECT SPECIFICATIONS • Durable Design • Shock and Vibration Resistant • Pull Down Lever Remains Down Until Reset • Custom Microcomputer ChipTechnology • Dynamic Supervision' • Reset with Allen Key r` ? %� _ • No Break Rods Necessary �'_ -� • TwoWire Operation .0- U s HERE, Q. • Surface or Semiflush Installation THEN • DPU orFP1 -32 Programs and Verifies Device's Address and Tests Device's Functionality iPULL DOWN PULL DOWN' • Electronic Address Programming is Easier and More Dependable ; ! SIEMENS SIEMENS • Single and Double Action Models Available { ^ • 0, Listed, CSFM, FM and NYMEA Approved Introduction Siemens BuildingTechnologies, Fire Safety MSI -10B The MSI -10B and 20B manual fire alarm boxes operate and 20B intelligent manual fire alarm boxes provide the with the MXL, IXUICON -1 and XL3 control panels. markets' most advanced method of address programming and supervision, combined with sophisticated control panel The manual fire alarm box's microcomputer chip has the communication. Each MSI manual fire alarm box incorpo- capacity of storing, in memory, identification information rates a new custom microcomputer chip.The microcom as well as important operating status information. puter chip technology, and its sophisticated bi- directional Fire Safety's innovative technology also allows all MSI communication capabilities with the control panel, achieves Series Intelligent manual fire alarm boxes to be pro - the state of an "Intelligent Initiating Device" grammed by using the Model DPU or FPI -32 Program - mer/Tester. The Programmer/Tester is a compact, Description portable, menu driven accessory which makes pro - The MSI 106 and 20B are constructed of durable molded gramming and testing a manual fire alarm box device polycarbonate material which is matte finished in red with faster, easier and more -32 dependable than the need methods. white lettering.The housing accommodates a "pull- methods. The DPU or FPI-32 eliminates the need for down" lever which, when operated, locks in position the device's mechanical addressing mechanisms, such indicating the manual fire alarm box has been activated. as program jumpers, dipswitches or rotary dials The pull down lever remains down and locked until the because the Programmer/Tester electronically sets the manual fire alarm box's address into its microcomputer manual fire alarm box is reset.The manual fire alarm box is reset only by opening the hinged housing cover with chip, nonvolatile memory. Vibration, corrosion and an alien key and then closing and locking the cover. CATALOG NUMBER 6187 Replaces Catalog No 6162 other conditions which deteriorate mechanical addressing Ordering Information mechanisms are no longer a cause for concern. _ Shipping Wt. The MSI -10B and 20B are fitted with screw terminals for Model Description Lb. Kg. connection to an addressable circuit.They can be either MSI -108 Addressable Manual fire 2 .90 surface or semif lush mounted. Alarm Box. Single Action The MSI Series manual fire alarm boxes derive their MSI -206 A larm B Manual Fire 2.5 1.13 Action power, communicate information and receive corn- SB -5R Surface Mounting Box 15 68 mands over a single pair of wires. LTP Reset Tool Package (Contains 2 Tools) .5 .23 The MSI Series is compatible on the same circuit with all IL and ID -60 Series ionization, photoelectric or thermal detectors, TRI Series interfaces or CZM Series addressable conventional zone modules. The MSI -10B and 20B intelligent manual fire alarm boxes are Underwriters Laboratories, Inc. listed. Current Draw 1mA Mounting Data c' i,..,>.. -< HOUSING iq W HINGED TO NAMEPLATE � ,` -T SB-5R BACKPLATE. \\ 5 1r1 1 Y116to p // HOUSING ® ` �,t�e4� ,� R , , 1 0 O ; ' \ / 0 J in k il G ` o 31/2 in DEEP a p SWITCH BOX LOCKING \ p 0 (USER SUPPLIED) SCREW BACKPLATE \\ .--- SURFACE MOUNTING ENCLOSURE • • Fire Safety Fire Safety 8 Fernwood Road 2 Kenview Boulevard Florham Park. NJ 07932 12/04 Brampton" Ontario Siemens Building Technologies Tel (973) 593 -2600 10M Canada L6T 5E4 g g I8S FAX' (973) 593-6670 SFS.iG Tel (905) 799 -9937 December2004 Fire Safety Website www.sbt siemens corn/f is Printed in U S A FAX (905) 799 -9858 Supersedes sheet dated 7103 • COOPER Notification Series E50 Speaker and Speaker Strobes tic t .5r SERIES E50 SERIES E50 Speaker Strobe Speaker Description Features The Wheelock Series E50 Speakers and Speaker Strobes feature • Approvals include. UL Standard 1971, UL Standard 1480, New high efficiency sound output, with dual voltage (25/70 VRMS) York City (MEA), California State Fire Marshal (CSFM), Factory capability and field selectable taps from 1/8 to 2 watts. They are Mutual (FM) and Chicago (BFP). See approvals by model in designed to provide a sleek, aesthetic appearance for emergency Specifications and Ordering Information voice /alarm communications systems. All Series E50 models ADA/NFPA/ANSI compliant • mount to standard 4" x 2 -1/8" electrical boxes (with no extension nng required) and incorporate a speaker mounting plate for faster • Complies with OSHA 29 Part 1910.165 installation. The grille cover snaps on so no mounting screws are • Wall mount speaker strobe models with field selectable candela visible. Attractive surface boxes are also available for surface settings of 15/30/75/110cd or 135/185cd (Multi - Candela installations. models), or 1575cd (Single Candela model) The Series E50 Speaker Strobe models use Wheelock low current • Field selectable taps for 25 or 70 VRMS operation from 1/8 watt draw Series RSS strobes for wall mounted applications. Strobe up to 2 watts options include patented MCW multi - candela strobes with field selectable candela settings of 15/30/75/110 cd or high intensity • High efficiency design for maximum output at minimum wattage MCWH strobes with field selectable 135 /185 candela Models with across a frequency range of 400 to 4000 HZ 1575 candela (75 cd on axis) are also offered. • 24 VDC strobes produce 1 flash per second with wide UL Series E50 Speakers and Speaker Strobes provide high audio output "Regulated Voltage" of 16 to 33 volts using filtered DC or with dear audibility and are designed to meet the critical needs of the unfiltered VRMS input voltage life safety industry for effective emergency voice communications, • Synchronize with Wheelock SM, DSM or Wheelock tone signaling and visible signaling to alert the hearing impaired. PS- 12/24 -8CP and PS- 12/24 -8MP Power Supply with built -in The strobe portion of all Series E Speaker Strobes may be sync protocol synchronized when used in conjunction with the Wheelock SM, Mount to 4" square x 2 -1/8" deep backbox with no extension DSM Sync Modules or the Wheeloc k's PS- 24 -8MC Power Supply ring required with Patented Sync Protocol. Wheelock synchronized strobes offer an easy way to comply with ADA and NFPA regulations concerning • Snap on grille cover with no visible mounting screws photosensitive epilepsy. • Fast installation with IN /OUT screw terminals using #12 to #18 Series E50 Speaker Strobes are UL Listed for indoor use under AWG wires Standard 1971 (Signaling Devices for the Hearing - Impaired) and Standard 1480 (Speaker Appliances). All inputs employ IN /OUT wiring terminals for fast installation using #12 to #18 AWG wiring and are compatible with FACP line supervision. Color options for the Series E50 Speakers and Speaker Strobes are red or off - white. ,.c.y. NM NA c . 1> MEA APPROVED S5391 151 -92 -E 7125-0785 165 7320 -0785 166 NOTE All CAUTIONS and WARNINGS are identified by the symbol A All warnings are punted in bold capital letters WARNING PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR 'PLYING THIS PRODUCT VISIT WWW COOPERWHEELOCKCOM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. ILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range ". Note that NFPA -72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 °F to 120 °F (0 °C to 49 °C) and maximum humidity of 93% (± 2 %). • Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range Pnor to this change UL used the terminology "Listed Voltage Range" Table 1 Average RMS Current * RMS current ratings are per UL average RMS E50 Strobe Current Wall Mount method. UL max current rating is the maximum E50 RMS current within the listed voltage range (16 -33v Speaker 241575W 24MCW 24MCWH for 24v units) For strobes the UL max current is Strobes 1575cd 15cd 30cd 75cd 110cd 135cd 185cd usually at the minimum listed voltage (16v for 24v 24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 units). For unfiltered FWR ratings, see installation instructions. UL max* 0.090 0.060 0.092 0.165 0.220 0.300 0.420 Table 2. E50 UL Reverberant dBA @ 10 Feet ** watts 1/8 1/4 1/2 1 2 '50 Speaker 77 79.5 82.5 85 88 1E50 Speaker Strobe 77 79.5 82.5 85 88 * *dBA ratings are based on UL testing under UL Standard 1480 Wiring Diagrams" SERIES E50 SPEAKER & STROBE OPERATE SERIES E50 SPEAKER STROBES SYNCHRONIZED INDEPENDENTLY (NON -SYNC OR SYNC) WITH MULTIPLE DSM MODULES DSM X1❑ F n PLIAN C E0 T - ❑ - FI'CI:J �� E❑ 4F Strobe NAC Cl[ S y "C FLI:.NE❑ LLLLLIII ON \OI CEO ,R EJLRO Fill irgi E S,Cli,T I:.N❑ PANEL. DSM X2❑ Note Figure shows =2 FRUD u...a ±[ 1 — — — — — — ±E3'-V`,',. AO Strobe NAC .�� v " =❑ �3 �� interconnection to _ C❑ ■$ t� ` strobe through sync ,TRoBE,❑ r y — — — — — o ❑ 21112 MNAJLE.I I ' r � 'DSM X30 module Speaker POWER SUPPLY❑ A s Y " =❑ ortion requires 2 PO -. P Q JR FACED g % % S P❑ strobe NAC C'r'f +R IMMIZN separate conductors +L - ■ +C} II — LL to communications DSM Interconnecting wiring shown. Maximum c system STROBE° SPEAKER° twenty (20)0 SERIES E50 SPEAKER STROBE APPLIANCES SERIES E50 SPEAKER STROBE APPLIANCES & RSS SYNCHRONIZED WITH DSM MODULE SINGLE STROBES SYNCHRONIZED WITH PS- 12/24 -8CP and CLASS "A" DSM❑ PS- 12/24 -8MP series PS- 12/24 -8MP or PS- 12/24 -8CP0 STP.OBE° NAC° SYNC° CIP.CUITO -1 :0 // II OUT o •OUT ❑ E" ‹ OUTPUTSD EOLRD / a IN w �� IETE1 F❑ 1 -40 J 9 - CLASS❑ MINUS 10 T1 ❑ 1-40 / AUDIBLEI CO 2- CLASS❑ MINUS 20 "A'❑ J o ®ENI �• P❑ �/ IN 20 STROBE': // + OUT z❑ _It a NACO CI RCUITO Series PS- 12/24 -8l PO RETURN❑ or PS- 12/24 -8C• Specifications and Ordering Information Surface Agency Approvals Model Order Wall Ceiling Strobe Gnll Flush Mount Mount Mounting 9 Y PP Code Mount Mount Candela Color Bacbox Backbox Options UL MEA CSFM FM BFP E50 -R 0222 X X - Red 4' x 4" x 2 -1/8" E5OSB -R E,O,P,Q,R,U,Y,AA X • X X • E50 -W 0223 X X - White 4' x 4" x 2 -1/8" E5OSB -W E,O,P,Q,R,U,Y,AA X * X X • E50- 241575W -FR 0224 X - 15 (75 on Axis) Red 4' x 4" x 2 -1/8" E5OSSB -R E,Q,U,BB X • X X • E50- 241575W -FW 0225 X - 15 (75 on Axis) White 4' x 4" x 2 -1/8" E50 -SSB -W E,Q,U,BB X • X X * E50- 24MCW -FR 0226 X - 15/30/75/110 Red 4' x 4" x 2 -1/8" E5OSSB -R E,Q,U,BB X ' X X E50- 24MCW -FW 0227 X - 15/30/75/110 White 4' x 4" x 2 -1/8" E50 -SSB -W E,Q,U,BB X • X X E50- 24MCW -MW 5219 X - 15 /30/75 /110 White 4' x 4" x 2 -1/8" E50 -SSB -W E,Q,U,BB X X X • E50- 24MCWH -FR 0228 X - 135/185 Red 4' x 4" x 2 -1/8" E5OSSB -R E,Q,U,BB X X X ' E50- 24MCWH -FW 0229 X - 135 /185 White 4' x 4" x 2 -1/8" E50 -SSB -W E,Q,U,BB X X X • * PENDING NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. Architects and Engineers Specifications The speaker appliances shall be Wheelock Series E50 Speakers and the speaker strobe appliances shall be Wheelock Series E50 Speaker Strobes or approved equals. The speakers shall be UL Listed under Standard 1480 for Fire Protective Service and speakers 'quipped with strobes shall be listed under UL Standard 1971 for Emergency Devices for the Hearing - Impaired. In addition, the strobes ,hall be certified to meet the requirements of FCC Part 15, Class B. All speakers shall be designed for a field selectable input of either 25 or 70 VRMS, with selectable power taps from 1/8 watt to 2 watts. All models shall have listed sound output of up to 89 dBA at 10 feet and a listed frequency response of 400 to 4000 Hz. The speaker shall incorporate a sealed back construction. All inputs shall employ terminals that accept #12 to #18 AWG wire sizes. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall be of low current design. Where Multi - Candela Speaker Strobes are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110cd or 135/185cd for wall mounting. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on -axis is required. When synchronization is required, the strobe portion of the appliance shall be compatible with the Wheelock's SM, DSM sync modules or Wheelock PS- 24 -8MC Power Supply with built -in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non - synchronized flash rate. The speaker and speaker strobe appliances shall be designed for indoor flush mounting to 4" x 2 -1/8" electncal boxes without need for an extension ring or surface mounting to Wheelock's E5OSB or E5OSSB surface boxes The speaker and speaker strobe shall incorporate a speaker mounting plate with a snap -on gnlle cover. The finish of the Series E50 speakers and speakers strobes shall be white or red XENIA WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY S0510 E50 02/08 NJ Location FL Location VA Location 273 Branchport Ave. 7565 Commerce Ct. P: 877 - 459 -7726 Long Branch, NJ 07740 Sarasota, FL 34243 F: 703 - 294 -6560 P: 800-631-2148 P: 941 -487 -2300 F: 732- 222 -8707 F: 941- 487 -2389 www.coopernotification.com Cooper Notification is Wheelock° 11'413 SAFEPATH' WAVE COOPER Notification • COOPER Notification Series E60 Speakers and Speaker Strobes • r Speaker Strobe Speaker Description Features The NEW Wheelock Series E60 Ceiling Speakers and Speaker • Approvals include. UL Standard 1971, UL Standard Strobes are designed for high efficiency sound output, with dual 1480, New York City (MEA), California State Fire Marshal voltage (25/70 VRMS) capability and field selectable taps from 1/8 (CSFM), Factory Mutual (FM) and Chicago (BFP) See to 2 watts. These E60 Multi - Candela ceiling appliances are part of approvals by model in Specifications and Ordering the new family of ceiling mount strobe appliances that will also be Information available on strobes, horns and horn /strobes. Optional Extender ADA/NFPA/ANSI compliant • (E60 Ext) is for mounting to 4" backboxes with no extension ring. • The Series E60 Speaker Strobe models incorporate the Low Current Complies with OSHA 29 Part 1910.165 draw Series RSS Strobes. These ceding mount round models are • Ceiling mount strobe models are available with available in Wheelock patented MCC multi - candela ceiling strobe field selectable candela settings of 15/30/75/95cd or with field selectable intensities of 15/30/75/95cd or the high intensity 115/177cd (Multi - candela models) MCCH strobe with field selectable 115/177cd. • Strobes produce 1 flash per second over the regulated Series E60 Speakers and Speaker Strobes provide high audio voltage range output with dear audibility and are designed to meet the critical • 24 VDC with wide UL "Regulated Voltage" needs of the life safety industry for effective emergency voice communications, tone signaling and visible signaling to alert the using filtered DC or unfiltered VRMS input voltage hearing impaired. Synchronize with Wheelock SM, DSM or Wheelock PS- The low profile design incorporates a speaker mounting plate for 24 -8MC Power Supply with built -in sync protocol faster and easier installation. Each model has a built -in level adjust- Field selectable taps for 25 or 70 VRMS operation from ment feature and snap -on cover with no visible mounting screws. 1/8 watt up to 2 watts The strobe portion of all Series E60 Speaker Strobes may be High efficiency design for maximum output at minimum synchronized when used in conjunction with the Wheelock SM, wattage across a frequency range of 400 to 4000 HZ DSM Sync Modules or the Wheelock PS- 24-8MC Power Supply with Patented Sync Protocol. Wheelock synchronized strobes offer • Fast installation with IN /OUT screw terminals using #12 an easy way to comply with ADA recommendations concerning to #18 AWG wires photosensitive epilepsy. • Optional Extender (E60 Ext) is for mounting to 4" Series E60 Speaker Strobes are UL Listed for indoor use under backboxes with no extension ring. Standard 1971 (Signaling Devices for the Hearing- Impaired) and Standard 1480 (Speaker Appliances), and use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan® lens to provide maximum reliability for effective visual signaling. All inputs are supervised and employ IN /OUT wiring terminals for fast installation using #12 to #18 AWG wiring. Color options for the Series E60 Speakers and Speaker Strobes are red and white. 42 0 (.1 11111 M EA 41i1 APPROVED S5391 151 -92 -E NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range ". Note that NFPA -72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Senes NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 °F to 120 °F (0 °C to 49 °C) and maximum humidity of 93% (± 2%). • Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology "Listed Voltage Range ". Table 1: Average RMS Current E60 Strobe Current - Ceiling Mount E60 Speaker 24MCC 24MCCH Strobes 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.045 0.070 0.119 0.159 0.195 0.270 UL max* 0.065 0.105 0.189 0.249 0.300 0.420 Table 2: E60 UL Reverberant dBA @ 10 Feet** * RMS current ratings are per UL average RMS watts 1/8 1!4 1!2 1 2 method. UL max current rating is the maximum RMS current within the listed voltage range (16 -33v for 24v E Speaker 77 79.5 82.5 85 88 units). For strobes the UL max current is usually at E Speaker Strobe 77 79.5 82.5 85 88 the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum *dBA ratings are based on testing under UL Standard 1480. listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. Wiring Diagrams" SERIES E60 SPEAKER & STROBE OPERATE SERIES E60 SPEAKER STROBES SYNCHRONIZED INDEPENDENTLY (NON -SYNC OR SYNC) WITH MULTIPLE DSM MODULES PROFC Audible Ac c4:5M NI0 Note: Figure PRECEDINGS + -14 1 0 NExTp g shows intercon- APPLIANCEO _D _ EOANCEp Strobe NBC Cl[ -� �!l R nection to strobe OR OR VOICED ii i4i through sync OR EOLRO FO 0 EVA[UATIONp Audible NAC t :SM 1120 9 Y PANELS W NExTO module. Speaker 1 1��MNBI Strobe NAC • , Y nc . PP C DIt. C C I r — — — — — — TLS9ROEE0 � ti ���� portion requires 2 sr u �;:IL - — n 1 r — — — — — —M..0 CO 0 LD7 PI[W L EOLRp Audible NAC L. M 1130 separate conduc- PGWER SVPPL /C PO � �� p❑ • ji3 � Q tors to FACP. FACP0 Strobe NAC C �ip + STROBE: SPEAKERO DSM Interconnecting wiring shown. Maximum of0 twenty (20)0 SERIES E60 SPEAKER STROBE APPLIANCES SERIES E60 SPEAKER STROBE APPLIANCES & RSS SYNCHRONIZED WITH DSM MODULE SINGLE STROBES SYNCHRONIZED WITH PS- 12/24 -8CP and CLASS "A" PS- 12 /24- 8MP Series P5- 12/24 -8MP0 DSM❑ STROBED •°0 Fn NACO SYNCO -E ell CIRCU ITO OUTPUT50 EOLPO ,, OUTS �� .OUT • F❑ 1 -40 ., pi ,' ♦ IN ID ED' ED' Eo ,'. 4-CLASSO • ./ MINUS to A❑ ORO ED 4 0 •re : .s + -LJ [ 2- CLASSO co AUUIELE CO MINUS 20 p❑ CO . IN 20 IIIIEEllrETEp / STROBEO NACU �� ' OUT 20 B ECID CIRCUITO RETURNO Series P5- 12/24 -8 •■ For wiring information on the PS- 24 -8MC power supply, please refer to Data Sheet # S8900. " For detail using SM or DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83123 for SM and P83177 for DSM. For wiring information on the power supplies refer to Installation Instructions P84662. Specifications and Ordering Information Strobe Sync w/ Model Model Agency Approvals Model Order Wall Ceiling Non- SM, DSM or Strobe Color Color Mounting Op- Code Mount Mount Sync PS- 12/24- 8CP /MP Candela RED White tions UL MEA FM BFP CSFM E60 -R 3746 X - - - X - Q,U X X X X E60 -W 3745 X - - - - X Q,U X X X • X E60- 24MCC -FR 3748 - X X X 15/30/75/95 X - Q,U,V X X X • X E60- 24MCC -FW 3747 - X X X 15/30/75/95 - X Q,U,V X X X • X E60- 24MCCH -FW 3749 - X X X 115/177 - X Q,U,V X X X * X E60- 24MCCH -FR 3750 - X X X 115/177 X - Q,U,V X X X X E60EXT -R" 3578 X X X • • E60EXT -W ' 3757 X X X • • * *E60 EXT is an attractive extender ring that mounts behind the speaker to permit 'PENDING mounting to a 4" square x 2 1/8" deep electrical box without need for an extension ring on the box. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. Architects and Engineers Specifications The speaker appliances shall be Wheelock Series E60 Speakers and the Speaker Strobe appliances shall be Wheelock Series E60 Speaker Strobes or approved equals. The speakers shall be UL Listed under Standard 1480 for Fire Protective Service and speakers quipped with strobes shall be listed under UL Standard 1971 for Emergency Devices for the Hearing- Impaired. In addition, the strobes shall be certified to meet the requirements of FCC Part 15, Class B. All speakers shall be designed for a field selectable input of either 25 or 70 VRMS, with selectable power taps from 1/8 watt to 2 watts. All models shall have listed sound output of up to 87 dB at 10 feet and a listed frequency response of 400 to 4000 Hz. The speaker shall also incorporate a sealed back construction. All inputs shall employ terminals that accept #12 to #18 AWG wire sizes. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The strobe shall be of low current design. Where Multi - Candela Speaker Strobes are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 15/30/75/95cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. When synchronization is required, the strobe portion of the appliance shall be compatible with Wheelock SM, DSM sync modules or the Wheelock PS- 24 -8MC Power Supply with built -in Patented Sync Protocol. The strobes shall not dnft out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain dosed), the strobe shall revert to a non - synchronized flash rate. The speaker and speaker strobe appliances shall be designed for indoor flush mounting. The speaker and speaker strobe shall incorporate a speaker mounting plate with a snap -on gnlle cover with no visible screws for a level, aesthetic finish and shall mount to standard electrical hardware. The finish of the Series E60 Speakers and Speaker Strobes shall be white or red. All speaker and speaker strobe appliances shall be backward compatible i Member WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY S1611 E60 02/08 NJ Location FL Location VA Location 273 Branchport Ave. 7565 Commerce Ct. P: 877- 459 -7726 Long Branch, NJ 07740 Sarasota, FL 34243 F: 703 - 294 -6560 P: 800-631-2148 P: 941-487-2300 F: 732 - 222 -8707 F: 941 - 487 -2389 www.coopernotification.com Cooper Notification is Wheelock° („ La .Tq SAFEPATH' WAVES, COOPER Notification COOPER Notification Series RSS and RSSP Strobes and Strobe Plates • FIRE ' ARE ' i • FIRE FIRE" } Series RSS Series RSS Series RSSWP RSS Round Description Features • The Wheelock patented Series RSS Strobe Appliances and Approvals include. UL Standard 1971, New York City (MEA), Series RSSP Strobe Plates have lower current draw while California State Fire Marshal (CSFM), Factory Mutual (FM), and maintaining outstanding performance, reliability and cost Chicago (BFP) See approvals by model in Specifications and effectiveness. These versatile appliances will satisfy virtually all Ordering Information requirements for indoor, wall or ceiling mount applications. • ADA/NFPA /UFC /ANSI compliant. Meets OSHA 29 Part Strobe options for wall mount models include 1575 or the 1910.165 Wheelock Patented MCW multi - candela strobe with field • Wall mount Multi - Candela models are available with Field selectable candela settings of 15/30/75/110cd or the high Selectable Candela Settings of 15/30/ 75/110cd or 135/185cd. intensity MCWH strobe with field selectable 135/185cd. Single Candela models are available in 1575cd Ceiling mount models include the patented MCC multi - candela Ceiling mount Multi - Candela models are • ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable available with field selectable candela settings of 15/30/75/95cd 115/177cd. or 115/177cd. (Round or Square) All models may be synchronized using the Wheelock SM, • Strobes produce 1 flash per second over the regulated voltage DSM Sync Modules, Wheelock Power Supplies or other range manufacturers panels incorporating the Wheelock Patented • 12 and 24 VDC models with wide UL "Regulated Voltage" us- Sync Protocol. Synchronized strobes can eliminate possible ing filtered (DC) or unfiltered VRMS input voltage restrictions on the number of strobes in the field of view. Wheelock's synchronized strobes offer an easy way to comply • Synchronize using the Wheelock sync modules or panels with with ADA recommendations concerning photosensitive epilepsy built -in Wheelock Patented Sync Protocol as well as meeting the requirements of NFPA 72. • Fast installation with IN /OUT screw terminals using #12 to #18 The Wheelock Series RSS Strobes employ a Patented Integral AWG wire Strobe Mounting Plate that can be mounted to a single gang, double gang, 4" square, 100mm European backboxes or the SHBB surface backbox. If the flush backbox has side or top space between it and the finished wall, the NATP (Notification For Weatherproof Senes RSS See Datatsheet S9004 Appliance Trimplate) may be used. It provides an additional .65" of trim for the Appliance. An attractive cover plate is provided for a clean, finished appearance on all models. The Series RSSP Multi- Candela Strobe Plates are a cost effective way to retrofit required wall strobe appliances to bells, horns, chimes, multitones or speakers and easily mounts to standard 4" backboxes or for surface mount use with the Wheelock SBL2 surface backbox. Pow narnr ® wr raa 11 > MEA I APPROVED S5391 151 -92 -E 7125-0785 141 7300 -0785 154 NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR °ERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU ID /OR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range ". Note that NFPA -72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 °F to 120 °F (0 °C to 49 °C) and maximum humidity of 93% (± 2 %). • Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology "Listed Voltage Range ". Table 1: Average RMS Current* RSS /RSSP - Wall Mount Ceiling Mount RSS /RSSP 241575W 24MCW 24MCWH 24MCC 24MCCH 24VDC Models 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd UL max* 0.090 0.060 0.092 0.165 0 220 0.300 0.420 0.065 0.105 0.189 0.249 0 300 0 420 RSS /RSSP RSS /RSSP 24VDC Wall Mount Models * RMS current ratings are per UL average RMS method. UL max current 121575W rating is the maximum RMS current within the listed voltage range (16 -33v for 24v units). For strobes the UL max current is usually at the minimum 12 vdc 0.152 listed voltage (16v for 24v units). For audibles the max current is usually at UL max* 0.255 the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. Table 2: Audibles /Speakers for RSSP Strobe Plate Product Series Multitone Appliances AMT, MT Wiring Diagrams # SERIES RSS /RSSP APPLIANCE Horns AH, NH, HS Motor Bells MB- G6 /G10 FROM + + TO NEXT PRECEDING _ APPLIANCE Speakers ET- 1010/1080, E70, ET70 APPLIANCE, SYNC OR EOLR Chimes CH70 MODULE, POWER ^ A SUPPLY OR FACP • SERIES RSS /RSSP APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS "A" NAC CIRCUIT SERIES RSS /RSSP APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM MODULES DSM DSM #1 STROBE + 0 SynC NAC CIRCUIT SYNC 0 Strobe NAC Cir + MEM _ OUT ..'our, F m - �� C + IN, �� "MOM I DSM #2 • A I © I Z • �� 0 + Strobe NAC Cir.'• S (a AUDIBLE /1 MINUS 2 1 � J I DSM #3 NA BE ..® ® ® Strobe NAC Cir. `S t Emir CIRCUIT RETURN DSM Interconnecting wiring shown. Maximum of twenty (20) STROBE /PLATE ASSEMBLY AUDIBLE & VISIBLE APPLIANCE OPERATE IN UNISON SERIES RSS /RSSP APPLIANCE SYNCHRONIZED WITH SM MODULE SINGLE CLASS "B" NAC CIRCUIT TO NEXT S M FROM + APPLIANCE + STROBE PRECEDING - - OR EOLR F APPLIANCE, SYNC II A StroNAC be STROBE MODULE, POWER /"� C o SUPPLY OR FACP 0 Iii C Circuit �� Q STROBE AUDIBLE - +Audible P EOLR Audible STROBE /PLATE ASSEMBLY SERIES RSS /RSSP APPLIANCES SYNCHRONIZED AUDIBLE & VISIBLE APPLIANCE OPERATE INDEPENDENTLY WITH PS- 12/24 -8CP or PS- 12/24 -8MP FROM + + Senes PS- 12/24 -8MP PRECEDING TO NEXT APPLIANCE OR APPLIANCE FACP - OR EOLR / AS el OUTPUTS EOLR J FROM - l — — — — + F 1 - 4 TO NEXT 4 - CLASS PRECEDING y r STROBE OR B. --1 STROBE, SYNC - — I I 1 r — — — — — - EOLR OR <I MODULE, POWER I 1 SUPPLY OR FACP 2 - CLASS AS Hi m P STROBE APPLIANCE As J a For detail using SM or DSM Sync Module refer to Data Series PS- 12/24 -8MP I Sheet S3000 or Installation Instructions P83123 for SM and P83177 for DSM. For wiring information on the power supplies refer PS- 24 -8MC. • Specifications and Ordering Information Order Wall Ceiling Non- Strobe 24 12 Color Color Square Agency Approvals Model Mounting Options*** Code Mount Mount Sync Candela VDC VDC RED WHITE or y Round UL MEA CSFM FM BFP RSS 24MCW - 940 X - X 15/30/75/110 X - X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS - 24MCW -FW 9401 X - X 15/30/75/110 X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS- 241575W -FR 7471 X - X 15 (75 on Axis) X - X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS- 241575W -FW 7788 X - X 15 (75 on Axis) X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS- 121575W -FR 7476 X - X 15 (75 on Axis) - X X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS- 121575W -FW 7468 X - X 15 (75 on Axis) - X - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS - 24MCC -FW 3158 - X X 15/30/75/95 X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X • RSS - 24MCC -FR 3157 - X X 15/30/75/95 X - X - B,D,E,F,G,H,J,N,O,R,X Square X X X X • RSS - 24MCCR -FW 3160 - X X 15/30/75/95 X - - X B,D,E,F,G,H,J,N,O,R,X Round X X X X • RSS-24MCCH-FW 3461 - X X 115/177 X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X • RSS- 24MCCHR -FW 3463 - X X 115/177 X - - X B,D,E,F,G,H,J,N,O,R,X Round X X X X ' RSS- 24MCWH -FR 3465 X X 135/185 X X B,D,E,F,G,H,J,N,O,R,X Square X X X X • RSS- 24MCWH -FW 3464 X X 135/185 X X B,D,E,F,G,H,J,N,O,R,X Square X X X X " RSSP-2475-FR** 9013 X - X 180@ 77 °F W W X X X - B,D,E,F,G,H,J,N,O,R,X Square X X X X 75@ -31°F RSSWP - 24751 -FW ' 3034 X - X 180@ 77°F X X - X B,D,E,F,G,H,J,N,O,R,X Square X X X X • 75@ -31°F RSSP- 121575W -FR 7798 X - X 15 (75 on Axis) - X X - D,E,Z Square X X X X X RSSP - 24MCW -FR 9402 X - X 15/30/75/110 X - X - D,E,Z Square X X X X X RSSP- 241575W -FR 7793 X - X 15 (75 on Axis) - - X - D,E,Z Square X X X X X *PENDING All models sync with Wheelock SM, DSM or PS -12/24 -8CP or PS- 12/24 -8MP. # Models are available in either Red or White. Call Customer Service for Order Code & Delivery. **For Weatherproof Series RSS Strobe specifications see data sheet S9004. **Refer to data sheet S7000 for mounting options. • Architects and Engineers Specifications The visual notification appliances shall be Wheelock Series RSS Strobe Appliances or approved equals. The Series RSS shall meet and be listed for UL Standard 1971 (Emergency Devices for the Hearing - Impaired) for Indoor Fire Protection Service. The strobe shall to listed for indoor use and shall meet the requirements of FCC Part 15 Class B. The strobe appliances shall produce a flash rate of .one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). When Strobe Plates are to be installed, they shall be the Wheelock Series RSSP Strobe Plate and shall have the same electronic circuitry as the Wheelock Series RSS. The Series RSS Strobe shall be of low current design. Where Multi- Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30175/110cd or 135/185cd for wall mount and 15/30/75/95cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compatible with Wheelock's SM, DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built -in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non - synchronized flash rate. The strobes shall be designed for indoor surface of flush mounting. The Series RSS Strobe Appliances shall incorporate a Patented, Integral Strobe Mounting Plate that shall allow mounting to single - gang, double -gang, 4 -inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided An attaching cover plate shall be provided to give the Appliance and attractive appearance The Appliance shall not have any mounting holes or screw heads visible when the installation is completed The Series RSSP Multi - Candela or single candela Strobe Plate shall mount to either a standard 4 inch square backbox for flush mounting, or the Wheelock SBL2 backbox for surface mounting All notification appliances shall be backward compatible. NOTE Due to continuous development of our products, specifications and offenngs are subled to change without notice in accordance with Wheelock. Inc standard terms and conditions AWN WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA SO410 RSS /RSSP 02/08 NJ Location FL Location VA Location 273 Branchport Ave. 7565 Commerce Ct. P: 877- 459 -7726 Long Branch, NJ 07740 Sarasota, FL 34243 F: 703 - 294 -6560 P: 800-631-2148 P: 941.487 -2300 F: 732-222-8707 F: 941-487-2389 www.coopernotification.com Cooper Notification is Wheelock' (, t I ,7 '19 SAFEPATH' WAVES, COOPER Notification FIRE SYSTEM FUNCTION MATRIX SIEMENS Washington Square Gap Kids • SYSTEM RESPONSE U) 0 co co a d co 2 N C c cii co o v a �, a o c m E s a E Q co c E m • 2 o. `m ¢ L17 co o) ¢ a) ,.. g c U) LL c _N LL >. 0 O C U) U) .7 co d LI T •7 Cl) (n m = a N N o j 0 O N J Q 2 N b L. N c m 0 0 o y CO o co > v m E g, a E co U L W (0 2 j U) O n INITIATION DE ACTIVATED Q co 5 Q F- co Q I co Area Smoke /Heat Detector X X X Air Handler Duct Smoke Detector X X X X Waterflow Switch X X X Valve Tamper Switch X X Fire System Trouble X X PROPRIETARY DOCUMENT FOR APPROVAL ONLY 1 1/30/2009 PANEL BATTERY CALCULATIONS SIEMENS Washington Square MAIN FIRE ALARM PANEL MXLV L il Requirement for standby current (24 Hours Design Supervisor Current = t 31 113 °, ;v Avip Hi:; E Requirement for alarm current . Minutes Design Alarm Current = i- 1 -,. Amp Hra E Spare Battery Capacity "1;x$20°---, , % Additional Capacity Current = ". ^6.49 r "Amp HC, ,t' ; - w H ; = Initiating Devices Assumed In Alarm F 9,1°,1.10 , I % Battery AH requirement = ,x.38.93 3 ° .esAnip -H6 CO Battery Size ( ' '.7.:',..., 5 5. 00 ' ,}', =Hr,k Module Part Number 8 Description Quantity Module Current EOL Current Device Current Total Standby 24 VDC Module Current Main Control Panel 1 175mA,A1Z.- - - , -''-,r - 0175 Amps MMB -1/2/3 NAC Circuits 0 . :' -: : ; , "w °`�; °' 12mA per NAC - , , 0 000 Amps IAC Devices 0 ;„ ,'>' - - - 1 1mA per device 0 000 Amps PSR -1 Remote Power Supply 0 70mA ; 0 ' - a , -0° i - ., 0 000 Amps MKB -2 Main Keyboard 1 5mA �, 0 �*: 3•e ' ' ` - 0 0 005 Amps RCC -1/1F Remote Command Center 0 75mA - `„ '.0 �,`° - _ 0 0 000 Amps Remote Command Center 0 75mA 1. 0 1 0 0 000 Amps RCC -2 s� Remote Command Center w/ PIM -1 0 95mA W` 0 ? 0�: - 0 000 Amps TSP-40 Pnnter 0 70mA °pF' ' =0 - _ - ; 0 .r ', `, 0.000 Amps CSM-4 Controllable Signal Module 0 10mA 0_. -" ,` • r -w - ;,- 5 - 0 000 Amps 12mA _ ',' ,.; - 0 000 Amps CRM-0 Controllable Relay Module 0 15mA 0 000 Amps Active Relay - - 0 . . • - _ - _ , - . _ - „:::::"3 15mA per active relay 0 000 Amps CZM-4 Remote Conventional Zone Module 0 55mA "-� �s� - • - 0 000 Amps - _,^' D a:; ,= s7:•-? .. ,- — - .. , 3mA 0 000 Amps Analog Loop Dnver 0 105mA - ° - - - ? - 6- , ” ' 0 000 Amps ALD -21 A p' IAC Devices - _ 0 :_' , s -y - -- _ - 1 1 mA per Device 0 000 Amps s P XLD -1 Analog Loop Dnver 0 215mA - ! D - - - " - 0 000 Amps IAC Devices K ip �, _ "- -, ," _ - •- 1 1 mA per Device 0 000 Amps ++ CMI -300 CXL Interface Module 0 30mA - ,0',", ; :,,,. , " ''i. , - 0.000 Amps C NET-4 Style 4 Network Interface Card 1 5mA g` ' - ':C31.-.1, : -''" .; `a_ 0 % _ 0005 Amps L NET -717M Style 7 Network Interface Card 0 30mA -, , y, - ,: , :o, - - ? "'_•; - , : - 0, "` - 0 000 Amps NIM -1W Network Interface Module 0 70mA - - =0u - =, - ='a _!VA; 0000 Amps U REP -1 Netowrk Repeater Module 0 40mA '" a 0? , - ,`- 0 °'i., 0 000 Amps PS -5A Power Supply 0 1/4 of 5V Load ` `. , R,:':0. •- :' � w r S. ''',' < - 0" '1: • 0 000 Amps PS -5N7 Network Interface/5V Powwr Supply 0 150mA + 1/4 of 5V Loac 4- - o,' 11 -- . _ ,_ :_0 i ., 0 000 Amps Q MOI -7 Voice and Annunciator Dnver 0 120mA ti- - , P.-<';';:4-; .-- . ° 0 - ` "=, 0 000 Amps N MOD -16 Output Dnver 0 2mA -o " ;;`,50 %eq., - -1 y , 0000 Amps P .� MID -16 Input Dnver 0 2mA ad °c, : °o.� "' :;1`, ...-":=4-.; , 0,' 0 000 Amps d 6mA , . " ° 14 . `9 - , ,:y " " 0 000 Amps 0. CZM -1B6 Conventional Zone Module 0 l', `_;a:y,;; "? ;� 5mA °• - 0 000 Amps = 4`, - - " r_ - r., - a : - ., NA ; 0 000 Amps CO ICP -B6 Intelligent Control Point 0 18mA 2 5mA ` 4. : : : : :1, 1 4 1 \; NA - 0 000 Amps PIM -1 Pnnter Interface Module 1 10mA ' _ „ „'0- ,' m,°• °,, ' ' ,,;y'; dNA_• • 0 010 Amps D2300CP Fiber Interface Module 0 50mA ;...'"P ; '4r r i ° ,'° 'ns` Oe4„ =,a 0 000 Amps SK- 5128/512 Digital Communicator o 60mA „ 1 9 ° ,' 0 000 Amps ACM -1 Audio Control Module 1 85mA , - • ;0*14i - , C' ,,',A,,; ri Z 0. 0 085 Amps DMC -1 Digital Message Card 1 50mA . `:4O Vii%" t.:f, 'J 2' '0 _ - ter - -' 0 050 Amps TMM -1 Telephone Master Module 0 71mA - . qF ' s,i - 0 0000 Amps ASC -1 Audio Supervision Module 1 22mA r ,,:a.' .011;",1;. ;..;r "n"r.:,rz`00 `��'1„", a 0 022 Amps ASC -2 Audio Supervision Module 0 39mA c. ".=0°"- s` >.4', ` r0 . r2' <- 0 000 Amps BTC -1 Backup Tone Card o 44mA W °0 =. , R i.-4- - 0 000 Amps EL -410D Amplifier Unit 3 200mA r ▪ 0 " 0 - _ 0600 Amps OCC -1 Output Control Card 1 17mA ^i', ,'-, g;r., ;4.1- ;- `;,s44 ;0 - "' +°` 0 017 Amps RCM -1 Audio Riser Control Module 1 150mA t --T t:F ,: 0 .t -M-;; ',,s,-..;.-7:2.0:0,::,2-,1,',' " 0 150 Amps VFM -1 Fan Control Module 0 17mA r'. ;� ;f -;'v`r 01 " F',, �,,: =; i - :a0 ,:,";', 0 000 Amps VLM -1 LED Annunciator Module 0 17mA '_- ° Oa Vi. z x' ",' ° 0 000 Amps VSM -1 Switching Module 6 17mA e"d; °: s ; y ;< r;4,: ;a0 ;, , :, ; ,,„ 0 102 Amps ZAC -30 Zone Amplification Card 0 160mA ,,,, ;; &1:,0ri' , = -;� ",; ;'O. F ,7'' 0000 Amps ZC1-8B Zone Control Card 4 19mA s 0;; ;; - - _g o; . 0 076 Amps ZC2 -4AB Zone Control Card 0 19mA r;,, ' :`04 1 ,w' r_ x-0' ;11, - 0 000 Amps ZC2 -8B Zone Control Card 0 19mA - - 'iO3d + ,° '' "zru PL-A, :" 0 000 Amps ZC3.4A8 Zone Control Card 0 18mA 9,' D $ : ; =� "; ' "C , 0 000 Amps ZCT -8B Zone Control Card 0 34mA ' ; ; : Zio, M,'T:l,i i 0 Amps Total Supervisory Current 1.297 Amps Propnetary document for approval only MAIN FIRE ALARM PANEL MXLV (Cont.) 24 VDC Current 5 VDC Current Module Part Number 8 Description Quantity Active / Module Total Active / Module Total MMB -1/2!3 Main Control Panel 1 0 175 500mA Provided - - , PSR -1 Remote Power Supply 0 70mA ii 800mA Provided PS -5A Power Supply 0 0 000 1 Amp Provided - PS -5N7 Network Interface/5V Poewr Supply 0 0 000 500mA Provided MKB-2 Main Keyboard 1 0 0 000 15mA 0 015 RCC -1/1 F Remote Command Center 0 75mA 0 000 0 0 000 RCC -2 Remote Command Center 0 75mA 0 000 0 0 000 Remote Command Center w/ PIM -1 0 95mA 0 000 0 0 000 TSP-40 Printer 0 70mA 0 000 0 0 000 4.0 CSM-4 Controllable Signal Module 0 34mA + 1 5A / circuit 0 000 3OmA 0 000 F. CRM-4 Controllable Relay Module 0 75mA 0 000 30mA 0 000 L CZM-4 Remote Conventional Zone Module 0 720mA 0 000 24mA 0 000 ■ ALD -2I Analog Loop Dnver 0 105mA + 1 1mA / device 0 000 0 0 000 U XLD -1 Analog Loop Dnver 0 215mA + 1 1 mA / device 0 000 0 0 000 CMI -300 CXL Interface Module 0 0 0 000 96mA 0 000 E NET-4 Style 4 Network Interface Card 1 0 0 000 20mA 0 020 L NET -7/7M Style 7 Network Interface Card 0 0 0 000 120mA 0 000 - NIM-1W Network Interface Module 0 0 0 000 160mA 0.000 Q REP -1 Netowrk Repeater Module 0 40mA 0 000 0 0.000 MOI -7 Voice and Annunciator Dnver 0 120mA 0 000 175mA 0 000 13 MOD -16 Output Dnver 0 850mA 0 000 2mA 0 000 O MID -16 Input Dnver 0 32mA 0000 2mA 0000 J CZM -1 B6 Conventional Zone Module 0 50mA 0 000 0 0.000 ICP-B6 Intelligent Control Point 0 1 5A 0 000 0 0 000 PIM -1 Pnnter Interface Module 1 0 0 000 25mA 0 025 Q D2300CP Fiber Interface Module 0 0 0 000 200mA 0 000 _ SK-5128/512 Digital Communicator 0 130mA 0.000 0 0 000 N ACM -1 Audio Control Module 1 85mA 0 085 176mA 0 176 8., TMM -1 Telephone Master Module 0 71mA 0 000 0 0 000 • ASC -1 Audio Supervision Module 1 41mA 0 041 29mA 0 029 ASC -2 Audio Supervision Module 0 61 mA 0 000 29mA 0 000 O BTC -1 Backup Tone Card 0 44mA 0 000 0 0 000 a OCC -1 Output Control Card 1 17mA 0 017 22mA 0 022 RCM -1 Audio Riser Control Module 1 130mA 0 130 80mA 0 080 VFM -1 Fan Control Module 0 90mA 0 000 0 0 000 VLM -1 LED Annunciator Module 0 160mA 0.000 0 0 000 VSM -1 Switching Module 6 160mA 0 960 0 0 000 ZAC -30 Zone Amplification Card 0 3A (a 30 Watts 0 000 0 0 000 ZC1-8B Zone Control Card 4 170mA 0 680 31mA 0 124 ZC2 -4AB Zone Control Card 0 167mA 0 000 30mA 0 000 ZC2-8B Zone Control Card 0 342mA 0 000 31mA 0 000 ZC3 -4AB Zone Control Card 0 168mA 0 000 28mA 0 000 ZCT-8B Zone Control Card 0 78mA 0 000 33mA 0 000 24 VDC Power Supply Needed MPS -6 24VDC Total t913 Amps 5VDC Total 0.491 Amps 24 VDC & 5 VDC Total Panel Alarm Current! 2.404 Amps C Descriptio Model Number Device Quantity Device Total Alarm 24 VDC ice Current Module Current IL L • Photoeletnc Smoke Detector / Thermal Detector FP -11 ! FPT -11 0 0 00075 Amps 0 000 Amps V Digital Communicator SK- 512815129 0 0 154 Amps 0 000 Amps 30 Watt Amplifier ZAC -30 0 3 000 Amps 0 000 Amps E 100 Watt Ampler EL -410D 3 9 500 Amps 28 500 Amps CU NAC -N7 0 0 Amps 0000 Amps Q NAC -N2 0 Amps 0 000 Amps Total Field Device Alarm Current 28.500 Amps Field Wiring Circuits Notes C urrent Footage Voltage Voltage Wire Draw of wire Drop Drop Guage fl■ Notification Circuit N1 0 000 000 0 0% 14 CD Notification Circuit N2 0 000 0.00 0.0% 14 0) 000 0 0% 14 CO 000 00% 14 ■ Note All figures are approximate until actual conduit routing is obtained > FOR SAMPLE OF CALCULATIONS SEE VOLTAGE DROP CALCULATION SHEET Proprietary document for approval only BATTERY SIZING CALCULATIONS SIEMENS Washington Square Panel Name: FAPS -5 Battery Size: 7 amp -hr Requirement for standby current: 24 hrs. Design Supervison Current = 1.44 amp -hr Requirement for alarm current: 15 min Design Alarm Current = 0.36 amp-hr Spare Battery Capacity: 25 % Additional Capacity Current = 0.45 amp -hr Initiating Devices Assumed In Alarm: 10 % Battery AH requirement = 2.25 amp -hr PANEL EQUIPMENT Standby Alarm TOTAL TOTAL (ma) (ma) (ma) (ma) Quantity Device Current Current Standby Current Alarm Current 1 Model PS- 12/24 -8MP 60 150 60 150 PANEL TOTALS 60 150 8 15cd STROBE 50 400 2 30cd STROBE 81 162 1 75cd STROBE 133 133 110cd STROBE 161 0 4 15cd SPKR /STROBE 47 188 2 30cd SPKR /STROBE 81 162 2 75cd SPKR /STROBE 130 260 110cd SPKR /STROBE 171 0 0 FIELD TOTALS 0 1305 I I I Standby Alarm GRAND TOTALS (field & panel) 60 I 1455 I Formula: [(A + B) x C] + [(D + E) x F] x G = Minimum Amp -Hour Battery Capacity I) Where: A = Internal panel standby current {amps }. B = External device standby current {amps }. C = Duration panel must remain operational {hours }. E = External device alarm current {amps }. F = Duration panel must remain in alarm after standby period ends {hours }. G = Spare battery capacity {percentage }. PROPRIETARY DOCUMENT FOR APPROVAL ONLY 1/30/2009 IAC CIRCUIT CALCULATIONS SIEMENS Washington Square 1 ;o. VZ ° a 3 ,' < ci,:.d r, ;.V;'z < d m d e. ¢` `if,. Y ,u, `Oa - m- c o � ' w b� % o.• - o• ' w:'d x , 0 Q a 0 t:. ` O` .e - .. o, ` ,�. . c3 r " 'S V =C - V : y • y v).. U) •bt U) (q y b C- U Y ' V A ' a b i' - >, - , -. `,. a on, -d- ' m . m b b b u- , 'O , b b - u O O a a —°, u' ' . F _- L x R R x 2 15 30 75 110 15 30 75 110 DH AUX # x l I x R 24 -VD FAPS -5 N5 -1 180 14 0.0026 0 47 0.94 5 0 0 0 3 2 0 0 0 0 0.65 0.61 23.39 2.6% 21.8% N0 305 44 >,''0.0026, ;, '• .79 ;; ;•' 0 " 1.59 3i s2 % . , - . ., `, „ 1 Zf_ r0 ` 1 .. . _0 . - ,. -- 0 : , 0 82 0 - _ 0." -..„ ..1:31 , - 22:69, ` 5 27.4 %' N5 -3 0 14 0 0026 0.00 0.00 0 0 0 0 0 0 0 0 0 0 0.00 0.00 24.00 0.0% 0.0% N5-4 0 14 0 0026 0 00 0.00 0 0 0 0 0 0 0 0 0 0 0.00 0.00 24.00 0.0% 0.0% 18.5% 1 48 AMPS 11 2 1 0 7 2 6 10 0 0 Enter Power Supply Capacity V:',8:0,,,,`,:-AMPS' Capacity Per Output Ika:taAMRSI Enter Strobe Wire Size1;4'Guage 15cd Strobe 2050 *• ;', q Multi Candela Strobes 30cd Strobe ' ; x081 r ° , v 75cd Strobe ' 1'33 ; 110cd Strobe 1'61 @ 15cd Spkr /Strobe 07,2 20'4 Multi Candela Speaker /Strobe 30cd Spkr /Strobe 094 x4 V C ' , 75cd Spkr /Strobe ?�:�1'53 >z 444,5 110cd Spkr/Strobe ::183' ',, �. DOORHOLDER 4,-s ' :096 `r , °: 150X OR EDUIVELANT (Supplied by Others) 24VDC RISER (AMPS) ?:0001, ° - Enter 24VDC Riser Wire Size14Guage PROPRIETARY DOCUMENT FOR APPROVAL ONLY 1130/2008