Correspondence /4111/ 01FIl t i' \ September 29, 2005 CITY OF TIGARD BEBE C/O Express Permits OREGON Cynthia Thornton 1327 Post Ave. # H Torrance, CA 90501 RE: T I MECHANICAL - REVIEW Project Information Building Permit: BUP2005 -00435 Construction Type: II-B Tenant Name: BEBE Occupancy Type: M Address: 9321 SW Washington Sq Occupant Load: 105 Area: . 3,495 sq ft Stories: 1 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; The submitted plans are approved subject to the following. Deferred submittals such as Fire Alarm, Fire Sprinkler, Truss Joist Shop Drawings, etc, will be charged a deferred submittal fee based on the valuation of the portion of the work being deferred. The minimum fee shall be $200.00. Deferred Items: A. Suspended Air Handling Unit lateral and vertical supports with attachment and installation details. 2. Smoke detectors shall be installed in return air systems with a design capacity greater than 2000 cfm. Upon activation, the smoke detector shall shut down the air distribution system. Smoke detectors shall be connected to a fire alarm system and shall activate an audible and visible alarm at a constantly attended location. 606.2, 606.4 & 606.4.1 OMSC 2. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer's installation instructions and this code. Manufacturer's installation instructions shall be available on the job site at the time of inspection. OMSC 304.1 3. A cooling tower used in conjunction with an air conditioning appliance shall be installed in accordance with the manufacturer's installation instructions. OMSC 908.1 4. Hydronic piping systems other than ground source heat pump loop systems shall be tested hydrostatically at one and one half times the maximum system design pressure, but not less than 100 psi (689 kPa). The duration of each test shall be not less than 15 minutes. 1208.1 OMSC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 • 5. The building or structure shall not be weakened by the installation of mechanical systems. Where floors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with the Building Code. The cutting, notching and boring of framing members shall comply with OMSC 302 Sections 302.3.1 through 302.5.3. 6. Ducts shall be supported with approved hangers at intervals not exceeding 10 feet or by other approved duct support systems designed in accordance with the Building Code. Flexible and other factory-made ducts shall be supported in accordance with the manufacturer's installation instructions. 603.10 OMSC 7. Metallic Ducts shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) — Flexible and other factory-made ducts shall be supported in accordance with the manufacturer's installation instructions. 603. OMSC 8. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC 10. Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC Mercury Thermostats. The State of Oregon prohibits the installation of thermostats that contain mercury in commercial and residential buildings. "In accordance with ORS 455.355, the disposal of thermostats that contain mercury shall be in accordance with programs established by thermostat manufacturers, their representative or distributor, or by delivery to sites that will ensure that the mercury does not become part of the solid waste stream or wastewater." Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfull_ Val Henzel, Senior Plans Examiner September 27, 2005 CITY OF TIGARD O REGON BEBE C/O Express Permits Cynthia Thornton 1327 Post Ave. # H Torrance, CA 90501 RE: BEBE - REVIEW Project Information Building Permit: BUP2005 -00435 Construction Type: II -B Tenant Name: BEBE Occupancy Type: M Address: 9321 SW Washington Sq Occupant Load: 105 Area: 3,495 sq ft Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and 2003 International Fire Code as amended by TVF &R. The following information is required in order to complete the review. 1. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. 1011.1 OSSC 2. All exit doors shall be operable from the inside without the use of a key or any special knowledge or effort. 1008.1.8 OSSC 3. Exit signs shall be illuminated at all times and shall be provided with a second source of power that will provide 1 '/z hours of illumination in case of primary power loss. 1006.3 OSSC FYI Additional exit signs may be required by the city field inspector to clearly indicate the path of egress. NOT PART OF THIS REVIEW: * Electrical * Mechanical * Plumbing 4. Accessible checkout aisles shall be on an accessible route and at least 36 inches wide. Counters in accessible checkout aisles shall be not more than 38 inches (965 mm) high and the top of the raised edge of the counter shall not exceed 40 inches (1016 mm) in height above the finished floor. Accessible checkout aisles shall be identified by the international symbol of access. OSSC s 1109.19; 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 5. American with Disabilities Act (ADA): It shall be the responsibility of the Architect, Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA requirements for the structure. The City of Tigard reviews the plans and'inspects the structure only for compliance with Chapter 11 of the OSSC, which may not include all of the requirements of the ADA Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC • Certificate of Occupancy: No building or structure shall be used or occupied until the Building Official has issued a certificate of occupancy 110.1 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectful 4r e f c' e Val Henzel Senior Plans Examiner • CORTLAND MORGAN, ARCHITECT :.:.:..:::.:::::<.:..::>.::.':::::::<::: :::::::::.::.::::::::::::...... ... v... vn v .h Nv {x4 xv} i}'•}:: �i: iti;;:. i}: �}}}}}}:; Oi: 9ii} :U } }i }i:4 } }iii::iO }:.'.:.:::.:: i:.:: i::.:'.>:: ;. >:.: ".:: i:. ' ..::::.::: :::'. :::::: :........:........:.::v:. �:.: �.v.: �:.... �;w� .. .:. v l . vd($ <.. 4..nvvv }: •;O'3": }�!4in;: •} }:pv::::;: �.. �::::::: mom::::::::; ::_ ::v:.::::::v. • Ms. Val Henzel City of Tigard, Oregon ® 13125 SW Hall Blvd. �1 ECE ii w Tigard, OR 97223 Tel: 503.639.4171 SEP CITY OF i I;;,,,,tir BUILDING i?, ,, ;c.,tr.:,, 12 September 2005 Re: bebe Sport Store, Washington Square Mall, suite # T05 Application Number: BUP2005 -00435 Dear Ms. Henzel, Enclosed, please find copies of the revised drawing sheets (All, Al2, A13) addressing your comments from 7 September 2005, as requested. Each item has been bubbled and marked REV. 1 for clarity. The following addresses comments from your office: ITEM SHEET(S) DESCRIPTION OF CHANGE Architectural: 1. A6- A10— Detail keys remain as previously noted, revisions occur only on the details themselves (see response below). No new sheets attached. 2. A6.1/A6.2 - We would like to defer the requirements for structural calculations to the rear storefront once the Structural Engineer has completed his analysis, drawings and calculations, as discussed. No new sheets attached. 3. z All — Updated details 4, 7, 8, 9, 10, 11 /Al l to add additional framing, attachment notes, and detail references, as discussed. 4. A 12 — Updated details 4, 7, 9/A 12 to add additional framing, attachment notes, and detail references, as discussed. 5. A13 — Updated details 1, 5, 9/A13 to add additional framing, attachment notes, and detail references, as discussed. If you have any questions please don't hesitate to call me directly. Sincerely, SSI34 ` ee CORTLAND MORGAN y Cortland organ • Cortland Morgan, Architect AIA • DALLAS, TEXAS 11 OF0 0 6910 Woodland Drive • Dallas, Texas 75225 • Tel: (214) 368 -3687 • rax: (214) 368 -3690 h a ady p ii �� V I '•� r� September 7, 2005 s'A CITY OF TIGARD OREGON BEBE C/O Express Permits Cynthia Thornton 1327 Post Ave. # H Torrance, CA 90501 RE: BEBE - REVIEW Project Information Building Permit: BUP2005 -00435 Construction Type: II -B Tenant Name: BEBE Occupancy Type: M Address: 9321 SW Washington Sq Occupant Load: 105 Area: 3,495 sq ft Stories: 1 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition; and 2003 International Fire Code as amended by TVF &R. The following information is required in order to complete the review. PRELIMINARY REVIEW 1. Provide framing details showing all construction details of work being done as shown on sheets A6 — A13. NOT PART OF THIS REVIEW: * Electrical * Fire Sprinklers * Fire Alarms * Mechanical System * Plumbing When submitting revised drawings or additional information, please attach a copy of the enclosed . City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respe lly al enzel, Senior Plans Examiner 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772