Bulletin 136 Rev L
. Reilabia M odel F1 FR
Model F1 FR Recessed 5
Quick Response
cm
Sprinklers
0
Model Fl FR Sprinkler Types
Standard Upright
Conven onal Pendent RECEIVED :: 5
L \` 1
Vertical Sidewall
• 075' -
Horizontal Sidewall SEP 14 2005
— HSW 1 Deflector ¶
Model F1FR Recessect i �� G I§VPOS a
Recessed Pendent
Recessed Horizontal Sidewall
- HSW 1 Deflector Upright Pendent
Listings & Approvals =° -:_..
1. Listed by Underwriters Laboratories, Inc. (UL)
2. Listed by Underwriters' Laboratories of Canada (ULC) 1 �,
3. Certified by FM Approvals - ,,
4. Loss Prevention Council (LPC, UK) a}
5. NYC BS&A No. 587 -75 -SA _ .
6. Meets MIL- S -901C and MIL -STD 167 -1 f
7. Verband der Schadenversicherer (VdS, Germany) aw ..
8. NYC MEA 258 -93 -E X
UL Listing Category
Sprinklers, Automatic & Open
Quick Response Sprinkler Vertical Sidewall Conventional
UL Guide Number
VNIV
Product Description
Reliable Models F1FR and F1FR Recessed Sprinklers are , 1 ' cr
quick response sprinklers which combine the durability of a i-, (or (--
standard sprinkler with the attractive low profile of a decorative ,;,, � " . ., ` '
• sprinkler. -
The Models Fl FR and Fl FR Recessed automatic sprinklers -
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response times in laboratory tests which are five
to ten times faster than standard response sprinklers. This Horizontal Sidewall Recessed Pendent
quick response enables the Model Fl FR and Fl FR Recessed HSW 1 Deflector
sprinklers to apply water to a fire much faster than standard
sprinklers of the same temperature rating. Application
The glass bulb consists of an accurately controlled amount Quick response sprinklers are used in fixed fire protec-
of special fluid hermetically sealed inside a precisely manufac- tion systems: Wet, Dry, Deluge or Preaction. Care must be
tured glass capsule. This glass bulb is specially constructed to exercised that the orifice size, temperature rating, deflector
provide fast thermal response. The balance of parts are made style and sprinkler type are in accordance with the latest
of brass, copper and beryllium nickel. published standards of the National Fire Protection Asso-
At normal temperatures, the glass bulb contains the fluid ciation or the approving Authority Having Jurisdiction.
in both the liquid and vapor phases. The vapor phase can Quick response sprinklers are intended for installation as
be seen as a small bubble. As heat is applied, the liquid ex- specified in NFPA 13. Quick response sprinklers and stan-
pands, forcing the bubble smaller and smaller as the liquid dard response sprinklers should not be intermixed.
pressure increases. Continued heating forces the liquid to
push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
The temperature rating of the sprinkler is identified by the
color of the glass bulb.
The Reliable Automatic Sprinkler Co., Inc. 525 North MacQuesten Parkway, Mount Vernon, New York 10552
Model Fl FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
•
Sprinkler Type K Factor S nkler royal Sprinkler Identification
Standard Upnght (SSU) and Pendent (SSP) U Metric Height Organization
Number (SIN)
Deflectors Marked to Indicate Position SSU SSP
X" (15mm) Standard Orifice with X" NPT (RX) Thread 5 6 80 2.2" (56mm) 1,2,3,4,5,6,7 R3625 R3615
' %' (20mm) Large Orifice with 3,1" NPT (R 8.0 115
231111' (58mm) 1,2,3,4,7,8 R3622 R3612 (11 \ " (17mm) Small Orifice with X" NPT (RX) Thread 4 2 60 25" (65mm) 1,2,8 R3623 R3613
3q" (10mm) Small Orifice with X" NPT (RX) Thread 2.8 40 2.5" (65mm) 1,2,8 R3621 R3611
10mm Orifice XLH with RX" Thread 4 2 60 56mm 4,6,7 R3624 R3614
Conventional-Install in Upright or Pendent Position
10mm Orifice XLH with R3a Thread 4 2 60 56mm — R3674
15mm Standard Orifice with Y2 NPT (RX) Thread 5 6 80 56 mm 4,6,7 R3675
20mm Large Onfice with 3 /4" NPT (R 8 0 115 58 mm 4,7 R3672
t iji)
i s
rk c
3 i
Upright Pendent Upright Conventional
. Model Fl FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model RC1 Sprinkler Wrench
Installation Data:
Nominal Thread K Factor Sprinkler Approvali Sprinkler Identification
Orifice Size US Metric Height Organizations Number (SIN)
X" (15mm) X" NPT (R'h) 5.6 80 2.2" (56mm) 1,2,3,4,5,7,8 R3615
'X;' (20mm) X" NPT (R 8.0 115 2 3" (58mm) 1,2,3 R3612
X (11mm) / NPT (R'/) 4.2 60 254" (65mm) 1,2,8 R3613
%" (10mm) X" NPT (R'h) 2.8 40 254" (65mm) 1,2,8 R3611
10mm RX 4.2 60 56 1mm 4,7 R3614
t Refer to escutcheon data table for approvals and dimensions.
2 r �• RiaeE 6rt
a7.�1
I 15/16 aw
..—
(49.2n .J
li- - — — r 1/1' x �• REDUCER
TARN anti.4R
AG
11 noir
AGAD,$T SPROPCUR
WRENCH 6055
I - I
P /T I — I f FOAM RP'
tilhal1-----.111NLI TAM 111 — rs7 mnl ,-,,,
/■ 1
1 27/.V DA
(72.2 ) 'T Isamu)
(f) RUM TO ESCUTCHEON DATA TABLE FOR APPROVALS AND miasma
2.
Model Fl FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
K Factor Approval Sprinkler identification
Nominal Orifice Thread Size US Metric Sprinkler Height Organizations Number (SIN)
'/2" '/2" NPT (R' /2) 5.6 80 2.2" (56mm) 1, 2, 3, 6, 8
R3685
15mm 'h" NPT (R1/2) 5.6 80 2.2" (56mm) 4 (')
(1) LPC Approval is for Pendent position only.
Orientation Deflector to Ceiling
Dimension (Min. - Max.)
. Upright 4" - 12" (102mm - 305mm)
ill Pendent 6" - 12" (152mm - 305mm)
V r3
Vertical Sidewall
Model Fl FR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Approval Organizations Sprinkler
K Factor and Type of Approval Identification
Nominal Thread Sprinkler LI ht Ordinary umber
Orifice Size US Metric Length Hazard Hazard (SIN)
X" (15mm) X" NPT(R'h) 5 6 80 2 63" (67mm) 1,2,3,5,8 1,2,5,8 R3635
NOTE: UL and ULC Listing permits use with F1 or F2 recessed escutcheon.
:,� r „F, a . v ff
7 T
: 1 � i t'N . . �� � if
EI S . V
Horizontal Sidewall
3.
I.
Installation Sprinkler Types
Quick response sprinklers are intended for installation Standard Upright
as specified in NFPA 13. Quick response sprinklers and Standard Pendent
standard response sprinklers should not be intermixed. Conventional
- The Model Fl FR Recessed Quick Response Sprinklers
are to be installed as shown. The Model Fl or F2 Escutch- Sidewall (Vertical, Horizontal HSW1)
eons illustrated are the only recessed escutcheons to be Recessed Pendent
used with the Model Fl FR Sprinklers. The use of any other Recessed Horizontal Sidewall HSW1
recessed escutcheon will void all approvals and negate all
warranties.
When installing Model Fl FR Sprinklers, use the Model D
Sprinkler Wrench. When installing Model Fl FR Recessed Finishes (1) (2)
Sidewall Sprinklers, use the Model GFR1 Sprinkler Standard Finishes
Wrench. Use the Model RC1 Wrench for installing F1FR Sprinider Escutcheon
Recessed Pendent Sprinklers. Any other type of wrench Bronze Brass
may damage these sprinklers. Chrome Plated Chrome Plated (3)
White Polyester Coated White Painted (3)
Temperature Ratings Special Application Finishes
Sprinkler Sprinkler Escutcheon
Classification Temperature Max. Ambient Bulb Bright Brass Bright Brass
°C °F Temp. Color Black Plated Black Plated
Ordinary 57 135 100°F (38°C) Orange Black Paint Black Paint
Ordinary 68 155 100'F(38°C) Red Off White Off White
Intermediate 79 175 150°F(66°C) Yellow '
Intermediate 93 200 150°F(66°C) Green Satin Chrome Satin Chrome
High (1) 141 286 225°F(107°C) Blue 1 Other finishes and colors are available on special order.
Consult the factory for details
(t) Not available for recessed sprinklers
(2) FM Approvals is limited to bronze and brass, chrome or black
plated finishes only.
Escutcheon Data ( FP Push- on/Thread -off escutcheon
Escutcheon "A"
Approvals Adjustment CargMingor Dimension model Wall Dimension
F1 1,2,4 X" 46 "-' Ordering Information
(19mm) (19mm) (5mm -24mm) Specify:
F2 1,2,3,4,5,7,8 y" 1 " ;6'-1X6" 1. Sprinkler Model
(13mm) (25mm) (5mm -17mm)
2. Sprinkler Type
FP 1,2 Fully Recessed 716 3. Orifice Size
Push-on/ (11 mm)
Thread -off 1,2 Fully Retracted 'K" 4. Deflector Type
(24mm) 5. Temperature Rating
Maintenance 6. Sprinkler Finish
The Models F1FR and F1FR Recessed Sprinklers 7. Escutcheon Type
should be inspected quarterly and the sprinkler system 8. Escutcheon Finish (where applicable)
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other Note: When Model F1FR Recessed sprinklers are
cleaning fluids. Remove dust by using a soft brush or gen- ordered, the sprinklers and escutcheons are packaged
tie vacuuming. Remove any sprinkler which has been separately.
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
I in the original cartons and packaging until used to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non - operation.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable
Products manufactured and distributed by Reliable have been protecting life and property for over B0 years, and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
® The Reliable Automatic Sprinkler Co., Inc. ts paper
Rellabil
(800)431 -1588 Sales Offices
(800)848 Sales Fax Revision lines indicate updated or new data
(914)668-3470 Corporate Offices
www rehabiesprinkier corn Internet Address EG Printed in U S A 3/03 PM9999970027
Bulletin 154 Rev E
® Model G c
Quick Response
Concealed
Automatic Sprinkler m
The Concealer
UL Quick Response '41P,-.....r r . „r„."...•,•„.....,..•.,-,.. Y . . : ,,.......,..4• T
, ,
FM Standard Response s ' -i,`. i > v � -4 ` ,, r '- Ili ', ..
Concealed Sprinkler With a �. '',14';'”, ,� ; ;, , c77.
.; _, i � ; ;.,. ; ■
1/2 11 ° 4: A. 1. :.••, .�t- ti... 1 ^ .`'' F �. .°
'/2 (13mm) or 1'/z (38mm) Adjustment . . ti _`•
Y. T '14, rl•J
Features , •
4c '''•,:,', ,.yi;,' - r ' ,.' 1
1. Cover plate attachment with / (13mm) �,. • " ' „:
assembly adjustment. ,� .- ;, , � ;Ty. .x „a
2. Smooth aesthetic ceiling profile. .:� .}4',�?, .
3. Factory installed protective cap. . `�'� -` -�. s: `�
4. Available in brass, chrome or black r` .. F r .� ; °..,,, .
plated and white painted finishes.
_ 5. Ordinary temperature rating. } r . :
6. Multiple orifices for design flexibility. ' ,I f -,
Approvals & Listings < - ▪ 5 -. r ' -
1. Underwriters Labortones, Inc. (UL)- _-- ;«may _-
Quick Response The Model G4A Concealer® is designed for use where
2. Underwriters Laboratories of Canada (ULC)- aesthetic appearance is important. Offices, hospitals, motels
Quick Response and restaurants are but a few of the applications where it can be
3. Factory Mutual Research Corp. (FM)- used. It is available in different orifice sizes allowing the designer
Standard Response to optimize system performance, thereby achieving a very
efficient installation.
• Light Hazard Occupanicies- The Model G4A Concealer® is a UL Listed Quick Response
No Limitations Concealed sprinkler intended for use in accordance with NFPA
• Ordinary Hazard Occupancies 13. FM Approves this sprinkler as a standard response
Groups 1 & 2 Wet Systems Only concealed sprinkler intended for use in accordance with FM
p y Loss Prevention Data Sheet 2-8N.
4. NYC MEA 258 -93-E - Quick Response
Product Description
The Reliable Model G4A Concealer uses a proven quick
U.S. Patent number 4,880,063. response fusible element in a standard style sprinkler frame
with a drop -down deflector. This assembly is recessed into the
Application ceiling and concealed by a flat cover plate assembly. The
pP threaded engagement provides h (13mm) of cover
The Reliable Model G4A adjustment. The flat cover plate is attached to the skirt using
Concealer" is the most versatile 135 °F (57 °C) ordinary temperature classification solder.
quick response concealed sprin- .. When the ceiling temperature rises, the solder holding the flat
kler available. It provides the best cover plate melts, the flat cover plate released thus exposing
form of fire protection while '` the sprinkler inside to the rising ambient temperature.
offering an attractive appearance The subsequent fusing of the element opens the waterway
and Yz" (13mm) of cover adjust- i and causes the deflector to distribute the water. Any secure
ment for ease of installation. The - - - engagement between the cover plate and cup will assure that
small diameter cover plate as- the drop -down deflector is properly located below the ceiling.
sembly is easily attached and
blends into the ceiling, concealing
the most dependable fire protec-
tion available, an automatic
sprinkler system.
The Reliable Automatic Sprinkler Co., Inc. , 525 North MacQuesten Parkway, Mount Vernon , New York, 10552
Installation Ordering Information
Do not install the G4A Concealer in ceilings which have 1. Sprinkler Model j )
positive pressure in the space above. 2. Nominal Orifice , .a .
• Cut a 2% inch (67mm) diameter hole is cut in the ceiling, the 3. Flat Cover Plate
sprinkler is easily installed with the Model G4 Wrench. The Assembly Finish
wrench has drive tangs which insert into the cup slots. 4. Inlet Type
When installing a sprinkler the wrench is first positioned into OR
the sprinkler /cup assembly until the wrench tangs engage
the drive slots in the top of the cup (there are two sets of Cover Plate Finishes"' ' drive slots in the cup). The sprinkler is then tightened into
the pipe fitting. When inserting or removing the wrench from Standard Finishes
the sprinkler /cup assembly, care should be taken to prevent Bronze Ir. 3
damage to the sprinkler. DO NOT WRENCH ON ANY Chrome
OTHER PART OF THE SPRINKLER/CUP ASSEMBLY. White Paint Model G4 Sprinkler
Install the cover plate by hand turning the cover in the Wrench
clockwise direction until it is tight against the ceiling. Special Application
A protective cap is provided to protect the drop -down sprinkler Finishes UL Listing Category
deflector from damage which could occur during construction Bright Brass
before the cover plate is installed. The cap is factory installed Black Plating Sprinklers, Automatic and
inside the sprinkler cup. Remove cap to install sprinkler, then Black Paint Open
re- install cap until the cover plate is installed. Off White Quick Response Sprinkler
Maintenance Satin Chrome UL Guide Number
The Model G4A Concealer' should be inspected quarterly t ' 1 Other finishes and colors are VNIV
and the sprinkler system maintained in accordance with NFPA Cons for orde
25. Do not clean sprinklers with soap and water, ammonia or any
other cleaning fluids. Remove any sprinkler that has been
painted (other than factory applied) or damaged in any way. A Temperature Rating
stock of spare sprinklers should be maintained to allow quick
replacement of damaged or operated sprinklers. Prior to Classification Sprinkler Cover Max. Ambient
. installation, sprinklers should be maintained in the original Plate Temp.
cartons and packaging to minimize the potential for damage to Ordinary 165F/74°C 135 °F /57 °C 100 °F /38 °C
sprinklers that would cause improper operation or non-operation.
Technical Data
Sprinkler Inlet Total Nominal Nominal K Factor Thread Approvals Identifcation Sprinkler SIN
Adjustment Orifice US Metric (SIN)
Non Adjustable '' /z" (13mm) 'h" (15mm) 5.6 80 '/z" NPT (R') 1,2,3,4 R5415
Non Adjustable %i' (13mm) y,, (11mm) 4.2 60 '/z "NPT (RY) 1,2,4 R5413
Non Adjustable ' /z" (13mm) 9" (10mm) 2.8 40 '/z "NPT (R' /z) 1,2,3,4 R5411
Adjustable 11/2" (38mm) 'h" (15mm) 5 6 80 1" NPT Male or Female 1,2,4 R5418
Adjustable 11/2" (38mm) ' /, (11mm) 4 2 60 1" NPT Male or Female 1,2,4 R5413
Adjustable 1'/2" (38mm) /" (10mm) 2 8 40 1" NPT Male or Female 1,2,4 R5412
Fig.1 - 1/2" NPT Non - Adjustable Inlet Fig. 2 - 1" NPT Male- Adjustable Inlet Fig. 3 - 1" NPT Female- Adjustable Inlet
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified
and reputable sprinkler contractors located throughout the United States, Canada and foreign countries
ivirailitiiiiimmummiimim ® Recycled
The Reliable Automatic Sprinkler Co., Inc. Paper
liab (800) 431 -1588 Sales Offices
(800) 848 -6051 Sales Fax Revision lines indicate updated or new data
(914) 668 -3470 Corporate Offices
www rehablespnnkler corn Internet Address EG Printed in USA 05/05 P/N 9999970150
•
Bulletin 153 Rev E
Co
ME
® Model F3
Dry Sprinklers ry p co
m
Features • 1. The Model F3 Sprinkler utilizes Belleville Spring ` i . •• ". °:•.;-- 14'.
Closure Technology ;i t - '
. . K
2. Styles available for Model F3 Dry Sprinklers: „ ! �; , ,
• Pendent ir µ `
• Recessed Pendent '
• Concealed '
• Horizontal Sidewall t r , • • Recessed Horizontal Sidewall f '' . �,, ;. u
3. 11/2" (38mm) escutcheon adjustment on pendent �A -
sprinkler. Concealed
4. 1" (13mm) escutcheon adjustment on recessed '1 • - ' ,, ` '
sprinkler with push -on /thread -off FP Model - ;.- - -- ;
escutcheon ring. = ". .. .4 "' :
5. %" (9.5mm) cover plate adjustment on concealed
- sprinkler with push -on / thread -off CCP cover. ti
6. Attractive appearance. Employs 5mm frangible glass bulb and galvanized nipple.
7. Lengths available to accommodate installation fit= - =y, si ' it
dimensions from 2" - to - 48" (51 mm - to - _�. .
1219mm), in ' /d' (6mm) increments. Y'
8. Available in a variety of plated and painted finishes. Recessed Pendent
9. For use with wet pipe, dry pipe and all preaction
sprinkler systems. a
U.S. Patent Numbers 5,775,431 and 5,967,240.
Approvals - ,
SIN Sprinlder Type Approvals
IT
Pendent
R5314 Recessed Pendent 1 (1) (2) , 2 0)13) , 3 ") (2), 4(1)(2)
CCP Concealed Pendent Pendent
R5334 Horizontal Sidewall 1 11 2) 2 0) , 4 (1)(2)
Recessed Horizontal Sidewall
Approval Organization •
1. Listed by Underwriters Laboratories Inc. and UL / ` 4
Certified for Canada (cULus) ' -
2. Certified by FM Approvals ., .,. ` ,
3. LPCB EC Certificate of Conformity (CE) ti ,')
6832 -CPD -2006 (EN12259 -1 ) ' t'r -
4. NYC MEA 258 -93 -E
Note: (1) Light Hazard
(2) Ordinary Hazard
(3) Ordinary Hazard, Group 1 & 2
Horizontal Sidewall
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York10552
Model F3 Dry Pendent Sprinkler
"A" Dim. 12" to 48" (51 mm to 1219mm) in 1 /4' (6mm) increments
Inlet Protrusion Erected
Finishes ") Atone Inside Pipe
'Sprinkler Escutcheon I -- - -1— 1 -- " —•
Bronze Brass 8' == -di 1 � r1.
Chrome Plated Chrome Plated
White Painted' White '. - J System Tee
Lead Plated
i Wax Coated " " �� 1• NPT Over Lead (3" 2 1/8' Dm. 'A' Olmenaon [53.98nvn] in
"Other finishes and colors are available on special order. Consult Adjustment Range Kale In Ceiling
factory for details. +1/1' ( -635mml
ry -1 1/4' [- 31.75mm] i 13/61' Die. l/2' [36 .1trnm]
(T White painted sprinklers will have chrome plated can. (1217mm] Teta Ad ustment
"' 155 °F (68 °C) to 200 °F (93 °C) rating only. Sprinkler can Ceding 1 1 /4' [3175mm)
"' 212 °F (100 °C) brown wax may be used on 286 °F (141°C) sprinklers Mill
' lie ce.ssmrsi
when maximum ceiling temperatures do not exceed 150 °F (66 °C) Escutcheon ^ c.ag , c�; u Escutcheon
Adjustment
Standard Temperature Ratings NaminW Position ! r
rill Spunkier of Escutcheon 1 5/8'
[4126mm]
Temperature Max. Bulb a
Classification Rating Ambient Temp. Color 1 / 4 ' m] —
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange r [7620mm]
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red °IA. 1Ji01 -`
Intermediate 200 °F (93 °C) 150 °F (66 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
Sprinkler can and escutcheon fabricated of brass for better weather
resistance in exterior applications.
Note: The sprinkler can protrudes 1 /4" when escutcheon
Sprinkler Guard: Model C -2 is in nominal position. Escutcheon adjustment
provides + 1/4" ( +6mm) to - 1 ( -32mm) "A"
- Sprinkler Installation Wrench: dimension adjustment range.
Model G3 Sprinkler Wrench
- Sprinkler Identification Number (SIN): R5314
Model F3 Dry Pendent Recessed Sprinkler
"A" Dim. 13 to 48" (89rrrn to 1219mm) in 1/4" (arm) inutit n ents
r,
Inlet Protrusion Elevoted :=4;? -- - r-- 1TC
Finishes "' Above Inside Pipe _ RR '
Ah '
Sprinkler Escutcheon
a==_: " - 1 - - r -- - "''
� r t , t t�
Bronze Brass ? ,
Chrome Plated Chrome Plated - System Tee
White Painted White imam.
(1) Other finishes and colors are available on special order f 1' NPT
Consult factory for details. Cup remains unfinished
Only the escutcheon will contain desired finish 2 1/2' Die.
'A' Dimension (63 50mm] III
Adjustment Dimension Hole e1 mm]
tt //'
Standard Temperature Ratings (±6.35mm] 2 19/6 Dia.
Sprinkler Max. [58.34mm]
Temperature Ambient Bulb Nominal Position Spr,nkler m
Classification Rating Temp. Color of Escutcheon Cup Assebly
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange _ I I I
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red r- n9 Escutcheon
Intermediate 200 °F (93 °C) 150 °F (66 °C) Green —~ cab ii i�tl0l� ,- ceTii;y-
High" 286 °F (141 °C) 225 °F(107 °C) Blue klo/
and FP Escutcheon fabricated of steel and 1 /h. [6.35 m] -'
S
1
prinkler cup Escutcheon Ad
recommended for interior applications.
1/4 (6.35mm] 3 7/32' Dia.
"Listed and Certified only by cULus Escutcheon Adjustment [81.76mm]
1/2' (12.70mm]
Total Adjustment I33iG02 -C
Sprinkler Installation Wrench:
Model G3 R/C Sprinkler Wrench
Sprinkler Identification Number (SIN): R5314 Note: Do not install the Model F3 Dry Pendent Recessed
Sprinkler in ceilings which have positive pressure
in space above.
2.
Model F3 Dry Pendent Concealed Sprinkler
"A" Dim. 13/," to 48" (89rrm to 1219mm) m'A" (6 increments
CCP Cover Plate" Finishest2, Intel Provisos Elevated =___ n r - - -f ------
Above Inside Pipe flT t -: Standard Finishes Special Application Finishes - 1I'
Chrome Plated Bright Brass Plated , .r- ;,' --_t
White Black Plated
Black Paint -- system Tee
Off White i
Satin Chrome %
III I- NM
(1) Utilizes the y" cover plate with " total adjustment.
(2) Other finishes and colors are available on special order [ 63 /w mmj ■
Consult factory for details •A Dime "s'°" Hole in Ceding
Adjustment Range
t 3/16' 1
Standard Temperature Ratings [14.76mm) 2 ia-
Sprinkler
Temperature Cover Plate Max. Ambient Nominal Position Sprmkln
Classification Rating Temp. Rating Temp. of Coverplate Cup Assembly
Ordinary 135 °F (57 °C) 135 °F (57 °C) 100 °F (38 °C) �i Coverplate
Ordinary 155 °F (68 °C) 135 °F (57 °C) 100 °F (38 °C) ; cedn 1; A......1), Intermediate 200 °F (93 °C) 165 °F (74 °C) 150 °F (66 °C) m---
I illg j- —
High' 2 °F (141 °C) 165 °F (74 °C) 150 °F (66 °C) 1 _1 — _ c e r n,
_
3/16" [4.76mm] J ‘ n
Sprinkler cup fabricated of steel and CCP Cover Plate fabricated of Coverplate Adjustment
brass and recommended for interior applications. 3 /1e [4.76mm] '
• Coverplate Adjustment 3 5/16 D
Listed and Certified only by cULus 3/8' [9.53mm] [84 13mm]
Total Adjustment 1537-005 -C
Sprinkler Installation Wrench
- Model G3 R/C Sprinkler Wrench
Sprinkler Identification Number SIN • R5314 Note: Do not install the Model F3 CCP Pendent
P (SIN): Concealed Sprinkler in ceilings which have
positive pressure in the space above.
Model F3 Dry Horizontal Sidewall Sprinkler
r --
A" Dim. I 2" to 48" (51 mm to 1219mm) in 1/4" (6mm) increments
Finishest'
Sprinkler Escutcheon 1 1/2 [3810 _
T otal Adjustment I
Bronze Brass r r --- -- -- ciI7 _ ---
Chrome Plated Chrome Plated
White Painted'' White 1 r j o r f
• Lead Plated "' l._J i .1 4 [101 Gomm] Mn
Wax Coated " "4' 1 1/4 [31.75mm] 12 [304.80mm] Moe
P(''' E Adjustment
Wax Over Lead ' j -' 1/4 [6 35mrr]
System tee _ Escutcheon Adjustment
"' Other finishes and colors are available on special order �, r 1-,
Consult factory for details. • ��N 2 3/32•
`� White painted sprinklers will have chrome plated can. - - - - -r l �, r 53,8,..., [F
-
"' 155 °F (68 °C) to 200 °F (93 °C) rating only. , = " - jjj iIill _ -_ I ' •_• —: 3 D
`; - ' o.
41 212 °F (100 °C) brown wax may be used on 286 °F (141 °C) sprinklers — IpII�IIIIII I [762
when maximum ceiling temperatures do not exceed 150 °F (66 °C). ` :,_ =
Standard Temperature Ratings 2 I /8 D,°. ! i •
[5398mm] L l
Hole Iy411 1/4' [635mm]
Sprinkler rf Prolruslon
Temperature Max. Ambient Sprnkler Cam J
Classification Rating Temp. Bulb Color . • A • Dimenswn
~ Adjustment of Escutcheon °n
Ordinary 135°F (57°C) 100°F (38°C) Orange Range + 1/4 [ +635mm]
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red rer.tea{ — I 1/4 [- 31.75mm]
Intermediate 200 °F (93 °C) 150 °F (66 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
Sprinkler can and escutcheon fabricated of brass for better weather
resistance in exterior applications. Note: The sprinkler can protrudes 1 /4" when escutcheon
is in nominal position. Escutcheon adjustment
Sprinkler Installation Wrench: provides + 1 /4" ( +6mm) to -1 ( -32mm) "A"
Model G3 Sprinkler Wrench. dimension adjustment range.
Sprinkler Identification Number (SIN): R5334
3.
Model F3 Dry Horizontal Recessed Sidewall Sprinkler
. ! "A" Dim. 13' / /'to 48" (89rrm to 1219m) in 'A" (6mm) roue 1 e+ts
Finisheso r .- ```n°
Sprinkler Escutcheon t ' - � + +s /�:
Bronze Brass E.outtMm r, +' IJt).7mmj
Chrome Plated Chrome Plated St,,�, T. a, i ; I e IX im]u°:.
White Painted White i
' "Other finishes and colors are available on special order. Consult +• NPf - _ —T
factory for details. il-
— fil -
Sprinkler's can and FP Escutcheon are fabricated of steel and �u+ ":1111 ; �� 111111/1 — � II1 ' ' s 7 /u-
recommended for interior applications UII
2 + /216 . i o Iol.emm)
gn NO IIIlllllE I
Mod. . ;;
1 No.
2 l0 /64158 7mmlDUl t J
Standard Temperature Ratings -earn ti2.7mm,
-A- 6msntion ECWCh A°ju.tmenl
•
Sprinkler Max. Bulb 's °.tm mow.
.+ /x' -o
Classification Temperature Rating Ambient Temp. Color N12.7 -Ot
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 200 °F (93 °C) 150 °F (66°C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue .
• Listed and Certified only by cULus. Notes: Do not Install the Model F3 Dry Horizontal
Recessed Sidewall Sprinkler in walls which
have positive pressure in their side space.
• Recessed Horizontal Sidewall sprinklers are
listed by cULus for installation of min. 4" (100mm)
Sprinkler Installation Wrench: - to - max. 6" (150mm) below ceiling, and FM
Model G3 R/C Sprinkler Wrench approved for installation of min. 4" (100mm) - to -
. Sprinkler Identification Number (SIN): R5334 max. 12" (306mm).
Technical Data Ordering Information
Orifice Size: 1 /2" (15mm) Specify:
Thread size: 1" NPT per ANSI B2.1 1. Sprinkler Type (select one):
Working Pressure: 175 psi (12 bar) (a) Model F3 Dry Pendent
Nominal K Factor - US / (Metric): 5.6 / (80) (b) Model F3 Dry Recessed Pendent
Product Description (c) Model F3 Dry Concealed Pendent
Reliable Model F3 Dry Sprinklers are standard (d) Model F3 Dry Horizontal sidewall
response sprinklers utilizing a durable 5mm frangible (e) Model F3 Dry Recessed Horizontal Sidewall
glass bulb. Model F3 Dry Sprinklers are intended for use 2. Sprinkler Temperature Rating.
in dry and preaction systems and in areas subjected to
freezing temperatures, such as freezers and unheated 3. Sprinkler Finish.
portions of buildings. 4. Cover Plate /FP Escutcheon Finish.
Environments wherein dry sprinklers are employed 5. Length: "A" Dimension (face of tee to face of ceiling
can be corrosive. For this reason, Model F3 Sprinklers or wall) in Y4 " (6.4mm) increments.
have a special wax fillet placed in the gap between the
cup that supports the bulb and the wrenching boss. This Note:
wax will not interfere with the operation of the sprinkler, 1. The "A" dimension is based on a nominally gauged
and it prevents contaminents from entering the internal pipe thread "make -up" of .600" (15mm) per ANSI
portion of the drop nipple. The wax must not be B2.1 [7' threads approximately].
removed. 2. All platings and paintings are decorative and
Operation intended for interior use.
The glass bulb consists of an accurately controlled 3. Acceptable appearance in conditions such as
amount of special fluid hermetically sealed inside a parking garages is generally provided with bronze
precisely manufactured glass capsule. When the sprinkler, brass cup and escutcheon for the Model F3
temperature increases sufficiently due to a fire, the bulb Pendent only.
shatters allowing operating parts to clear the waterway.
This enables the inlet seal to release air or water and
subsequently, cause water flow over the deflector in a
uniform spray pattern, controlling or extinguishing the fire.
4.
General Installation Instructions
Model F3 dry sprinklers must be installed only in
. standard (ANSI B 16.3 class 150 and ANSI B 16.4 class
125) pipe tees even at branch line ends. For these and = ;"
ether fittings including CPVC, the dry sprinkler should be ` t `
installed into a fitting to conform with protrusion into the 4
fitting in accordance with the diagrams. Dry sprinklers ,--
4 S3
should not be installed into elbows and into pipe s A g ■s,�
couplings located on drop nipples to the sprinklers. The �,
"A" dimension of a dry sprinkler, which extends into , • q ,
freezers from wet pipe systems, should be selected to '.,
provide at least 14" (356mm) between the freezer's ;'
outside wall or ceiling and the wet pipe line.
1. Cut the specified size hole (see illustrations) for the
sprinkler in the ceiling directly in line with the tee.
2. Apply pipe joint compound to the 1" (25mm) pipe Fig. 1 - G3 R/C Wrench •
threads and install sprinkler using the Model G3 or
G3 R/C Sprinkler Wrench as specified.
3. Install the Model FP push -on / thread -off escutcheon or -
CCP cover plate if required.
Note: Installation of the Model F3 Sprinklers in „
copper pipe systems is not recommended, r .
k7.'
as this may reduce the life expectancy
of the sprinklers. - t`,_3. ; s. /' ,
Model F3 Concealed and Recessed 7x
Installation Instructions '
• The Model G3 R/C Wrench (Fig. 1) is designed to f '
locate on the wrenching ads of the Recessed
sprinkler while centering in the cup. A standard W ,?•• -- ••
drive ratchet may be used to drive this wrench.
Figures 1 and 2 show sequentially the insertion of the F.
wrench. First, the wrench, with its jaws above the
• sprinkler deflector, is moved laterally until centered Fig. 2 - G3 R/C Wrench
with the cup. Then raise the wrench inside the cup
until its jaws engage the sprinkler's square wrenching
pads (Fig. 3). To remove the wrench, follow this
procedure in reverse order. Care should be taken to -: -;A.
avoid striking the deflector with the wrench. • Model G3 Wrench (Fig. 4) is used for installation of Pendent and Horizontal sidewall sprinklers.
Maintenance The Model F3 Dry Sprinklers should be inspected quarterly and the sprinkler system maintained in accordance with NFPA 25. Do not remove the factory _______ applied thermally sensitive wax fillet between the bulb supporting cup and the wrenching boss. Do not replace this wax with a substitute substance. An Alternate
substance may interfere with proper operation of the
sprinkler. Do not clean sprinklers with soap and water,
ammonia or any other cleaning fluids. Remove dust by Fig. 3 - G3 R/C Wrench
using a soft brush or gently vacuuming. Remove any
sprinkler which has been painted (other than factory
applied) or damaged in any way. A stock of spare I:.
sprinklers should be maintained to allow quick .:41Z,
replacement of damaged or operated sprinklers. Prior ',
to installation, sprinklers should be maintained in the .
original cartons and packaging until used to minimize l
the potential for damage to sprinklers that would cause l i l ' ° ..
improper operation or non - operation. n ` . !
Fig. 4 - G3 Wrench
5.
I•
Reflable...For Comp!ete Protecflon
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision -made Reliable products that guard life and property from fire around the clock
• Automatic sprinklers • Deluge valves
• Flush automatic sprinklers • Detector check valves
• Recessed automatic sprinklers • Check valves
• Concealed automatic sprinklers • Supertrol electrical system
• Adjustable automatic sprinklers • Sprinkler emergency cabinets
• Dry automatic sprinklers • Sprinkler wrenches
• Intermediate level sprinklers • Sprinkler escutcheons and guards
• Open sprinklers • Inspectors test connections
• Spray nozzles • Sight drains
• Alarm valves • Ball drips and drum drips
• • Retarding chambers • Control valve seals
• Dry pipe valves • Air maintenance devices
• Accelerators for dry pipe valves • Air compressors
• Mechanical sprinkler alarms • Pressure gauges
• Electrical sprinkler alarm switches • Identification signs
• Water flow detectors • Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association. Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable
Products manufactured and distributed by Reliable have been protecting life and property for over B0 years, and are installed and serviced by the most highly qualified and
reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
•• Recycled
The Reliable Automatic Sprinkler Co., Inc. Pape
laReibld (800) 431 -1588 Sales Office
(800) 848 -6051 Sales Fax
(914) 668 -3470 Corporate Offices Revision lines indicate updated or new data
www reliabiespnnkler corn Internet Address E G Printed In U S A 1/05 P/N 9999970146