Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 �t R ; February 6, 2007 RE_ First Call Heating & Cooling Dave Schoennoehl 1650 NE Lombard Portland, OR 97211 RE: MECHANICAL SYSTEM Project Information Building Permit Mec2007 -00055 Construction Type: II -B Tenant Name: Macy's Occupancy Type: M Address: 9300 Washington Sq The plan review was performed under the State of Mechanical Structural Specialty Code (OMSC) 2004 edition and 2004 Oregon Fire Code as amended by TVF &R The submitted plans are approved subject to the following conditions. 1. The building or structure shall not be weakened by the installation of mechanical systems. Where floors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with the Oregon Building Code. 302.1 OMSC 2. Condensate drain systems shall be provided for equipment and appliances containing evaporators or cooling coils. Condensate drain systems shall be designed, constructed and installed in accordance with Sections 307.2.1 through 307.2.4 of OMSC. 307.2 OMSC 3. Gas piping systems under 14 inches (3.5 kPa) water column pressure, shall be tested at a pressure of not less than 10 pounds per square inch gage. Test pressures shall be held for not less than 15 minutes with no perceptible drop in pressure. For welded piping, and for piping carrying gas at pressures exceeding 14 inches water column (3484 Pa) pressure, the test pressure shall be at least 60 pounds per square inch for not less than 30 minutes. C406 OMSC NOT PART OF THIS REVIEW: * Electrical * Fire Sprinklers or Alarms * Mechanical System * Plumbing Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, al enzel, Senior Plans Examiner