Specifications , Jun 13 00 03:13p R Professional Fire 503 -032 -4035 p.2 93 Q 4 'Pao� 100 LI tqcci I Fire & Building FIVE® Products R JUN 1 3 2006 Technical Services: Tel: (800) 381-9312 / Fax: (BOO) 791 -5500 CM( OF TIGA BUILDING D IVISION Series 7T/ -FRB — 2.8, 4.2, 5.6, and 8.0 K- factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General mospheres. Although corrosion resis- tant coated sprinklers have passed the standard corrosion tests of the appli- - Description cable approval agencies, the testing is " The Series TY-FRB, 2.8, 4.2, 5.6, and not representative of all possible cor- , rosive atmospheres. Consequently, it 8.0 K- factor, Upright and Pendent is recommended that the end user be I • 1 Sprinklers described in this data sheet consulted with respect to the suitability Sige.1 are quick response - standard cover- of these coatings for any given corro- age, decorative 3 mm glass bulb type sive environment. The effects of ambi- . • spray sprinklers designed for use in ent temperature, concentration of light or ordinary hazard, commercial chemicals, and gas /chemical velocity, - occupancies such as banks, hotels, should be considered, as a minimum, - shopping malls, etc. along with the corrosive nature of the • The recessed version of the Series chemical to which the sprinklers will be TY FRB Pendent Sprinkler, where ap- exposed. plicable, is intended for use in areas An intermediate level versions of the with a finished ceiling. It uses either a Series TY FRB Pendent Sprinklers are two -piece Style 10 (1/2 inch NPT) or detailed in Technical Data Sheet /'N+ .) Style 40 (3/4 inch NPT) Recessed Es- TFP356, and Sprinkler Guards are de- / ,` '' 1 cutcheon with 1/2 inch (12,7 mm) of tailed in Technical Data Sheet TFP780 i i recessed adjustment or up to 3/4 inch 1 (19,1 mm) of total adjustment from the WARNINGS . flush pendent position, or a two-piece The Series TY -FRB Sprinklers de- k .I ., Style 20 (1/2 inch NPT) or Style 30 (3/4 scribed herein must be installed and inch NPT) Recessed Escutcheon with maintained in compliance with this .2`. •rr:.� 1/4 inch (6,4 mm) of recessed adjust- document, as well as with the applica- z ment or up to 1/2 inch (12,7 mm) of ble standards of the National Fire Pro- TY3231 - Pendent 5.6K, 1f2 "NPT total adjustment from the flush pen- section Association, in addition to the TY4131 - Upright 8.0K, 314 "NPT dent position. The adjustment provided standards of any otherauthorites hay- TY4231 - Pendent 8.0K, 3/4 "NPT by the Recessed Escutcheon reduces ing Jurisdiction. Failure to do so may the accuracy to which the fixed pipe impair the performance of these da- drops to the sprinklers must be cut. vices. Technical Corrosion resistant coatings, where The owner is responsible for maintain- Data applicable, are utilized to extend the ing their fire protection system and de- life of copper alloy sprinklers beyond vices in proper operating condition. that which would otherwise be ob- The installing contractor or sprinkler Approvals • tained when exposed to corrosive at- manufacturer should be contacted UL and C -UL Listed. with any questions. FM. LPCB, and NYC Approved. (Refer to Table A for complete approval IMPORTANT information including corrosion resis- Always refer to Technical Data tant status.) Sheet TFP700 for the "INSTALLER Model/Sprinkler Maximum Working Pressure WARNING" that provides cautions 175 psi (12,1 bar) with respect to handling and instal- Identification latfon of sprinkler systems and corn- Discharge Coefficient ponents. Improper handling and in- numbers K = 2.8 GPM /psil/ (40,3 LPM/barl / stallatron can permanently damage K = 4.2 GPM /psil/ (60,5 LPM/barl/ a sprinkler system or Its compo- TY1131 - Upright 2.8K, 1/2"NPT K = 5.6 GPM/psi / (80,6 LPM/barl / Hants and cause the sprinkler to fail TY1231 - Pendent 2.8K, 1/2 "NPT K = 8.0 GPM /psil / (115,2 LPM /bar to operate in a fire situation or cause TY2131 - Upright 4.2K, 1/2"NPT Temperature Ratings it to operate prematurely. TY2231 - Pendent 4.2K, 1/2"NPT Refer to Table A and B TY3131 - Upright 5.6K, 1/2 "NPT Page 1 of 8 JULY, 2004 TFP171 Jun 13 06 03:13p R Professional Fire 503 - 632 -4835 P.3 Page 2 of 8 TFP171 ESCUTCHEON 7116' (11,1 mm) STYLE 10 or 20 PLATE SEATING 1/2 "„ NOMINAL RECESSED SSU* • SURFACE NPT MAKE IN ESCUTCHEON DEFLECTOR 6 �- 21 5 7/16" 2 -1/4' �r�� (11,1 mm) i 4 m (57,2 m) f 11 A . A p-- , NOMINAL J' lilt ' MAKE -IN 2 1 -9/16' I 1111120 r b' 3 (39,7 mm) I' WRENCH ( 2-3/16' 55,6 mm) �� T III . FLATS 0 ; 1 Iwo ` 7 . SSP DEFLECTOR * - - 2 -7/8' (73,0 mm) DIA - 1/2' NPT ** I PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 1 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 7/16' (11,1 mm) STYLE 10 or 20 PLATE SEATING NOMINAL RECESSED SSU* " SURFACE NP T MAKE -IN ESCUTCHEON DEFLECTOR — °'r 6* —ter — /ll1Q t';iy�1(�117a f�. s ue— W ' �ry. -g I (55,6 mm) �A I (11,1 1 mm) 5 2 -3/16° I I tit X11: NOMINAL 4 I �n MAKE•IN 1 -1/2° (38,1 mm) �' WRENCH rte, ( 6/ m) Y 1 _ 2 ■ . FLATS _ - 1 �� r V 3 6 f 1 1 SSP DEFLECTOR * - 2 -7/8' (73,0 mm) DIA. ---I 1/2 NPT ** I PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating Is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * *Pipe thread connections p per ISO 7/1 can be provided on special request FIGURE 2 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT Y Finishes Bulb Glass 1 Sprinkler: Refer to Table A and B Compression Screw Bronze Operation Recessed Escutcheon: White Coated, Deflector . . ... Copper /Bronze - Chrome Plated, or Brass Plated Bushing (K =2.8) .. . . Bronze The glass Bulb contains a fluid which 2 expands when exposed to heat. When 5 Physical Characteristics the rated temperature is reached, the Frame Bronze fluid expands sufficiently to shatter the Q Button Brass/Copper glass Bulb, allowing the sprinkler to Z' Sealing Assembly activate and water to flow. r; . . . . Beryllium Nickel w/Teflont Jun 13 06 03:13p R Professional Fire 503 - 632 -4835 p.4 TFP171 Page 3 of 8 ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or20 PLATE SEATING .* NOMINAL RECESSED ,. SSU SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR 6 } — fO 7T i .rTY1i*llTt"A 5 7 = . e g, 2-3/16' I ■f,� 7/16" (55,6 mm) /MNA � � NO NAL } ���`�_� I NOMINAL I 1011' I M -IN , 4 1 112" I I`� I 2 -3/1 � 2 WRENCH t (55,6 mm) . V 1 -.A ._ _. -.- r. FLATS = 3 (38,1 mm) . SSP DEFLECTOR * - m• -- 2 -7/8" (73,0 mm) DIA. -- y 1/2" NPT' I PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 4 - Bulb 6 - Delleclor * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40 PLATE SEATING 3/4„ ** NOMINAL RECESSED SSU* SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR 2-5/16° � ii (12,7mm) r3' S (58,7 mm) I * . il l NOMINAL _ m MAKE -IN 1 -9 /16" 2 -1/4" ! T `� 2 (39,7 mm) WRENCH �L (5 mm) • FLATS 7,2 red 3 SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. 3/4" NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 • Frame 3 4 -Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 4 - QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 80 K- FACTOR, 3/4 INCH NPT Listing is based on the requirements of R / Design NFPA 13, and FM Approval is based Installation on the requirements of FM's Loss Pre- Criteria vention Data Sheets ). Only the Style The Series TY-FRB Sprinklers must be 10, 20, 30, or 40 Recessed Escutch- installed in accordance with the follow - The Series TY Pendent and Up - eon, as applicable, is to be used for ing instructions: right Sprinklers are intended for fire recessed pendent installations. protection systems designed in ac- NOTES cordance with the standard installation Do not install any bulb type sprinkler if rules recognized by the applicable the bulb is cracked or there is a loss of Listing or Approval agency (e.g., UL liquid from the bulb. With the sprinkler Jun 13 06 03:14p R Professional Fire 503 - 632 -4835 p.5 Page 4 of 8 TFP171 SPRINKLER FINISH (See Note 7) inch NPT sprinkler joint should be ob- `� K TYPE TEMP. BULB NATURAL CHROME WHITE"" tained with a torque of 10 to 20 nibs. UGUID BRASS PLATED POLYESTER (13,4 to 26,8 Nm) Nm). A u e i s to be of 30 ft -lbs. (40,7 Nm) of torque is to be used 135 °Fl57 °C Orange to install sprinklers with 3/4 NPT con - PENDENT ° nections. Higher levels of torque may P ENDED 155 F/68 °C Red distort the sprinkler inlet and cause and 175 °F /79 °C Yellow 1, 2, 3, 5 leakage or impairment of (he sprinkler. UPRIGHT 200 °F /93 °C Green Do not attempt to make -up for insuffi- 28 (TY1131) cleat adjustment in the escutcheon 286 °F /141 °C Blue plate by under- or over - tightening the 1/2" sprinkler. Readjust the position of the NPT 135 F /57 °C Orange sprinkler fitting to suit. RECESSED 155 °F /68 °C Red PENDENT The Series TY -FRB Pendent and Up- (TY1231)* 175 °F /79°C Yellow right Sprinklers must be installed in Figure 5 accordance with the following instruc- 200 °F/93 °C Green 1, 2, 5 tions. 135 °F /57 °C Orange Step 1. Pendent sprinklers are to be RECESSED 155 °F /68 °C Red - installed in the pendent position, and PENDENT upright sprinklers are to be installed in (TY1231)° 175 °F /79 °C Yellow the upright position. Figure 6 200°F /93 °C Green Step 2. With pipe thread sealant ap- 135°F/57°C Orange plied to the pipe threads, hand tighten PENDENT 155 °F /68 Red the sprinkler into the sprinkler fitting. (TY2231) Step 3. Tighten the sprinkler into the and 175 °F /79 °C Yellow sprinkler fitting using only the W -Type UPRIGHT 200 °F /93°C Green 6 Sprinkler Wrench (Ref. Figure 13). 4� (TY2131) With reference to Figures 1, 2, 3, and 4.2 286°F/141 °C Blue 2 4, the W -Type 6 Sprinkler Wrench is to NPT 135 °F /57°C Orange be applied to the sprinkler wrench RECESSED ° flats. PENDENT 155 F /68 °C Red (TY2231)• 175 °Fr79 °C Yellow The Series TY -FRB Recessed Pen- Figure 7 200 °F /93 °C Green dent Sprinklers must be installed in accordance with the following Instruc- 135°F/57°C Orange dons. PEND N T 155 °F /68°C Red Step A. After installing the Style 10. SE PENDE T 175 °Fr79"C Yellow 20, 30, or 40 Mounting Plate, as appli- Figure 8 20 cable, over the sprinkler threads and 0 °F /93°C Green with pipe thread sealant applied to the - pipe threads, hand tighten the sprin- NOTES: kler into the sprinkler fitting. 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. Step B. Tighten the sprinkler into the 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers. sprinkler fitting using only the W -Type 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin- 7 Recessed Sprinkler Wrench (Ref. klers. Figure 14). With reference to Figure 1, 5. Approved by the City of New York under MEA 354-01-E. 2, 3, and 4, the W -Type 7 Recessed 7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the span- Sprinkler Wrench is to be applied to klers are UL and C -UL Listed as Corrosion Resistant Sprinklers. the sprinkler wrench flats. • Installed with Style 10 (1/2° NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Step C. After the ceiling has been in- Recessed Escutcheon, as applicable. stalled or the finish coat has been a - ' Installed with Style 20 (112" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment or Recessed Escutcheon, as applicable. plied, slide on the Style 10, 20, 30, or """ Frame and Deflector only. Listings and approvals apply to color (Special Order) 40 Closure over the Series TY -FRB N/A: Not Available Sprinkler and push the Closure over • TABLE A the Mounting Plate until its flange comes in contact with the ceiling. LABORATORY LISTINGS AND APPROVALS 28 AND 4.2 K- FACTOR SPRINKLERS held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint should be present. The diameter of the should be obtained with a torque of 7 air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- (1,6 mm) for the 135 °F /57 °C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque inch (2,4 mm) for the 286 °F /141 °C may be used to Install sprinklers with temperature ratings. 1/2 NPT connections. A leak tight 3/4 Jun 13 06 03:14p A Professional Fire 503 - 632 -4835 p.6 TFP171 Page 5 of 8 SPRINKLER FINISH (See Note 8) K TYPE TEMP. BULB NATURAL CHROME WHITE''' LEAD LIQUID BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY3231) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 5.6 (TY31S1) 286 °F /141 °C Blue 1/2" NPT 135 °F /57°C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 4, 5 N/A (TY3231)' 175 °F /79 °C Yellow Figtae 9 2O0F/93°C Green 135 °F /57°C Orange RECESSED 155 °F /68 °C Red . PENDENT 1,2,3,4,5 1, 2, 4, 5 N/A (TY3231)• 175 °F /79°C Yellow Figure 10 200 °F /93 °C Green 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY4231) and 175 °F /79 °C Yellow 1,2,3,4,5, 6, 7 1, 2, 5 UPRIGHT 200 °F /93 °C Green (TY4131) - 8.0 8.0 286'F/141°C Blue NPT 135 °F /57°C Green RECESSED 155 °F /68 °C Orange PENDENT 1, 2, 4, 5 N/A (TY4231)' 175 °F /79 °C Red Figure 11 P00 °F /93 °C Yellow 135 °F /57 °C Orange RECESSED 155 °F /68°C Red PENDENT 1, 2, 3, 4, 5 (TY4231)" 175 °F /79°C Yellow N/A Figure 12 200 °F /93°C Green NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31- 53-428- 4444/Fax 31 -53 -428- 3377). 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/O6) as Quick Response Sprinklers 8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion Resistant Sprinklers. • Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. Installed with Style 20 (1/2" NPT) or Style 30 (3/4' NPT) 1/2' Total Adjustment Recessed Escutcheon, as applicable. "" Frame and Deflector only. Listings and approvals apply to color (Special Order) N /A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS 5.6 AND 8.0 K- FACTOR SPRINKLERS Jun 13 06 03:14p Fl Professional Fire 503 - 4835 p.7 • Page 6 of 8 TFP171 2-7/8" DIA 2-7/8' DIA 5/8±1/4' (73,0 '0 mm) 3/4' (19,1 mm) 1 1/8, (73,0mm) 1/2' (12,7 mm) • (15,916,4 mm) 2 -1/4' DIA 1/4" (6,4 mm) (12,7132 mm) FACE OF (57,2 mm) 1 PLATE (57,2 DIA 1/4' (6,4 mm} MOUNTING FACE OF (�'2 mm} I MOUNTING SPRINKLER FITTING PLATE SPRINKLER FITTING 1/8" 1/8' (3,2 mm) (3 2 mm) i - --, , . MOUNTING �, SURFACE IIP SURFACE • vices , CLOSURE SERIES 1-5/16' (33,3 mm) 1 -5116' (33,3 mm TY-FRB CLOSURE SERIES mm) 13/16' (20,6 mm) TY -FRB 1 -1/16' (27,0 mm) FIGURE 5 FIGURE 6 SERIES TY-FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 28 K- FACTOR, 112 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT 2-7/8" DIA _ 2-7/8" DIA (73A) 112±1/8' 1/2" (12,7 mm) 5/8x1/4' 3/4' (19,1 mm) (73,0 mm) (15,9±6,4 mm) 2 -1 /4" DIA. —�{ 1/4" (6,4 mm) (12,7x3,2 iron) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 ) 1 MOUNTING FACE OF (57,2 mm) 1 SPRINKLER PLATE SPRINKLER MOUNTING FITTING FITTING PLATE 118' 118' . . " (3,2 mm) . ( mm) AI -- i t X111 . M OUNTING MOUNTING : SURFACE SURFACE , CLOSURE SERIES 1 -1/4' (31,8 mm) CLOSURE SERIES 1 -1/4' (31,8 mm) TY -FRB 3/4 (19,1 mm) TY-FRB 1' (25,4 mm) FIGURE 7 FIGURE 8 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 314 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT Care and used to cover a clearance hole, may and after installation. Sprinklers dam - delay the time to sprinkler operation in . aged by dropping, striking, wrench Maintenance a fire situation twist/slippage, or the like, must be re- Also, rlace anrinkler that Sprinklers that are found to be leaking has a cracked bulb or th i has lost The Series TY-FRB Sprinklers must be or exhibiting visible signs of corrosion liquid from its bulb. (Ref. Installation maintained and serviced in accord- must be replaced. Section). ance with the following instructions: Automatic sprinklers must never be painted, plated, coated or otherwise Frequent visual inspections are rec NOTES altered after leaving the factory. Modi- ommended to be initially performed for Before closing a fire protection system Pied sprinklers must be replaced. corrosion resistant coated sprinklers, . main control valve for maintenance Sprinklers that have been exposed to after the installation has been corn- work on the fire protection system that corrosive products of combustion, but plated, to verify the integrity of the cor- it controls, permission to shutdown the have not operated, should be replaced rosion resistant coating. Thereafter, affected hre protection system must be if they cannot be completely cleaned annual inspections per NFPA 25 obtained from the proper authorities by wiping the sprinkler with a cloth or should suffice; however, instead of in- and all personnel who maybe affected by brushing it with a soft bristle brush. spatting from the floor level, a random by this action must be notified, sampling of close -up visual inspec- Care must be exercised to avoid dam- tions should be made, so as to better v Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi- Jun 13 06 03:15p A Professional Fire 503 - 632 -4835 p.8 TEP171 Page 7 of 8 2 -7/8' DIA. 2-7/8' DIA (73,0 mm) ,9:6,4 mm) 3/4' (19,1 mm) 11 (73.0 mm) 1/2' (12,7 mm) 15 ( ) 2 -114' DIA. 1/4' (6,4 mm) (12,7,2 mm) 4— 2.1/4' DIA. 1/4' (6.4 mm) FACE OF (57.2 mm) MOUNTING FACE OF (57,2 mm) 1 SPRINKLER PLATE SPRINKLER MOUNTING FITTING FITTING PLATE 1/8' 1/6' T 111, (3 2 mm) •� (3,2 mm) ii i' - -:lilt! 'fey SURFACE MOUNTING 1,�, . MOUNTING 1 SURFACE _ -•- CLOSURE SERIES 1 -1/4' (31,8 mm) CLOSURE 1.1/4• (31,8 mm) TY-FRB 3/4' (19,1 mm) TY -FRB 1' (25,4 mm) FIGURE 9 FIGURE 10 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT 2 -7/8' DIA. 2 -7/8' 01A 5/8±1/4' (73,0 mm) 3/4' (19,1 mm) 12±118' ( mm) 1/2' (12,7 mm) (15,9:6,4 mm) 2 -1/4' DIA. 1/4' (6,4 mm) (12,7±3,2 mm) , 2 -1/4' DIA 1/4' (6,4 mm) (57,2 mm) (57,2 mm) FACE OF MOUNTING FACE OF MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8' I 1/8' II (3,2 mm) m) - (3,2 mm) 1 ` ' 1 rA . J f \ // I m - } i MOUN MOUNTING SURFACE SURFACE CLOSURE SERIES 1-5/16° (33,3 mm) CLOSURE SERIES 1 -5/16' (33,3 mm)I TY-FRB 13/16' (20,6 mm) TY-FRB 1 -1/16' (27,0 mm) FIGURE 11 FIGURE 12 SERIES TY -FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT tion and the long term integrity of the corrosion resistant coating, as it may WRENCH be affected by the corrosive conditions �'' RECESS present. WRENCH RECESS The owner is responsible for the in- (END 'A^ USED FOR 00..!. spection, testing, and maintenance of 1/2" NPT MODELS) ��' their fire protection system and de- / �� � vices in compliance with this docu- \ (� ment, as well as with the applicable `• standards of the National Fire Protec- WRENCH RECESS tion Association (e.g., NFPA 25), in (END'S' USED FOR PUSH WRENCH addition to the standards of any other 3/4" NPT MODELS) INTO ENSURE ENGAGEMENT authorities having jurisdiction. The in- WITH SPRINKLER stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA lecturer should be contacted relative to W - TYPE 6 SPRINKLER any questions. WRENCH It is recommended that automatic FIGURE 14 sprinkler systems be inspected, local requirements and /or national W TYPE7 RECESSED ona tested, and maintained by a qualified codes. SPRINKLER WRENCH Inspection Service in accordance with Jun 13 06 03:15p R Professional Fire 503- 632 -4835 10.9 t c® I Fire & Building Products Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series RFIi -- 5.6 K- factor . "Royal Flush II" Pendent Concealed Sprinklers Quick & Standard Response, Standard Coverage General Cap. The Protective Cap is temporarily removed for installation, and then it can be replaced to help protect the mak Description sprinkler while the ceiling is being in- The Series RFII Quick Response stalled or finished. The tip of the Pro- -- P onse tective Cap can also be used to mark 4;l�* (3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas- - +? mm bulb), 5.6 K- Factor, "Royal Flush ter board, ceiling tiles, etc by gently ..:: II" Concealed Pendent Sprinklers are pushing the ceiling product against the decorative sprinklers featuring a flat Protective Cap. When the ceiling in- cover plate designed to conceal the stallation is complete the Protective sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate tecturally sensitive areas such as hotel Assembly installed lobbies, office buildings, churches, A an option, the Series RFII Standard and restaurants. Response (5 mm bulb) "Royal Flush II" Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be sembly that conceals the sprinkler op- fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175 erasing components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM. The separable two-piece design of the intended for sensitive areas where it is Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical blies allows installation of the sprin- through the cover plate from the area �■ klers and pressure testing of the fire above the ceiling. Data protection system prior to installation of a suspended ceiling or application WARNINGS of the finish coating to a fixed ceiling. The Series RFII Concealed Pendent Approvals for Series RFII They also permit removal of sus- Spr described herein must be UL and C -UL Listed. FM Approved. pended ceiling panels for access to installed and maintained in compli NYC under MEA 353-01-E. LPCB (Ref. building service equipment without ante with this document, as well as No. 094a/09 for TY3551 & 094a/10 for having to first shut down the fire pro- with the applicable standards of the TY3531) Approved. section system and remove sprinklers. National Fire Protection Association The approvals apply only to the serv- Also, the separable two -piece design in addition to the standards of any ice conditions indicated in the Design of the the Sprinkler provides for 1/2 other authorities having jurisdiction Critena section and maximum pros inch (12,7 mm) of vertical adjustment, Failure to do so may impair the per sure ratings indicated in the to reduce the accuracy to which the formance of these devices. Model /Sprinkler Identification Num- length of fixed pipe drops to the sprin- The owner is responsible for maintain- tiers section. klers must be cut. ing their fire protection system and de- Approvals for Air & Dust Seal The Series RFII Sprinklers are vices in proper operating condition. (Part #10908100) shipped with a Disposable Protective The installing contractor or sprinkler UL and C -UL Listed for use with the manufacturer should be contacted RFII (TY3551 & TY3504) Standard Re- with any questions. sponse Concealed Sprinkler. IMPORTANT /Sinkler 5mp6e Ratings Always refer er to to Technical Data A lodel pr 1 Temperature 155E /68C 8C Sprinkler - 135F/57C Plate Sheet TFP700 for the "INSTALLER 200F/93C Sprinkler - 165F/74C Plate WARNING° that provides cautions Identification Discharge Coefficient with respect to handling and instal- K = 5.6 GPM /psi (80,6 LPM /bar lation of sprinkler systems and corn Numbers Adjustment ponents. improper handling and in 1/2 inch (12,7 mm) stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm ishes Fin a sprinkler system or its compo bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass nents and cause the spnnkler to fail UL, C -UL, FM, LPCB and NYC. to operate in a fire situation or cause TY3504 (5 mm bulb) & TY3505 (3 aim Plated, or White Painted (Custom paint it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by matches and colors other than white are available on request ) Page 1 of 4 JULY, 2004 TFP181 Jun 13 06 03:16p R Professional Fire 503 -632 -4835 p.10 Page 2 of 4 TFP181 Physical Characteristics is NPr Frame Bronze ` � —� ASSEMBLY Support Cup . Chrome Plated Steel ` Guide Pins Stainless Steel I Deflector Bronze FRAME - _ �l Compression Screw Brass I� L _ CAP Bulb Glass I Cap . .. . . Bronze or Copper SUPPOT l Sealing Assembly cuawr -i Beryllium Nickel w/Teflon` ROLL FORMED ) — Cover Plate Brass THREAD Retainer COMPRESSION Brass J — Ejection Spring . .. Stainless Steel _ ll j SCREW GUIDE Patents PINS(2) i U.S.A.4,014,388 I O ® j N DEFLECTOR peration DEFLECTOR G -_ r '�_� ( POSITION) When exposed to heat from a fire, the SPRINKLER/SUPPORTCUP Cover Plate, which is normally sol- ASSEMBLY dered to the Retainer at three points, falls away to expose the Sprinkler As- THREAD INTO I I RETAINER sembly. At this point the Deflector sup- SUPPORT CUP ( WITH THREAD ported by the Guide Pins drops down UNTIL MOUNTING } 0 o DIMPLES SURFACE IS to its operational position. FLUSH GTH EJECTION The glass Bulb contains a fluid that I SPRING expands when exposed to heat. When • i the rated temperature Is reached, the •• ) �i fluid expands sufficiently to shatter the �•__I _ glass Bulb, activating the sprinkler and` allowing water to flow. SOLDER ' '------- COVER TABS (3) COVER PLATF_METAINER PLATE Design FIGURE 1 Criteria SERIES RFII CONCEALED SPRINKLER ASSEMBLY The RFII (TY3551 & TY3504), 5 mm Bulb Type, Concealed Pendent Sprin Step 1. The sprinkler must only be klers are UL and C -UL Listed as stand- Installation installed in the pendent position and and response standard spray sprin- with the centerline of the sprinkler per - klers for use in accordance with the The Series RFII must be installed in pendicular to the mounting surface. current NFPA standard. They are FM accordance with the following instruc- Approved as standard response - lions: Step 2. Remove the Protective Cap. standard spray sprinklers for use in NOTES Step 3. With pipe thread sealant ap- accordance with the current FM Loss plied to the pipe threads, hand tighten Prevention Data Sheets. Do not install any bulb type sprinkler if the sprinkler into the sprinkler fitting. The RFII (TY3531 & TY3505) 3 mm the bulb is cracked or there is a loss of Step 4. Wrench tighten the sprinkler Bulb Type, Concealed Pendent 3pri liquid from the bulb. With the sprinkler using only the RFII Sprinkler Wrench Beta are o n e algid P end t tin- held horizontally, a small air bubble quick should be present. The diameter of the (Re Figure 3). The RFII Sprinkler response - standard spray sprinklers air bubble is approximately 1/16 inch Wrench is to be applied to the Sprin - for use in accordance with the current (1,6 mm) for the 155 ° F /68 °C and 3/32 kler as shown in Figure 3. NFPA standard. They are FM Ap- inch (2,4 mm) for the 200 °F /93 °C tern- Step 5. Replace the Protective Cap proved as standard response - stand ( Ref. Fi gure 4 ) by pushing it upwards and spray sprinklers for use in accord- perature ratings A leak tight 1/2 inch NPT s nnkler oint until it bottoms out against the Support ante with the current FM Loss g p Cup The Protective Cap helps prevent Preventi D ata Sh eets should be obtained with a torque of 7 damage to the Deflector and Arms dur- to 14 ft.lbs 9, 5 to 19, 0 Nm). A maxi- The Series RFII Concealed Pendent Ing ceiling installation and /or during Sprinklers are only listed and ap- mum of 21 ribs. (28,5 Nm) of torque application of the finish coating of the proved is to be used to install sprinklers. roved with the Series RFII Concealed ceiling. it may also be used to locate Cover Plates having a metallic or white Higher levels of torque may distort the the center of the clearance hole by sprinkler inlet with consequent leak- finish. gently pushing the ceiling material up The Series RFII must not be used in age or impairment of the sprinkler. against the center point of the Protec- T Do not attempt to compensate for in- tive Cap. applications where must not air used i n above the ceiling is where greater than that sufficient adjustment in the Sprinkler above the drafts through g ea greater the Sup- Assembly by under- or over - tightening NOTE bert Cup could aelay soghler operp- the Sprinkler /Support Cup Assembly As long as the Protective Cap remains tio in a fire situation. Readjust the position of the sprinkle in place, the system is considered to fining to suit. be "Out of Service". ' Registered Trademark of DuPont I Jun 13 06 03:16p A Professional Fire 503 -632 -4635 p.11 TFP181 Page 3of4 FACE, OF CLEARANCE HOLE ._ CLEARANCE SPRINKLER DIAMETER HOLE \ FITTING DIMENSION C SPRINKLER , rte • SUPPORT CUP ��� ASSEMBLY I � I i __r_ .— ] ME THREADED -- \ 1 -- a ADJUSTMENT ) I ��= FACE OF CEILING, 7 RETAINING RING ( -- FIGURE 4 MOUNTING ( DISPOSABLE PROTECTIVE CAP SURFACE j i 1 i ; � � ( 1 ' ;i/ { I I I ; Ptep 6. After the ceiling has been com- ��r _ / feted with the 2 -1/2 inch (63,5 mm) Z�..111■ diameter clearance hole and in prepa- � ^ 1 \ ■ i ' ration for installing the Cover Plate As- r_, sembly, remove and discard the Pro - � tective Cap, and verify that the 3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE Deflector moves up and down freely If (4.8 to 17,5 mm) PRESET GAP •IN DROPPED RETAINER the Sprinkler has been damaged and REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY the Deflector does not move up and down freely, replace the entire Sprin- COVER PLATE COVER PLATE kler assembly. Do not attempt to mod- • — PROFILE DEPTH -*- DIAMETER ify or repair a damaged sprinkler. DIMENSION B DIMENSION A Step 7. When installing an Air and Dust Seal, refer to Figure 5, otherwise • A: 31/4" (82,6 mm) C: 2 -3/8" to 2 -5/8' (60,3 to 66,7 mm) proceed to Step 8 To attach the Air and Dust Seal, verify the angle of the out - B: 3/16" (4,8 mm) D 1 -3/4" to 2 -1/4" (44,5 to 57,2 mm) side edge of the seal is oriented ac- cording to Figure 5. Start the edge of `J FIGURE the Retainer in the grooved slot of the SERIES RF11 CONCEALED SPRINKLER Air and Dust Seal and continue around • INSTALLATION DIMENSIONS Dust Seal retainer until the entire Air and Dust Seal is engaged. NOTE The Air and Dust Seal is only to be installed on the periphery of the Re- 1 = - 4' FRAME r .. ,► ` �' �I tamer. I Step 8. Screw on the Cover Plate /Re- tainer Assembly until the Retainer _ - Figure 2 (or Air and Dust Seal - Figure `SUPPORT / 5) contacts with the ceiling. Do not l i i i CUP 1 I - I continue to screw on the Cover E Plate /Retainer Assembly such that it 0 i + lifts a ceiling panel out of its normal ii sr sa. position. If the Cover Plate /Retainer II _ 2G7` r••� Assembly cannot be engaged with the y Support Cup or the Cover Plate /Re- 7/a' (23 mm) ^ tamer Assembly cannot be engaged SQUARE sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. ALIGN O ARROWS WITH care and FRAME ARMS Maintenance A CCEPTS The Series RFII must be maintained 1 /2SOCKET and serviced in accordance with the DRIVE following instructions: NOTES FIGURE 3 Absence of the Cover Plate Assembly RF1I SPRINKLER WRENCH may delay sprinkler operation in a fire situation. t • ■ it Jun 13 06 03:17p R Professional Fire 503 - 632 -4835 p.12 • Page 4 of 4 TFPI S 1 When properly installed, there is a SuPPORT SPRINKLER FACE OF ORIENT nominal 3/32 inch (2,4 mm) air gap cur CE+uNG SEAL between the lip of the Cover Plate and BEVEL AS the ceiling, as shown in Figure 2. This = 1 �� = - -- air gap is necessary for proper opera- � i ' PLATE � � � � SHOWN tion of the sprinkler. If the ceiling is to i ` r `, RET AINER E MBLY 2 .� be repainted after the nstallation of ' - ASS the Sprinkler, care must be exercised � --. to ensure that the new paint does NOT seal off any of the air gap. +! �„ CLEAN Factory painted Cover Plates MUST /� i ���� WI��/ / -� ROOM NOT be repainted. They should be re- = - LIP OF COVER S placed, If necessary, by factory RETAINER PLATE painted units FIGURE 5 Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFiI (TY3551 & TY3504) the Enclosure. Separation may result. Before closing a fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT main control valve for maintenance local requirements and /or national SHALL TYCO FIRE PRODUCTS' LI- work on the fire protection system that codes. ABILITY EXCEED AN AMOUNT it controls, permission to shut down the EQUAL TO THE SALES PRICE. affected fire protection system must be obtained from the proper authorities � .jj�j t ed THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL and all personnel who may be affected by this action must be notified. Warranty OTHER WARRANTIES EXPRESS OR I Sprinklers that are found to be leaking or exhibiting visible signs of corrosion Products manufactured by Tyco Fire OF MERCHANTABILITY AND FIT - must be replaced. Products are warranted solely to the NESS FOR A PARTICULAR FUR- Automatic sprinklers must never be original Buyer for ten (10) years POSE • painted, plated, coated or otherwise against defects in material and work - altered after leaving the factory. Marti- ma installed when maintained paid for and r properly rml fled sprinklers must be replaced. Ordering and maintained under normal Sprinklers that have been exposed to use and service. This warranty will ex- j• ®�wedure corrosive products of combustion, but pire ten (10) years from date of ship - have not operated, should be replaced ment by Tyco Fire Products. No war- When placing an order, indicate the full if they cannot be completely cleaned ranty is given for products or product name. Contact your local dis- by wiping the sprinkler with a cloth or components manufactured by comps- tributor for availability. by brushing it with a soft bristle brush. nies not affiliated b y ownership with Sprinkler Assembly: Tyco Fire Products or for products and p Y - Care must be exercised to avoid dam- components which have been subject Specify: (SIN), (specify temperature age to the sprinklers - before, during, to misuse, improper installation, cor rating) Series RFII Concealed Pen - m and after installation. Sprinklers dam- sion, or which have not been installed, dent Sprinkler, P/N (specify). aged by dropping, striking, wrench maintained, modified or repaired in ac- twist/slippage, or the like, must be re- cordance with applicable Standards of Tr3551 51 -15 51 - 1-� placed Also, replace any sprinkler that the National Fire Protection Associa- TY3504 51 -796 -1 -155 51 -796 -1 -200 has a cracked bulb or that has lost tion, and /or the standards of any other T''3531 51- 792 -1 -155 51 -792 -1 -200 liquid from its bulb. (Ref Installation Authorities Having Jurisdiction. Mate - TY35Q5 51- 797 -1 -155 51 -797 -1 -200 Section). rials found by Tyco Fire Products to be If a sprinkler must be removed, do not defective shall be either repaired or Separately Ordered Cover Plate: reinstall it or a replacement without replaced, at Tyco Fire Products' sole Specify: (specify temperature rating) reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate if a Cover Plate Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify). dislodged during service, replace it im- assume for it, any other obligation in mediately. connection with the sale of products or 135F/57C(a) 165Fn4C1b) parts of products. Tyco Fire Products Brass 56-792 -1 -135 56- 792 -1 -165 Bright Brass 56- 792 -2 -135 56 -792 -2 -165 The owner is responsible for the in- shall not be responsible for sprinkler Chrome 56- 792 -9-135 56-792-9-165 spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome 56- 792 -6- 1 56- 792 -6-1 their fire protection system and de- incomplete information supplied by wr,�te 56792 0 135 35 517 g vices in compliance with this docu- Buyer or Buyer's r resentatives. White (RAL9010)• 56 - 3 - 135 56 y y ment. as well as with the applicable IN NO EVENT SHALL TYCO FIRE Ot t W 56-792-5-135 56-792-4-185 - . standards of the National Fire Protec- PRODUCTS BE LIABLE, IN CON- et a` 56 -792 -6.135 56 -792 -6-165 . tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR Custom 56-792-X-135 5s 752 -x -165 addition to the standards of any other UNDER ANY OTHER LEGAL THE- (a) For use with 155F /68C sprinklers. authorities having jurisdiction. The in- ORY, FOR INCIDENTAL, INDIRECT, • E astern Hemisphere sales only ers. stalling contractor or sprinkler manu- SPECIAL OR CONSEQUENTIAL facturer should be contacted relative to DAMAGES, INCLUDING BUT NOT Sprinkler Wrench: any questions. LIMITED TO LABOR CHARGES, RE- Specify: RFII Sprinkler Wrench, It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56 -000 -1 -075. sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal: tested, and maintained by a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal, P/N 56 -90B -1 -001. TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 i