Plans .. , qo a 0 tde1A -11, 5 P J.c 52
t qCO Fire & Building
Products
Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500
Series TY -FRB — 2.8, 4.2, 5. • , and 8.0 K- factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
tained when exposed to corrosive at-
G eneral mospheres. Although corrosion resis -,_ -,
tent coated sprinklers have passed the , °' = t :,,- i,::;r�
Description standard corrosion tests of the appli .,19.A
cable approval agencies, the testing is { ° >" Y• �;
The Series TY -FRB, 2.8, 4.2, 5.6, and not representative of all possible cor
8.0 K- factor, Upright and Pendent rosive atmospheres. Consequently, it
Sprinklers described in this data sheet is recommended that the end user be
are quick response - standard cover- consulted with respect to the suitability i l .
age, decorative 3 mm glass bulb type of these coatings for any given corro- $• . A 1 S ^. ;.
spray sprinklers designed for use in sive environment. The effects of ambi-
light or ordinary hazard, commercial ent temperature, concentration of n „,,„ ..:
occupancies such as banks, hotels, chemicals, and gas /chemical velocity, - .:s
shopping malls, etc. should be considered, as a minimum,
The recessed version of the Series along with the corrosive nature of the
TY -FRB Pendent Sprinkler, where ap- chemical to which the sprinklers will be
plicable, is intended for use in areas exposed. ---
with a finished ceiling. It uses either a An intermediate level versions of the t
two -piece Style 10 (1/2 inch NPT) or Series TY -FRB Pendent Sprinklers
Style 40 (3/4 inch NPT) Recessed Es- are detailed in Technical Data Sheet
cutcheon with 1/2 inch (12,7 mm) of TFP356, and Sprinkler Guards are de- . x
recessed adjustment or up to 3/4 inch tailed in Technical Data Sheet TFP780 .. K w ., '
(19,1 mm) of total adjustment from the
flush pendent position, or a two -piece WARNINGS t* d
Style 20 (1/2 inch NPT) or Style 30 (3/4 The Series TY -FRB Sprinklers de " ""
inch NPT) Recessed Escutcheon with scribed herein must be installed and ,
1/4 inch (6,4 mm) of recessed adjust- maintained in compliance with this
ment or up to 1/2 inch (12,7 mm) of document, as well as with the applica-
total adjustment from the flush pen- ble standards of the National Fire Pro -
dent position. The adjustment pro- tection Association, in addition to the
vided by the Recessed Escutcheon re- standards of any other authorities hay- Model/Sprinkler
duces the accuracy to which the fixed ing jurisdiction. Failure to do so may
pipe drops to the sprinklers must be impair the performance of these de- Identification
cut. vices.
Corrosion resistant coatings, where The owner is responsible for maintain- Numbers
applicable, are utilized to extend the ing their fire protection system and de-
life of copper alloy sprinklers beyond vices in proper operating condition. TY1131 - Upright 2.8K, 1/2 "NPT
that which would otherwise be ob- The installing contractor or sprinkler TY1231 - Pendent 2.8K, 1/2 "NPT
manufacturer should be contacted TY2131 - Upright 4.2K, 1/2"NPT
with any questions. TY2231 - Pendent 4.2K, 1/2 "NPT
IMPORTANT TY3131 - Upright 5.6K, 1/2 "NPT
Always refer to Technical Data TY3231 - Pendent 5.6K, 1/2 "NPT
Sheet TFP700 for the "INSTALLER TY4131 - Upright 8.0K, 3/4"NPT
WARNING" that provides cautions TY4231 - Pendent 8.0K, 3/4 "NPT
with respect to handling and instal - TY4831- Upright 8.0K, 1/2 "NPT
lation of sprinkler systems and corn- TY4931- Pendent 8.0K, 1/2 "NPT
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 MARCH, 2007 TFP171
Page 2 of 10 TFP171
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED SSU*
SURFACE
1/2" MAKE -IN ESCUTCHEON
DEFLECTOR
=1 r O 7/16" ,1 mm) 4
(57,2 mm) 'M' 5
2 -1/4" -� i �� l � (11 i 1 NOMIN �- I NL
lir 2 1 I l �t MAKE
1 -9/16" I t�r 2 -3/16" 3
(39,7 mm) I WRENCH (55,6 mm)
Iv
FLAT 1 II
i
„J!„ „., I = lL 7
SSP DEFLECTOR* 2 -7/8" (73,0 mm) DIA. - � - I 1/2" NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw
FIGURE 1
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED SSU*
SURFACE 1/2° MAKE -IN ESCUTCHEON SSU
NPT I DEFLECTOR
6
M 7/16"
i1 �1' -� 4
NOMINAL
2 -3/16" - � .� (11,1 6"
1 A ∎����- I lir
i (55,6 mm) f `7�1 MAKE -IN
1 -1/2"
up �I/ I It_r � 5
2- 3/16" % , 1,4114
•' I 2
(38,1 mm) WRENCH _ (55,6 mm) f
- --... 11 FLATS _ _ I °
SSP DEFLECTOR * --- 2 -7/8" (73,0 mm) DIA. - -1 1/2" NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 2
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K- FACTOR, 1/2 INCH NPT
k 14
TFP171 Page 3 of 10
ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20
PLATE SEATING NOMINAL RECESSED
SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR
` ■
6
W 7/16" !Er 5
2- 3/16" _ 1 i l�l:' � (11,1 mm) i
(55,6 mm) �A ��1�- NOMIN I 4
` 1I pi 1 I E -IN w
1 -1/2" I , � 1 2-3/16" VII* 2
(38,1 mm) WRENCH 1 (55,6 mm) 1 3
- -. _ _ _ FLATS
Ms
gMt
SSP DEFLECTOR - 2 -7/8 (73,0 mm) DIA. 1/2" NPT 1 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 3
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K- FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40
PLATE SEATING NOMINAL RECESSED
SURFACE NP MAKE -IN ESCUTCHEON DEFLECTOR
i — ..---
`I * 6 *
1/2" n' 5
2- 5/16" ' (12,7 mm)
(58,7 mm) II r NOMINAL 4
� ��- MAKE -IN r • 2 -1/4" 2
1 9,16" I Ir APTT
(39,7 mm) WRENCH (57,2 mm)
. FLATS
SSP DEFLECTOR * 2 -7/8" (73,0 mm) DIA. 3/4" NPT 1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 4
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K- FACTOR, 3/4 INCH NPT
Page 4 of 10 TFP171
7/16" (11,1 mm)
1/2" NOMINAL SSU
NPT MAKE -IN DEFLECTOR
tll'I j I W I 1, J r ;iii G‘ * 6
— ' 5
2 -1/4" ' 2 -3/16" I
(57,2 mm) A =A' p (55 ,6 mm) i 4
1 -9/16" 1Ij WRENCH L _ 'rj 2
(39,7mm) FLATS
SSP 1
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw
FIGURE 5
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K- FACTOR, 1/2 INCH NPT
Technical Operation
Data The glass Bulb contains a fluid which
expands when exposed to heat. When
Approvals the rated temperature is reached, the
UL and C -UL Listed. fluid expands sufficiently to shatter the
FM, LPCB, and NYC Approved. glass Bulb, allowing the sprinkler to
(Refer to Table A and B for complete activate and water to flow.
approval information including corro-
sion resistant status.) Design
Maximum Working Pressure
Refer to Table C. Criteria
Discharge Coefficient
K = 2.8 GPM /psi (40,3 LPM /bar112) The Series TY -FRB Pendent and Up-
K = 4.2 GPM /psi (60,5 LPM /bar1 /2) right Sprinklers are intended for fire
K = 5.6 GPM /psi (80,6 LPM /bar1 /2 protection systems designed in ac-
K = 8.0 GPM /psi (115,2 LPM /bar112) cordance with the standard installation
rules recognized by the applicable
Temperature Ratings Listing or Approval agency (e.g., UL
Refer to Table A and B Listing is based on the requirements of
Finishes NFPA 13, and FM Approval is based •
Sprinkler: Refer to Table A and B. on the requirements of FM's Loss Pre -
Recessed Escutcheon: White Coated, vention Data Sheets ). Only the Style
Chrome Plated, or Brass Plated. 10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations. , �
Physical Characteristics •
Frame Bronze E
Button Brass /Copper m
Sealing Assembly I—
Beryllium Nickel w /Teflont -0
Bulb Glass F-
Compression Screw Bronze o,
Deflector Copper /Bronze W
Bushing (K =2.8) Bronze 15
0
a
7
0
4-
•
•
TFP171 Page 5 of 10
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB NATURAL CHROME WHITE""
LIQUID BRASS PLATED POLYESTER
135 °F /57 °C Orange
PENDENT
155F/68°C Red
(TY1231) 1, 2, 3, 5
and 175 °F /79 °C Yellow
UPRIGHT 200 °F /93 °C Green
2.8 (TYI131) 286 °F /141 °C Blue
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 ° C Red
PENDENT
(TY1231)* 175 °F /79 °C Yellow
Figure 6 200 °F /93 °C Green 1, 2, 5
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT
(TY1231)•• 175"F/79°C Yellow
Figure 7 200 °F /93 °C Green
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY2231)
and 175 °F /79 °C Yellow
UPRIGHT 200 °F /93 °C Green
4.2 (TY2131)
286"F/141°C Blue 1 2
1/2"
NPT 135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT
(TY2231)• 175 °F /79 °C Yellow
Figure 8 200"F/93°C Green
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT
(TY2231)•• 175 °F /79 °C Yellow
Figure 9 200 °F /93 °C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Re-
sponse Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354 -01 -E.
7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin-
klers are UL and C -UL Listed as Corrosion Resistant Sprinklers.
• Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
• Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
"' Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K- FACTOR SPRINKLERS
Page 6 of 10 TFP171
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL CHROME WHITE * ** LEAD
LIQUID BRASS PLATED POLYESTER COATED
135"F/57°C Orange
PENDENT 155 °F /68 °C Red
(TY3231) 1, 2, 3, 4, 5, 6, 7 1,2,3,5
and 175"F/79°C Yellow
UPRIGHT 200 °F /93 °C Green
5.6 (TY3131) 286 °F /141 °C Blue
1/2"
NPT 135"F/57°C Orange
RECESSED 155F/68°C Red
PENDENT 1, 2, 4, 5 N/A
(TY3231)* 175"F/79°C Yellow
Figure 10 200 °F /93 °C Green
135"F/57°C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A
(TY3231) ** 175 °F /79 °C Yellow
Figure 11 200"F193°C Green
135 °F /57 °C Orange
PENDENT 155 °F /68 °C Red
(TY4231) 1, 2, 5
and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7
UPRIGHT 200"F/93°C Green
8.0 (TY4131)
286 °F /141 °C Blue
3/4"
NPT 135 °F /57 °C Green
RECESSED 155"F/68°C Orange
PENDENT 1, 2, 4, 5 N/A
(TY4231)* 175 °F /79 °C Red
Figure 12 200 °F /93 °C Yellow
135 °F /57 °C Orange
RECESSED 155 °F /68 °C Red
PENDENT 1, 2, 3, 4, 5 N/A
(TY4231)** 175 °F /79 °C Yellow
Figure 13 200 °F /93 °C Green
135 °F /57 °C Orange
PENDENT 155"F/68°C Red
8.0 (TY4931) 1, 2, 5
1/2" and 175 °F /79 °C Yellow 1, 2, 4, 5, 6
NPT UPRIGHT 200 °F /93 °C Green
(TY4831)
286 °F /141 °C Blue
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k /04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354 -01 -E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428 - 3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
* ** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N /A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K- FACTOR SPRINKLERS
•
TFP171 Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD
BRASS PLATED POLYESTER COATED
PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/2" RECESSED PENDENT
NPT (1Y323)
PENDENT (TY4231)
and
4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
3/4" RECESSED PENDENT
NPT (TY4231)
PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 UPRIGHT (TY3131) OR
1/2" RECESSED PENDENT 175 PSI (12,1 BAR)
NPT (TY3231) N/A
(SEE NOTE 1)
PENDENT (TY4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8 UPRIGHT (TY4131)
3/4" RECESSED PENDENT
NPT (TY4231) N/A
8.0 PENDENT (TY4931)
1/2" and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4831)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C -UL); and , the Approval by the City of New York.
TABLE C, MAXIMUM WORKING PRESSURE
tained with a torque of 10 to 20 ft.lbs. the sprinkler into the sprinkler fitting.
Installation (13,4 to 26,8 Nm). A maximum of 30 Step 3. Tighten the sprinkler into the
ft.lbs. (40,7 Nm) of torque is to be used fitting pe
ing using only the he W-Type
Series TY -FRB Sprinklers must to install sprinklers with 3/4 NPT con- 6 sprinkler fit Wrench (Re W e 1 pe
be installed in accordance with the fol- nections. Higher levels of torque may With reference to Figures 1, 2, 3, 4,
lowing instructions: distort the sprinkler inlet and cause and 5, the W -Type 6 Sprinkler Wrench
leakage or impairment of the sprinkler. i s to be applied ed to the sprinkler wrench
Do not install any bulb type sprinkler if Do not attempt to make -up for insuffi- flats.
the bulb is cracked or there is a loss of cient adjustment in the escutcheon The Series TY -FRB Recessed Pen -
liquid from the bulb. With the sprinkler plate by under- or over - tightening the dent Sprinklers must be installed in
held horizontally, a small air bubble sprinkler. Readjust the position of the accordance with the following instruc-
should be present. The diameter of the sprinkler fitting to suit. tions.
air bubble is approximately 1/16 inch The Series TY -FRB Pendent and Up- Step A. After installing the Style 10.
(1,6 mm) for the 135!F/57°C to 3/32 right Sprinklers must be installed in 20, 30, or 40 Mounting Plate, as appli-
inch (2,4 mm) for the 286 ° F /141 °C accordance with the following instruc- cable, over the sprinkler threads and
temperature ratings. tions. with pipe thread sealant applied to the
A leak tight 1/2 inch NPT sprinkler joint Step 1. Pendent sprinklers are to be pipe threads, hand tighten the sprin-
should be obtained with a torque of 7 installed in the pendent position, and kler into the sprinkler fitting.
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- upright sprinklers are to be installed in Step B. Tighten the sprinkler into the
mum of 21 ft. lbs. (28,5 Nm) of torque the upright position. sprinkler fitting using only the W -Type
may be used to install sprinklers with St 2. With pipe thread sealant ap- 7 Recessed Sprinkler Wrench (Ref.
ep
1/2 NPT connections. A leak tight 3/4 St p 2 the hpe a, g
2, 3, and 4, the W -Type 7 Recessed
Page 8 of 10 TFP171
2 -7/8" DIA. 2 -7/8" DIA.
(73,0 mm) 3/4" (19,1 mm) 1/2±1/8" (73,0 mm)
5/8±1/4" 1/2" (12,7 mm)
(15,916,4 mm) 1/4" (6,4 mm) (12,7±3,2 mm)
2 -1/4" DIA. 2 -1/4" DIA. 1/4" (6.4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
1 r ,
Immw i _J I i }
MOUNTING
,�, SURFACE
� 1Ir
SURFACE • ia
1- 5/16" (33,3 mm) SERIES 1- 5/16" (33,3 mm)
TY-FRB 13/16" (20,6 mm)
CLOSURE SERIES CLOSURE TY -FRB 1 -1/16" (27,0 mm)
-FR
FIGURE 6 FIGURE 7
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT
2 -7/8" DIA. 2 -7/8" DIA.
(73,0 mm) 3/4" (19,1 mm) 1/2±1/8" (73,0 mm) 1/2" (12,7 mm)
5/8±1/4"
(15,9±6,4 mm) 1/4" (6,4 mm) (12,7±3,2 mm)
2 -1/4" DIA. 2-1/4" DIA. 114° (6,4 mm)
FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
•�' (3 mm) _ G • . (3,2 mm)
�liil�i r 1 ]IU' ��i.
9117 Al __J MOUNTING
, SURFACE I
MOUNTING � . ■
SURFACE - -- ..
CLOSURE SERIES 1 -1/4" (31,8 mm) SERIES 1 -1/4" (31,8 mm)
CLOSURE
TY -FRB Ty-FRB 1' (25.4 mm
3/4" (19,1 mm) mm)
FIGURE 8 FIGURE 9
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT
Sprinkler Wrench is to be applied to work on the fire protection system that altered after leaving the factory. Modi-
the sprinkler wrench flats. it controls, permission to shut down the Pied sprinklers must be replaced.
Step C. After the ceiling has been affected fire protection system must be Sprinklers that have been exposed to
S the in-
S talled the finish coat has been n- obtained from the proper authorities corrosive products of combustion, but
plied, slide on the Style 10, 20, 30, or and all personnel who maybe affected have not operated, should be replaced
40 Closure over the Series TY -FRB by th action must be notified. if they cannot be completely cleaned
Sprinkler and push the Closure over The owner must assure that the sprin- by wiping the sprinkler with a cloth or
S
P P by brushing it with a soft bristle brush.
the Mounting Plate until its flange klers are not used for hanging of any
comes in contact with the ceiling. objects; otherwise, non - operation in Care must be exercised to avoid dam -
the event of a fire or inadvertent opera- age to the sprinklers - before, during,
are and tion may result. and after installation. Sprinklers darn -
Absence of an escutcheon, which is aged by dropping, striking, wrench
Maintenance used to cover a clearance hole, may twist/slippage, or the like, must be re-
delay the time to sprinkler operation in placed. Also, replace any sprinkler
a fire situation. that has a cracked bulb or that has lost
The Series TY -FRB Sprinklers must liquid from its bulb. (Ref. Installation
be maintained and serviced in accord- Sprinklers that are found to be leaking Section).
ance with the following instructions: or exhibiting visible signs of corrosion
must be replaced. Frequent visual inspections are rec
' NOTES ommended to be initially performed for
Before closing a fire protection system Automatic sprinklers must never be corrosion resistant coated sprinklers,
main control valve for maintenance painted, plated, coated or otherwise after the installation has been corn-
TFP171 Page 9 of 10
2 -7/8" DIA. 2 -7/8" DIA. -
(73,0 m 3/4" (19,1 mm) 1/2±1/8" (73,0 mm) 1/2" (12,7 mm)
5/8±1/4"
(15,9±6,4 mm) 1/4" (6,4 mm) (12,7±3,2 mm)
2 -1/4" DIA. 2-1/4" DIA. 1/4" (6,4 mm)
(57,2 mm) FACE OF (57,2 mm) MOUNTING
FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
(3,2 mm) �� (3,2 mm) Am.. • r
7 , w } MOUNTING N r
II,
MOUNTING SURFAC II
SURFACE
CLOSURE SERIES 1 -1/4" (31,8 mm) SERIES 1 -1/4" (31,8 mm)
CLOSURE TY -FRB
TY -FRB 3/4" (19,1 mm) 1" (25,4 mm)
FIGURE 10 FIGURE 11
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT
2 -7/8" DIA. _ 2 -7/8" DIA. -
5/8±1/4" (73,0 mm) 3/4" (19,1 mm) 1/2±1/8" (73,0 mm) 1/2" (12,7 mm)
(6,4 mm)
(15,9±6,4 mm) 2 -1/4" DIA. J 1/4 "(6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4' (
57,2 mm )
FACE OF (57,2 mm) ( MOUNTING FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
�� (3,2 mm) (3,2 mm)
-. Ili Mr .
'i } MOUNTING � I�
MOUNTING SURFACE
SURFACE • ____. "
CLOSURE SERIES 1 -5/16" (33,3 mm) CLOSURE SERIES 1 -5/16" (33,3 mm)
TY -FRB 13/16" (20,6 mm) TY -FRB 1 -1/16' (27,0 mm)
FIGURE 12 FIGURE 13
SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT
WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT
pleted, to verify the integrity of the cor- L� RECESS
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in- WRENCH RECESS �".
specting from the floor level, a random (END "A" USED FOR � �
sampling of close-up visual inspec 1/2" NPT MODELS)
tions should be made, so as to better � i
determine the exact sprinkler condi-
tion and the long term integrity of the .�'
corrosion resistant coating, as it may WRENCH RECESS
END "B" USED FOR PUSH WRENCH
(
be affected by the corrosive conditions EN " " B " MODELS IN TO ENSURE
present. > ENGAGEMENT
The owner is responsible for the in- FIGURE 14 WITH SPRINKLER WRENCHING AREA
spection, testing, and maintenance of W -TYPE 6 SPRINKLER FIGURE 15
their fire protection system and de- WRENCH
vices in compliance with this docu- W -TYPE 7 RECESSED
ment, as well as with the applicable SPRINKLER WRENCH
standards of the National Fire Protec facturer should be contacted relative
to any questions
tion Association (e.g., NFPA 25), in .
addition to the standards of any other It is recommended that automatic Inspection requirements Service in and/or national
nati an with
authorities having jurisdiction. The in- sprinkler systems be inspected, codesequiremen
stalling contractor or sprinkler manu- tested, and maintained by a qualified
Page 10 of 10 TFP171
P/N 57 - XXX - X - XXX
I I
TEMPERATURE
MODEUSIN RATING
SPRINKLER
330 2.8K UPRIGHT (1/2 "NPT) TY1131 135 135 °F /57 °C
331 2.8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155F/68°C
340 4.2K UPRIGHT (1/2 "NPT) TY2131 4 WHITE POLYESTER 175 175 °F /79 °C
341 4.2K PENDENT (1/2 "NPT) TY2231 3 WHITE (RAL9010)* 200 200FI93°C
370 5.6K UPRIGHT (1/2 "NPT) TY3131 9 CHROME PLATED 286 286 °F /141 °C
371 5.6K PENDENT (1/2 "NPT) TY3231 7 LEAD COATED
390 8.0K UPRIGHT (3/4 "NPT) TY4131
391 8.0K PENDENT (3/4 "NPT) TY4231 * Eastern Hemisphere sales only.
360 8.0K UPRIGHT (1/2 "NPT) TY4831
361 8.0K PENDENT (1/2 "NPT) TY4931
TABLE D
PART NUMBER SELECTION
SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS
Limited contract, event shall TFBP be or under ordering
contrtr act, tort, strict liability or under
any other legal theory, for incidental,
Warranty indirect, special or consequential darn- Procedure
ages, including but not limited to labor
Products manufactured by Tyco Fire & charges, regardless of whether TFBP When placing an order, indicate the
Building Products (TFBP) are war- was informed about the possibility of full product name. Refer to the Price
ranted solely to the original Buyer for such damages, and in no event shall List for complete listing of Part Num-
ten (10) years against defects in mate- TFBP's liability exceed an amount bers.
rial and workmanship when paid for equal to the sales price. Contact your local distributor for avail -
and properly installed and maintained The foregoing warranty is made in lieu ability.
under normal use and service. This
warranty will expire ten (10) years of any and all other warranties. ex
from date of shipment by TFBP. No press or implied. including warranties Sprinkler Assemblies with NPT
warranty is given for products or corn- of merchantability and fitness fora par- Thread Connections:
ponents manufactured by companies ticular purpose, Specify: (Specify Model /SIN), Quick
Response, (specify K- factor), (specify
not affiliated by ownership with TFBP This limited warranty sets forth the ex- temperature rating), Series TY -FRB
or for products and components which clusive remedy for claims based on (specify Pendent or Upright) Sprinkler
have been subject to misuse, improper failure of or defect in products, materi- with (specify type of finish or coating),
installation, corrosion, or which have als or components, whether the claim P/N (specify from Table D).
not been installed, maintained, modi- is made in contract, tort, strict liability
fled or repaired in accordance with ap- or any other legal theory. Recessed Escutcheon:
plicable Standards of the National Fire 20 Re
standards of any other Authorities
Protection Association, and /or the This warranty will apply to the full ex- Specify: St le Y ( 10, 40)
tent permitted by law. The invalidity, in c
i essed Escutcheon with 30, or 40 th (specify)
ish, P/N f i n -
Having Jurisdiction. Materials found whole or part, of any portion of this (specify*).
by TFBP to be defective shall be either warranty will not affect the remainder. • Refer to Technical Data Sheet TFP770.
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor Sprinkler Wrench:
authorizes any person to assume for it, Specify: W -Type 6 Sprinkler Wrench,
any other obligation in connection with P/N 56- 000 -6 -387.
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for Specify: W -Type 7 Sprinkler Wrench,
sprinkler system design errors or inac- P/N 56- 850 -4 -001.
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446