Plans )40,j/(4.°a °�(10 iJ L 'oav 444/, . S , lc" 3c."-o t Flo Fire & Building RECEIVED Products A i ailh Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 CITY OF TlGARD BUILDING DlviSfOry Series TY -B — 2.8, 5.6, and 8.0 K- factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General cable approval agencies, the testing is not representative of all possible cor- D escription rosive atmospheres. Consequently, it #, «._µ . . is recommended that the end user be -;. , consulted with respect to the suitability , „ilk The Series TY -B, 2.8, 5.6, and 8.0 of these coatings for any given corro- K- factor, Upright and Pendent Sprin- sive environment. The effects of ambi- 1 klers described in this data sheet are ent temperature, concentration of i- standard response - standard cover- chemicals, and gas /chemical velocity, age, decorative 5 mm glass bulb type should be considered, as a minimum, ._ spray sprinklers designed for use in along with the corrosive nature of the light, ordinary, or extra hazard, corn- chemical to which the sprinklers will be mercial occupancies such as banks, exposed. `" ` hotels, shopping malls, factories, refin- eries, chemical plants, etc. An intermediate level version of the Series TY -B Pendent Sprinkler can be The recessed version of the Series obtained by utilizing the Series TY -B � . TY -B Pendent Sprinkler, where appli- Pendent Sprinkler in combination with cable, is intended for use in areas with the Model S2 Shield. a finished ceiling. It uses a two-piece r Style 10 (1/2 inch NPT) or Style 40 (3/4 WARNINGS ; inch NPT) Recessed Escutcheon. The The Series TY -B Sprinklers described Recessed Escutcheon provides 1/2 herein must be installed and main - inch (12,7 mm) of recessed adjust- tained in compliance with this docu- ment or up to 3/4 inch (19,1 mm) of ment, as well as with the applicable � total adjustment from the flush pen- standards of the National Fire Protec- dent position. The adjustment pro- tion Association, in addition to the lift, 0 vided by the Recessed Escutcheon re- standards of any other authorities hav- ‹ duces the accuracy to which the fixed ing jurisdiction. Failure to do so may ` 1 " :'" pipe drops to the sprinklers must be impair the performance of these de- cut. vices. Corrosion resistant coatings, where The owner is responsible for maintain - applicable, are utilized to extend the ing their fire protection system and de- life of copper alloy sprinklers beyond vices in proper operating condition. that which would otherwise be ob- The installing contractor or sprinkler tained when exposed to corrosive at- manufacturer should be contacted mospheres. Although corrosion resis- with any questions. tant coated sprinklers have passed the standard corrosion tests of the appli- Model/Sprinkler prinkler IMPORTANT Identification Always refer to Technical Data Sheet TFP700 for the "INSTALLER Numbers WARNING" that provides cautions m with respect to handling and instal - TY1151 - Upright 2.8K, 1/2 "NPT t- lation of sprinkler systems and com- TY1251 - Pendent 2.8K, 1/2 "NPT 2 ponents. Improper handling and in- TY3151 - Upright 5.6K, 1/2 "NPT stallation can permanently damage TY3251 - Pendent 5.6K, 1/2 "NPT o, a sprinkler system or its compo- TY4151 - Upright 8.0K, 3/4 "NPT ce nents and cause the sprinkler to fail TY4251 - Pendent 8.0K, 3/4 "NPT a g to operate in a fire situation or cause TY4851 - Upright 8.0K, 1/2 "NPT a it to operate prematurely. TY4951 - Pendent 8.0K, 1/2 "NPT o 4- Page 1 of 8 OCTOBER, 2005 TFP151 Page 2 of 8 TFP151 ESCUTCHEON 7/16" (11,1 mm) PLATE SEATING * NOMINAL SSU SURFACE NPT MAKE -IN DEFLECTOR =� ru i -i nr ?T1S *� 6 i r ifr 5 2 -1/4" f 2 -3/16" 4 (57,2 mm) f =11 1 (55,6 mm) I 1 -9/16" WRENCH C '!! . r ?El i\ ` 3 2 jk (39,7 mm) FLATS i III SSP 7 DEFLECTOR CROSS PENDENT UPRIGHT SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 1 STANDARD RESPONSE SERIES TY-B UPRIGHT (TY1151) AND PENDENT (TY1251) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 7/16" (11,1 mm) STYLE 10 PLATE SEATING ** NOMINAL RECESSED SURFACE 1/2" T - IN ESCUTCHEON DEFLECTOR 6 7/16" SN% 5 2 -3/16" - mUr (11,1 mm) (55,6 mm) �� A1176 I NOMINAL 4 MAKE -IN I I 1 -1/2" ,�� 2 -3/16" (38,1 mm) y ..: � 2 ! (55,6 mm) } � WREN H 3 i� s- - ��i� s- FLATS 1 SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. — •- - 1 1/2 " NPT ** f PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 2 STANDARD RESPONSE SERIES TY-B UPRIGHT (TY3151) AND PENDENT (TY3251) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT • TFP151 Page 3 of 8 ESCUTCHEON 1/2" (12,7 mm) STYLE 40 . PLATE SEATING NOMINAL RECESSED SURFACE NF T MAKE-IN ESCUTCHEON DEFLECTOR i 6 — 1/2" 3r 5 2 -5/16" ' (12,7 mm) (58,7 mm) 111// IA� E1 7 ' NOMINAL 4 i -- �� , I MAKE -IN *4 , h- ; - 2 1 -9/16" ��� �r� ` : 2-1/4" �' (39,7 mm) I J� (57,2 mm) to 2, , i III Illf WRENCH 3 FLATS 4 1 SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. 3/4" NPT ** PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Ejection orifice seat on frame. Screw Spnng ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 3 STANDARD RESPONSE SERIES TY -B UPRIGHT (TY4151) AND PENDENT (TY4251) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT ESCUTCHEON 7/16" (11,1 mm) PLATE SEATING 1/2 ** NOMINAL SSU SURFACE NPT MAKE -IN DEFLECTOR I 5 2 -1/4" 2- 3/16" (57,2 mm) IN =1; ill (55,6 mm) I I 4 1 -9/16" WRENCH I! -- IPA � ��f 2 (39,7 mm) I FLATS � 7 ■ SSP 1 DEFLECTOR CROSS PENDENT UPRIGHT SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 4 STANDARD RESPONSE SERIES TY -B UPRIGHT (TY4851) AND PENDENT (TY4951) SPRINKLERS 8.0 K- FACTOR, 1/2 INCH NPT • Page 4 of 8 TFP151 SPRINKLER FINISH (See Note 8) K TYPE TEMP. BULB NATURAL CHROME WHITE"' LEAD WAX WAX OVER LIQUID BRASS PLATED POLYESTER COATED COATED LEAD COATED 135F/57°C Orange PENDENT 155 °F /68 °C Red 2 8 (TY1251) 1, 2, 3 N/A 1/2" and 175 °F /79 °C Yellow NPT UPRIGHT 200 °F /93 °C Green (TY1151) 286 °F /141 °C Blue 360 °F /182 °C Mauve 1, 2 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY3251) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 1, 2, 3, 5 1, 2, 3, 5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 5.6 (TY3151) 286°F/141 °C Blue 1 ",2", 3" 5" 1" 2" 3" 5** 1/2" NPT 360 °F /182 °C Mauve N/A 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A (TY3251)* 175 °F /79 °C Yellow Figure 4 200 °F /93 °C Green 286 °F /141 °C Blue 1, 2 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY4251) 1, 2, 5 1, 2, 3, 5 1, 2, 5 and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7 8.0 UPRIGHT 200 °F /93 °C Green 3/4" (TY4151) 286 °F /141 °C Blue 1 "2" 3" 5** 1" 2" 5" NPT 360 °F /182 °C Mauve N/A 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 N/A (TY4251)* 175 °F /79 °C Yellow Figure 5 200 °F /93 °C Green 286 °F /141 °C Blue 1, 2 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red 8.0 (TY4951) 1/2" and 175 °F /79 °C Yellow 1, 2, 3, 5 N/A NPT UPRIGHT 200 °F /93 °C Green (TY4851) 286 °F /141 °C Blue 360 °F /182 °C Mauve NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL). 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL). 3. Approved by Factory Mutual Research Corporation (FM). 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/03) 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details contact Tyco Fire 8 Building Products, Enschede, Netherlands, Tel. 31- 53- 428 -4444 /Fax 31 -53 -428- 3377). 7 Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05). 8. Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers. • Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. • 150 °F /66 °C Maximum Ceiling Temperature. "' Frame and deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE A, LABORATORY LISTINGS AND APPROVALS TFP151 Page 5 of 8 2 -7/8" DIA. L� 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) (15,9±6,4 mm) 2.1/4" DIA. 1/4" (6,4 mm) RECESS (END "A" USED FOR FACE OF (57,2 mm) MOUNTING 1/2" NPT MODELS) SPRINKLER PLATE — FITTING 1/8" WRENCH RECESS '� (3,2 mm) (END "B" USED FOR 1�I 3/4" NPT MODELS) %, FIGURE 7 �� W -TYPE 6 SPRINKLER MOUNTING SURFACE • WRENCH CLOSURE SERIES 1 -1/4" (31,8 mm) RECESS TY B 3/4" (19,1 mm) FIGURE 5 SERIES TY -B RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT PUSH WRENCH INTO ENSURE 2 -7/8" DIA. ENGAGEMENT (73,0 mm) 3/4" (19,1 mm) WITH SPRINKLER 5/8±1/4" WRENCHING AREA (15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (57,2 mm) FIGURE 8 FACE OF MOUNTING W -TYPE 7 RECESSED SPRINKLER PLATE SPRINKLER WRENCH FITTING 1/8" (3,2 mm) �rll� / A , MOUNTING ■11 SURFACE �• CLOSURE SERIES 1- 5/16" (33,3 mm) TY B 13/16" (20,6 mm) FIGURE 6 SERIES TY -B RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON 8.0 K-FACTOR, 3/4 INCH NPT Page 6 of 8 TFP151 ing the wax coating. Before wrench Technical Installation tightening the sprinkler, the jaws of the wrench are to be adjusted to just con - Data The Series TY -B Sprinklers must be tact the sprinkler wrench flats. After installed in accordance with the follow- wrench tightening the sprinkler, loosen Approvals ing instructions: the wrench jaws before removing the UL and C -UL Listed. wrench. FM, LPCB, VdS, and NYC Approved. NOTES After installation, the sprinkler wrench (Refer to Table A for complete ap- Do not install any bulb type sprinkler if flats and frame arms must be in- proval information including corrosion the bulb is cracked or there is a loss of resistant status.) liquid from the bulb. With the sprinkler spected and the wax coating re- held horizontally, a small air bubble touched (repaired) whenever the coat - Maximum Working Pressure should be present. The diameter of the ing has been damaged and bare metal 175 psi (12,1 bar) air bubble is approximately 1/16 inch is exposed. The wax coating on the Discharge Coefficient (1,6 mm) for the 135 °F /57 °C to 3/32 wrench flats can be retouched by gen- K = 2.8 GPM /psi (40,3 LPM /bar inch (2,4 mm) for the 360 °F /182 °C tly applying a heated 1/8 inch diameter K = 5.6 GPM /psi (80,6 LPM /bar temperature ratings. steel rod to the areas of wax that have K = 8.0 GPM /psi (115,2 LPM /bar1 /2) been damaged, to smooth it back over A leak tight 1/2 inch NPT sprinkler joint areas where bare metal is exposed. Temperature Ratings should be obtained with a torque of 7 Refer to Table A to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- NOTES Finishes mum of 21 ft. lbs. (28,5 Nm) of torque Only retouching of the wax coating ap- Sprinkler: Reessed Escutcheon: may. be used to install sprinklers with plied to the wrench flats and frame White Coated, Chrome Plated, or 1/2 NPT connections. A leak tight 3/4 arms is permitted, and the retouching Brass Plated inch NPT sprinkler joint should be ob- is to be performed only at the time of tained with a torque of 10 to 20 ft.lbs. the initial sprinkler installation. Physical Characteristics (13,4 (40,7 26,8 ) ). A maximum of 30 The steel rod should be heated onl y to Frame Bronze ft.lbs. Nm oftor ueistobeused Button Brass /Copper to install sprinklers with 3/4 NPT con- the point at which it can begin to melt Sealing Assembly nections. Higher levels of torque may the wax, and appropriate precautions Beryllium Nickel w/Teflont distort the sprinkler inlet and cause need to be taken, when handling the Bulb Glass leakage or impairment of the sprinkler. heated rod, in order to prevent the Compression Screw Bronze installer from being burned. ffi Deflector Co Do not attem to make -u for insu- Copper cient adjustment in the escutcheon If attempts to retouch the wax coating . Bushing (K =2.8) Bronze plate by under- or over-tightening the with complete coverage are unsuc- sprinkler. Readjust the position of the cessful, additional wax can be ordered sprinkler fitting to suit. in the form of a wax stick (the end of which is color coded). Only the correct Operation The Series TY -B Pendent and Up- color coded wax is to be used, and The glass Bulb contains a fluid which right Sprinklers must be installed in retouching of wrench flats and frame accordance with the following instruc- arms is only permitted at the time of expands when exposed to heat. When tions. initial sprinkler installation. With the the rated temperature is reached, the steel rod heated as previously de- fluid expands sufficiently to shatter the Step 1. Pendent sprinklers are to be p y glass Bulb, allowing the sprinkler to installed in the pendent position, and scribed, touch the rod to the area re- activate and water to flow. upright sprinklers are to be installed in quiring additional wax with the rod an- the upright position. gled downward, and then touch the wax stick to the rod approximately Design Step 2. With pipe thread sealant ap- one -half inch away from the area re- plied to the pipe threads, hand tighten quiring retouching. The wax will melt C riteria the sprinkler into the sprinkler fitting. and run down onto the sprinkler. Step 3. Tighten the sprinkler into the The Series TY -B Pendent and Upright sprinkler fitting using only the W -Type The Series TY -B Recessed Pendent Sprinklers are intended for fire protec- 6 Sprinkler Wrench (Ref. Figure 7), Sprinklers must be installed in ac- tion systems designed in accordance except that an 8 or 10 inch adjustable cordance with the following instruc- with the standard installation rules rec- Crescent wrench is to be used for wax tions. ognized by the applicable Listing or coated sprinklers. With reference to Step A. A fter installing the Style 10 or Approval agency (e.g., UL Listing is Figures 1, 2, 3, and 4 the W -Type 7 p g ty based on the requirements of NFPA Sprinkler Wrench or the adjustable 40 Mounting Plate, as applicable, over 13, and FM Approval is based on the Crescent wrench, as applicable is to the sprinkler threads and with pipe requirements of FM's Loss Prevention be applied to the wrench flats. thread sealant applied to the pipe Data Sheets). Only the Style 10 or 40 threads, hand tighten the sprinkler into Recessed Escutcheon, as applicable, When installing wax coated sprinklers the sprinkler fitting. is to be used for recessed pendent with the adjustable Crescent wrench, Step B. Tighten the s rinkler into the installations. additional care needs to be exercised p g p sprinkler to prevent damage to the wax coating fitting using only the W -Type on the sprinkler wrench flats or frame 7 Recessed Sprinkler Wrench (Ref. arms and, consequently, exposure of Figure 8). With reference to Figure 3 bare metal to the corrosive environ- or 4, the W -Type 7 Recessed Sprinkler ment. The jaws of the wrench should Wrench is to be applied to the sprinkler be opened sufficiently wide to pass wrench flats. over the wrench flats without damag- Step C. After the ceiling has been in- • TFP151 Page 7of8 stalled or the finish coat has been ap- The owner is responsible for the in- . plied, slide on the Style 10 or 40 Clo- spection, testing, and maintenance of ___ sure over the Series TY -B Sprinkler their fire protection system and de- — and push the Closure over the Mount- vices in compliance with this docu- Warranty ing Plate until its flange comes in con- ment, as well as with the applicable tact with the ceiling. standards of the National Fire Protec- Products manufactured by Tyco Fire & tion Association (e.g., NFPA 25), in Building Products are warranted solely Care and addition to the standards of any other to the original Buyer for ten (10) years authorities having jurisdiction. The in- against defects in material and work - stalling contractor or sprinkler manu- manship when paid for and properly Maintenance facturer should be contacted relative installed and maintained under normal The Series TY -B Sprinklers must be to any questions. use and service. This warranty will ex- P pire ten (10) years from date of ship - maintained and serviced in accord- It is recommended that automatic ment by Tyco Fire & Building Products. ance with the following instructions: sprinkler systems be inspected, No warranty is given for products or tested, and maintained by a qualified components manufactured by compa- NOTES Inspection Service in accordance with nies not affiliated by ownership with Before closing a fire protection system local requirements and /or national Tyco Fire & Building Products or for main control valve for maintenance codes. products and components which have work on the fire protection system that been subject to misuse, improper in- it controls, permission to shut down the stallation, corrosion, or which have not affected fire protection system must be been installed, maintained, modified obtained from the proper authorities or repaired in accordance with applica- and all personnel who maybe affected ble Standards of the National Fire Pro - by this action must be notified. tection Association, and /or the stand - Absence of an escutcheon, which is ards of any other Authorities Having used to cover a clearance hole, may Jurisdiction. Materials found by Tyco delay the time to sprinkler operation in Fire & Building Products to be defec- a fire situation. tive shall be either repaired or re- placed, at Tyco Fire & Building Prod - Sprinklers that are found to be leaking ucts' sole option. Tyco Fire & Building or exhibiting visible signs of corrosion Products neither assumes, nor author - must be replaced. izes any person to assume for it, any • Automatic sprinklers must never be other obligation in connection with the painted, plated, coated or otherwise sale of products or parts of products. altered after leaving the factory. Modi- Tyco Fire & Building Products shall not fied sprinklers must be replaced. be responsible for sprinkler system de- Sprinklers that have been exposed to sign errors or inaccurate or incomplete corrosive products of combustion, but information supplied by Buyer or have not operated, should be replaced Buyer's representatives. if they cannot be completely cleaned IN NO EVENT SHALL TYCO FIRE & by wiping the sprinkler with a cloth or BUILDING PRODUCTS BE LIABLE, by brushing it with a soft bristle brush. IN CONTRACT, TORT, STRICT LI- Care must be exercised to avoid dam- ABILITY OR UNDER ANY OTHER age to the sprinklers - before, during, LEGAL THEORY, FOR INCIDENTAL, and after installation. Sprinklers dam- INDIRECT, SPECIAL OR CONSE- aged by dropping, striking, wrench QUENTIAL DAMAGES, INCLUDING twist/slippage, or the like, must be re- BUT NOT LIMITED TO LABOR placed. Also, replace any sprinkler that CHARGES, REGARDLESS OF has a cracked bulb or that has lost WHETHER TYCO FIRE & BUILDING liquid from its bulb. (Ref. Installation PRODUCTS WAS INFORMED Section). ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT Frequent visual inspections are rec- SHALL TYCO FIRE & BUILDING ommended to be initially performed for PRODUCTS' LIABILITY EXCEED AN corrosion resistant coated sprinklers, AMOUNT EQUAL TO THE SALES after the installation has been corn- PRICE. pleted, to verify the integrity of the cor- THE FOREGOING WARRANTY IS rosion resistant coating. Thereafter, annual inspections per NFPA 25 MADE IN LIEU OF ANY AND ALL should suffice; however, instead of in- OTHER WARRANTIES EXPRESS specting from the floor level, a random OR IMPLIED. INCLUDING WARRAN- sampling of close -up visual inspec- TIES OF MERCHANTABILITY AND tions should be made, so as to better FITNESS FORA PARTICULAR PUR- determine the exact sprinkler condi- POSE, tion and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions present. Page 8 of 8 TFP151 P/N 57- XXX -X -XXX I I SPRINKLER TEMPERATURE MODEL/SIN RATING 530 2.8K UPRIGHT (1/2 "NPT) TY1151 1 NATURAL BRASS 135 135"F157°C 531 2.8K PENDENT (112 "NPT) TY1251 4 WHITE POLYESTER 155 155 °F /68 °C 570 5.6K UPRIGHT (1/2 "NPT) TY3151 3 WHITE (RAL9010)` 175 175 °F /79 °C 571 5.6K PENDENT (1/2 "NPT) TY3251 9 CHROME PLATED 200 200 °F /93 °C 590 8.0K UPRIGHT (3/4 "NPT) TY4151 7 LEAD COATED 286 286 °F /141 °C 591 8.0K PENDENT (3/4 "NPT) TY4251 6 WAX COATED 360 360 °F /182 °C 286 °F /141 °C MAX. 560 8.0K UPRIGHT (1/2 "NPT) TY4851 8 WAX OVER LEAD 561 8.0K PENDENT (1/2 "NPT) TY4951 286 °F /141 °C MAX. Eastern Hemisphere sales only. TABLE B PART NUMBER SELECTION SERIES TY-B PENDENT AND UPRIGHT SPRINKLERS Recessed Escutcheon: Wax Sticks: Ordering Specify: Style (specify) Recessed Es- (for retouching wrench damaged • Procedure (spec fy) with (specify finish), P/N wax coating) Specify: (Specify color) color coded When placing an order, indicate the full 1/2" (15 mm) Wax Stick for retouching (specify tern- product name. Refer to the Price List Style 10 perature rating) temperature rated Se- • for complete listing of Part Numbers. Chrome Plated P/N 56- 701 -9 -010 ries TY -B Sprinklers, P/N (specify). 1/2" (15 mm) Contact your local distributor for avail- Style 10 Black for 135 °F P/N 56 -065 -1 -135 ability. White Color Red for 155 °F P/N 56- 065 -1 -155 Coated P/N 56-701-4-010 Yellow for 175 °F P/N 56- 065 -1 -175 1/2" (15 mm) Blue for 200 °F and Sprinkler Assemblies with NPT Style 10 Thread Connections: White RAL9010° .. ... P/N 56- 701 -3 -010 286°F P/N 56- 065 -1 -286 Specify: (Specify Model /SIN), Stand- 1/2" (15 mm) and R(specify K- factor), Style 10 NOTES e, Brass Plated P/N 56- 701 -2 -010 Each wax stick is suitable for retouch - (specify on fY P (sre (specify rating), Series 3/4" (20 mm) ing up to twenty-five sprinklers. TY -B (specify Pendent or Upright) Style 40 Sprinkler with (specify type of finish or Chrome Plated . .. P/N 56- 700 -9 -010 The wax used for 286 °F sprinklers is coating), P/N (specify from Table B). 3/4" (20 mm) the same as for 200 °F sprinklers, and, 40 Style White Color therefore, the 286 °F sprinkler is limited Coated P/N 56-700-4-010 to the same maximum ceiling tempera - 3/4" (20 mm) ture as the 200 °F sprinkler (i.e., Style 40 150 °F). White RAL9010° P/N 56- 700 -3 -010 3/4" (20 mm) Style 40 Brass Plated P/N 56- 700 -2 -010 • Eastern Hemisphere sales only. Sprinkler Wrench: Specify: W -Type 6 Sprinkler Wrench, P/N 56- 000 -6 -387. Specify: W -Type 7 Sprinkler Wrench, P/N 56 -850 -4 -001. TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446