RE: FOWLER MIDDLE SCHOOL, MECHANICAL
Project Information
Building Permit: MEC2003 -00202 Construction Type: V -N
t enant Name: Tigard- Tualatin School District Occupancy Type: E -1
Address: 10865 SW Walnut Occupant Load: ?
Area: 136,000 Sq Ft Stories: 1
Sprinkled: YES Alarms: Manual
The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002
edition. The submitted plans are approved subject to the following.
1. Equipment and appliances regulated by this code requiring electrical connections shall have a
positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC
2. Appliances shall be accessible for inspection, service, repair or replacement without removal
of permanent construction. 306.1 OMSC
° 3. Appliances installed on roofs or elevated structures exceeding 16 feet in height shall be
provided with a permanent means of access grade or floor level. 306.5 OMSC
4. Manufacturer's installation instructions shall be available on the jobsite at the time of
inspection. 304.1 OMSC
5. Condensate from cooling coils or evaporators shall be collected and discharged to an
approved plumbing fixture or disposal area. 307.1 OMSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout
all phases of construction. 106.4.2 OSSC