Correspondence (2) CALLISON August 20, 2009 RECEIVED Mr. Dan Nelson City of Tigard AUG 2 5 2009 13125 SW Hall Boulevard Tigard, OR 97223 CITY OFTIGARD BUILDING DIVISION RE: Nordstrom Washington Square (025) Building Permit # BUP2008 -00269 Response to City of Tigard Conditions Letter, dated September 18, 2008 Dear Mr. Nelson: In response to conditions listed in the City of Tigard Conditions Letter, dated 9/18/08 (attached), we are submitting revised drawings as outlined below: Condition #1 Every structure, and portion thereof including non - structural components that are permanently attached to structures and their supports and attachments, shall be designed and constructed to resist the effects of earthquake motions in accordance with ASCE 7 as modified by Section 1613.7. The seismic design category for a structure is permitted to be determined in accordance with Section 1613 or ASCE 7. OSSC 1613.1. Please submit plans and calculations as needed. Response: Per my conversation with Dan Nelson on 9/19/08, this plan check comment is in reference to the two -level stock storage system described on Sheet A -001, under the section pertaining to SEPARATE PLAN SUBMITTALS. This is to confirm that drawings and calculations will be issued to the building department as a separate plan submittal demonstrating conformance with ASCE 7. ASCE 7 requirements have been noted under the section pertaining to separate plan submittals. See Cover Sheet A -001 — SEPARATE PLAN SUBMITTALS (revision is clouded). Condition #2 Your request to have the building evaluated under the current edition of the OSSC as JIB construction has been approved. The 1 -hour exiting enclosures should remain rated due to the travel distance. Please provide new plans indicating these changes. Response: A. Code information has.been updated to reflect current applicable code requirements for Type IIB Construction. See Cover Sheet A -001 - APPLICABLE CODES and CODE SUMMARY (revisions are clouded). B. Per my conversation with Dan Nelson on 10/1/08, we have reviewed travel distances and have confirmed that travel distances to stair exit enclosures are achievable within the 250 -ft maximum allowed under OSSC Table 1016.1. Therefore, existing one - hour -rated wall construction at CALLISON ARCHITECTURE, INC. 1 4 2 0 FIFTH AVENUE #2400 SEATTLE, WASHINGTON 98101 - 2343 T 206 623 4646 F 206 623 4625 www.callison.com • • + Mr. Dan Nelson, City of Tigard Nordstrom- Washington Square (025), Pioject Number 207245.00 August 20, 2009 Page 2 Corridors 1032, 1067, 2028, 2084, and 2117 are not required to be maintained. Refer to Sheet A -002 for travel distance diagrams. The following drawings have been revised to indicate non- rated wall construction at Corridors 1032, 1067, 2028, 2084, and 2117 (revisions are clouded): Sheets A -002, A -111 through A -115, A -121 through A -124, and A-406. Condition #3 Rated wall designs shall included nailing schedules. Response: Based on the explanation provided in response to Condition #2, nailing schedules for rated walls are not applicable, given there is no new rated wall construction in the scope of work. Additional Revision unrelated to Plan Check Comments We have corrected a typographical error pertaining to the door exit width provided at Second Floor to indicate 406 ". See Cover Sheet A -001 (revision is clouded). Please feel free to contact me directly if you have any questions. Sincerely, El (37°17 /44/ Lisa Kirby, AIA RECEIVED Associate AUG 2 5 2009 LK:cm CITY OF TIGARD Enclosure BUILDING DIVISION c: Nordstrom: Galen Dolstad R &H Construction: Jon Dingwall Callison: Erie Stone, File # 207245.00 H.\Remxlel\Projects\Renx dels\0257\Project Administration \09-Code Agencies \ letters \ 0257- PernutRevtstonc•Itr- 082009 doc September 18, 2008 RE: TENANT IMPROVEMENT Project Information Building Permit: BUP2008 -00269 Construction Type: 2 -B Address: 9700 SW Washington Sq. Occupancy Type: M Area: 180,000 Sq. Ft. Stories: 2 Name: Nordstrom Sprinklers: Yes The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code. Please respond to conditions below. 1) Every structure, and portion thereof, including non structural components that are permanently attached to structures and their supports and attachments, shall be designed and constructed to resist the effects of earthquake motions in accordance with ASCE 7 as modified by Section 1613.7. The seismic design category for a structure is permitted to be determined in accordance with Section 1613 or ASCE 7. OSSC 1613.1. Please submit plans and calculations as needed. 2) Your request to have the building evaluated under the current edition of the OSSC as IIB construction has been approved. The 1 hour exit enclosures should remain rated due to the travel distance. Please provide new plans indicating these changes. 3) Rated wall designs shall include nailing schedules. When responding, provide an itemized letter stating in what way each numbered issue has been addressed in the revision. When submitting revised drawings or additional information, please use a copy of the City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Dan Nelson Senior Plans Examiner (503) 718 -2436 �T�� dann@tigard-or.gov CE1 d AUG 2 5 200 C1 1. G DIVISION BUllr J • • TRANSMITTAL • CALLISON Date: Thursday, August 20, 2009 To: Jon Dingwall R &H Construction 1530 SW Taylor Street Portland, OR 97205 Re: Response to City of Tigard Conditions Letter Phone: 503.228.7177 Fax: 503.528.2129 Ship Via: Fed Ex - Standard (3:00PM) Project: Nordstrom Washington Square (025) 2009 Remodel Project #: 207245.00 We are sending you the following: For Your: Action Required: Q Attached Ej Under Separate Cover 12 Info and Use 12 As Indicated Q Prints El Originals El Review and Comment ❑ Sign And Return Submittal El Samples El Other El As Requested El No Action Required Enclosed please find the following documents for submission to the City of Tigard: Callison letter, dated 8/20/09, with the following attachments: 1. City of Tigard Conditions Letter, dated 9/18/08 2. (2) Sets Full -Size Original Architectural Stamped Drawings (revisions clouded): Sheets A -001 - A -124, and A -406 Please also find the following documents for your own records: Callison letter, dated 8/20/09, with the following attachments: 1. City of Tigard Conditions Letter, dated 9/18/08 2. (1) Set Full -Size Original Architectural Stamped Drawings (revisions clouded): Sheets A -001 - A -124, and A -406. Thank you. Caela McKeever Associate D Nordstrom - Store Planning (805) - Galen Dolstad RE EDTE AEI` 2 5 2009 CITDOGDwis ON BULL - 1420 FIFTH AVENUE, SUITE 2400 SEATTLE, WA 98101 -2343 - T1 206 623 4646 F1 206 623 4625 www callison com R S ciIIRIvER 63 I vy La n e, St e. 220 E NGINEERING Phone (301) 220-1212 Fax (301) 220 -2256 Fire Protection • Code Consulting • Risk Control • Security Consulting September 9, 2008 • Mr. Brian Blaylock APPROVED Building Official City of Tigard ql (e t Oe 13125 SW Hall Blvd. l l Tigard, OR 97223 PO? 2 6 1 C8 — 00-& c t RE: Nordstrom Remodel Washington Square Mall 7c 1 SEC Project No. 1508143 -000 Dear Mr. Nelson: As you may be aware a set of plans has been submitted to the Building Department for a proposed interior renovation of the Nordstrom Store located at the Washington Square Mall. After submitting the drawings for review, a meeting was held to discuss the project. During that meeting Mr. Daniel Nelson, Senior Reviewer, proposed to the Lisa Kirby of Callison Architecture that the project apply to have the entire Nordstrom Store reclassified so that the remodel could be conducted utilizing the current Oregon Structural Specialty Code (OSSC) (which adopts the International Building Code, 2006 edition). This code would then be used in place of the Uniform Building Code, 1991 edition (UBC) which was in effect at the time of initial construction. After reviewing the impact of this proposal we respectfully request that your office approve the reclassification of the Nordstrom Washington Square Mall from a UBC Type IIFR building to an OSSC Construction Type 2B building. Our justification for this request is based upon the ability of the existing store to comply with all fire protection and life safety requirements of the OSSC applicable to Cover Mall Anchor Buildings as detailed below: COMPARISON OF CURRENT OREGON STRUCTURAL SPECIALTY CODE REQUIREMENTS VS. THE EXISTING CONDITIONS AT THE NORDSTROM WASHINGTON SQUARE MALL Oregon Structural Specialty Code Requirement Referenced Section Summary of Requirements Existing Condltlon Anchor Building are defined as An Except as previously permitted egress from exterior perimeter building of a group the Nordstrom Store is independent of the Section 402.2 other than H having direct access to the mall. The proposed change will not reduce mall building, but having required the level of life safety provided by the means of egress separate from t he existing means of egress arrangement. mall.° The area of anchor buildings 3 or less The existing mall complies with the Section 402.6 stories in height and Construction Type requirements for 60 feet of open area, and I, II, III, and IV shall not be limited when the fire resistance ratings required by UBC Schirmer Engineering Corporation www.schlrmereng.com j R Mr. Brian Blaylock 2 September 9, 2008 Nordstrom — Washington Square Mall SEC Project No. 1508143-000 COMPARISON OF CURRENT OREGON STRUCTURAL SPECIALTY CODE REQUIREMENTS VS. THE EXISTING CONDITIONS AT THE NORDSTROM WASHINGTON SQUARE MALL Oregon Structural Specialty Code Requirement Referenced Section Summary of Requirements Existing Condition the mall and anchor building is Type IIFR construction are higher than surrounded by 60 feet of open space. those required for the new proposed OSSC Construction Type IIB. Anchor building not more than 3 stories The existing mall separation walls meet or Section 402.7.3 exception shall be separated from the mall by a 2 exceed the requirements for a 2 hour fire hour fire barrier. barrier. The anchor store is required to be The existing sprinkler systems meets or equipped with an automatic sprinkler exceeds the requirements of NFPA 13 and Section 402.8 system in accordance with NFPA 13. will be modified as required by the renovation to maintain this level of protection. Group M occupancies with an occupant The existing fire alarm system provides load greater than 500 are required to be audible and visual notification of occupants Section 907.2.7 equipped with a manual fire alarm throughout the building. This system will be system and occupant notification. modified as required by the renovation to maintain the existing level of protection. As demonstrated by the table above, the fire protection and life safety features present at the Nordstrom Washington Square Mall meet or exceed the requirements of the current Oregon State Building Code. Based upon this ability for the store to comply with current requirements it is requested that the store be reclassified from UBC Construction Type IIFR to OSSC Construction Type IIB and that the proposed renovation be reviewed from compliance with requirements of the current OSSC. Thank you for your consideration of this issue and we look forward to your favorable response. Sincerely, SCHIRMER ENGINEERING CORPORATION LeJay Slocum Cc: Dan Nelson — City of Tigard Lisa Kirby — Callison Randy Olsen — Nordstrom John Dingwall — RH Construction Rondi Felton — Faster Permits r SCHIRIV1ER 6305 Ivy Lane, Ste. 220 EI%IGII%IEERII%IG Phone (301 2 220-1212 Fax (301) 220 -2256 Fire Protection • Code Consulting • Risk Control • Security Consulting _/ September 9, 2008 0 '\ V Mr. Dan Nelson Building Official _ City of Tigard \___-" 13125 SW Hall Blvd. Tigard, OR 97223 RE: Nordstrom Remodel Washington Square Mall SEC Project No. 1508143 -000 Dear Mr. Nelson: As you may be aware a set of plans has been submitted to the Building Department for a proposed interior renovation of the Nordstrom Store located at the Washington Square Mall. After submitting the drawings for review, a meeting was held to discuss the project. During that meeting Mr. Daniel Nelson, Senior Reviewer, proposed to the Lisa Kirby of Callison Architecture that the project apply to have the entire Nordstrom Store reclassified so that the remodel could be conducted utilizing the current Oregon Structural Specialty Code (OSSC) (which adopts the International Building Code, 2006 edition). This code would then be used in place of the Uniform Building Code, 1991 edition (UBC) which was in effect at the time of initial construction. After reviewing the impact of this proposal we respectfully request that your office approve the reclassification of the Nordstrom Washington Square Mall from a UBC Type IIFR building to an OSSC Construction Type 2B building. Our justification for this request is based upon the ability of the existing store to comply with all fire protection and life safety requirements of the OSSC applicable to Cover Mall Anchor Buildings as detailed below: COMPARISON OF CURRENT OREGON STRUCTURAL SPECIALTY CODE REQUIREMENTS VS. THE EXISTING CONDITIONS AT THE NORDSTROM WASHINGTON SQUARE MALL Oregon Structural Specialty Code Requirement Referenced Section Summery of Requirements Existing Condltlon Anchor Building are defined as An Except as previously permitted egress from exterior perimeter building of a group the Nordstrom Store is independent of the Section 402.2 other than H having direct access to the mall. The proposed change will not reduce mall building, but having required the level of life safety provided by the means of egress separate from t he existing means of egress arrangement. mall.° The area of anchor buildings 3 or less The existing mall complies with the Section 402.6 stories in height and Construction Type requirements for 60 feet of open area, and I, II, Ill, and IV shall not be limited when the fire resistance ratings required by UBC Schirmer Engineering Corporation www.schlrmereng.com •—" T, • Mr. Dan Nelson 2 September 9, 2008 Nordstrom — Washington Square Mall SEC Project No. 1508143-000 COMPARISON OF CURRENT OREGON STRUCTURAL SPECIALTY CODE REQUIREMENTS VS. THE EXISTING CONDITIONS AT THE NORDSTROM WASHINGTON SQUARE MALL Oregon Structural Specialty Code Requirement Referenced Section Summary of Requirements Existing Condition the mall and anchor building is Type IIFR construction are higher than surrounded by 60 feet of open space. those required for the new proposed OSSC Construction Type IIB. Anchor building not more than 3 stones The existing mall separation walls meet or Section 402.7.3 exception shall be separated from the mall by a 2 exceed the requirements for a 2 hour fire hour fire barrier. barrier. The anchor store is required to be The existing sprinkler systems meets or equipped with an automatic sprinkler exceeds the requirements of NFPA 13 and Section 402.8 system in accordance with NFPA 13. will be modified as required by the renovation to maintain this level of protection. Group M occupancies with an occupant The existing fire alarm system provides load greater than 500 are required to be audible and visual notification of occupants Section 907.2.7 equipped with a manual fire alarm throughout the building. This system will be system and occupant notification. modified as required by the renovation to maintain the existing level of protection. As demonstrated by the table above, the fire protection and life safety features present at the Nordstrom Washington Square Mall meet or exceed the requirements of the current Oregon State Building Code. Based upon this ability for the store to comply with current requirements it is requested that the store be reclassified from UBC Construction Type IIFR to OSSC Construction Type 118 and that the proposed renovation be reviewed from compliance with requirements of the current OSSC. Thank you for your consideration of this issue and we look forward to your favorable response. Sincerely, SCHIRMER ENGINEERING CORPORATION LeJay Slocum Cc: Lisa Kirby — Callison Randy Olsen — Nordstrom John Dingwall — RH Construction Rondi Felton — Faster Permits 7 ),tmlocr - oa- 0 Dan Nelson . From: Lisa Kirby [Lisa.Kirby@callison.com] Sent: , Friday, August 29, 2008 11:46 AM To: Dan Nelson Cc: Olsen, Randy; JDINGWALL@ncconst.com; Rondi Felton; Susan Freeman Subject: Nordstrom- Washington Square Remodel: Construction Type Classification and Callison Project Team Contacts Dan, Per our conversation this morning, Callison has reviewed the original construction detailing for the Nordstrom building and has confirmed the east mall wall construction exceeds the 2 hour wall rating that would be required for Type 2B construction under the current code. This should simplify the case favoring reclassification of the building's construction type from Type II -FR (UBC) to Type 2B (IBC). We are having our code consultant evaluate the proposed reclassification, so that we may report back to Nordstrom the information they need to make an informed decision. We anticipate that we will issue a letter to the building department, the week of September 8. I will be out of the office Sept 1 Sept 12. ,Susan Freeman will be covering project management during my absence, so we request that you copy. her on' any communications, in addition to myself. Susan's email address is susan: freeman a@callison.com. If you need to speak w ith a Callison representative, during my absence, please contact Susan directly at (206).623 -4646. - Thank you, Lisa Kirby, AIA Associate Principal lisa.kirbv @callison.com - CALLISON 1420 FIFTH, AVENUE #2400 SEATTLE, WASHINGTON.98101 -2343 T 1 206 623 4646 F 206 623 4625 • This message is private or privileged. If you are not the person for whom this message is intended, please delete it, notify me immediately, and do not copy send this message to anyone else. • • 1 City of Tigard, Oregon • 1125'S Hall Blvd. • Tigard, OR 97223 September 18, 2008 • RE: TENANT IMPROVEMENT T I GARD Project Information Building Permit: BUP2008 -00269 Construction Type: 2 -B Address: 9700 SW Washington Sq. Occupancy Type: M Area 180,000 Sq. Ft. Stories: 2 Name; Nordstrom Sprinklers: Yes The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; 2007 Oregon Fire Code. Please respond to conditions below. 1) Every structure, and portion thereof, including non structural components that are permanently attached to structures and their supports and attachments, shall be designed and constructed to resist the effects of' earthquake motions in accordance with ASCE 7 as modified by Section 1613.-7. The seismic design category for a structure is permitted to be determined in accordance with Section 1613 or ASCE 7. OSSC 1613.1. Please submit plans and calculations as needed. 2) Your request to have the building, evaluated under the current edition of the OSSC as IIB'construction has been approved. The 1 hour exit enclosures should remain rated due to the travel distance. Please provide new plans indicating these changes. 3) Rated wall designs shall include nailing schedules. When responding, provide an itemized letter stating in what way each numbered issue has,been addressed in the revision. When submitting revised drawings or additional information, please use a copy of the City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfull , o l • an Nelson Senior Plans Examiner (503) 718 -2436 dann @tigard -or.gov Phone : , 503.639.4171 • Fax: 503.684.7297 . • www.tigard - or.gov • TTY Relay: 503.684.2772 f Tidemark Advant4r2,r. [ 1 1 . 1 1 1 t [ 1 1 . 1 1 1 1 i , - DAN] - [Activity for BUP2008- 00269] 1— 1 IT I0 . Ede Edit Qptions Window 'Restore Down 1 111 0 0 a A• - NNR Open <. . TMkLM A O! 1 v .-. i w Add t - rt Do et. - e te2 Date3 Assigned To Disp Done By Notes Application received 816(2008 RECD JMT Permit created 1020 8/6/2008 DONE JMT Check for parcel tagsA 1030 8/6(2008 DONE BTT Building plans routed ti 1060 816(2008 DONE BTT Begin plan review 1065 8(18/2008 DONE DAN RevisionsAnfo request 1070 9(18/2008 DONE DAN H HOLD for (see r1420 11/12/2008 HOLD DAN Permit will be placed on hold for two years from date of application without written extenait 1.41 i 0 1YiewIAddActivities go Irb ox Microsoft Out „, Tideri�art: Advantage .., My Cum a rch D eskto , start re uter Desktop p t \ ite t BUILDING DIVISION: HOURS OF OPERATION ARE CHANGING To better \ serve you, the Building Division will be changing its hours of operation. Beginning August 10, 2009 the Building Division will be closed on Mondays.. This is a temporary solution to budget issues, and a direct result of the current economic climate. However, by closing one day a week, the Building Division will be able to offer additional inspections in the afternoons, and open an hour earlier, at 7 a.m., Tuesday through Friday. New Hours of Operation. Tuesday - Friday 7 a.m. - 5 p.m. • If you have any questions, comments, or concerns, please contact i Mark VanDomelen, Building Official, at markv @tigard - or.gov, or phone him at 503- 718 -2448. TIGARD 74 CITY OF TIGARD FEE AND PAYMENT HISTORY v g .. -. 13125 SW Hall Blvd., Tigard OR 97223 503.639.4171 TIGARD BUP2008 -00269 - 9700 SW WASHINGTON SQUARE RD Revenue Payment Fee Description Account Number Fee Amount Invoiced Paid Date Paid Method Receipt # Due [BUPPLN] Pln Rv 245 - 0000 - 433000 $9,940.26 $9,940.26 $9,940.26 8/6/08 CreditCard 2720080000 $0.00 0000002780 [FLS] FLS Pln Rv 245- 0000 - 433020 $6,117.08 $6,117.08 $6,117.08 8/6/08 CreditCard 2720080000 $0.00 0000002780 [BUILD] Permit Fee 245- 0000 - 432000 $15,292.70 $15,292.70 $15,292.70 [TAX] 12% State Surcharge 100 - 0000 - 207020 $1,835.12 $1,835.12 $1,835.12 [METCET] Metro Const Excise Tx 245- 0000 - 229202 $7,200.00 $7,200.00 $7,200.00 Totals for Fees $40,385.16 $40,385.16 $16,057.34 $24,327.82 Receipt # Payment Method Check # Pavor: Receipt Date Receipt Amount 27200800000000002780 CreditCard RONDI FELTON / 08/06/2008 $16,057.34 FASTER PERMITS Total Payments: 16 057.34 :a ance Due: $24,327.82 System Information Schedule An Inspection Cancel An Inspection In an ongoing commitment to improve Step 1: Access Main Menu. Step 1: Access Main Menu. customer service, the City of Tigard building division has installed an automated inspection Press [1] To schedule an inspection. Press [2] To cancel an inspection. request system for inspections, 24 hours a day, Step 2: Enter Permit Type. Step 2: Follow Steps 2 - 4 for 7 days a week, with a cut -off time of 7:00 AM "Schedule An Inspection ". for inspections that business day. Press [01] BUP Building - structural Note: Service is suspended between the hours of Press [02] ELC Electrical 2:00 AM and 3:00 AM for system maintenance. Press [03] ELR Restricted Energy Step 3: Additional Options. Press [04] MEC Mechanical • Reschedule the inspection. Normal inspection hours: Press [05] MST Master - Residential Combo • Cancel another inspection for the same Tuesday Friday, 8:00 AM to 3:30 PM* Press [06] PLM Plumbing or a different permit. Press [07] SIT Site Work • Get a confirmation number. The system prompts will guide you to: Press [08] SWR Sewer Connectio • Return to the Main Menu. • Schedule Inspections Press [09] FPS Fire Protection System • Cancel Ins ections Press [10] RER Re -Roof P Press [11] CMS Commercial Manufact. Struct. Note: If you call after 7:00 AM to cancel • Obtain Inspection Results Press [12] SFM Single - Family Manufact. Struct an inspection for that day, you will need Before you call, you will need: to call building staff at 503.718.2439. • A touch - tone telephone . • Step 3: Enter Permit Number. A permit number. Obtain Inspection Results • An inspection code (see Inspection Code Enter all digits of your permit number, including all l� List on the back of this User Guide). zeros, followed by the # sign. Example: For permit number BUP2009- 00246, enter 200900246 #. Step 1: Access Main Menu. To access the system, call The system will verify your permit number and the Press [3] To obtain inspection results. 503.639.4175 job site address. (24 hours a day) Step 2: Follow Steps 2 -4 for Step 4: Enter Inspection Code. "Schedule An Inspection ". • At the Main Menu, choose from the See the list of inspection codes on the back of this following options: User Guide, or use the system prompts to hear a list of Step 3: Additional Options. Press [1] To schedule an inspection. inspectio codes. • Hear message from the inspector. Press [2] To cancel an inspection. • Listen to more results for the same Press [3] To obtain inspection results. Step 5: Additional Options. or a different permit. Press [0] To speak with department staff. • Get a confirmation number. • • Leave a message for the inspector. • Reschedule failed inspections. Press r] To repeat these options. • Request another inspection on the same p or a different permit. • Return to Main Menu. *Note: Inspections will not be scheduled on the p • Get a confirmation number. following holidays in 2009: • Return to the Main Menu. Reinspection fees must be paid by 4:30 PM for 1/1,1/19, 2/16, 5/25, 7/3, 9/7,11/11,11/26,11 /27 inspections the next business day. and 12/25. I: \Bwldmg \Brochures \Brorhr -IVR User Gwde.doc 7/27/09 • Inspection iCode List Building Electrical 205 Footing 105 Underground /slab cover User Guide 210 Foundation walls 110 Temporary electrical service 215 Footing drain 115 Electrical service 220 Slab 120 Electrical rough -in 225 Post /beam structural 125 Wall cover 230 Underfloor insulation 130 Ceiling cover Automated 235 Shear walls /anchors .135 Low voltage 240 Exterior sheathing 140 Sign installation 242 Interior shear walls 145 A/C or heating unit circuit Inspection 245 Firewall - 150 "Hot tub /spa /pool 250 Roof nailing 195 Misc. inspection 255 Wtr proofing basement walls 199 Electrical final Request 260 Tilt -up panel 265 Masonry Mechanical 270 Reinforcing steel (rebar) 605 Post /beam mechanical 275 Framing 610 Gas line 503.639.4175 280 Insulation 615 Mechanical rough -in (24 hours a day) 285 Drywall nailing 620 Hydronic piping 287 Suspended ceiling 625 Duct work 289 Approach /sidewalk 630 Fire damper 295 Misc. inspection 635 Smoke detector shutdown 299 Final inspection 640 Exhaust hood Fire Protection System 695 Misc. inspection , 905 Sprinkler underfloor /slab 699 Mechanical final 1111 . 907 Sprinkler hydro test = il 910 Sprinkler rough -in /test Plumbing 915 Fire alarm rough -in 305 Plumbing underslab 920 Suppression trip test 310 Crawl drain 995 Misc. inspection 315 Post /beam plumbing T I GAR D 998 Alarm final 320 Plumbing rough -in 999 Sprinkler final - 322 Shower pan Site Work 330 Water service 405 Excavation 335 Rain drain 410 Fill 340 Storm drain CITY OF TIGARD 415 Grading 345 Culvert /catch basin 420 Sprinkler supply lines 350 Septic tank Building Division 495 Misc. inspection 395 Misc. inspection 13125 SW Hall Blvd. 498 Grading final 399 Plumbing final Tigard, OR 97223 499 Final inspection 503.639.4171 Manufactured Structure Sewer www.tigard or.gov 805 MFG - Sructure grading /footing 505 Sanitary sewer 810 MFG- Structure set -up 595 Misc. inspection 899 MFG Structure final 599 Final inspection August 10, 2009 • •