Correspondence OFFICE COPY June 4, 2004 CITY OF TIGARD Dean Ferguson OREGON Guardian Fire Protection 1012 SW A Street Corvallis, OR 97333 RE: FIRE SUPPRESSION SYSTEM Building Permit: BUP2004 -00232 Construction Type: V -1HR Tenant Name: B.A.P.S. Temple Occupancy Type: A2.1 Address: 11365 SW Tigard Street Occupant Load: 1,132 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99- 01) 1999 edition. The submitted plans are approved subject to the following. 1. Provide City of Tigard Inspector with Ansul Installation Manual for inspection. 2. A readily accessible manual activation device shall be located at or near a means of egress from the cooking area, a minimum of 10 feet and a maximum of 20 feet from the kitchen exhaust system. The manual activation device shall be located a minimum of 4 V2 feet and a maximum of 5 feet above the finished floor. Instructions for operating the fire suppression system shall be posted adjacent to manual activation device. 509.4 OMSC 3. The automatic fire suppression system shall be interconnected to the fuel or current supply for the cooking equipment and arranged to automatically shut off all equipment under the hood when the suppression system is activated. Shut off valves or switches shall be of a type that requires manual operation to reset. 509.5 OMSC 4. An approved K -type portable fire extinguisher shall be installed within 30 feet of the cooking equipment, as measured along an unobstructed path of travel. 1006.2.7 TVFR99 -01 5. Extinguishing systems shall be serviced at least every six months. 1006.2.8 TVFR99- 01 Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall PP PP P � g Y g PP mP� be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 t. Ansel wet ehemcial fire suppression system. " Model R -102 6 gallon capacity. • Flow point capacity: 22 Flow points used: 17 2W - - _ _ _ _.ILL 14 Type I Hood n 4 Srne [— i It Ansul iN iN iN 245 ,W 5� IN O Remote Manual Actuator I , r-i Li (in egress) J I.. ,IL , ,-"-, 24" 24" Steam 1 0' Automatic Gas Griddle Range Kettle Stock Shut Off Valve. Pot Range Fire System Drawing Front _ _ Notes: —Make up air & receptacles located under the Hood #i hood moat shut down upon 'fire system actuation. — Ansel must be tied into building fire alarm system if present. — Exhaust fan to be left running. BY: Guardian Fire Prot. Inc. FOR: H.A.P.S. Temple West Notes: System installed in accordance with 1012 SW "A" ST. 11435 SW Tigard St. Ansul Design, Installation, Recharge, Corvallis OR 97333 Tigard OR and Maintenance Manual. (541) 752 -2258 System tested in accordance with CCBi 100355 exp. 6 -23 -06 Scale: None ILL. Standard # 300. 'his dr■ slag not be reproduced without written permbaton from Date: 5 Drawn By: MAP -- - Guardian Fire Protection Inc. M y state, county agencies — - - - - -- - are eze eptad d uping the course plan review or permit process. : Ansul wet chemcial fire suppression system. Model R -102 6 gallon capacity. Flow point capacity: 22 Flow points used: 17 2W iI__t_ 14' Type I 260 asp 860 Hood N iR Ansul _ iF iF iF iF 40' 40 40' 4d' 1N 48" 48" 411' 48" - 30" O Remote 40' Manual Actuator -- -- (in egress) .3 . -C / / 18" 12" 12" 12" 12" Automatic Gas Stock Single Single Single Single Shut Off Valve. Pot burner burner burner burner Range range range range range Fire System Drawing _ Front View _ Notes: —Make up air & receptacles located under the Hood #2 hood must shut down upon fire system actuation. — Ansul must be tied into building fire alarm system if present. — Exhaust fan to be left running. By: Guardian Fire Prot. Inc. FOR: B.A.P.S. Temple West Notes: System installed in accordance with 1012 SW "A" ST. 11435 SW Tigard st. Ansul Design, Installation, Recharge, Corvallis OR 97333 Tigard OR and Maintenance Manual. (541) 752 -2258 System tested in accordance with CCB# 100355 exp. 6-23-06 Scale: None U.L. Standard # 300. This drawing may not be reproduced without written permission from Date: 5 Drawn By: MAP -- Guardian Fire Protection Inc. City, state, county agencies are excepted during the course of plan review or permit process.