Correspondence (2) OFFICE COPY
In
r l i 4 l � ll �
July 25, 2003 �`=A''��
CITY OF TIGARD
Paresh Patel
PO Box 41160 OREGON
San Jose, CA 95160
RE: NEW COMMERCIAL STRUCTURE
Project Information
Building Permit: BUP2003 -00050 Construction Type: V -1HR
Mechanical Permit: MEC2003 -00042 Occupancy Type: A -2.1
Tenant Name: B.A.P.S. Temple Occupant Load: 1132
Address: 11365 SW Tigard Street Stories: 2
Area: 19,690 Sq Ft Alarms: Manual
Sprinklers: NA
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC)
1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999
edition. The submitted plans are approved subject to the following conditions.
• Fire /Smoke Dampers are required at all penetrations of the rated corridor including
the shoe rooms.
• The Mechanical unit anchorage calculations and designs have still not been submitted
and are considered deferred submittals. Deferred submittals such as Mechanical Unit
Anchorage, Fire Alarm, Truss Joist Shop Drawings, etc, will be charged a deferred
submittal fee based on the valuation of the portion of the work being deferred. The
minimum fee shall be $200.00.
• Special Inspection: Special inspection is required for items listed on sheet S1.0 The
special inspection agency of record, shall furnish inspection reports to the Engineer of
Record, Dean W. Briggs, the General Contractor, and the City of Tigard, Building
Division, attention Hap Watkins. All discrepancies shall be brought to the
immediate attention of the general contractor for correction. The special inspector
shall submit a final signed report stating whether the work requiring special
inspection was, to the best of the inspector's knowledge, in conformance with the
approved plans and specifications and the applicable workmanship provisions of the
code. 1701.3 OSSC
• Exit doors shall be provided with panic hardware.1007.2.5 OSSC
• Exit signs shall be illuminated at all times and shall be provided with a second source
of power that will provide 1 V2 hours of illumination in case of primary power loss.
1003.2.8.5 OSSC
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
• The means of egress shall be provided with illumination of not less than 1 foot candle
at the floor level anytime the building is occupied. The means of egress illumination
shall be provided with a second source of power in case of primary power loss.
1003.2.9.2 OSSC
• Provide 2 -A rated fire extinguishers throughout the building. The extinguisher shall
be located so that no usable space has a distance greater than 75 feet to the
extinguisher. Standard 10 -1, Chapter 3 TVFR99 -01.
• An Elevator Permit will be required from the State of Oregon, Building Codes
Division. Contact number 503- 378 -3866
American with Disabilities Act (ADA): It shall be the responsibility of the Architect,
Engineer, Designer, Contractor, Owner and Lessee to research the applicability of the ADA
requirements for the structure. The City of Tigard reviews the plans and inspects the structure
only for compliance with Chapter 11 of the OSSC which may not include all of the
requirements of the ADA.
Live Loads Posted: The live loads for which each floor has been designed shall be
conspicuously posted by the owner in that part of each story in which they apply, using
durable metal signs, and it shall be unlawful to remove or deface such notices. The occupant
of the building shall be responsible for keeping the actual load below the allowable limits.
1607.3.5 OSSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Certificate of Occupancy: No building or structure shall be used or occupied until the
Building Official has issued a certificate of occupancy 109.1 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfu
ian Blab. ,
Senior P ns Examiner