Date: September 10, 2009
Re: Plan review for 7904 Hunziker Road
For Dickenson Electric
The plans are acceptable with the following provisions:
1.) A grounding terminal bar as provided for in NEC 250.8 shall be installed adjacent to the
main service for the connection of all required grounding and bonding conductors.
2.) Current limiting fuses are to be installed at the service to reduce the available fault
current to the withstand rating of all downstream devices.
3.) The plans including this letter shall be available to the inspector at the time of any
inspection. The approvals of the plans do not allow for any provisions other than the
current 2008National Electrical Code 2008.