Correspondence o zcz 7- croy &/ v City of Tigard, Oregon ° 13125 SW Hall Blvd. o Tigard, OR 97223 41';.):1.3!::1. « 7 r }:. I er RD Date: September 10, 2009 Re: Plan review for 7904 Hunziker Road For Dickenson Electric The plans are acceptable with the following provisions: 1.) A grounding terminal bar as provided for in NEC 250.8 shall be installed adjacent to the main service for the connection of all required grounding and bonding conductors. 2.) Current limiting fuses are to be installed at the service to reduce the available fault current to the withstand rating of all downstream devices. 3.) The plans including this letter shall be available to the inspector at the time of any inspection. The approvals of the plans do not allow for any provisions other than the current 2008National Electrical Code 2008. Herb Stabenow Electrical Inspector Phone: 503.639.4171 o Fax: 503.684.7297 o www.tigard- or.gov ® TTY Relay: 503.684.2772