Plans 00 (c) TWE° Submittal / Trane A Division of American Standard Inc. Prepared For: Date: September 13, 2006 HVAC Inc. Job Name: Fanno Creek Bldg B Trane is pleased to provide the enclosed submittal for your review and approval. RECEIVED Product Summary Qty Product NOV 2 2006 2 Commercial Rooftop Air Conditioning Units (Midrange) CITY OF TIGARD 4 Variable Air Volume Single Duct Terminal Units BUILDING DIVISION 14 Variable Air Volume Fan Powered Terminal Units The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval. Y Daniel Driver TraneOregon Phone: (503)620 -8031 Fax: (503)639 -1454 J :IJOBSI124129026.A15Isub ver 01.doc • Table Of Contents - Product Summary 1 Commercial Rooftop Air Conditioning Units (Midrange) (Item Al) Tag Data 3 Product Data 3 Performance Data 3 Mechanical Specifications 5 Unit Dimensions 9 Fan Curve 14 Weight, Clearance & Rigging Diagram 15 Accessory 16 Field Wiring 17 Variable Air Volume Single Duct Terminal Units (Items B1 - B3) Tag Data 20 Product Data 20 Performance Data 20 Mechanical Specifications 21 Unit Dimensions 24 Field Wiring 27 Variable Air Volume Fan Powered Terminal Units (Items Cl, C2) Tag Data 30 Product Data 30 Performance Data 30 Mechanical Specifications 32 Unit Dimensions 36 Accessory 38 Field Wiring 39 - Field Installed Options - Part/Order Number Summary Commercial Rooftop Air Conditioning Units (Midrange) 41 Fanno Creek Bldg B September 13, 2006 Tag Data - Commercial Rooftop Air Conditioning Units (Midrange) (Qty: 2) Item Tag(s) Qty Description Model Number Al RTU - 1, RTU - 2 2 75 Ton Packaged Industrial Rooftop ( SFHFC754 Product Data - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 2 Tag(s): RTU -1, RTU -2 DX Cooling With Natural Gas Heat 75 Ton Unit 460 Volt -60 Hertz -3 Phase 2 Stage Low gas heat capacity 100% Exhaust - 15 Hp with Statitrac 700 rpm - Exhaust fan High- efficiency throwaway filters 40 Hp - Supply motor 1100 rpm - Supply fan 0 -100% Economizer Economizer Control w /dry bulb 2.00" [51 mm] Spring isolators Supply and Exhaust Fan with VFD with out Bypass Standard ambient control UL approval Nonfused Unit Disconnect Switch Temperature sensor (Fld) Access doors Trane communication interface module Flat roof curb (Fld) Year 1 Labor Warranty Heating & Cooling Performance Data - Commercial Rooftop Air Conditioning Units (Midrange) Tags RTU -1 Design airflow (cfm) 30000 Exhaust fan airflow (cfm) 26000 Cooling EDB (F) 77.30 Cooling EWB (F) 61.00 Ent air relative humidity ( %) 38.70 Ambient temp (F) 95.00 Leaving Coil DB (F) 52.02 Leaving Coil WB (F) 51.02 Leaving Unit DB (F) 55.69 Leaving Unit WB (F) 52.59 Gross total capacity (MBh) 835.96 Gross sensible capacity (MBh) 835.96 Gross latent capacity (MBh) 0.00 Net total capacity (MBh) 724.18 Net sensible capacity (MBh) 724.18 Net sensible heat ratio ( %) 100.00 Input htg capacity (MBh) 500.00 Output htg capacity (MBh) 410.00 Output htg capacity w /fan (MBh) 511.79 Heating EAT (F) 55.00 Heating LAT (F) 67.60 Heating delta T (F) 12.60 Supply duct static pressure (in H2O) 1.75 Return duct static pressure (in H2O) 0.50 Component S.P. drop (in H2O) 2.18 Total static pressure (in H2O) 4.43 Supply motor BHP calculated (bhp) 39.97 Supply fan RPM calculated (rpm) 1037 Exhaust static pressure (in H2O) 0.50 Exhaust motor BHP calculated (bhp) 13.26 FLD > Furnished by Trane / Installed by Others Trane Equipment Submittal Page 3 of 41 , Fanno Creek Bldg B September 13, 2006 Tags RTU -1 Exhaust fan RPM calculated (rpm) 689 System power (kW) 109.79 ' EER @ ARI (EER) 9.4 IPLV @ARI (IPLV) 11.5 Minimum circuit ampacity (A) 221.13 Maximum overcurrent protection (A) 250.00 Minimum disconnect switch size (A) 240.00 Recommended dual element (A) 250.00 Compressor 1 count (Each) 2.00 Compressor 1 RLA (A) 27.30 Compressor 2 count (Each) 4.00 Compressor 2 RLA (A) 18.20 Supply fan motor FLA (A) 48.50 Supply fan count (Each) 1.00 Condenser fan FLA (A) 10.80 Exhaust fan motor FLA (A) 19.30 Other FLA (A) 3.00 Evaporator face area (sq ft) 43.10 Evaporator fin spacing (Per Foot) 148 Evaporator rows (Each) 4.00 Condenser rows (Each) 4.00 Condenser fin spacing (Per Foot) 144 Min. unit operating weight (Ib) 8970.0 Max. unit operating weight (Ib) 12143.0 Fan motor heat (MBh) 111.77 FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 4 of 41 ' Fanno Creek Bldg B September 13, 2006 Mechanical Specifications - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Oty: 2 Tag(s): RTU -1, RTU -2 . General Unit will be specifically designed for outdoor rooftop installation on a roof curb. The unit will be completely factory assembled, run tested, piped, internally wired, and fully charged with R -22, and the compressor will be oil charged. Cooling capacity will be rated in accordance with ARI Standard 360. Unit will have decals and tags to aid in service and indicate caution areas. Electrical diagrams will be printed on long life water resistant material and will ship attached to control panel door. Unit Casing Exterior panels have a minimum of 1.25 ounce zinc coating per square foot of steel, phosphatized and will be painted with an oven dried, water based enamel finish which meets a 672 hour salt spray test based on the ASTM 8117 standard for salt spray resistance. Screws will be coated with zinc - plus -zinc chromate. Interior surfaces or exterior casing members will have 1/2 " [12.7 mm] Tuf -Skin fiberglass insulation. Unit base will be watertight with 14 gauge formed load bearing members, formed recess and curb overhang. Unit lifting lugs will accept chains or cables for rigging. Lifting lugs will also serve as unit tiedown points. Scroll Compressors Trane 3 -D Scroll compressors will have a simple mechanical design with only three major moving parts. Scroll type compression and 3 -D compliance will provide a completely enclosed compression chamber with no leakage paths. Trane 3 -D Scroll compressors will include a direct- drive, 3600 rpm, suction gas cooled hermetic motor, centrifugal oil pump, oil sight glass and oil charging valve. The control system will allow lead /lag of multiple compressors (on single circuit units), or circuits (for multiple circuit units) for even run time, if so desired. Evaporator Coil Internally enhanced seamless copper tubing of 1/2" [12.7 mm] O.D. will be mechanically bonded to heavy -duty aluminum fins of configurated design. Coil will be equipped with thermal expansion valves and factory pressure and leak tested at 300 psig [2068.5 kPa]. Aluminum Fin Condenser Coil Configurated aluminum fin secondary surface will be mechanically bonded to primary surface of 3/8" [9.53 mm] O.D. copper tubing. Subcooling circuits will be provided as standard. Coils will be factory tested at 450 psig [3102.8 kPa] air pressure and vacuum dehydrated. Condenser Fans and Motors All condenser fans will be vertical discharge, direct drive fans, statically balanced, with steel blades and zinc plated steel hubs. Condenser fan motors will be three -phase motors with permanently lubricated ball bearings, built -in current and thermal overload protection and weathertight slingers over motor bearings. Forward Curved Fans Supply fans will have two double inlet, forward - curved fans mounted on common shaft with fixed sheave drive and will be dynamically balanced and tested in factory. Supply fan will be test run in unit as part of unit test and unit will reach rated rpm before the fan shaft passes through first critical speed. Fan shaft will be mounted on two grease lubricated ball bearings designed for 200,000 hours average life. Fan motor and fan assembly will be mounted on common base to allow consistent belt tension with no relative motion between fan and motor shafts. Supply and exhaust fan (If applicable) assemblies are isolated with 2" [50.8 mm] nominal deflection spring isolators. All supply fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Variable Frequency Drive General Description: The AC Drive and all associated optional equipment are UL listed according to Power Conversation Equipment UL 508C and CSA certified. The AC Drive is designed, constructed and tested in accordance with NEMA ICS, NFPA, and IEC standards. The Drive is housed in a metal NEMA 1 enclosure. All standard and optional features are included within the Drive enclosure, unless otherwise specified. The Drive converts incoming fixed frequency three -phase AC power into a variable frequency and voltage for controlling the speed of three -phase AC motors. DC link reactors are provided on both the positive and negative rails of the DC bus equal to 3% impedance to minimize power line - harmonics. Full load amp ratings meet or exceed NEC Table 430 -150. The Drive provides full rated output current continuously, 110% of rated current for 60 seconds and 160% of rated current for up to 0.5 second while starting. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 5 of 41 Fanno Creek Bldg B September 13, 2006 Isolation is provided between the Drive's power circuitry and control circuitry to ensure operator safety and to protect connected electronic control equipment from damage caused by voltage spikes, current surges, and ground loop currents. Audible motor noise is minimized through the use of an adjustable carrier frequency. Carrier frequency is automatically adjusted to optimize motor and AC Drive efficiencies while reducing motor noise. Operating range, ambient temperature, -10 to 50°C (14 to 104 °F), 0 to 95% relative humidity, non - condensing, AC line voltage variation, -10 to +10% of nominal with full output. Protective Features Class 10 12t electronic motor overload protection for single motor applications is provided. Protection against input transients, loss of AC line phase, output short circuit, output ground fault, over - voltage, under - voltage, AC Drive over - temperature and motor over - temperature. All faults are displayed in plain English. Protection from AC Drive sustained power or phase loss. Full rated output with an input voltage as low as 90% of nominal. Continuous operation with reduced output with an input voltage as low as 164 V AC for 208/230 volt units, 313 V AC for 460 volt units, and 394 volts for 600 volts units. Semi - conductor rated input fuses to protect power components. A "signal loss detection" circuit senses the loss of an analog input signal such as 4 to 20 mA or 0 to 10 V DC, and is programmable to react as desired in such an instance. Default: After 10- second time out the Drive will shut off. Will function normally when the keypad is removed while the AC Drive is running and continue to follow remote commands. AC Drive catches rotating motor operating forward or reverse up to full speed. The AC Drive is rated for 100,000 amperes interrupting capacity (AIC). Includes current sensors on three output phases to detect and report phase loss to the motor. Identifies which of the output phases is low or lost. Continues to operate without faulting until input voltage reaches 300 V AC on 208/230 volt units, 539 V AC on 460 volt units, and 690 volts on 600 volt units Interface Features Off /Stop and Auto /Start selector switches provided to start and stop the AC Drive and determine the speed reference. On units with bypass, an AC Drive /Off /Bypass Hand selector switch will be provided in the unit control box. In case of an external current overload, a normally closed dry contact will stop the motor whether in DRIVE or BYPASS mode. In DRIVE mode speed reference is provided by a 0 to 10 V DC analog input. The display is programmable to display in 9 languages including English, Spanish and French. The display has four lines, with 20 characters on three lines and eight large characters on one line. The following points are controlled and /or accessible: AC Drive Start/Stop. Speed reference, Fault diagnostics, Meter points to include - Motor power in HP, Motor power in kW, Motor kW -hr, Motor current, Motor voltage, Hours run, DC link voltage, Thermal load on motor, Thermal load on AC Drive and Heatsink temperature. The AC Drive stores in memory the last 10 faults and related operational data. Four simultaneous displays are available, frequency or speed, run time, output amps and output power. The following displays are accessible from the keypad. Reference Signal Value, Output Frequency in Hz or percent, Output Amps, Motor HP, Motor kW, kW hour, Output Voltage, DC Bus Voltage, AC Drive Temperature in degrees, and Motor Speed in RPM. A quick setup menu with factory preset parameters is provided on the AC Drive eliminating the need for macros. A red FAULT light, a yellow WARNING light and a green POWER -ON light are provided. These indications are visible both on the keypad and on the AC Drive when the keypad is removed. The AC Drive includes a standard EIA -485 communication port and capability for future connection to a Modbus communication interface. If the temperature of the AC Drive's heat sink rises to 80°C, the AC Drive automatically reduces its carrier frequency to reduce the heat sink temperature. If the temperature of the heat sink continues to rise the AC Drive automatically reduces its output frequency to the motor. As the AC Drive's heat sink temperature returns to normal, the AC Drive automatically increases the output frequency to the motor and returns the carrier frequency to its normal switching speed. The AC Drive has temperature controlled cooling fans for quiet operation and minimized losses. Adjustments and Factory Default Settings AC Drive carrier frequency is adjustable in steps of not less than 0.1 kHz to allow tuning the AC Drive to the motor. Four, acceleration and four deceleration ramps are provided. Acceleration and deceleration time is adjustable over the range from 0 to 3,600 seconds to base speed. The shape of these curves is automatically contoured to ensure no -trip acceleration and deceleration. Factory Default: The Drive is programmed for an acceleration and deceleration time of 30 seconds. Four current limit settings will be provided. Factory Default: The Drive is programmed for 1 X rated current. If the AC Drive trips on one of the following conditions, the AC Drive will be programmable for automatic or manual reset: under - voltage, over - voltage, current limit and inverter overload. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 6 of 41 • Fanno Creek Bldg B September 13, 2006 Factory Default: The Drive is programmed for 1 X rated current. If the AC Drive trips on one of the following p g p 9 conditions, the AC Drive will be programmable for automatic or manual reset: under - voltage, over - voltage, current limit and inverter overload. Factory Default: The Drive is programmed for automatic reset. The number of restart attempts is selectable from 0 through infinity and the time between attempts is adjustable from 0 through 600 seconds. Factory Default: 3 attempts, 10 seconds between attempts. After 3 failed restart attempts, the drive • automatically reverts to the manual reset mode. An automatic "on delay" may be selected from 0 to 120 seconds. Factory Default: The Drive is programmed for 0 seconds delay. Natural Gas Heat Gas furnace is a completely assembled, wired, and run tested system within the rooftop unit. Furnace has UL or CSA agency approved specifically for outdoor applications. All gas piping is threaded with side or through- the -base main gas supply access. Heat exchanger is a tubular two pass free floating design with 16 gauge stainless steel primary and 18 gauge stainless steel secondary surface. A flue tube /turbulator clean out plate is provided. The burner assembly is industrial type which includes ignition electrode, flame sensing rod, and ceramic cone. An air proving switch is provided to prevent operation during loss of combustion or supply air flow. The combustion blower assembly consists of a centrifugal fan powered by a direct drive internally protected motor. Gas safety controls include an electronic ignition module with 60 second pre -purge cycle and continuous flame sensing capability. The ignition module is microprocessor based and includes operation sequence LED'S for monitoring the furnace operation. 2 Stage Gas Heat The firing rate of the unit can be either half fire or the heating nameplate rating of the unit. A sixty second delay between gas valve stages is provided. 100% Exhaust with Statitrac Two centrifugal fans mounted on a common shaft with fixed sheaves. The fan is factory dynamically balanced and tested. Shaft bearings are grease lubricated ball type designed for 200,000 hours average life. Fan motor and fan assembly are mounted on common base. Entire assembly is isolated from the unit by double deflection rubber in shear isolators or spring isolation with motor sizes larger than five horsepower. For both CV and VAV applications, Statitrac, a differential pressure control system, compares the indoor building pressure to the atmospheric pressure. The exhaust fan is turned on and the discharge dampers at the fan outlet modulates when the building pressure exceeds the specified deadband configured in the Rooftop Human Interface Control. All exhaust fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). High Efficiency Throwaway Filter Filters are 2" [50.8 mm] high efficiency media type with average dust spot efficiency of 25 -35 percent and an average arrestance in excess of 90 percent when tested in accordance with ASHRAE 52 -76. 0 - 100 Percent Economizer Automatically modulating return and outside air dampers assist in the maintaining of the control temperature setpoint to allow "free" cooling. The economizer is equipped with an automatic lockout when the outdoor enthalpy /temperature is not suitable for space temperature control. Minimum position is standard and adjustable with either the Human Interface Control, remote potentiometer, or through the building management system. A spring return actuator insures closure of the outside air dampers during shutdown or power interruption. Mechanical cooling is available to assist the economizing mode. Low leak dampers are standard with a leakage rate of 2.5 percent of nominal airflow of 400 Cfm [189 Us] per ton at a static pressure of 1" [25.4 mm] w.c. Standard Ambient Cooling for 70 & 75 Ton Units Compressor operation is allowed down to 45 degrees F [7.2 C]. Unit Non - Fused Disconnect This switch is nonfused and is located inside the unit control box. An external handle allows power disconnection without having to open the control box door. Access Doors Hinged access doors provide easy access to service areas. These access doors feature double wall construction with dual density insulation sandwiched between 18- gauge and 20 -gauge galvanized steel panels for strength and durability. Trane Communication Interface Module (TCI) The TCI provides interface to Trane's Integrated Comfort system (ICS), which allows control and monitoring of the rooftop by Tracer building management system. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 7 of 41 f s - 1 . Fanno Creek Bldg B September 13, 2006 Temperature Thermister The temperature thermisteris, used to communicate temperature changes in either the Zone, Return Air, Supply Air or Outside Ambient. Roof Curb Roof mounted curb is 14 -gauge zinc coated steel with a nominal two -inch by four -inch nailer. Supply /Return air opening gasket is provided. The curb is manufactured to the National Roofing Contractors Association guidelines and ships non - assembled. The return duct opening location is adjustable using the provided curb channel. Economizer Control Dry Bulb Dry bulb temperature control option an outdoor temperature sensor is included for comparing the outdoor dry bulb temperature to a locally adjustable temperature setpoint programmed either at the human interface or remote human interface to determine if outdoor air temperature is suitable for economizer operation. • • r ' FLD = Furnished by Trane / Installed by Others Trane Equipment, Submittal Page 8 of 41 Fanno Creek Bldg B September 13, 2006 Unit Dimensions - Commercial Rooftop Air Conditioning Units (Midrange) Item: Al Qty: 2 Tag(s): RTU -1, RTU -2 ELECTRICAL / GENERAL DATA • TONS 75 UNIT OPERATING VOLTAGE RANGE 414 — 506 UNIT PRIMARY VOLTAGE 460 UNIT HERTZ 60 UNIT PHASE 3 HEATING - PERFORMANCE HEATING - GENERAL DATA HEATING INPUT 500 GAS INLET PRESSURE MIN7.0" w c MA)04.0" w.c. HEATING OUTPUT 410 GAS PIPE CONNECTION SIZE 1 -1/4" NPT CAPACITY STEPS 2 COMPRESSOR Circuit 41 Circuit 42 NUMBER 3 3 TONS (EACH) (5) 15/10/10 — 36 0 kW 15/10/10 — 36 0 kW COMPRESSOR RATED LOAD AMPS (EACH) 27.3/18 2/18 2 27.3/18.2/18.2 LOCKED ROTOR AMPS (EACH) 178/117 178/117 SUPPLY FAN MOTOR NUMBER 1 HORSEPOWER (EACH) 40.0 — 29.84 kW SUPPLY FAN MOTOR FULL LOAD AMPS 48.5 CONDENSOR FAN MOTOR NUMBER 6 HORSEPOWER (EACH) 10 — 0.75 kW CONDENSOR FAN MOTOR FULL LOAD AMPS 1 8 EXHAUST FAN MOTOR NUMBER 1 HORSEPOWER (EACH) 15.0 — 11.19 kW EXHAUST FAN MOTOR FULL LOAD AMPS 19.3 ELECTRIC HEATER ELECTRIC HEATER KW ELECTRIC HEATER FULL LOAD AMPS FILTERS - TYPE High- EthciencyThrowaway REFRIGERANT TYPE R -22 FURNISHED Yes FACTORY CHARGE (CIRCUIT 41) (6) 60.0 lb NUMBER 35 FACTORY CHARGE (CIRCUIT 62) (6) 61.0 lb RECOMMENDED SIZE 16 x 20 x 2 Cooling MCA = (1.25 x LOAD 1) + LOAD 2 + LOAD 4 Cooling MOP = (2.25 a LOAD 1) + LOAD 2 + LOAD 4 Cooling RDE _ (1 5 x LOAD 1) + LOAD 2 + LOAD 4 Notes: 1 LOAD 1= Current of the largest motor (compressor or fan motor); LOAD 2 =Sum of the currents of all remaining motors; LOAD 3 = Current of electric heaters LOAD 4 =Control Power Transformer (20 -40 ton units add 3 FL amps for wire sizing formula, 50 -75 ton units add 6 FL amps) 2. For Electric Heat MCA, MOP, RDE values, calculate for both cooling and heating modes. (When determining LOADS, the compressors do not operate when the unit is in heating mode) (On 70 - 75 ton single source units, heating Load 4 = 12 amps on 200,230 volt units and 9 amps on 460,575 volt units) 3. If selected Max Over Cur Is less than the Min Clr Amp, then select the lowest maximum fuse size which is equal to or larger than the Min Cir Amp, provided the selected fuse size does not exceed 800 amps. 4. If the selected Recommended Dual Element fuse size Is greater than the selected Max Over Cur Protection value, then select the Recommended Dual Element fuse size value to equal the Max Over Protection value. 5. Compressor KW at ARI rating conditions of 80/67 -95 6. Refrigerant charge is an approx. value. For a more precise value, see unit nameplate and service instructions. FLO = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 9 of 41