June 18, 2007
•.
RE: ALARM TENANT IMPROVEMENT ;'.
F T I' GARD
Permit Number BUP 2007 -00278 Construction Type: 2B
Tenant Name: Fanno Creek B Occupancy Type: B
Address: 16083 SW Upper Boones Ferry Occupant Load: 532
Area: 55,387 Sq. Ft. Stories: 3
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC),
2007 edition; the Oregon Fire Code (OFC), 2007 edition and NFPA 72 Alarm Code. The
submitted plans are approved subject to the following.
Manual Devices
1. Manual Fire Alarm activation devices shall be mounted a minimum of 42 inches and a
maximum of 48 inches measured vertically from the floor to the activating handle or
lever of the device. Section 907.4.2 OFC.
2. A test of the manual fire alarm shall be performed for the structural inspector at the final
inspection.
Visual Devices (Section 1109.14 OSSC)
1 Visual signal appliances shall be provided in the building in each area
2. Visual alarms shall be located not less than 80 inches and not more than 96 inches above
the floor level. When a low ceiling exists, the visual alarm shall be mounted at least 6
inches below the ceiling.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be
maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road fronting
the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfully,
Ai 10.
Dan Nelson,
Senior Plans Examiner
Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772
City 'of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
June 18, 2007
•
I1
RE: ALARM TENANT IMPROVEMENT
TI GARD
Permit Number BUP 2007 -00278 Construction Type: 2B
Tenant Name: Fanno Creek B Occupancy Type: B
Address: 16083 SW Upper Boones Ferry Occupant Load: 632
Area: 54396 Sq. Ft. Stories: 3
The plan review was performed under the State of Oregon Structural Specialty Code (OSSC),
2007 edition; the Oregon Fire Code (OFC), 2007 edition and NFPA 72 Alarm Code. The
submitted plans are subject to the following.
1) Provide revised plans showing deletion of fire /smoke dampers at the corridors.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectfully,
Dan Nelson,
Senior Plans Examiner