JOHN H. ROMISH ARCHITECT
2216 S.E. 24th Portland, Oregon 97214 503/236 -6306
RECEIVED
November 20, 1995 NOV 2 0 1995
COMMUNITY DEVELOPMENT
City of Tigard
Building Department
Plans Examiner James Funk
13125 SW Hall Boulevard
Tigard, Oregon 97223
Re: American Show Management Plan Check #10 -57C
�1 -69.60-S-W:- Upper- Boones -Fern oad
Your letter of 11/16/95
Dear Jim,
We have addressed the items in your letter and this is a summary review.
Accessi 'Iity
. The budget of 106,000.00 dollars for this renovation includes 25%
or 26,500.00 dollars for ADA upgrades. We are revamping the toilet
rooms, we are changing all door hardware to levers, and we are
rebuilding the lunch room counter to meet ADA requirements. These
costs are in excess of the 26,500.00 and therefore we did not correct
the clearances for door 110.
Fire and Life Safety
4 _ 1 7 . All relights shall use tempered glass' per the requirements of 5406 (d) 3.
2. Electrical plans that have been submitted show the require•
� / illumination for this space.
6
Fire extinguishers will be provided per the code in locations agreed by
the fire inspector prior to occupancy.
Mechanical
1. The mechanical contractor has submitted plans for this renovation with
the required application.
•
Fire Sprinklers
V1. The fire sprinkler contractor has submitted his plans with the required
application.
Sincerely,
7
/John H. Romish
cc: Richard Krippaehne
ProTemp
,a
Atik
CITY OF TIGARD
November 16, 1995
. OREGON
John Romish
2216 SE 24th Avenue
Portland, OR 97214
Re: AMERICAN SHOW
16160 SW Upper Boones Ferry Road
PC10 -57C BUP95 -0450
The plans and specifications have been reviewed for conformity to
applicable codes. Please submit three (3) sets of revised plans
and specifications incorporating the following requirements:
Accessibility
Doors accessible for persons with disabilities shall have an
18" w}}de maneuvering space adjacent to the latch side of the
pit.., do r./[Section 3109 (1) 3, Table 31E and Figure 25] . Doors
is& �ing closer and a latch shall have a latch side approach of
lh� 41J 18" on the pull side and 12" on the push side for a front
approach [Section 3109(1 -3) and Table 31F]. Provide
� accessible egress from Room 110.
0 LEI w ay
Fire and Life Safety
G(/ Glazing, in fixed or operable panels adjacent to a door where
the nearest exposed edge of the glazing is within a 24" arc of
either vertical edge of the door in a closed position and
where the bottom exposed edge of the glazing is less than 60"
above the walking surface, shall be tempered [5406(d)3].
Provide specifications for all relites.
2. Provide exit illumination having an intensity of not less than
1 foot candle at floor level, and provide a separate power
source, such as an on -site generator or storage batteries to
operate the lighting system in the exiting system [Section
3313 (a) (b)] .
Provide Type 2 -A fire extinguishers throughout so that the
travel distance to a unit does not exceed 75 feet
[NFPA 10 3.2.1] .
Mechanical
il
� A permit is required for any modification to the mechanical
system. Submit an application and three (3) sets of plans for
review.
1-
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
,.
John Romish
November 16, 1995
pg. 2
T F Sprinklers
1. A permit is required for any modification to the sprinkler
system. Submit an application and three (3) sets of plans and
calculations for review.
If you wish to discuss any of these items, please give me a call.
Sincerely,
James Fun
Plans Examiner
bup95- 0450 \pc10 -57c