Permit „^ I # CITY OF TIGARD BUILDING PERMIT
' ly. PERMIT #: BUP2007 -00278
° COMMUNITY DEVELOPMENT DATE ISSUED: 10/2/2007
TIGARD 13125 SW Hall Blvd., Tigard, OR 97223 503.639.4171
PARCEL: 2S113AB -00300
SITE ADDRESS: 16083 SW UPPER BOONES FERRY RD ZONING: I -L
SUBDIVISION: FANNO CREEK PLACE LOT: JURISDICTION: TIG
PROJECT: FANNO CREEK PLACE
Project Description: Building B Fire Alarm.
•
REISSUE: FLOOR AREAS EXTERIOR WALL CONSTRUCTION
CLASS OF WORK: FPS FIRST: 0 sf N: S: E: W:
TYPE OF USE: COM SECOND: 0 sf PROJECT OPENINGS?
TYPE OF CONST: 2N 0 sf N: S: E: W:
OCCUPANCY GRP: B TOTAL AREA: 0 sf ROOF CONST: FIRE RET?
OCCUPANCY LOAD: 532 BASEMENT: sf AREA SEP. RATED:
STOR: 3 HT: ft GARAGE: sf OCCU SEP. RATED:
BSMT ?: MEZZ ?: REQD SETBACKS REQUIRED
FLOOR LOAD: psf LEFT: ft RGHT: ft FIR SPKL: Y SMOK DET:N
DWELLING UNITS: FRNT: ft REAR: ft FIR ALRM : Y HNDICP ACC:
BEDRMS: BATHS: IMP SURFACE: PRO CORR: N PARKING:
VALUE: $ 7,451.00
Owner: Contractor:
OPUS NORTHWEST LLC BERGELECTRIC CORP
1500 SW FIRST AVE. STE 1100 6026 NE 112TH AVE.
PORTLAND, OR 97201 PORTLAND, OR 97220
Contact #: PRI 503 - 255 -1818
Phone: 503 - 916 -8963 FAX 503 - 255 -1919
Reg #: LIC 110521
FEES
Description Date Amount REQUIRED ITEMS AND REPORTS
[TAX] 8% State Surcha 5/24/2007 $9.16
[FLS] FLS PIn Rv 5/24/2007 $48.04 .
[BUILD] Permit Fee 5/24/2007 $120.55
[BUILD] Permit Fee 6/18/2007 $120.10
(additional fees not listed here)
Total $177.75
This permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes and all other
applicable law. All work will be done in accordance with approved plans. This permit will expire if work is not started within 180 days of
issuance, or if work is suspended for more than 180 days. ATTENTION: Oregon law requires you to follow the rules adopted by the
Oregon Utility Notification Center. Those rules are set forth in OAR 952 - 001 -0010 through OAR 952 - 001 -0100. You may obtain a copy
of these rules or direct questions to OUNC by calling 503.246.6699 or 1.800.332.2344.
Issued By: / Permittee Signature: OAkING”
Call 503.639.4175 by 7:00 a.m. for an inspection that busi s day.
This permit card shall be kept in a conspicuous place on the job site until completion of the project.
Approved plans are required on the job site at the time of each inspection.
. � P rotection System RECEIVED t X83 l9P' -fit- t`sxg_
Build
mg Permit Application ,,, ]
. , . FOR OF FI C E.USE ONLY
200 Received ,,
City of Tigard 1 y GF TIGI�RD Date/By. 49 D� Permit No 2 — - ••
71 ° 13125 SW Hall Blvd., Ti OR,9 2 Plan Revs: % r Gj y `
Other Permit. ^ v( 2'
I..: Phone: 503 639.4171 Fax: 503.5AkJ lING DIVISION Date /B •,AMC `
- G'AR D Inspection Line: 503.639.4175 ate Rear y � ® See Page 2 for
Internet: www.tigard or.gov Nottf • ethod. �QMO/ /4 Supplemental Information
■nT i _
' ' 4.-„ r, - ',... : TYPE, OF WORK' �` ti, : - ;.; , , u �; , RE 1 ED' DATA: 1- :AND 2=FAMILY DWELLING,:,`
Z New construction ❑ Demolition Permi are based on the value of the work performed.
Indicate the value (rounded to the nearest dollar) of all
❑ Addition/alteration/replacement ❑ Other: equipment, materials, labor, overhead, and the profit for the
CATEGORY OF.�CONSTRUCTION,- x`42,.', work indicated on this application.
El 1- and 2- family dwelling ® Commercial /industrial Valuation: S
❑ Accessory building ❑ Multi - family Number of bedrooms:
❑ Master builder ❑ Other: Number of bathrooms:
"1. ,;;'JOB INFORMATION :ANDrtLOCATION ' °r ?.' Total number of floors:
Job site address: 16083 SW Upper Boones Ferry Road New dwelling area: square feet
City /State /ZIP: Tigard, OR 97224 Garage /carport area: square feet
Suite/bldg. /apt. no.: Project name: Fanno Creek - Building B Covered porch area: square feet
Cross strect/directions to job site: Deck area: square feet
Other structure area: square feet
REQUIRED,DATA: COMMERCIAL -USE, CHECKLIST ,
Subdivision: I Lot no.: Permit fees* are based on the value of the work performed.
Tax map /parcel no.: Indicate the value (rounded to the nearest dollar) of all
equipment, materials, labor, overhead, and the profit for the
' ' -r DESCRIPTION OF WORK _ _.;' ' , work indicated on this application.
Complete Fire Alarm System Valuation: $7,451.50
Existing building area: square feet
New building area: 55387 square feet
, ❑ • PROPERTY OWNER; ' - I , ❑ a TENANT' ' Number of stories: 3
Name: Type of construction: Tilt up Z
Address: Occupancy groups: 13
City /State /ZIP: Existing: 53?----
Phone: ( ) Fax:
( ) New: Group B Office BCS`(p� =.
. ..;',. : 13Y , ' APPLICANT, : ' - ❑'CONTACT , PERSON t; ' ,y • - 'NOTICE . . ' '
Business name: Bergelectric Corp All contractors and subcontractors are required to be
Contact name: Phil Waymire licensed with the Oregon Construction Contractors Board
under ORS 701 and may be required to be licensed in the
Address: 6026 NE 112th Ave jurisdiction in which work is being performed. If the
City /State /ZIP: Portland, OR 97220 applicant is exempt from licensing, the following reasons
apply:
Phone: (503) 255 -1818 Fax: : (503) 255 -1919 Z ti7 g (?Z
E -mail: pwaymire @bergelectric.com
. % - ,, • ' CONTRACTOR ',
, , ,,, ;„ . '.,1 „ � - , • 43 � � BUILDING. PERMIT FEES" '
Business name: Bergelectric Corp
' . ' • (Please refer to jee scheduler " . ' ` ' 1
Permit fee: /ZOO"'
Address: 6026 NE 112th Ave
City /State /ZIP: Portland, OR 97220 State surcharge (8% of permit fee): 9*
Phone: (503 255 -1818. Fax: (503) 255 -1919 FLS plan review (40% of permit fee): ,/ o
( ) (Due upon application.) 'Y
CCB lie.: 110521 ('` y43\oq Total permit fees: / 77 75
Authorized signature:
Amount received:
This permit application expires if a permit is not obtained
Print name: Phil Waymire Date: 05/23/07 within 180 days after it has been accepted as complete.
* Fee methodology set by Tri -County Building Industry
Service Board.
I \Budding'Permits\FPS- PermnApp doc 03/23/06 440461 3T(I I /02 /COM/WEB) '7,
! ,..
`41 Bergelectric Corporation • Contractors & Engineers
Project: Fanno Creek
16075 SW Upper Boones Ferry Road
Tigard, OR 97224
Opus W.O. #90187.00 RECEIVED
BEC W.O. # 10300
t`i 1 2007
Specification Section: 16000 UI N
BUILD IN G DIVISION
Description: Fire Alarm Submittal
Submittal No: 16000.001
Contractor: Bergelectric Corporation
6026 NE 112 Ave
Portland, OR 97220
It is hereby certified that the equipment/material article shown or marked in these submittals and proposed to be incorporated into the work is in complete
compliance with the Contract Documents and can be installed in the allocated spaces.
NAME OF SUBCONTRACTOR: BERGELECTRIC CORPORATION
AUTHORIZED SIGNATURE:
4/ `9.l -
TITLE OR POSITION: PROJECT MANAGER
DATE: May 22, 2007
. /tall
/It lh, 'y, .1hip;
1.1,
l
I '
6026 NE 112 Ave, Portland, OR Tel (503) 255 -1818 Fax (503) 255 -1919 CCB# 110521
VV7- (
FUNDAMENTALS OF FIRE ALARM SYSTEMS
FIRE ALARM SYSTEM FILE COPY
RECORD OF COMPLETION
2 72 -31
Name of protected, •per CP r/4/ 0 L C
Address: .. a tairaleC Ol �47
Representative of protected property (name/phone):
Authority having jurisdiction: -
Address/telephone number
Organization name I phone Represe�(ttative name /p hone
Install. 11 e c, - i ` C c., 03 —�5$ 'j g �5' H H �L � (9-Yow re,
Supplier ,° tr•zo - - '// /l /Q.£'r. /F
Service organization
Location of record (as- built) drawings:
Location of operation and maintenance manuals:
Location of test reports:
A contract for test and inspection in accordance with NFPA standard(s)
Contract No(s): Effective date: Expiration date:
System Software
(a) Operating system (executive) software revision level(s):
(b) Site-specific software revision date: 1, ()
(c) Revision completed b y : / e • ` , .' / 4 F C A P .1 f
(name) (fine)
1. Type(s) of System or Service
NFPA 72, Chapter 6 — Local
If alarm is transmitted to location(s) off premises, list where received: T ili&n 1 I I i
NFPA 72, Chapter 8 — Remote Station
Telephone numbers of the organization receiving alarm:
Alarm
Supervisory:
Trouble:
If alarms are retransmitted to public fire service communications centers or others, indicate location and telephone
numbers of the organization receiving alarm:
Indicate how alarm is retransmitted:
NFPA 72, Chapter 8 — Proprietary
Telephone numbers of the organization receiving alarm:
Alarm:
Supervisory:
Trouble:
If alarms are retransmitted to public fire service communications centers or others, indicate location and telephone
numbers of the organization receiving alarm:
Indicate how alarm is retransmitted:
NFPA 72, Chapter 8 — Central Station
Prime contractor. •
Central station location:
N j9)j�O ® 1 O
FIGURE 4.5.2.1 Record of Completion. (NFPA r I or 4)
18007 j 8 - -1 . 2002 Edition
re -created by fccari
C131\135/14
NATIONAL FIRE ALARM CODS
72 -32
Means of transmission of signals from the protected premises to the central station:
McCulloh Multiplex One -way radio
Digital alarm communicator Two-way radio Others
Means of transmission of alarms to the public fire service communications center:
(a)
(b)
System Location:
NFPA 72, Chapter 9 -- Auxiliary
Indicate type of connection: Local energy Shunt Parallel telephone
Location of telephone number for receipt of signals:
2. Record of System Installation
(Fill out after installation is complete and wiring is checked for opens, shorts, ground faults, and improper branching,
but prior to conducting operational acceptance tests.)
Thrjs systRm has been ' lled in accordance with the NFPA standards as hown below, was inspected by
�( 1Y t t 4 7 ST on ii/ b b' , includes the devices shown
in 5 and 6, and has been in service since 1/ 4 . 7r •
NFPA 72, Chapters 1 2 3 4 5 6 7 8 9 10 11 (circle all that apply)
NFPA 70, National Electrical Code, Article 760
Manufacturer's instructions
Other (specify): I
Signed IIfit Date: f �/D
Or ganiratio
3. Record of System Opera on
Documentation in accordance with Inspection Testing Form, Figure 1 .6.2 , is attached
All operational features and functions of this system were tested by.l a h ii, p sf re So date / / r/ C / , .
and found to be operating properly in accordance with the requirements of
� FPA 72, Chapters 1 2 3 4 5 6 7 8 9 10 11 (circle all that apply)
Z IFPA 70, National Electrical Code, Article 760
Manufacturer's instructions
Other (spe
Signed: /' /%' 4 4 i Aziw x 1 " Date: Y
Organi.ation: / / / c_-
4. Signaling Line Circuits •
Quantity and class of signaling line circuits connected to system (see NFPA 72, Table 6.6.1):
Quantity: 1 Style: Class:
FIGURE 4.5.2. t Record of Completion. (NFPA 72,2 of 4)
2002 Edition
re•creehcd by fcorn
i
FUNDAMENTALS OF FIRE ALARM SYSTEMS
72 -33
5. Alarm - Initiating Devices and Circuits
Quantity and class of initiating device circuits (see NFPA 72, Table 6.5):
Quantity: Style: Class:
•
MANUAL
(a) Manual stations Noncoded Transmitters Coded Addressable /
(b) Combination manual fire alarm and guard's tour coded stations
AUTOMATIC
Coverage: Complete Partial
Selective Nomequired
(a) Smoke detectors Ion Photo Addressable
(b) Duct detectors Ion Photo Addressable
(c) Heat detectors FT RR FT/RR RC Addressable
(d) Sprinkler waterflow indicators: Transmitters Noncoded Coded Addressable
(e) The alarm verification feature is disabled or enabled , changed from seconds to seconds.
(f) Other (list):
6. Supervisory Signal- Initiating Devices and Circuits (use blanks to indicate quantity of devices)
GUARD'S OUR
(a) Coded ..bons
(b) Noncod - ..Y I ons
(c) ComPu so 1 . .'s tour system comprised of transmitter stations and intermediate stations
Note: Corrb1nation dev ..• are recorded under 5(b), Manual, and 6(a), Guard's Tour.
SPRINKLER SYSTEM
Check if provided
(a) 3 Valve supervisory switches
(b) Building temperature points
(c) Site water temperature points
(d) Site water supply level points
Electi fire pump: _
(e) ' ' - pump wer
(1) F .ump running
(g) Pbase -versal
Enginea iven fire N- (h) Sel r°5 auto position
(i) control panel trouble
(j) ire pip ' g
ENGINES RIPEN GENERATOR:
(a) i Sel or in auto position
(b) Con panel trouble
(e) Trar�},sfe switches
(d) Algine Arming
Other.Supervisory ction(s) (specify):
FIGURE 4.5.2.1 Record of Completion. (NFPA 72,3 of 4)
2002 Edition
rc-c ealed by fconri
NATIONAL FIRE ALARM CODE
72-34
7. Annunciator(s)
Number. / Type: ) Location: /'-' 1 h
S. Alarm Notification Appliances and Circuits
NFPA 72, Chapter 6 - Emergency Voice/Alarm Service
Quantity of voice/alarm channels: Single: Multiple:
Quantity of speakers installed: Quantity of speaker zones:
Quantity of telephones or telephone jacks included in system:
Quantity and the class of notification appliance circuits connected to system (see NFPA 72, Table 6.7):
Quantity: Style: Class:
Types and quantities of notification appliances installed:
(a) Bells With Visible
(b) Speakers With Visible
(c) Horns With Visi f q
(d) Chimes With Visible
(e) Other: Wi Visible
(f) Visible appliances without audible
9. System Power Supplies
(a) Fire Alarm Control Panel: Nominal voltage: / T U' Cu rent rating:
Overcurrent protection: Type: 4 it �, . / N< Current rating.
Location: ',, _
(b) Secondary (standby):
Storage battery: f '/''Vj (f Amp -hour rating /
Calculated capacity fo drive system, in hours:
Engine-driven generator dedicated to fire alarm system:
Location of fuel storage:
(c) Emergency system used as backup to primary power supply:
Emergency system described in NFPA 70, Article 700:
10. Comments
Frequency of routine tests and inspections, if other than in accordance with the referenced NFPA standard(s):
System deviations from the referenced NFPA standard(s) are: •
' i
Tl x—C-e-
Crg l l U
(s s ed) for installa t• contract•r/ • • (title / (date)
4.-- (41046ct ) tor alarm ser company c yt , , , � (title) date
(signed) for central station (title) (date)
Upon completion of the system(s) satisfactory test(s) witnessed (if required by the authority having jurisdiction):
(signed) representative of the authority having Jurisdiction (title) (date)
FIGURE 4.5.2.1 Record of Completion. 0.7 PA n, 4 ar 4)
2002 Edition
re-created by fcoari
COTY OF TOGARD
is OVOSOON PERMIT #:
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: /1,:d")(30i
Phone: (503) 639 -4171 a�'�mt�'�A
Inspection Requests (24 Hrs.): (503) 639 -4175 '"' 'ly�i ''=
a .
INSPECTION WORKSHEET FOR DATE: 16/20011 TIME: 7:0OAIVI PAGE: 3Q
SITE ADDRESS: 16083 SW UPPER I.BOONf S FERRY RD CLASS OF WORK:
SUBDIVISION: f ANNO CREEK PLACE LOT #: TYPE OF USE:
PROJECT NAME: FAI-4NO CREEK PLACE
DESCRIPTION: (,ld B
OWNER: OPlJ`. HORYI s I.,!_C. PHONE #: 601918
CONTRACTOR: OPUS NORTHWEST ST CO1T3T LL Cr'l 11001 PHONE #: 503-91641%3
Inspection Request Scheduled For: Date: 2R42088 Pour Time:
Code # Inspection Description Confirm # Contact # Mes 11
F°in I inspection 08459!.:J-01 603- 672 -0122 Y =
ections /Comments /Instructions:
1,
_
PASS / P. 'TIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL L FOR INSPECTION ❑ ADDITIONAL FEES ASSESSED
• I
Inspector: Date: Co a Phone #: (503) 718- Z--64/
CITY OF TIGARD
BUILDING DIVISION PERMIT #: BUJP2007 -00278
13125 SW Hall Blvd., Tigard, OR 97223 DATE ISSUED: '1012j
Phone: (503) 639 -4171 � l t i l
Inspection Requests (24 Hrs.): (503) 639 -4175 ''-
INSPECTION WORKSHEET FOR DATE: 1/15/2008 TIME: 7:02AM PAGE: 42
SITE ADDRESS: 16083 SW UPPER BOONES FERRY RD CLASS OF WORK:
SUBDIVISION: FANNO CREEK PLACE LOT #: TYPE OF USE:
PROJECT NAME: FANNO CREEK PLACE
DESCRIPTION: Building B Fire Alarm.
OWNER: OPUS NORTHWEST LLC, PHONE #: 503 - 916 -8963
CONTRACTOR: BERGELECTRIC CORP PHONE #: 503255.16113
E
Inspection Request Scheduled For: Date: //1512008 Pour Time:
Code # Inspection Description Confirm # Contact # Mes
411. 998 Alarm final 063214 U1 971.246-9032 tAliZ '
9 coo ,9,P'
Corrections/Comments/Instructions:
O ll C. O ■_ 2 d . 9- __
r ZI. e--111a. _ff. L__Z/ .0C:
❑ PASS A�, 'ARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
❑ FAIL r ' - z- , `ECTION ❑ ADDITIONAL FEES ASSESSED
, ../ 2_6'‘41.
Inspector: J Date: l S O/ Phone #: (503) 718-
CITY OF TIGARD .
BUILDING DIVISION r 4 PERMIT #: 13UP 00278
13125 SW Hall Blvd.; Tigard, OR 97223 DATE ISSUED: 10/2/2007
Phone: (503) 639 -4171 V
Inspection Requests (24 Hrs.): (503) 639 -4175 ...'II�..
INSPECTION WORKSHEET FOR DATE: 1/10/2008 TIME: 7 :00AM PAGE: 64
SITE ADDRESS: 16083 SW UPPER E300NES FERRY RD CLASS OF WORK:
SUBDIVISION: FANNO CREEK PLACE LOT #: TYPE OF USE:
PROJECT NAME: FANNO CREEK PLACE
DESCRIPTION: e.3uai1 ding B Fire Alarm.
OWNER: OPUS NORTHWEST LLC, PHONE #: 503916 -B963
' CONTRACTOR: F3ERGELECTRIC CORP PHONE #: 503-255 -1818
Inspection Request Scheduled For: Date: 1/10/2008 Pour Time:
Code # Inspection Description Confirm # Contact # Message
993 Alarm final 062930-01 971-246-9032 Y
Corrections /Comments /Instructions:
l..1 - ' n. 4 s i 4 L
A
■
•
PASS II PARTIAL APPROVAL ❑ CANCEL ❑ NO ACCESS
!4 FAIL MI CALL FOR INSPECTION ❑ ADDITI NAL FEES ASSESSED
b
Inspector: Date: f / 6 b 0 Phone #: (503) 718- __ZL±