Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223
June 23, 2008
RE: MECHANICAL 4{
Project Information TIG
Building Permit: MEC2008 -00322 Construction Type: 2B
Tenant Name: 20 - 20 Occupancy Type: B
Address: 16037 SW Upper Boones Ferry Occupant Load: 50
Area: NA Stories: 3
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition. The
submitted plans are approved subject to the following.
1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning
Contractors National Association, Inc. (SMACNA)
2. Each appliance shall be provided with a shutoff valve separate from the
appliance. The shutoff valve shall be located in the same room and within six feet
of the appliance served. Access shall be provided to the shutoff valve. C409.5
OMSC
3. Equipment and appliances regulated by this code requiring electrical connections
shall have a positive means of disconnect in accordance with the Electrical Code.
301.7 OMSC
4. Appliances shall be accessible for inspection, service, repair or replacement
without removal of permanent construction. 306.1 OMSC
5. Manufacturer's installation instructions shall be available on the jobsite at the
time of inspection. 304.1 OMSC
6. Condensate from cooling coils or evaporators shall be collected and discharged
to an approved plumbing fixture or disposal area. 307.1 OMSC
7. Suspended -type unit heaters shall be supported by non - combustible elements
that are designed and constructed to accommodate the weight and dynamic
loads and shall be sway braced. 920.2 OMSC
8. Inspector may require additional sway bracing at the final installation inspection.
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp,
shall be maintained on the jobsite. The plans shall be available to the Building Division
• inspectors throughout all phases of construction. 106.4.2 OSSC
Phone: 503.639.4171 • Fax: 503.684.7297 . • www.tigard - or.gov • TTY Relay: 503.684.2772
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
,, fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City
of Tigard in tracking and processing the documents.