Correspondence •
EXPIRED A , 4±
July 28, 1997 CITY OF TIGARD
OREGON
Protec Associates
807 NE Couch
Portland, OR 97232
RE: Oregon Business Park Mechanical Plan Review
15860 SW Upper Boones Ferry Road
PC #: 7 -65c MEC #: 97 -0265
Submittal documents for the above referenced project have been reviewed for
conformance with the applicable 1996 Oregon Specialty Codes and other applicable
codes and standards. The following comments are noted:
_. C a y . 9 3 '7'777.---A' , w 1 E s t Y ,0 A7,: " 7 , ' 3 '�" ,7 ti 'T'7--7-.A`-1,,.
_�_...A_ [ .4._C .I.. � ��� , ;`� . T,•r4HrC�- kf *`: '�'� , .,:._...._._.;..b,.i.....�; tr 4 ie
1. Submit completed applicable Forms 4a through 4j, and required duct insulation
Form 4a through 4c of the Energy Code Compliance Manual (Revised April 1996).
� -� m 'r `, +3 4 i 7 �e ' � W � �k _ SF ,I� ` • :4 /. Z } a c J.� t�7. >u.. �z � r n� t "`' i "
1. Provide an engineer's analysis of each structural member supporting the
additional HVAC units [OSSC, Section 106.3.2].
2. Each individual roof - mounted HVAC shall be permanently labeled as to the areas
, it serves [OMSC, Section 305.5]. In addition, each unit shall be equipped with a
power disconnect. A 120 -volt receptacle shall be located within 25' of each unit
[OMSC, Section 309.1].
Please submit four copies of revised submittal documents and a letter indicating your
response to the above comments for review. Please call me at (503) 639 -4171 if you
have any questions.
Sincerely,
Ro ea ki O
P NS EXAMINER