Loading...
Specifications /60 37 TRANS` Submittal Trane A Division of American Standard Inc. 1)( ,EcDOOG, --bog3g Prepared For: Date: September 13, 2006 HVAC Inc. Job Name: Fanno\Creek Bldg A RECEWED NUV Z 2006 Trane is pleased to provide the enclosed submittal for your review and approval. CITY OF TIGARD Product Summary BUILDING DIVISION Qty Product 2 Commercial Rooftop Air Conditioning Units (Large) 4 Variable Air Volume Single Duct Terminal Units 14 Variable Air Volume Fan Powered Terminal Units The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval. Daniel Driver TraneOregon Phone: (503)620 -8031 Fax: (503)639 -1454 0 f 4 r 11 J:IJOBSI124129024.A161sub ver 2.doc Table Of Contents Product Summary 1 r- . Commercial Rooftop Air Conditioning Units (Large) (Item Al) Tag Data 3 Product Data 3 Performance Data 3 Mechanical Specifications 5 Unit Dimensions 9 Fan Curve 12 Weight, Clearance & Rigging Diagram 13 Accessory 14 Field Wiring 15 Variable Air Volume Single Duct Terminal Units (Items B1 - B4) Tag Data 17 Product Data 17 Performance Data 17 Mechanical Specifications 19 Unit Dimensions 22 Field Wiring 26 Variable Air Volume Fan Powered Terminal Units (Items Cl - C4) Tag Data 28 Product Data 28 Performance Data 28 Mechanical Specifications 30 Unit Dimensions 34 Accessory 38 Field Wiring 39 Field Installed Options - Part/Order Number Summary Commercial Rooftop Air Conditioning Units (Large) 41 Fanno Creek Bldg A September 13, 2006 Tag Data - Commercial Rooftop Air Conditioning Units (Large) (Qty: 2) Item Tag(s) Qty Description Model Number '- A l RTU -1, RTU -2 2 90 -130 ton Packaged Industrial Rooftop SFHGC904 Product Data - Commercial Rooftop Air Conditioning Units (Large) Item: Al Qty: 2 Tag(s): RTU -1, RTU -2 - Self- Contained, Natural Gas Heat . 90 Ton Unit 460 Volt -60 Hertz -3 Phase 2 Stage Gas Heat Capacity 100% Exhaust 20 HP With Statitrac 600 RPM Exhaust Fan High- Efficiency Throwaway Filters 40 Hp (2 -20 Hp Motors) Supply Motor 1300 RPM Supply Fan 0- 100% Economizer Economizer control w /dry bulb Supply and Exhaust Fan with VFD with out Bypass UL Approval Nonfused Unit Disconnect Switch Temperature Sensor (Fld) Access Doors Trane communication interface module Standard Flat Roof Curb (Fld) Year 1 Labor Warranty Heating & Cooling Performance Data - Commercial Rooftop Air Conditioning Units (Large) Tags RTU -1, RTU -2 Design airflow (cfm) 38100 Exhaust fan airflow (cfm) 30000 Cooling EDB (F) 78.20 Cooling EWB (F) 61.50 Ent air relative humidity ( %) 38.12 Ambient temp (F) 95.00 Leaving Coil DB (F) 55.25 Leaving Coil WB (F) 52.57 Leaving Unit DB (F) 58.36 Leaving Unit WB (F) 53.87 Gross total capacity (MBh) 962.62 Gross sensible capacity (MBh) 957.59 Gross latent capacity (MBh) 5.03 Net total capacity (MBh) 845.36 Net sensible capacity (MBh) 840.34 Net sensible heat ratio ( %) 99.41 Input htg capacity (MBh) 1000.00 Output htg capacity (MBh) 820.00 Output htg capacity w /fan (MBh) 923.85 Heating EAT (F) 55.00 Heating LAT (F) 74.84 Heating delta T (F) 19.84 Supply duct static pressure (in H2O) 2.00 Return duct static pressure (in H2O) 0.75 �, Component S.P. drop (in H2O) 1.74 Total static pressure (in H2O) 4.49 Supply motor brake horsepower (bhp) 40.77 Supply fan RPM (rpm) 1305 Exhaust static pressure (in H2O) 0.75 Exhaust motor brake horsepower (bhp) 16.00 Exhaust fan RPM calculated (rpm) 616 FLO = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 3 of 41 Fanno Creek Bldg A September 13, 2006 Tags RTU -1, RTU -2 System power (kW) 125.08 (■ EER @ ARI (EER) 9.3 IPLV @ ARI (IPLV) 10.5 Minimum circuit ampacity (A) 246.32 Maximum overcurrent protection (A) 250.00 Minimum disconnect switch size (A) 275.00 Recommended dual element (A) 250.00 Compressor 1 count (Each) 4.00 Compressor 1 RLA (A) 27.30 Compressor 2 count (Each) 2.00 Compressor 2 RLA (A) 18.20 Supply fan motor FLA (A) 25.50 Supply fan count (Each) 2.00 Condenser fan FLA (A) 14.40 Exhaust fan motor FLA (A) 25.50 Other FLA (A) 2.00 Evaporator face area (sq ft) 59.30 Evaporator rows (Each) 3.00 Evaporator fin spacing (Per Foot) 148 Condenser rows (Each) 3.00 Condenser fin spacing (Per Foot) 144 Min. unit operating weight (Ib) 13240.0 Max. unit operating weight (Ib) 17270.0 Fan motor heat (MBh) _117.25 FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 4 of 41 Fanno Creek Bldg A September 13, 2006 Mechanical Specifications - Commercial Rooftop Air Conditioning Units (Large) Item: Al Qty: 2 Tag(s): RTU -1, RTU -2 General (UL Approved Units) Unit will be specifically designed for outdoor rooftop installation on a roof curb. The unit will be completely factory assembled, run tested, UL 1995 approved, piped, internally wired, fully charged with R -22 and the compressor will be oil charged. Cooling capacity will be rated in accordance with ARI Standard 360. Unit will have decals and tags to aid in service and to indicate caution areas. Electrical diagrams will be printed on long life water resist and material and will ship attached to control panel door. Unit Casing Exterior panels will have a minimum of 1.25 oz. [.035 Kg] zinc coating per square foot of steel, phosphatized and painted with an oven dried, water based enamel which meets a 672 hour salt spray test based on the ASTM 6117 standard for salt spray resistance. Screws will be coated with zinc - plus -zinc chromate. Interior surfaces or exterior • casing members will have 1/2" [12.7 mm] Tuf -Skin fiberglass insulation. Unit base will be watertight with 14 gauge formed load bearing members, formed recess and curb overhang. Unit lifting lugs will accept chains or cables for rigging. Lifting lugs will also serve as unit tiedown points. Scroll Compressors Trane 3 -D Scroll compressors will have a simple mechanical design with only three major moving parts and no suction or discharge valves. Scroll type compression and 3 -D compliance will provide a completely enclosed compression chamber with no leakage paths. Trane 3 -D Scroll compressor will include a direct - drive, 3600 rpm, suction gas cooled hermetic motor, centrifugal oil pump, oil sight glass and oil charging valve. Control of compressor will allow lead /lag of multiple compressors /circuits for even run time to increase life of compressors. Supply Fan Assembly The unit has two centrifugal fan assemblies mounted independently within the unit. The fan assembly and fan motor with fixed sheaves are mounted on an independent base. Both assemblies are completely isolated from the unit by two -inch spring isolators. The fans are dynamically balanced and run tested at the factory. Shaft bearings are grease lubricated ball type designed for 200,000 hours average life. All supply fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Condenser Coil Configurated aluminum fin secondary surface will be mechanically bonded to primary surface of 3/8" [9.53 mm] O.D. copper tubing. Subcooling circuits will be provided as standard. Coils will be factory tested at 450 psig [3102.8 kPa] air pressure and vacuum dehydrated. Evaporator Coil Internally enhanced seamless copper tubing of 1/2 " [12.7 mm] O.D. will be mechanically bonded to heavy -duty aluminum fins of configurated design. The coils will be equipped with thermal expansion valves and factory pressure and leak tested at 300 psi [2068.5 kPa]. Natural Gas Heat Gas furnaces are a completely assembled, wired, and run tested system within the rooftop unit. Furnaces are UL/CSA agency approved specifically for outdoor applications. All gas piping is threaded with side or through -the- base main gas supply access. Heat exchangers are tubular two pass free floating design with 16 gauge stainless steel primary and 18 gauge stainless steel secondary surfaces. A flue tube /turbulator clean out plate is provided. The burner assembly is industrial type which includes ignition electrode, flame sensing rod, and ceramic cone. An air proving switch is provided to prevent operation during loss of combustion or supply air flow. The combustion blower assembly consists of a centrifugal fan powered by a direct drive thermally protected motor. Gas safety controls include an electronic ignition module with 60 second pre -purge cycle and continuous flame sensing capability. The ignition module is microprocessor based and includes operation sequence LED's for monitoring the furnace operation. 2 Stage Gas Heat The firing rate of the unit can be either half fire or the heating nameplate rating of the unit. A sixty second delay between gas valve stages is provided. 100% Exhaust with Statitrac Two centrifugal fans mounted on a common shaft with fixed sheaves. The fan is factory dynamically balanced and tested. Shaft bearings are grease lubricated ball type designed for 200,000 hours average life. Optional extended grease lines allow greasing the bearing from the filter section. Fan motor and fan assembly are mounted on a FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 5 of 41 Fanno Creek Bldg A September 13, 2006 common base. Entire assembly is isolated from the unit by double deflection rubber in shear isolators with motor sizes larger than five horsepower. For both CV and VAV applications, Statitrac, a differential pressure control system, compares the indoor building pressure to the atmospheric pressure. The exhaust fan is turned on and the discharge dampers at the fan outlet modulates when the building pressure exceeds the specified deadband configured in the Rooftop Human Interface Control. All exhaust fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). High Efficiency Filters Filters are two -inch [50.8 mm] high efficiency media type with average dust spot efficiency of 25 -35 percent and an average arrestance in excess of 90 percent when tested in accordance with ASHRAE 52 -76. 0 -100 Percent Economizer Automatically modulating return and outside air dampers assist in the maintaining of the control temperature setpoint to allow "free" cooling. The economizer is equipped with an automatic lockout when the outdoor enthalpy /temperature is not suitable for space temperature control. Minimum position is standard and adjustable with either the Human Interface Control, remote potentiometer, or through the building management system. A spring return actuator insures closure of the outside air dampers during shutdown or power interruption. Mechanical cooling is available to assist the economizing mode. Low leak dampers are standard with a leakage rate of 2.5 percent of nominal airflow of 400 Cfm /ton [189 Us] per ton at a static pressure of 1" [25.8 mm] w.c. Variable Frequency Drive General Description: The AC Drive and all associated optional equipment are UL listed according to Power Conversation Equipment UL 508C and CSA certified. The AC Drive is designed, constructed and tested in accordance with NEMA ICS, NFPA, and IEC standards. The Drive is housed in a metal NEMA 1 enclosure. All standard and optional features are included within the Drive enclosure, unless otherwise specified. The Drive converts incoming fixed frequency three -phase AC power into a variable frequency and voltage for controlling the speed of three -phase AC motors. DC link reactors are provided on both the positive and negative rails of the DC bus equal to 3% impedance to minimize power line harmonics. Full load amp ratings meet or exceed NEC Table 430 -150. The Drive provides full rated output current continuously, 110% of rated current for 60 seconds and 160% of rated current for up to 0.5 second while starting. Isolation is provided between the Drive's power circuitry and control circuitry to ensure operator safety and to protect connected electronic control equipment from damage caused by voltage spikes, current surges, and ground loop currents. Audible motor noise is minimized through the use of an adjustable carrier frequency. Carrier frequency is automatically adjusted to optimize motor and AC Drive efficiencies while reducing motor noise. Operating range, ambient temperature, -10 to 50°C (14 to 104°F), 0 to 95% relative humidity, non - condensing, AC line voltage variation, -10 to +10% of nominal with full output. Default: After 10- second time out the Drive will shut off. Will function normally when the keypad is removed while the AC Drive is running and continue to follow remote commands. AC Drive catches rotating motor operating forward or reverse up to full speed. The AC Drive is rated for 100,000 amperes interrupting capacity (AIC). Includes current sensors on three output phases to detect and report phase loss to the motor. Identifies which of the output phases is low or lost. Continues to operate without faulting until input voltage reaches 300 V AC on 208/230 volt units, 539 V AC on 460 volt units, and 690 volts on 600 volt units. Interface Features Off /Stop and Auto /Start selector switches provided to start and stop the AC Drive and determine the speed reference. On units with bypass, an AC Drive /Off /Bypass Hand selector switch will be provided in the unit control box. In case of an external current overload, a normally closed dry contact will stop the motor whether in DRIVE or BYPASS mode. In DRIVE mode speed reference is provided by a 0 to 10 V DC analog input. The display is programmable to display in 9 languages including English, Spanish and French. The display has four lines, with 20 characters on three lines and eight large characters on one line. The following points are controlled and /or accessible: AC Drive Start/Stop. Speed reference, Fault diagnostics, Meter points to include - Motor power in HP, Motor power in kW, Motor kW -hr, Motor current, Motor voltage, Hours run, DC link voltage, Thermal load on motor, Thermal load on AC Drive and Heatsink temperature. The AC Drive stores in memory the last 10 faults and related operational data. c. Four simultaneous displays are available, frequency or speed, run time, output amps and output power. The following displays are accessible from the keypad. Reference Signal Value, Output Frequency in Hz or percent, Output Amps, Motor HP, Motor kW, kW hour, Output Voltage, DC Bus Voltage, AC Drive Temperature in degrees, and Motor Speed in RPM. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 6 of 41 Fanno Creek Bldg A September 13, 2006 A quick setup menu with factory preset parameters is provided on the AC Drive eliminating the need for macros. A red FAULT light, a yellow WARNING light and a green POWER -ON light are provided. These indications are visible both on the keypad and on the AC Drive when the keypad is removed. The AC Drive includes a standard EIA -485 communication port and capability for future connection to a Modbus communication interface. If the temperature of the AC Drive's heat sink rises to 80°C, the AC Drive automatically reduces its carrier frequency to reduce the heat sink temperature. If the temperature of the heat sink continues to rise the AC Drive automatically reduces its output frequency to the motor. As the AC Drive's heat sink temperature returns to normal, the AC Drive automatically increases the output frequency to the motor and returns the carrier frequency to its normal switching speed. The AC Drive has temperature controlled cooling fans for quiet operation and minimized losses. Adjustments and Factory Default Settings AC Drive carrier frequency is adjustable in steps of not less than 0.1 kHz to allow tuning the AC Drive to the motor. Four, acceleration and four deceleration ramps are provided. Acceleration and deceleration time is adjustable over the range from 0 to 3,600 seconds to base speed. The shape of these curves is automatically contoured to ensure no -trip acceleration and deceleration. Factory Default: The Drive is programmed for an acceleration and deceleration time of 30 seconds. Four current limit settings will be provided. Factory Default: The Drive is programmed for 1 X rated current. If the AC Drive trips on one of the following conditions, the AC Drive will be programmable for automatic or manual reset: under - voltage, over - voltage, current limit and inverter overload. Factory Default: The Drive is programmed for automatic reset. The number of restart attempts is selectable from 0 through infinity and the time between attempts is adjustable from 0 through 600 seconds. Factory Default: 3 attempts, 10 seconds between attempts. After 3 failed restart attempts, the drive automatically reverts to the manual reset mode. An automatic "on delay" may be selected from 0 to 120 seconds. Factory Default: The Drive is programmed for 0 seconds delay. Protective Features Class 10 12t electronic motor overload protection for single motor applications is provided. Protection against input transients, loss of AC line phase, output short circuit, output ground fault, over - voltage, under - voltage, AC Drive over - temperature and motor over - temperature. All faults are displayed in plain English. Protection from AC Drive sustained power or phase loss. Full rated output with an input voltage as low as 90% of nominal. Continuous operation with reduced output with an input voltage as low as 164 V AC for 208/230 volt units, 313 V AC for 460 volt units, and 394 volts for 600 volts units. Semi - conductor rated input fuses to protect power components. A "signal loss detection" circuit senses the loss of an analog input signal such as 4 to 20 mA or 0 to 10 V DC, and is programmable to react as desired in such an instance. Unit Non - Fused Disconnect This switch is non -fused and is located inside the unit control box. An external handle allows power disconnection without having to open the control box door. Economizer Dry Bulb Control Dry bulb temperature control option an outdoor temperature sensor is included for comparing the outdoor dry bulb temperature to a locally adjustable temperature setpoint programmed either at the human interface or remote human interface to determine if outdoor air temperature is suitable for economizer operation. Access Doors Hinged access doors provide easy access to service areas. These access doors feature double wall construction with dual density insulation sandwiched between 18 -gauge galvanized steel panels for strength and durability. Trane Communication Interface Module (TCI) The TCI provides interface to Trane's Integrated Comfort System (ICS), which allows control and monitoring of the rooftop by Tracer building management system. Temperature Thermistor Temperature thermistor is used to communicate temperature changes in either the zone, return air, supply air or outside ambient. Roof Curb Roof mounted curb is 14 -gauge zinc coated steel with a nominal two -inch [50.8 mm] by four -inch [101.6 mm] nailer. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 7 of 41 Fanno Creek Bldg A September 13, 2006 Supply /Return air opening gasket is provided. The curb is manufactured to the National Roofing Contractors Association guidelines and ships non - assembled. The return duct opening location is adjustable using the provided channel. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 8 of 41 N o O 0) ci y ea N N m a E m d 0 co m n T7-1 o v vvv,6vvvvy,vvv„vvvvvvvvvvlvvvv \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \\ - - -... - \M \ \ \ \ \ \ \\ \ \ \ \ \ \\ M% \%\ \ m !o, = :off\ Ai, mu ry r9 \``` 1 \``` 1 u \ - \\ \ \ \ \ \ % \\\\\\\\ \\\\\\\\\ \ \ \ \ , I % \ \ % \\\\\\\\ \ \ \\ , .' • \\ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ % \� "`� - °� // \"`c`�'� /! \```� =�'�U .0 1 !:.:'M \ �J %% c% m m N 0/, V A\\vVy\IVAA\\AVAVAV ,o 40 0 - cl r ' i l , ' i Yi j immnumm�nm�nnr -f i� i� i� i� A N 0 iii ; ',;l ! / / / / / / / / / / / / / / / / / /0 / / /0 /00� It I S- \ �\ IIL !a\�\ !I/i !.�\�\ IIG c A 1 ? L //// / / /I ///////////////////�//1 l 1 \�` l \``` 1 0` „1 ' \� t • ea . 1 � ail \ / / ////II/I/0///I/I/// ////////I// — 3 D / /////////////////////////////// t c ,,,,n m „mmm, m mn, E c -1 1 c E S o O W :ei 4 h m o N It , o 4 N N [! y e, O � M / ( Y N =1 CD E -- E V as m I I Q ~ O 12:: ., C N N v O T o Y CO .y Q / / H d C N a) m 6 ET u_ ii E o J LL ' M n U. N I .. kf Fanno Creek Bldg A September 13, 2006 Unit Dimensions - Commercial Rooftop Air Conditioning Units (Large) Item: Al Qty: 2 Tag(s): RTU -1, RTU -2 ELECTRICAL / GENERAL DATA TONS 90 UNIT OPERATING VOLTAGE RANGE 414 506 UNIT PRIMARY VOLTAGE 460 UNIT HERTZ 60 UNIT PHASE 3 HEATING - PERFORMANCE HEATING - GENERAL DATA HEAT INPUT 1000 GAS INLET PRESSURE MIN 7.00 psi MAX 14 00 psi HEAT OUTPUT 820 Mbh GAS PIPE CONNECTION SIZE 1.1/4' CAPACITY STEPS 2 COMPRESSOR Circuit #1 Circuit #2 NUMBER 3 3 TONS (EACH) (5) 15/15/10 16.3/10.92 kW 15/15/10 16.3/10.9 kW COMPRESSOR RATED LOAD AMPS (EACH) 27 3/18.2 27.3/18 2 LOCKED ROTOR AMPS (EACH) 1781117 178/117 SUPPLY FAN MOTOR NUMBER 2 HORSEPOWER (EACH) 20.0 14.92 kW SUPPLY FAN MOTOR FULL LOAD AMPS 25.5 CONDENSOR FAN MOTOR NUMBER 8 HORSEPOWER (EACH) 1.0 0.75 kW CONDENSOR FAN MOTOR FULL LOAD AMPS 1.8 EXHAUST FAN MOTOR NUMBER 1 HORSEPOWER (EACH) 20.0 14 92 kW EXHAUST FAM MOTOR FULL LOAD AMPS 25.5 s ELECTRIC HEATER ELECTRIC HEATER KW ELECTRIC HEATER FULL LOAD AMPS • FILTERS High efficiency throwaway FURNISHED YES NUMBER P5 RECOMMENDED SIZE 24 X 24 X 2 REFRIGERANT TYPE R - 22 FACTORY CHARGE (CIRCUIT #1) (6) 101.0 lb FACTORY CHARGE (CIRCUIT #2) (6) 101.0 lb Cooling MCA = (1 25 x LOAD 1) + LOAD 2 + LOAD 4 Cooling MOP= (2.25 x LOAD 1) • LOAD 2 • LOAD 4 Cooling FIDE= (1.5 x LOAD 1) a LOAD 2 + LOAD 4 Notes: 1 LOAD 1 =Current of the largest motor (compressor or fan motor); LOAD 2 =Sum of the currents of all remaining motors; LOAD 3 =Current of electric heaters LOAD 4 =Control Power Transformer (90.130 ton units add 6 FL amps for wire sizing formula) 2 For Elecinc Heat MCA, MOP, RDE values, calculate for both cooling and heating modes using the larger value for sizing. (When determining LOADS, the compressors do not operate when the unit is in heating mode) (Heating Load 4 = 12 amp on 200,230 volt units and 9 amps on 460,575 volt units). 3. II selected Max Over Cur is less than the Min Clr Amp, then select the lowest maximum fuse size which is equal to or larger than the Min Cir Amp, provided the selected fuse size does not exceed 800 amps 4. If the selected Recommended Dual Element fuse size is greater than the selected Max Over Cur Protection value, then select the Recommended Dual Element fuse size value to equal the Max Over Protection value. 5 Compressor KW at ARI rating conditions of 80/67.95 6. Refrigerant charge is an approx. value. For a more precise value, see unit nameplate and service instructions. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 10 of 41 Fanno Creek Bldg A September 13, 2006 Unit Dimensions - Commercial Rooftop Air Conditioning Units (Large) Item: Al Oty: 2 Tag(s): RTU -1, RTU -2 TYPICAL ROOF CURB AND BASE PAN DETAIL Unit Base Ships with Curb, / I.Ulting Lug 4' Lonp Feld Installed Gasket ..; C --- - [76 �Im] I 1 1W32' ] -I . ` 140 m] A hi 15mm Y [63mm] 2' X 4' Nailer [50mm u 101 mm] (Famished with Kit) 1- 79132' r . 3 I -7It6' (9mm] (36mm) Root Cult - -2- 13/16' --- (71 mm] TYPICAL PEDESTAL AND BASE PAN DETAIL I Unit Base / Ming Lug 4' Long . ' L li , Pedestal 19/32* x [1mm] i 1 -7/16' [36mm] —2- 13/16' -- 171mm] FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 11 of 41 Fanno Creek Bldg A September 13, 2006 Fan Curve - Commercial Rooftop Air Conditioning Units (Large) Item: Al Qty: 2 Tag(s): RTU -1, RTU -2 r S_HG 13 1 0 uNtSae 41 %WO (aerating Airflow 36100 00 dm / — 50 %WO (aerating Static Pressure 4 49 in H2O (aerating erating RPM 130500 / \ (aerating Brake Horse Power: 40 77 bhp — 60 %vup Altitude 000 _ \ Design Temp. 76 20 F 8 ■ �u06RPM j \ \ Date 9/13)06 O — ' ... N 7 50O c ra .1.,,,,,,g__ '. — 400 R — N _ t300R'.i � - __--4 \ \\ a) _ -- Sao i lk lZ _ 1200 RPM - ' 4 _ 1700 RPM , -- -.4� - t000RPM � as 3 - -- pp/ - 900 RPA: , \ 0 %WO 2 � \ \ \ 1 '� \ t HT _ \� \ \ a 1 a a c 0— 1---1-1 i _ ° ° i t i n i Y l Si l i 1 0 10000 20000 30000 40000 50000 60000 70000 Airflow (cfm) FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 12 of 41 Fanno Creek Bldg A September 13, 2006 Weight, Clearance & Rigging Diagram - Commercial Rooftop Air Conditioning Units (Large) Item: Al Qty: 2 Tag(s): RTU -1, RTU -2 NOTES: 1 The actual weight is stamped on the unit nameplate lk-1111111 2 The weight shown represent tho typical i-, ` unit operating weights 4 for the unit selected. 144�I I ' II'� 41 ,1j[pp Total Weight I 144' Spreader Bar Alo 16050 0 Ib _ Turnbuckle Adjustment Weight Add For Double -Wall RIGGING POINT WEIGHTS I 2 3 4 5 6 7 8 9 10 1550.0 lb 1430 0 lb 1540.0 lb 1420.0 lb 1530.0 lb 1860 0 l 1520.0 lb 1850.0 lb 1510.0 lb 1840 0 lb X / Y 4- / 4- 4' /136' 120 4' 1201136' 2151 4' 215' /136' 309' / 4- 309' /136' 3961 4- 396 /136 - 216- v Clearance Line 96' J 96' n n n 7 2 4 6 10 e low 1 Y 0 73' D 9 5 9 u u u X Center of Gravity 96' 1 Front of Unit CENTER OF GRAVITY AND CLEARANCES 72' FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 13 of 41 Fanno Creek Bldg A September 13, 2006 Accessory - Commercial Rooftop Air Conditioning Units (Large) Item: Al Qty: 2 Tag(s): RTU -1, RTU -2 4 7 RETURN OPENING 1 SUPPLY OPENING ROOFCURB WEIGHT 770 O ItLBS ov oo / r ISOMETRIC VIEW �— - SUPPLY 8400 AIR OPENING RETURN 64 38 AIR 1 OPENING 3 00 2500 r F = 1 88 19.25 84.00 117.31 160 00 l 220 25 25350 f -4500 NOTE: SEE S%HG -IOM -2 FOR SPECIFIC DIMENSIONS AND INSTALLATION TOP VIEW INSTRUCTIONS FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 14 of 41 • r a' 11 d O V 3a; B o TN 01J O (12 0^ Q. I I ''� A a Remove jumper and Install high duct temp N O D t -slat 8./or field supplied device. Contacts -1 3 7 rated 12 MA @ 24 VDC minimum al 3 Remove jumper when field H n supplied external auto /stop . co switch is installed. Contacts O1 WARNING � rated12MA @24VDCminimum. 4 HAZARDOUS VOLTAGE! 537+ 5567 C 0 EME ` DISCONNECT ALL ELECTRIC POWER OPR SWITCH SNITCH EXTER 65TOP ° 0 O INCLUDING REMOTE DISCONNECTS wTCH BEFORE SERVICING. I—��o —4 \0 O to FAILURE TO DISCONNECT POWER i -� '—' I D BEFORE SERVICING CAN CAUSE - 1 C SEVERE PERSONAL INJURY OR 435 .31 434 439 N n DEATH. I i AVERTISSEMENT 17E14 1 CL _ VOLTAGE HASARDEUXI + 409 418 12 Cli 7 DECONNECTEZ TOUTES LES SOURCES 3 , o 403 O i = m ELECTRIQUES INCLUANT LES . 412 a +s I 7 . � Ett DISJONCTEURS SITUES A DISTANCE s .31 +e - -) _ (CI C AVANT D'EFFECTUER L'ENTRETIEN. 9 .17 .3 7 ���JJJ C FAUTE DE DECONNECTER LA SOURCE 7 413 439 i° 1 - - - - - ---, 7 co ELECTRIQUE AVANT D'EFFECTUER 8 414 437 19 1-- H L PEUT ENTRAINER DES 9 415 537 20 BLESSURES CORPORELLES SEVERES o ne 538 21 I Field supplied and installed I G OU LA MORT. t 1 ' 25 '38 a I occupied/unoccupied contacts for 0) 3 J use on units without remote panel 4" 0 CA UT ION <C �B I t y with night setback or TCI. v USE COPPER CONDUCTORS ONLY! r -:_:1 L, UNIT TERMINALS ARE NOT I.,..1 I„ DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. ° OCCUPIED/ FAILURE TO DO SO MAY CAUSE UNOCCUPIED DAMAGE TO THE EQUIPMENT. L IMPORTANTI DO NOT ENERGIZE UNIT UNTIL CHECK -OUT AND START -UP PROCEDURE HAS BEEN COMPLETED DEVICE PREFIX LOCATION CODE AREA LOCATION Cn 1 INSIDE UNR CONTROL BOX N 2 CONDENSER SECTION N ID 3 AIR HANDLE SECTION CF CDD W 4 HEATING SECTION Gt 5 EXTERNAL FIELD MOUNTED DEVICE W O 0 A 0 Note: All wing and components shown dashed to be supplied and installed by the customer in accordance with local electrical codes. co ..-I o 3 a' R D O ri 1 5 . a �N - ca Oc co Eli a N O m -1 3 n z o) 3 rD cfl c■ 5- N ! in 0 WARNING ., XI Q _ VOLTAGE! —I C Cr DISCONNECT ALL ELECTRIC POWER C O O I NCLUDING REMOTE DISCONNECTS = BEFORE SERVICING. O co XI - 0 FAILURE TO DISCONNECT POWER —I rn BEFORE SERVICING CAN CAUSE C n SEVERE PERSONAL INJURY OR . -I DEATH. C A\ AVERTISSEMENT 0. y VOLTAGE HASARDEUXI •'! phi DECONNECTEZ TOUTES LES SOURCES O ELECTRIQUES INCLUANT LES 3 m DISJONCTEURS SITUES A DISTANCE 1 T 3 B m (Q Ja AVANT D L'ENTRETIEN. , .22 .75 ,2 C FAUTE DE DECONNECTER LA SOURCE 2 '90 'TS 13 C 3 ELECTRIQUE AVANT D'EFFECTUER 3 523 525 54 2 . 524 529 55 "') L'ENTRETIEN PEUT ENTRAINER DES Cl) BLESSURES CORPORELLES SEVERES 5 525 530 55 B 525 534 V Cl) OU LA MORT. T 522 532 55 5 5V 53019 -- a 3 CAUTION 9 550 504 20 , -- - ----i v 9 µa 21 m .n USE COPPER CONDUCTORS ONLY! ' 429 22 I UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT. IMPORTANTI DO NOT ENERGIZE UNIT UNTIL CHECK -OUT AND START -UP PROCEDURE HAS BEEN COMPLETED DEVICE PREFIX LOCATION CODE �.„-, AREA LOCATION ca.u 1CATIMS N I INSIDE UNIT CONTROL BOX N 2 CONDENSER SECTION \ Required with TCI Module option. m 3 AIR HANDLER SECTION shielded boosted pair wire. cr 03 to 2 1D 4 HEATING SECTION W OS 5 EXTERNAL FIELD MOUNTED DEVICE - O 0 A p a t Note: AO wiring and Components shown dashed to be suppled and Installed by the customer In accordance with local electrical codes. Fanno Creek Bldg A September 13, 2006 Tag Data - Variable Air Volume Single Duct Terminal Units (Qty: 4) Item Tag(s) Qty Description Model Number B1 VAV1 -1 1 Variable Air Volume Single Duct Terminal VCEF10 B2 VAV1 -2 1 Variable Air Volume Single Duct Termina VCEF10 B3 VAV2 -1 1 Variable Air Volume Single Duct Termina VCEF08 B4 VAV3 -1 1 Variable Air Volume Single Duct Termina VCEF06 Product Data - Variable Air Volume Single Duct Terminal Units All Units Single duct with electric heat Matte faced insulation - 1/2" (13 mm) DDC, controls on /off electric heat control Standard actuator 480/24 volt transformer Disconnect switch Power Fuse 480 volt, 3 phase Magnetic contactors - 24 volt 1st year labor warranty whole unit Item: B1 Qty: 1 Tag(s): VAV1 -1 10" inlet size, 1400 cfm (254mm inlet, 661 Its) Right hand Electric heater kW - 3.0 Stages - 2 - equal Item: B2 Qty: 1 Tag(s): VAV1 -2 10" inlet size, 1400 cfm (254mm inlet, 661 Its) Left hand & /or same side connection (control & /or hot water coil) Electric heater kW - 4.0 Stages - 2 - equal Item: B3 Qty: 1 Tag(s): VAV2 -1 8" inlet size, 900 cfm (203mm inlet, 425 Its) Right hand Electric heater kW - 3.0 Stage -1 Item: B4 Qty: 1 Tag(s): VAV3 -1 6" inlet size, 500 cfm (152mm inlet, 236 Ifs) Right hand Electric heater kW - 2.0 Stage -1 Performance Data - Variable Air Volume Single Duct Terminal Units Tags VAV1 -1 VAV1 -2 VAV2 -1 VAV3 -1 Design cooling airflow (cfm) 1200 1000 600 480 Min cooling airflow (cfm) 360 300 180 144 Valve heating airflow (cfm) 360 540 420 336 Cooling inlet diameter 10" 10" 8" 6" Cooling inlet velocity (ft/min) 2200 1833 1719 2445 APD t@ cooling airflow (in 0.04 0.03 0.05 0.21 H2O) Full load amps (A) 3.61 4.81 3.61 2.41 Min circuit ampacity (A) 4.51 6.01 4.51 3.01 Max fuse size (A) 15.00 15.00 15.00 15.00 Operating weight (lb) 46.0 46.0 38.0 38.0 Coil heating capacity (MBh) 10.24 13.66 10.24 6.83 Room heat loss (MBh) 9.85 13.07 9.79 6.47 Room heating setpoint (F) 70.00 70.00 70.00 70.00 Primary EDB (F) 69.00 69.00 69.00 _69.00 FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 17 of 41 Fanno Creek Bldg A September 13, 2006 Tags VAV1 -1 VAV1 -2 VAV2 -1 VAV3 -1 Unit LAT (F) 95.23 92.31 91.48 87.73 Electric heat kW (kW) 3.00 4.00 3.00 2.00 FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 18 of 41 Fanno Creek Bldg A September 13, 2006 Mechanical Specifications - Variable Air Volume Single Duct Terminal Units Item: B1 - B4 Qty: 4 Tag(s): VAV1 -1, VAV1 -2, VAV2 -1, VAV3 -1 General Unit Information The unit casing is comprised of 22 gauge galvanized steel. Outlet connection is slip and drive. Agency Listing - The unit is UL and Canadian UL listed as a room air terminal unit. UL Control # 9N65. All Trane terminal units are ARI 880 - 98 certified. General Unit Clearance Allow adequate clearance to meet NEC on control box side of unit to meet NEC. A minimum of one and one half duct diameters of straight duct work, upstream of the air inlet connection, should be present for optimum airflow measurement performance. Upstream duct work should be the same diameter as the primary inlet connection. 1/2" Matte - Faced Insulation The interior surface of the unit casing is acoustically and thermally lined with 1/2" 1.50 lb.cu. ft. [24.00 kg. /cu. m.] composite density glass fiber with 4.0 lb. cu.ft. [64 kg. /cu. m.] high density facing. The insulation is UL listed and meets NFPA -90A and UL 181 standards. The insulation R -value is 1.9. All cut edges of insulation are completely encapsulated in metal to prevent erosion. Air Valve Round The air inlet connection is an 18 gauge galvanized steel cylinder sized to fit standard round duct. A multiple point, averaging flow sensing ring is provided with balancing taps for measuring within +/- 5% of unit cataloged airflow. An airflow versus pressure differential calibration chart is provided. The damper blade is constructed of a closed cell foam seal mechanically locked between two 22 gauge galvanized steel disks. The damper blade assembly is connected to a cast zinc shaft supported by self lubricating bearings. The shaft is cast with a damper position indicator. The valve assembly includes a mechanical stop to prevent over stroking. At 4.0" w.g. air valve leakage does not exceed 1% of cataloged airflow. Air Valve Size - 06 Air Valve is 500.0 cfm 6 "inlet. Air Valve Size - 08 Air Valve is 900.0 cfm 8" inlet. Air Valve Size -10 Air Valve is 1400.0 cfm 10" inlet. Electric Heat Coil Factory provided and mounted, UL recognized, resistance open -type heater with airflow switch, a disc -type automatic pilot duty thermal primary cutoff, and manual reset load carrying thermal secondary device. Heater element material is nickel- chromium. The heater terminal box is provided with 7/8" knockouts for customer power supply. Terminal connections are plated steel with ceramic insulators. Heater control access is left hand. Right hand control access is optional. Magnetic Contactor An electric heater 24 volt contact for use with Direct Digital Control (D.D.C.) or Analog Electronic VAV Controls. Power Disconnect Switch (for VCEF) A factory provided interlocking door disconnect switch located on the electric heater control panel. Line Fuse A safety fuse located in the electric heater's line of power to prevent power surge damage to the electric heater for VCEF. For VCCF and VCWF, the fuse is installed on the primary voltage hot leg in a control box. Slip & Drive Connection • _ A slip and drive connection has two straight flanges on the top and bottom, and two drive connections on the left and right sides. This is a standard option on all VAV single duct terminal units. Electric Heat Transformer A 40VA or 75VA transformer will be an integral component of the heater control panel dependent on unit load requirements to provide 24 VAC for controls. D.D.C. Actuator FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 19 of 41 Fanno Creek Bldg A September 13, 2006 Trane 3 wire, 26 GA, 3.4 VA, 1.7 W, 24 VAC, 50/60 Hz floating point control actuator with linkage release button. Running torque is 35 in -lb (4 Nm) minimum and is non - spring return with a 90 second drive time. Travel is terminated by end stops at fully opened and closed positions. An integral magnetic clutch eliminates motor stall. When Trane controls are not provided an integral 3 screw terminal is provided for field wiring. Operating temperature is 32 to 125 degrees Fahrenheit (0 to 50 degrees Celsius). Direct Digital Controller The microprocessor based terminal unit controller provides accurate, pressure independent control through the use of a proportional integral control algorithm and direct digital control technology. The controller monitors zone temperature set points, zone temperature and its rate of change, and valve airflow using a differential pressure signal. Optionally, the controller can monitor either supply duct air temperature or CO2 concentration via appropriate sensors. The controller is provided in an enclosure with 7/8" knockouts for remote control wiring. A Trane zone sensor is required. System Communications The controller is designed to send and receive data from a Tracer Summit or other Trane Controllers, or a Varitrac Central Control Panel. Current unit status conditions and set points may be monitored and /or edited via this data communication feature. The network type is a twisted wire pair serial communication. Override Commands The following override commands may be received by the Unit Control Module (U.C.M.) from the Tracer System. Control Mode, Action, Offset & Commands * Control Mode - Occupied or Unoccupied * Control Action - Heating or Cooling * Control Offset - Enabling Control Offset will increase the cooling temperature setpoint and decrease the heating temperature setpoint by a control offset value. * Drive damper fully open. * Drive damper fully closed. * Drive damper to maximum airflow setpoint. Drive damper to minimum airflow setpoint. * Disable unit heat. * Reset - Enabling the reset function forces the controller and the flow sensor to recalibrate. Editable Set points and Functions Occupied and unoccupied cooling temperature set point (30 °- 100 °F) [-1.1°- 37.8°C] Occupied and unoccupied heating temperature set point (30 °- 100°F) [ -1.1 °- 37.8°C] Maximum flow set point (10- 100% of unit equivalent cataloged airflow) Minimum heating and cooling flow set point (0, 10- 100% of unit equivalent cataloged airflow) Cooling set point low and high limit Low (30 °- 100°F) [-1.1°- 37.8°C] High (30 °- 102 °F) [-1.1°- 37.8°C] Heating set point high and low limit (30 °- 100 °F) [-1.1°- 37.8°C] Hot water valve drive time Air valve drive time Fan Control Offset - determines at what point a parallel fan is energized. This can be a function of temperature (degrees above heating set point) or primary airflow Series Fan Configuration - allows series fan powered to shut off fan and close air valve when unit is unoccupied. Fan will operate in unoccupied mode if reheat is active. Local heating flow set point enable /disable and set point Analog input mode - auxiliary temperature sensor or CO2 detector Binary input mode - generic or occupancy detector Zone temperature, auxiliary temperature, and zone set point calibration corrections (± 10 ° F) [± -12°C] Flow measurement calibration correction (60- 150 %) Additional Status Information Available Active cooling set point Active heating set point Current unit primary airflow Current zone temperature Reheat status (on /off) FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 20 of 41 Fanno Creek Bldg A September 13, 2006 Fan status (on /off) Calibration status (calibrating /not calibrating) Auxiliary air temperature (if unit has auxiliary temperature sensor) Not available if CO2 sensor used. CO2 concentration (if unit has CO2 sensor) Not available if auxiliary temperature sensor used. Ventilation ratio BIP state Failure indicators • Temperature sensor failures • Flow Sensor failure • Local zone sensor set point failure DDC Sequence of Operation The unit controller continuously monitors the zone temperature against its set point and varies the primary airflow as required to meet zone set points. Airflow is limited by minimum and maximum airflow set points. DDC Controls Option DD04 Basic Operation: On /Off Staged Electric Heat (Normally Open Outputs) (DDC /UCM) A voltage signal from the zone sensor indicates the zone temperature is used by the unit controller to determine an error from the set point. This error, as well as primary flow differential pressure, is used to determine damper position within minimum and maximum cooling airflow set points. As the zone temperature drops to the heating set point, primary airflow is controlled to minimum heating flow set point. Staged electric heat is energized. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 21 of 41 Fanno Creek Bldg A September 13, 2006 Unit Dimensions - Variable Air Volume Single Duct Terminal Units Item: B1 Qty: 1 Tag(s): VAV1 -1 - — 10' --► F 2 3/4' CONTROL BOX ELECTRIC HEATER CONTROLS AREA � AR VA VE s ; /2 . A AIR FLOW ACTUATOR \ . 431/2' 26' Customer Notes // 1 V 1. Air Inlet is centered in unit front panel. SLIP & DRIVE — 2. Slip & Drive discharge outlet on heater CONNECTION standard. a 15 1l2' a 3 Allow 45' of straight duct downstream of unit before first runout & inside of the duct should be equal discharge size. (AxB) TOP VIEW 4. For electric heater access, side hinged door must have minimum distance per NEC or local code. 5. Knockouts for power supply provided 20' p in top & bottom of terminal box. 14- 6. Coils are provided without internal insulation. If the unit is to be installed in a location with high humidity, external insulation around the heating coil should be installed as — required 131/2" 12' ! B4" t Approximate Dry Weight 46.0 lb Weight reflected may vary s5 Ibs(2 27kgs) based upon options selected BACK VIEW FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 22 of 41 Fanno Creek Bldg A September 13, 2006 Unit Dimensions - Variable Air Volume Single Duct Terminal Units Item: B2 Oty: 1 Tag(s): VAV1 -2 2 3/4' ' ' 10' 45 1/2 D ELECTRIC HEATER CONTROLS AREA CONTROL BOX\ 4' ARVALVE 612" ACTUATOR AIR FLOW 0110 0 0 43 1/2' 26' Customer Notes 1. Air Inlet is centered in unit front panel 2. Slip & Drive discharge outlet on heater standard. 5'—fl 3. Allow 46' of straight duct downstream of unit before first runout & inside of the duct should be equal discharge size. (AxB) � — 15 1/2' CONNECTION SLIP 8 DRIVE 4. For electric heater access, side TOP VIEW hinged door must have minimum distance per NEC or local code. 5. Knockouts for power supply provided In top 8 bottom of terminal box 20* 6. Cods are provided without internal insulation. II the unit is to be installed in a location 14' with high humidity, external insulation around the heating coil should be installed as required 4 — 8 1/4• a 12' 13 1/2 Approximate Dry Weight 46.0 lb Weights reflected may vary ±5.0 lb based upon options BACK VIEW selected. FLO = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 23 of 41 Fanno Creek Bldg A September 13, 2006 Unit Dimensions - Variable Air Volume Single Duct Terminal Units Item: B3 Qty: 1 Tag(s): VAV2 -1 < 8' —y r 2 1/4' CONTROL BOX Q 1/2' — • 4' A ELECTRIC HEATER CONTROLS AREA / VALVE 61/2 - AIR j FLOW ACTUATOR Olt . 43 1/2' 28' Customer Notes 1. Air Inlet is centered in unit front panel V 2. Slip 8 Drive discharge outlet on heater standard. SLIP 8 DRIVE 3. Allow 48' of straight duct downstream 1/2 —�i CONNECTION - 12 1/2' of unit before first nlnout 8 inside of the duct should be equal discharge size. (AxB) TOP VIEW 4 For electric heater access, side hinged door must have minimum distance per NEC or local code. 5. Knockouts for power supply provided in top 8 bottom of terminal box. 6 Cods are provided without internal insulation. If the unit is to be installed to a location — with high humidity, external insulation around the heating cod should be Installed as required 11 1/2' 10' G 8 1/4' 1 _1 Approximate 36.0 lb Dry Weight Weight reflected may vary BACK VIEW ±5 Ibs(2.27kgs) based upon options selected. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 24 of 41 Fanno Creek Bldg A September 13, 2006 Unit Dimensions - Variable Air Volume Single Duct Terminal Units Item: B4 Qty: 1 Tag(s): VAV3 -1 - - 2 3/4' ONTROL BOX • �6'� X51 /2•--a AIR ELECTRIC HEATER VALVE ili ONTROLS AREA 612' AIR FLOW ACTUATOR V ?. 41% 45 12' 31 Customer Notes 1 Air Inlet is centered in unit front panel. 2. Slip 8 Drive discharge outlet on heater standard. 3. Allow 48' of straight duct downstream SLIP & DRIVE — 5•—m of unit before first runout 8 inside of the CONNECTION 11 12 ') duct should be equal discharge size (AxB) 4. For electric heater access, side hinged door must have minimum distance TOP VIEW per NEC or local code. 5. Knockouts for power supply provided 18• .I in top 8 bottom of terminal box 6 ds vieit n II Co tha un it is pro to be dd installed whout m a ternal location insulation \ with high humidity, external Insulation around the heating coil should be installed as required. 9 1/2' 8' B 8 1/4' • Approximate 3801b Dry Weight BACK VIEW Weight reflected may vary :5 lbs(2.27kgs) based upon options selected. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 25 of 41 Fanno Creek Bldg A September 13, 2006 Field Wiring - Variable Air Volume Single Duct Terminal Units Item: B1 - B4 Qty: 4 Tag(s): VAV1 -1, VAV1 -2, VAV2 -1, VAV3 -1 HEATER STAGE 24VAC 60HZ CONTACTOR(S) NEC CLASS -2 B OPTIONAL CONTROL CIRCUIT TRANSFORMER LOAD. I I r TB32 7 co lb - I (WITTHOU ` 1 T HEAT) T83.I 1 TE3.3 I I /� � TBI 1 I 1 T82.5 -— -— i .----- 1 —A T M I I ` 1 1 1 1 1 TBI11 1 1 1 1 1 T82.11 d I 1 1 ( 1 11 I : g In 1 6666666 2 R 2 > E1 I 1 2 1 2 3 1 2 n - @ Tel TB2 TB3 a > o I DIGITAL If g I ZONE SENSOR 1 OPTIONAL FIELD L INSTALLED DIGITAL ZONE SENSOR J I 1 I TB26 TB3 I 1 I I 1 I TB25 Ta72 1 I I I I I 1 Tt1 1 I r I J I 66 I I I 5 4 3 2 I r I ZONE SENSOR '�tI s�r�' J1 O O O O O O I I 7 � W/ COMM JACK SLJ L ACT i REMOTE MTD NIP GND 24V ADDRESS D.D.0 \U.0 M 1 OPTIONAL FIELD J3 SWITCH CONTROL BOARD o L INSTALLED ZONE SENSOR J o L BRIE E _ B r I ; - (TBL1124V I 24V _ _ _ y �yy � y _ 11' CO2 ♦ (TB3.6) GND I Q I° K K i� Fa T G❑ l 20 G S 00 i SENSOR GND D - _ _ O2 _ 1 OUT V - (TB }51 NCO2 _ E AICO2 GND 1 1 II I I I OPTIONAL FIELD INSTALLED I II II I L CO2 SENSOR J I I I I I a1 a1 51 I 1 r T133.5 , r TB34 I I 0 1 I I I I __.—,,---J I I I SHIELDED TWISTED PAIR I / I I COMMUNICATIONS WIRING � — � I I OPTIONAL FACTORY INSTALLED WIRELESS OPTIONAL FIELD INSTALLED r , L. AUK TEMP SENSOR J r 8L OPTIONAL — — — FACTORY INSTALLED 1 _ _ Y WIRELESS 7 I I _ _ — (TBa .- , • CDMMQNI_ — I I RB4I)BP V BK QdJNC GQNT — ITB1 �12�DC 24VAC B 1 444444 I — — — — NOT CONVECTED I ,4I 6' I OPTIONAL FIELD INSTALLED L OCCUPANCY SENSOR J GND 24V VV550 Board ,,WARNING L J HAZARDOUS VOLTAGE, DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH ® CAUTION Customer Notes: USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF 1. Factory Installed. CONDUCTORS. _ — Installed by others. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 26 of 41 Fanno Creek Bldg A September 13, 2006 Field Wiring - Variable Air Volume Single Duct Terminal Units Item: B1 - B4 Qty: 4 Tag(s): VAV1 -1, VAV1 -2, VAV2 -1, VAV3 -1 NOTE BALANCED LINE VOLTAGE REFERS TO AN EQUAL AMP LOAD ON 3 HOT WIRES L1 =L2 =L3 480 Volt, 3 Phase L3 L2 L1 I I I —� I I I I I I I I I bid GI Heater Controls Wrong FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 27 of 41 Fanno Creek Bldg A September 13, 2006 Tag Data - Variable Air Volume Fan Powered Terminal Units (Qty: 14) Item Tag(s) Qty Description Model Number C1 FPB1 -1, FPB1 -4, 6 VAV Fan Powered Terminal Units VPEF1003SQ FPB2 -1, FPB2 -4, FPB3 -1, FPB3 -4 C2 FPB1 -2, FPB1 -3, 6 VAV Fan Powered Terminal Units VPEF1003SQ • FPB2 -2, FPB2 -3, FPB3 -2, FPB3 -3 C3 FPB1 -5 1 VAV Fan Powered Terminal Units ( VPEF0803SQ FP ) C4 FPB1 -6 1 VAV Fan Powered Terminal Units ( VPEF0803SQ FP) Product Data - Variable Air Volume Fan Powered Terminal Units All Units Parallel with electric heat 03 super quiet fan 1/2" [13mm] matte faced insulation Flanged connection 277/60/1 motor voltage Single speed motor w/ SCR DDC with on /off electric heat control Power fuse 480 volt, 3 phase 2 stages of heat - equal increments 24 volt magnetic contactors Disconnect switch Electric heater air flow switch 1st year labor warranty - whole unit Item: Cl Qty: 6 Tag(s): FPB1 -1, FPB1 -4, FPB2 -1, FPB2 -4, FPB3 -1, FPB3 -4 10" (254 mm) inlet size Right hand connection 6.0 kilowatt Item: C2 Qty: 6 Tag(s): FPB1 -2, FPB1 -3, FPB2 -2, FPB2 -3, FPB3 -2, FPB3 -3 10" (254 mm) inlet size Left hand connection 6.0 kilowatt Item: C3 Qty: 1 Tag(s): FPB1 -5 8" (203 mm) inlet size Left hand connection 3.0 kilowatt Item: C4 Qty: 1 Tag(s): FPB1 -6 8" (203 mm) inlet size Right hand connection 3.0 kilowatt Performance Data - Variable Air Volume Fan Powered Terminal Units FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 28 of 41 Fanno Creek Bldg A September 13, 2006 Tags FPB1 -1, FPB1 -5, FPB1 -4, FPB1 -6 FPB2 -1, FPB2 -4, FPB3-1, FPB3 -4, FPB1 -2, FPB1 -3, FPB2 -2, FPB2 -3, FPB3 -2, FPB3 -3 Design cooling airflow (cfm) 1200 580 Min cooling airflow (cfm) 360 174 Valve heating airflow (cfm) 360 100 Cooling inlet diameter (in) 10.000 8.000 Cooling inlet velocity (ft/min) 2200 1662 APD @ cooling airflow (in H2O) 0.05 0.08 Fan airflow (cfm) 480 306 Downstream SP (in H2O) 0.50 0.50 Fan TSP (in H2O) 0.51 0.50 % of fan range ( %) 34.00 8.00 Fan power (hp) 0.333 0.333 Plenum EAT (F) 72.00 72.00 Primary EDB (F) 60.00 60.00 Operating weight (lb) 113.0 112.0 Unit heating airflow (cfm) 840 406 Coil heating capacity (MBh) 20.49 10.24 Room heat loss (MBh) 17.63 9.82 Room heating setpoint (F) 70.00 70.00 Coil EAT (F) 66.86 69.04 Unit LAT (F) 89.34 92.30 Coil LAT (F) 89.34 92.30 Full load amps (A) 8.82 5.21 Min circuit ampacity (A) 11.02 6.51 Max overcurrent protection (A) 15.00 15.00 Electric heater kW (kW) 6.00 3.00 FLD = Furnished by Trane I Installed by Others Trane Equipment Submittal Page 29 of 41 Fenno Creek Bldg A September 13, 2006 Mechanical Specifications - Variable Air Volume Fan Powered Terminal Units Item: C1 - C4 Qty: 14 Tag(s): FPB1 -1, FPB1 -4, FPB2 -1, FPB2 -4, FPB3 -1, FPB3 -4, FPB1 -2, FPB1 -3, FPB2 -2, FPB2 -3, FPB3 -2, FPB3 -3, FPB1 -5, FPB1 -6 General Unit Information Casing - The unit casing is 22 gauge galvanized steel. Outlet duct connection is flanged. Total metal encapsulation of all insulation edges. Hanger Brackets provided. Side access is provided. • Filter - A filter is provided on the plenum inlet. Agency Listing - UL and Canadian UL listed as environmental air terminal unit. UL Control #9N65. All Trane terminal units are ARI 880 -98 certified. General Unit Clearance Leave a minimum of 36" on control box side of unit for adequate service access. Allow at least 12" on remaining sides for unit clearance. A minimum of one and one half duct diameters of straight duct work, upstream of the air inlet connection, should be present for optimum airflow measurement performance. Upstream duct work should be the same diameter as the primary inlet connection. 1/2" Matte - Faced Insulation The interior surface of the unit casing is acoustically and thermally lined with 1/2 ", 1.8 lb /cu. ft composite density glass fiber with high density facing. The insulation is UL listed and meets NFPA -90A and UL 181 standards. All insulation options will meet the 25/50 smoke developed and flame spread rating (per ASTM E 84 and UL 723 and CAN /ULC S102 -M88) Meets NFPA- 90B. The insulation R -value is 1.9. All cut edges of insulation are completely encapsulated in metal to prevent erosion. Air Valve & Fan Description (Parallel) (Series) The air inlet connection is an 18 gauge galvanized steel cylinder sized to fit standard round duct. A multiple point, averaging flow sensing ring is provided with balancing taps for measuring airflow within +/- 5% of unit cataloged airflow. Also provided with each unit is a calibration chart indicating airflow versus flow sensor pressure differential. The damper blade is constructed of a closed cell foam seal mechanically locked between two 22 gauge galvanized steel disks. The damper blade assembly is connected to a cast zinc shaft which rotates in a self lubricating bearing. The shaft is cast with a damper position indicator. The valve assembly includes a mechanical stop to prevent over stroking. Air valve leakage <1% at 4 ". 0803SQ Air Valve /Fan Combination Size (Parallel) 8" Inlet designed for up to 900.0 cfm. Fan is 1100.0 cfm for Std Motor and 1085.0 cfm for ECM Motor. 1003SQ Air Valve /Fan Combination Size (Parallel) 10" Inlet designed for up to 1400.0 cfm. Fan is 1100.0 cfm for Std Motor and 1085.0 cfm for ECM Motor.. Motor Single Speed, direct drive induction, permanent split capacitor type. Thermal overload protection provided. Motors will be designed specifically for use with an open SCR which is standard. Motors will accommodate anti - backward rotation at start up. Motor and Fan assembly are isolated from terminal unit. Transformer The 50 VA transformer is factory mounted in the fan control box to provide 24 VAC for controls. Fuse Any electric heat unit with a calculated MCA greater or equal to 30 will have a fan fuse provided. SCR- Variable Fan Speed Control Switch The SCR speed control device allows the operator infinite fan speed adjustment so the fan output may be modified to achieve exact CFM requirements. Electric Heat Coil Factory provided and mounted. UL recognized, resistance open -type heater, a disc -type automatic thermal primary safety device and manual reset load thermal secondary device. Heater element material is nickel- chromium. The FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 30 of 41 Fanno Creek Bldg A September 13, 2006 heater terminal box is provided with 7/8" knockouts for customer power supply. Terminal connections are plated steel with ceramic or phenolic insulators. All fan - powered units with electric reheat are single -point power connections. For 480 volt 3 phase and 575 volt 3 phase heaters a 4 wire (includes neutral) power supply is required. Electric Heat Coil Factory provided and mounted. Resistance open -type heater, a disc -type automatic thermal primary safety device and manual reset load thermal secondary device. Heater element material is nickel- chromium. The heater terminal box is provided with knockouts for customer power supply. Terminal connections are plated steel with ceramic or phenolic insulators. All fan - powered units with electric reheat are single -point power connections. For 480 volt 3 phase and 575 volt 3 phase heaters a 4 wire (includes neutral) power supply is required. Magnetic Contactor An electric heater 24 volt contact for use with Direct Digital Control (D.D.C.) or Analog Electronic VAV Controls. Power Disconnect Switch (for VSEF & VPEF) A factory provided interlocking door disconnect switch located on the electric heater control panel. Airflow Switch An air pressure device designed to disable the heater when the unit fan is off. Power Fuse A safety fuse located in the electric heater's line of power to prevent power surge damage to the electric heater. Flanged Connection A rectangular opening on the unit discharge to accept a 90 degree flanged duct work connection. D.D.C. Actuator Trane 3 wire, 26 GA, 3.4 VA, 1.7W, 24 VAC, 50/60 Hz. with floating point control actuator with linkage release button. Running torque is 35 in -lb minimum and is non - spring return with 90 second drive time. Travel is terminated by end stops at fully opened and closed positions. An integral magnetic clutch eliminates motor stall when Trane controls are not provided. An integral 3 screw terminal is provided for field wiring. Operating temperature 32.0 F to 125.0 F. Direct Digital Controller • The microprocessor based terminal unit controller provides accurate, pressure independent control through the use of a proportional integral control algorithm and direct control technology. The controller monitors zone temperature set points, zone temperature and its rate of change, and valve airflow, using a differential pressure signal. Optionally, the controller can monitor either supply duct air temperature or CO2 concentration via appropriate sensors. The controller and pressure transducer are installed and factory wired in an enclosure with 7/8" knockouts for remote control wiring. A Trane zone sensor is required. System Communications The Controller is designed to send and receive data from a Central Control Panel or other Tracer family products, or a Varitrac CCP. Current unit status conditions and set points may be monitored and /or edited via this data communication feature. The network type is a twisted wire pair serial communication. Override Commands The following override commands may be received by the Unit Control Module (U.C.M.) from the Tracer System. Control Mode, Action, & Offset (1 thru 12) 1. Control Mode - The U.C.M. Control Mode may be edited from occupied to unoccupied to accommodate night setback/setup. 2. Control Action- The Control Action may be edited from cooling to heating, changing the primary air damper to a heating source. This will accommodate a cooling /heating changeover system. 3. Control Offset- Enabling Control Offset will increase the cooling temperature set point and decrease the heating temperature set point by a control offset value stored at the U.C.M. This function facilitates demand limiting in the occupied mode. 4. Drive damper fully open. 5. Drive damper fully closed. 6. Drive damper to maximum airflow set point. 7. Drive damper to minimum airflow set point. 8. Disable unit fan. 9. Disable unit heat. 10. Reset- Enabling the reset function forces the controller and the flow sensor to recalibrate. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 31 0141 Fanno Creek Bldg A September 13, 2006 11. Programmable hot water valve drive time. 12. Programmable air valve drive time. Following Unit Set points The following unit set points reside in the U.C.M. in nonvolatile memory. These set points are editable from the Command Unit or Tracer via the communications link. Set points in Nonvolatile Memory (1 thru 8) 1. Occupied cooling temperature set point 60.0 F - 80.0 F. 2. Occupied heating temperature set point 60.0 F - 80.0 F. 3. Unoccupied cooling temperature set point 60.0 F - 100.0 F. 4. Unoccupied heating temperature set point 30.0 F - 100.0 F. 5. Minimum cooling flow set point (0, 10 - 100% of unit equivalent cataloged airflow). 6. Minimum heating flow set point (0, 10 - 100% of unit equivalent cataloged airflow). 7. Maximum flow set point (0,10 - 100% of unit equivalent cataloged airflow). 8. Fan Control Offset - This determines at what operating point the fan in a parallel fan powered unit is energized. This can be specified as a function of temperature, degrees above heating set point, or primary airflow. 0.0 F - 10.0 F or 0, 10 - 100% of unit equivalent cataloged airflow). Set points in Nonvolatile Memory (9 Thru 15) 9. Heating Set point Offset - This determines at what point the 1st. stage of reheat turns on. Expressed in degrees below cooling set point, only applicable when local thumb wheel is enabled. 10. Zone temperature, auxiliary temperature, and zone set point calibration corrections ( +/- 10.0 F). 11. Flow measurement calibration correction (50 - 150 %). 12. Cooling Set point Low Limit - Applies low limit to programmed occupied cooling set point or zone sensor cooling set point (30.0 F - 100.0 F). 13. Heating Set point High Limit - Applies high limit to programmed occupied heating set point or zone sensor heating set point (30.0 F - 100.0 F). 14. RTD / Thermistor - Determines what type of zone temperature sensor will be used. 15. Occupied and Unoccupied Outside Air Requirements - Determines the percent of outdoor air required in the zone for air quality requirements. Set points in Nonvolatile Memory (16 thru 21) 16. Series Fan Configuration- allows option of series fan powered box to shut off fan and close air valve when unit is unoccupied. Fan will operate in unoccupied mode if reheat is active. 17. Heating set point low limit. 18. Cooling set point high limit. 19. Local heating flow set point enable /disable & set point. 20. Auxiliary analog input mode select for either auxiliary temperature sensor or CO2 detector. 21. Binary input mode select for either generic or occupancy detector. Additional Status Information (1 thru 8) In addition to the above set points, the following status information can be transmitted to the Command Control Unit and Tracer. 1. Active cooling temperature set point. 2. Active heating temperature set point. 3. Current unit primary airflow. 4. Current zone temperature. 5. Re -heat status (On /Off). 6. Auxiliary Air Temperature - Available only if the unit has an auxiliary temperature sensor. 7. Failure Indicators - The U.C.M. will indicate the following: *Temperature Sensor Failure *Flow Sensor Failure *Local Zone Sensor Set point Failure 8. Ventilation Ratio. Additional Status Information (9 thru 12) 9. Fan Status (on /off) 10. Calibration Status (calibrating /not - calibrating) 11. BIP state 12. CO2 Concentration- available only if the unit has an auxiliary CO2 sensor. This mode and auxiliary air temperature are mutually exclusive. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 32 of 41 Fanno Creek Bldg A September 13, 2006 DDC Sequence of Operation The unit controller continuously monitors the zone temperature against its set point and varies the primary airflow as required to meet zone set points. Airflow is limited by minimum and maximum airflow set points. Parallel Unit Fan Energization As the zone temperature reaches the heating set point, the microprocessor controls airflow to the heating temperature set point and energizes the auxiliary fan when necessary. At or below the heating set point, reheat is energized. The heating minimum airflow set point is factory set, field adjustable, and is separate from the cooling minimum set point. Parallel unit fan energization is a function of primary airflow or zone temperature. 1. Primary Airflow - The fan energizes when primary airflow drops below the fan set point airflow. The fan automatically starts when the zone temperature drops to the heating temperature set point. 2. Zone Temperature - The fan energizes when the zone temperature drops to a selectable number of degrees above the heating temperature set point. Controls Option DD04 Basic Operation: On /Off Staged Electric Heat (Normally Open Outputs) (DDC /UCM) (Parallel Units) A voltage signal from the zone sensor indicating zone temperature is used by the unit controller to determine an error from the set point. This error, as well as primary flow differential pressure, is used to determine damper position within minimum and maximum cooling airflow set points. As the zone temperature reaches the heating set point, primary airflow is controlled to the minimum heating flow set point. The fan operation is intermittent in both modes and is energized as the first stage of heat. The staged electric heat is energized for unit reheat. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 33 of 41 Fanno Creek Bldg A September 13, 2006 Unit Dimensions - Variable Air Volume Fan Powered Terminal Units Item: C1 City: 6 Tag(s): FPB1 -1, FPB1 -4, FPB2 -1, FPB2 -4, FPB3 -1, FPB3 -4 Unit Size VPEF1003S0 Nominal 10' DIa. x 4' Depth Valve Size 8 Depth Nominal 03S0 Fan 11#1A Fan Size Filler Size 16' x 20' z 1' (OTY 1) P0• 4104' 5 ' 111111111 s - AIRFLOW 16.50 %1130 U 1 321/2' NOTES: TOP VIEW 1. Allow a minimum 6' plenum inlet clearance for un-ducted installations 22' 2. Filter is secured in filler frame located in unit inlet a 3. For Motor access, remove bottom screws on HEATER hanger brackets to slide panel as shown in drawing PANEL SLIDES 6' 4. See Installation Documents for exact hanger FOR MOTOR ACCESS \!1 5' bracket location 5. Alr valve centered between top & bottom panel. AIRFLOW DISCHARGE OUTLET 6 Heating coil un- insulated. External insulation may be field supplied and installed as required. 7. All high & low voltage controls have same -side NEC jumpback clearance. 8. Allow 48' of straight duct downstream of unit before first runout and inside of the duct should be equal discharge size. 9 Terminal box access door is side hinged Allow for 40' clearance. 10 A 4 wire power supply required for 480\3 & 575\3 d p single point connection units 17 1/2' 1s' �-- 20• Approximate 113.0 lb Dry Weight DISCHARGE VIEW Weights reflected may vary ±5.0 lb based upon options selected. FLO = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 34 o141 Fanno Creek Bldg A September 13, 2006 Unit Dimensions - Variable Air Volume Fan Powered Terminal Units Item: C2 Qty: 6 Tag(s): FPB1 -2, FPB1 -3, FPB2 -2, FPB2 -3, FPB3 -2, FPB3 -3 Unit Size VPEF1003SQ Nominal 10' Da x 4' Depth IIIIIIIII Valve Size 8 Depth Nominal 0350 Fan 3 a• ?•�• Fan Size •> s • ■ �•� •' + 4 tn ■ Filter Size 16' x 20' x 1' (OTY 1) <•` a3 .? ��,? 4"* \O TOP VIEW 20' ► a•10-10•—t1 s• I Z r NOTES A IRFLOW 1 Allow a minimum 6' plenum inlet clearance is so xx l p o for un- ducted installations. co 2. Filter is secured in frame located in unit let. 1/2' 3. a oor ac rottom scre ha brack to slide panel a s h o wn in dra m 4 See Installation Documents emove b for exact hanger 5. Air valve centered between top 8 bottom panel. 3 br acket M lowOon. 22' ig 32 r 6 Heating coil un- insulated. External insulation may HEATER be field supplied and installed as required. 7 As high 8 low voltage controls have same - side PANEL SLIDES NEC jumpback clearance. FOR MOTOR ACCESS 6. Allow 48' of straight duct downstream of AIRFLOW unit before first runout and inside of the duct should DISCHARGE OUTLET be equal discharge sae. 9 Terminal box access door is side hinged. Allow for clearance. 10 A 4 wire power supply required for 480/3 8 575■3 5• 1 I.e 40' : I single point connection units. 1 16' 17 1/2' I Approximate 113.OIb I _2_ Dry Weight Weights reflected may vary 20. -1 ±5.0 lb based upon options DISCHARGE VIEW selected. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 35 0141 Fanno Creek Bldg A September 13, 2006 Unit Dimensions - Variable Air Volume Fan Powered Terminal Units Item: C3 Qty: 1 Tag(s): FPB1 -5 Unit Sue VPEF0803S0 • Nominal 8' Dia a 4' Depth Valve Size & Depth Nominal 0350 Fan Fan Size i• >r�.• ae nya.yr j s:. ‘ W‘.,' : Eller Size 16'x20'x 1'(OTy 1) c; ∎ - U ' t:a„kr., 1 ,� TOP VIEW • 20' i F1 _ i NOTES AIRFLOW � 16 50 x 11 30 I 1. Allow a minimum 6' plenum inlet clearance rV y for un -ducted Installations. 2. Filter is secured in filter frame located in unit inlet. 12 . 3 For Motor access, remove bottom screws on hanger brackets to slide panel as shown in drawing m 4. See Installation Documents for exact hanger hrackel fixation. 2 22' 5 Air valve centered between top & bottom panel. I r 6. Heating cod un- insulated External insulation may HEATER be field supplied and installed as required. 0 7. All high & low voltage controls have same -side \!/ PANEL SLIDES NEC jumpback clearance. FOR MOTOR ACCESS 8 Allow 48' of straight duct downstream of AIRFLOW unit before first runout and inside of the duct should DISCHARGE OUTLET be equal discharge size. 9. Terminal box access door is side hinged. Allow for clearance. 10 A 4 wire power supply required for 480\3 & 57513 5' 1 h 40' single point connection units . I 16" 17 2' i / Approximate 112.0lb Dry Weight 1600tb Weights reflected may vary 2e" ±5.0 lb based upon options DISCHARGE VIEW selected. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 36 of 41 Fanno Creek Bldg A September 13, 2006 Unit Dimensions - Variable Air Volume Fan Powered Terminal Units Item: C4 Oty: 1 Tag(s): FPB1 -6 unit Size VPEF0803SQ • Nominal 8" Dia. x 4" Depth Valve Size 8 Depth Nominal 0350 Fan 114411111 / Fan Size Filter Size 16'x20'x 1'(OTY 1) %/' . 20 " i c)-8*—c.4' s E 0 7 F IIIIIIII ` AIRFLOW I in 501(1130 V 1 . 32 1/2' NOTES TOP VIEW M 1 Allow a minimum 6' plenum inlet clearance 7 for un- ducted installations. g 22' 2. Filter is secured in filter frame located in unit inlet. a g I x 3. For Motor access, remove bottom screws on V l HEATER hanger brackets to slide panel as shown in drawing PANEL SLIDES 6' 1 4. See Installation Documents for exact hanger FOR MOTOR ACCESS vl 5' bracket location. 5. Air valve centered between top 8 bottom panel AIRFLOW DISCHARGE OUTLET 6. Healing coil un- insulated. External Insulation may be field supplied and installed as required. 7. All high 8 low voltage controls have same -side NEC jumpback clearance 8. Allow 48' of straight duct downstream of unit before first runout and inside of the duct should be equal discharge size. 9. Terminal box access door is side hinged Allow for 1 . 40' I clearance. 10 A 4 wire power supply required for 480'.3 8 57513 Q ❑ } single point connection units 17 1/2' 16' I' 1 .- 2 Cr --'1 Approximate 112.0lb Dry Weight DISCHARGE VIEW Weights reflected may vary ±5.0 lb based upon options selected. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 37 0141 Fanno Creek Bldg A September 13, 2006 Accessory - Variable Air Volume Fan Powered Terminal Units Item: C1 - C4 Qty: 14 Tag(s): FPB1 -1, FPB1 -4, FPB2 -1, FPB2 -4, FPB3 -1, FPB3 -4, FPB1 -2, FPB1 -3, FPB2 -2, FPB2 -3, FPB3 -2, FPB3 -3, FPB1 -5, FPB1 -6 Pa in. wg Parallel Fan Size 03SCa --PSC 199 0.80 1 , , 1 \\ I 174 0.70 - -- i . I -- - -- • ■ N. ___L____' \ \ 150 0.60 — \ — i ' — -- +- - - - -! - - - \ • \ - N -- C • \ --- - - 125 0.50 — E » \ — i - - E� \ \ _ I a. • 100 0.40 -- /3 r- \ \ _ ! _ - -- \ \ (n — • \ --- --- --- y • • E 75 0.30 — • \• \\ C O • \ '5 50 0.20 — \. \ - I 25 0.10 \ 200 300 400 500 600 700 800 900 1000 1100 1200 1300 Cfm 94 142 189 236 283 330 378 425 472 519 566 814 Us Airflow FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 38 of 41 Fanno Creek Bldg A September 13, 2006 Field Wiring - Variable Air Volume Fan Powered Terminal Units Item: C1 - C4 Oty: 14 Tag(s): FPB1 -1, FPB1 -4, FPB2 -1, FPB2 -4, FPB3 -1, FPB3 -4, FPB1 -2, FPB1 -3, FPB2 -2, FPB2 -3, FPB3 -2, FPB3 -3, FPB1 -5, FPB1 -6 480 Volt, 3 Phase, 4 wire L3 L2 L1 N I I I I I I I I I I I I I I I I I I I T Heater Control Winng A WARNING HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH A CAUTION USE COPPER CONDUCTORS ONLYI UNIT TERMINALS ARE NOT DESIGNED Customer Notes: TO ACCEPT OTHER TYPES OF 1. Factory installed. CONDUCTORS. FAILURE TO DO SO MAY CAUSE — — — — Optional or installed by others. - DAMAGE TO THE EQUIPMENT. FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 39 of 41 Fanno Creek Bldg A September 13, 2006 Field Wiring - Variable Air Volume Fan Powered Terminal Units Item: Cl - C4 Qty: 14 Tag(s): FPB1 -1, FPB1 -4, FPB2 -1, FPB2 -4, FPB3 -1, FPB3 -4, FPB1 -2, FPB1 -3, FPB2 -2, FPB2 -3, FPB3 -2, FPB3 -3, FPB1 -5, FPB1 -6 HEATER TERMINAL DAMPER BOX WIRING ACTUATOR FAN CONTROL WIRING BOX WIRING r raT2 2 I TB3B TB12 I I I IB25 -- -_ I C -- I- T131-1 I I I I I TB25 1 1 1 I I I 1 I I I I I I I ND STG HEAT 1 6 6 6 6 1 > i `702 1 Z 1 2 3 1 2 pp pp a 1ST STG HEAT m Y Y 0 0 TB1 T62 TB3 0 DIGITAL 2(1NF CFNCTIR OPTIONAL FIELD L INSTALLED DIGITAL ZONE SENSOR J R FAN BR r TB26 TB3.1 Y I TB25 TB3-2 00 1 I TB33 1 I pic 24VAC BL m\ ,If, _ 66 -r o - ' _n JI 000000 I Tn � r 5 4 3 2 1 t- l Ul ACT mL - ZONE SENSOR DIP CND 2411 PRESSURE W/ COMM JACK TRANSDUCER REMOTE MID ADDRESS D.D.C. \U.C.M. J3 Q Q SWITCH CONTROL BOARD — eK + OPTIONAL FIELD ., V OUT L INSTALLED ZONE SENSOR J BBBBBB G a e J -I ��I 'Yr I 'I I .'! 4� 1 4 '4 TEL 7 'C 'P 0S� 24V ITB1-1124V _ 0I I u 0 1 - T 1 0 1 - T 1 0 � 0 ❑ ❑ GRN L U SENSOR GND D - I B3.61GND II II ) ZONE GPO Si A/L02 GND OUT V _ - A/CO2 I I I I I I OPTIONAL FIELD INSTALLED - I I 1 1 I I L CO2 SENSOR J I I I I I I Z I Z I 1 I D.D.C. \U.C.M. I BL -I 1 01 o CONTROL BOX OPTIONAL - Y 1 1 FACTORY � // _ INSTALLED _ WIRELESS OPTIONAL FACTORY INSTALLED r , SHIELDED TWISTED PAIR TB3-5 -1 r T63-8 WIRELESS 1 I ___ Y I I COMMUNICATIONS WIRING 24VAC FL` r � am_ _ _ _ (TBt.t)24VAC I L - U U l LOMMONI_ - - (184 1) BIP IC13 1 BUR R ETURNL - _ (T B1 2) CND OPTIONAL FIELD INSTALLED ONO 24V Y AU AU %TEMP SENSOR U W5'B Scowl - NOT CONNECTED L J OPTIONAL FIELD INSTALLED L OCCUPANCY SENSOR J NOTE ,1, WARNING 1 FACTORY WIRING FIELD WIRING HAZARDOUS VOLTAGE? O DISCONNECT ALL ELECTRIC POWER OPTIONAL OR ALTERNATE WIRING INCLUDING REMOTE DISCONNECTS 2 1/4' QUICK CONNECT REQUIRED FOR ALL FIELD CONNECTIONS BEFORE SERVICING 3 I ZONE SENSOR TERMINALS 4 AND 5 REQUIRE SHIELDED TWISTED PAIR WIRING FOR COMMUNICATIONS FAILURE DISCONNECT POWER JACK EQUIPPED ZONE SENSOR OPTION BEFORE RE PEE RS CAN CAUSE SEVERE PERSOONAL NAL INJURY OR DEATH <1 ADDITIONAL W IRING REQUIRED FOR NIGHT SETBACK OVERRIDE (ON /CANCEL) ® CAUTION THE OPTIONAL BINARY INPUT CONNECTS BETWEEN TB4 -1 (BIP) AND 24VAC (HOT) FROM USE COPPER CONDUCTORS ONLY? TRANSFORMER. INPUT CAN BE RECONFIGURED AS AN OCCUPANCY INPUT VIA THE COMMUNICATIONS UNIT TERMINALS ARE NOT DESIGNED INTERFACE TO ACCEPT OTHER TYPES OF © AS SHIPPED, THE AUX INPUT IS CONFIGURED AS AN AUX TEMP INPUT. THE AUX INPUT CAN BE CONDUCTORS RECONFIGURED AS A CO2 SENSOR INPUT VIA THE COMMUNICATIONS INTERFACE FAILURE TO DO SO MAY CAUSE Q S TERMINAL NOT TO BE USED WITH VARITRANE. DAMAGE TO THE EQUIPMENT FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 40 of 41 Fanno Creek Bldg A September 13, 2006 Field Installed Options - Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job. Product Family - Commercial Rooftop Air Conditioning Units (Large) ( Item Tag(s) Oty Description Model Number Al RTU -1, RTU -2 2 90 -130 ton Packaged Industrial Rooftop SFHGC904 Field Installed Option Description Part/Ordering Number Temperature Sensor Standard Flat Roof Curb 0368 - 0166 -0100 FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 41 of 41 AL �`. . Air Commodities /Oregon fc _ A DIVISION OF AIR COMMODITIES INC. m• - HEATING • VENTILATING • AIR CONDITIONING EQUIPMENT • PROJECT: IFAINTNO CREEK PLACE - BUILDING` "A" LOCATION: LT1GAI, OR . ; • , . • • ARCHITECT: - ENGINEER: • • • .. _ - _ ° - : : ; ; , • = .; i1' ia. -∎ •• - • CONTRACTOR: HV ▪ - IN C : ,, , r - t '- - 1 -, -r - a. .,e: Ci t. ,.1..— � � :„..:. lr .(= _ _ � • •;41 •r 5- .:A.:•1•! • _ _ .. • CONTRACTOR PO # : : -_ ;_._,: _ :.x - :.4 ; , ._r. . __..z:.:.�,, • — d :ham - _ _ Fr.:,d:- -1 -•'�1 c t , :. ' , ^• =IA 't . ti DATE SUBMITTED: September 8, 2 006 = AC /O CONTACT: KEITH'HAWKINS " r : - AC /O QUOTE #: S993 ; " C ITEM SUBMITTED: Fi E /SMOKE= DAMPER ` ., _ r ' 1` \ \\ - _ MANUFACTURER: RUSKIN - _ > _ A {please see attached literature) \\*"...... .........) 1500 N.E. SANDY BOULEVARD, PORTLAND, OR 97232 - (503) 238 -6900 FAX: (503) 238 -8764 1- 800 -575 -2473 -' — - -. -• : ' . - ,- ■ ‘,...,... ':, „.... L,.'• ',, "; :-.."... ',,, 1 t' ' ' , • '..:. -4 . ' .5 , • - ,J `.:.- : 0- .. '_._ - S _•,.- ,,,,t,.,....,-, , , • - •,- ' e. 1 , a - ,, -... , LI_ r • „I 4 .- .1..F q ,I... ■agq, I , .•.. ,., ,,,,,. ,3,, .. i ,. ; .. e• . ... . ... I ' :-.,. .1 IIKE: -ERS , .,.•.,....: + 4 ..--,',..,, - , , J ' - ,g 1-.. I. , '. , - - . r .,-,- : ` ..!. - r , -. ;,......t., ' ' ' - '- . ' ''' - . , .I L•ti , :I' m, t • 3 1. - - - L - . - - . , - . . PROJECT: FANNO CREEK BLDG A ' - . _ QUANTITY 23T - ' JOB #: .899337 • . - : ` •: : .:. - ,- '._ . : .: , .. _ - .- - ., ,„ . . . _ .. , TAG . QTY. ' MODEL . DAIVIF'ER SIZE SLEEVE LENGTH :ACTUATOR • - REMARKS FSD-V 1 FSDR25 12" RD 17" 120V Ret plates FSD-V 12 FSDR25 22" RD 17" 120V Ret plates FSD-V 6 FSD36 60X20 17" 120V FMRA FSD-V 2 FSD36-G 30X6 17" 120V FMRA FSD-V 2 FSD36-G 30X10 17" 120V FMRA — — — — N 0 **FMRA. = FAST MOUNT RETAINING ANGLE - REQ ONE SIDE ONLY T E .. - S i ,,,,...-, . 1, , : ._:,;1 ..;,,,, :::..-.: -.---- ::::7*,:' •, ,, ;;;A::;.. — ,-- .- ,-*.,-...,...., ..i* .. , ',-- •:.54' ' '-,. - ,I-iY - --, ,,: ' -- 3] , " - ,.:-.' . ,., .': ,.r. ' • ?v All 'dathpers are 2509 constriction with' 166"...glectio-theril Iiiikaiiiiiitilaelloileywell ac , ....: .• e":-.-e-..-.4 ..-..■.-, a `. •-,-..., - ......g• ..... :....-1/4•1 .. -_ :CI: •:: ",:: ' . • •: ' : ' ' - •'.- '-';',‘• •••• :,--- " ...%,,,-.?..; - - ,,.. . ?,..j 1 .7 • 5-,:•yi'.. : ":" ...tZ .;" .:‘ - :,.: t -::. - .. - 7 'I :„; W .7;4 :,".::. 1 3.: ..1_ e:.• .. . ,, ,,, , I.-... - .. -I „''....''' - .F... t.i I: t".5 L' C'. I'' 1 • .. 1. , ; , ...4: ° ■ Z4,,j-,■:7' 7. '. ''11: ...";. i :: '..'..-: ".:. c'' .■ ".. ' rt. , - , , :'' . .•!..1 , ! ‘f...-4.::y t...:,.; - ;41 . -Pr' •.‘,E; .4 ' " r-....13. 'I: Air tii iiitiditieilategbifiitirpoiis toitiiiplithgalitiUlii project. It is the 'Sole' responsibility of - ,," ,, R.:-.,.. , -,-,..,— •,i---. - ..• . , • -, 't'''••"•.-r ":%:-•• ';E:■-'4‘ il';';—. e• ,•_;. _--.; :J..: I ,--..• 4... .• l a, ,.• ., , : 5 , .i.,,..,,A .,..,,o.ck....,:, .;.• '7 ^117, 40 ; z !.... 11 , , ,,,_;.,,,, •-• ,:- •,..f., t- 1 :f .--;-- ..; 1:-7-' i.A.•01-;'.• r Y ,-. 2.r..1 ,. : F =:9=:;7%;:,r,.: ,::::: ..:,:=.,,z;':-.,+:_,,F ,:-'.‘-. -, -- i.l...',...... '- , r,,!.1.,•:::,.;-.".y_.,i,..;,.-,;_c:a.;..• 7 ' , -'•''',": 0, :.: 0- .."3"i;':...::: Z.- j. 4% ::: fi '''' 7' .......'1'4".4.1- ' 7 ' ;. ' 3 1 '1 € ' '' ' +'Fi v t :' 4 7 2' k''' , V...... 4.- .7 . . ,-." '..-1 r:.. : ...,...,.. ,. . R ,_ 3900 Dr. Greaves Rd. • Kansas City, MO 64030 • (816) 761 -7476 • FAX (816) 765 -8955 • FSDR25 COMBINATION FIRE SMOKE DAMPER UL555 and UL555S Leakage Class 1 Classified FOR USE IN DYNAMIC AND STATIC SYSTEMS APPUCATION The FSDR25 is a 'true round" Class 1 leakage rated combination Model FSDR25 meets the requirements for fire, smoke and fire and smoke damper designed for use in metal, wood or con - combination fire /smoke dampers established by: crete fire and smoke rated partitions and concrete floors. The • National Fire Protection Association NFPA Standards FSDR25 is the ideal choice when round duct is used on a project. 90A, 92A, 92B and 101 The damper Is rated for maximum velocity of 3,000 fpm and 4" • BOCA National Building Codes (102) static pressure. The integral frame and unique "cinch plate" • ICBO Uniform Building Codes design provide a low cost, easy to install, high performing damper. SBCCI Standard Building Codes • STANDARD CONSTRUCTION • ICC International Building Codes FRAME/SLEEVE • CSFM California State Fire Marshal Fire Damper Listing 20 gage (.9) galvanized steel, standard 17" (432) long ( #3225- 245:102) and Smoke Damper Listing (#3230 - Frame /sleeves available up to 36" (914) In length. See mini- N w York mum sleeve length chart on page 2 for assistance in choosing New City (BSA Listing #176 82 -SM) correct frame /sleeve length. BLADES Two -piece 14 gage (1.9) equivalent thickness galvanized steel. UL CLASSIFIED BEARINGS UL555 Listing R5531, UL555S Listing R10525 Stainless steel sleeve, pressed into frame. BLADE SEALS Silicone edge type sandwiched between two piece blade. Full FEATURES circumference smoke seal to 450 °F (232°C). The FSDR25 offers: LINKAGE • EFL (Electric Fuse Link) or PFL (Pneumatic Fuse Link) heat - Jackshaft to blade. actuated release devices permit controlled (rather than AXLE Instantaneous) closure through the damper actuator. The EFL 1 /2" (13) diameter. and PFL allow the damper to automatically reopen after a CONTROLLED CLOSURE DEVICE (HEAT- ACTUATED) test, smoke detection or power failure condition. 165 °F (74°C) standard. 212 °F (100 °C), 250 °F (121°C), 285 °F • EFL is standard on dampers with electric actuators. (141 °C) or 350 °F (177 °C) are available at no additional cost. • PFL is standard on dampers with pneumatic actuators. • EFL's may be ordered on dampers with pneumatic actuators but require an additional EP switch. DAMPER SIZES MINIMUM SIZE 6" diameter (152). MAXIMUM SIZE ,"'''.\ Vertical / Horizontal Installation — 24 " diameter (610 ). o � See page 2 for dimensional information. /° \/ Retaining 'Cinch" Plate OPTIONS \ \ • TS150 FireStat for reopenable operation in dynamic smoke A management systems. � ° >> �� • DSDF Flow Duct Smoke Detector — Consult Ruskin. I \ • SP100 Switch Package to remotely indicate damper blade posi- lion. - 4 \ • • Sleeve /Frame of various lengths to insure field compliance with UL installation requirements. LLLL \ • Access Door factory mounted in common sleeve to insure com- pliance with UL installation requirements. • MCP control panels for test purposes or smoke management i a systems. \ \ 1 . yam' NOTES \\ �. 0 ' 1. Units furnished approximately t /9" (3) smaller than given size. \ r 2. Dimensions shown in parentheses ( ) indicate millimeters. ° Spoe FSDR25- 303lReplaces FSDR25 -702 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. °Ruskin 2003 DIMENSIONAL INFORMATION - MINIMUM — L SLEEVE LENGTH 2" - r • Wall /Floor Min. Sleeve (51) (51) The "L" dimension is the dimension the Thickness Length a_ [1 sleeve, on the actuator side of the 102 17" (432) damper, can extend beyond the wall or 4 " (102) ) floor In a standard installation. The "L" 5" (127) 1 " (432) dimension is designed to provide the 0 0 installer with Information to make installa- 6" (152) 20" (508) I lion easier. The table below provides a 7" (178) 20" (508) ; range for the "L" dimension. I 8" (203) 20" (508) 9 "(229) 27'(559) 10" (254) 22" (559) "L" DIMENSIONS 11" (279) 23" (584) WALL THICKNESS 12 "(305) 24 "(610) _ 4" 5" 6" 7" 8" 9" 10" (102) (127) (152) (178) (203) (229) (254) Add 1" (25) Over 12" (305) for every inch Minimum 8 8 8 8 8 8 8 Thru 24" (609) of wall/floor Standard 9" 9" 9" 9" 9" 9" 9" depth Maximum 10" 10" 10" 10" 10" 10" 10" Note: 36" (914) maximum sleeve length. NOTE. The 2" (51) dimension is for duct connections. The "1" dimension includes the 2" (51) for duct connection. GENERAL INSTALLATION INFORMATION . METAL/WOOD/MASONRY WALL RETAINING "CINCH" PLATE OR CONCRETE FLOOR INSTALLATION Expansion Gap ° ° Retaining Layout Dimension Cinch Device on one Cinch _ + e ° L or both sides (see Plate Installation Instruction for details) ( 1 Electronic Fuse Link Approved Fastener (EFL) Breakaway I VA Damper • .1 I . . I . III Actuator j I H I I Ii Blade Axle Note: + /:" (13) I ri I Diameter + 6" Minimum Overlap (152) = plate size of WaiirFloor Opening iit' L_ �,''•. Blade Il I .: ill , ,,,... y e . Overcenter Link A square opening in wood or metal stud walls or masonry walls and floors shall be ° \ a minimum of 1" (25) and a maximum of 2 (64) larger than the damper diameter. See wood stud and metal stud framing for fire dampers installation instructions sup• ° plement for complete framing details. A round opening In masonry walls or floors shall be a minimum of 1" (25) and a maximum of 2 (64) larger than the damper diameter. Factory supplied retaining "cinch" plates hold the damper within the wall opening. The plates must overlap the opening a minimum of 1 /2" (13). The plate fits snugly REFER TO THE FSDR25 INSTALLATION INSTRUC- around the integral sleeve. The plates are fastened directly to the wall or floor. TIONS FOR COMPLETE INSTALLATION DETAILS. RusKiN ,.. 3900 Dr. Greaves Rd. • Kansas City, MO 64030 • (816) 761 -7476 • FAX (816) 765 -8955 EFL ELECTRIC RESETTABLE "FUSE" LINK OPERATION INSTRUCTIONS SUPPLEMENT APPUCATION The EFL Electric Resettable 'Fuse' Link Is a UL Classified heat a responsive device is used in conjunction with Ruskin fire /smoke 0 dampers The EFL Is standard on all fire /smoke dampers ordered wall . with electric actuators. Fire /smoke dampers ordered with pneu- matic actuators may be ordered with the EFL and an EP 1� (electro/pneumatic) switch. The EFL doses and locks the damper IiiiI whe temperatures exceed 165 °F (74 °C) or 212 °F (100 °C) or 0 250 °F (121 °C) or 350 °F (177 °C) depending on model ordered and Damper with Installed The EFL must be factory installed and cannot be ' Aua tor and EFL added in the field. Replacement EFL's may be field installed 0 Ill with the approval of the local authority. OPERATION 0 WWII 0 Fire Conditions — When temperatures in excess of 165 °F (74 °C), ` 212 °F (100 °C), 250 °F (121 °C) or 350 °F (177 °C) are detected, the 0 damper will close and lock. Upon cessation of fire conditions the Q damper can be reopened by pressing the reset button located on IIIII the damper assembly. JL Smoke Conditions — When smoke signal Is detected, the damper will dose and remain closed until the smoke signal ceases (or the smoke detector Is reset). The system will then reset and the 0 damper will open. • The damper may be closed at any time by placing a control switch (optional) in the CLOSED position. • If the EFL is tripped accidentally or during system testing, the ITEM DESCRIPTION EFL must be reset by pressing the RESET button located on the damper assembly. 1 EFL165, EFL212, EFL250 or EFL350 • Refer to the appropriate damper installation instructions for Electnc Reset Link details on damper installation. 2. Flex Conduit 3. Junction Box 4. Actuator or EP Switch ` p ur& 5. Over - Center Lock 4 ®O SEE COMPLETE MARKING ON 6. Damper Sleeve PRODUCT 7. FAST, PFMA or conventional mounting angles 8. Sleeve to Duct Connection (by others) Pneumatic actuators to be piped per local codes. Electric actuators to be wired per the National Electric Code Add,tlonai (NEC) and local codes. See actuator for wiring diagrams. Motors II Required - L2 Brn l I EFL t ..., 4 1 Wlring I Lt Compartment 0 (,.,,, �C L ``�-� Y Smoke Neat detector Switch (Il Peed) L J Manual t20 VAC or NO VAC • Reset Button Fuzee Circuit II. EFL402/Repbees II-ER-32000 ORusldn 2002 .. ._ RUS KIN® 3900 Dr. Greaves Rd. • Kansas City, MO 64030 • (816) 761 -7476 FAX (816) 765 -8955 INSTALLATION INSTRUCTIONS FSDR25 COMBINATION FIRE AND SMOKE DAMPER 11/2 HOUR UL555 RATED UL555S LEAKAGE CLASS 1 RATED APPLICATION 1. Expansion Clearance The FSDR25 is a "true' round, single blade, combination A square opening in wood or metal stud walls or masonry walls fire /smoke damper. It is designed for use with round duct in round and floors shall be a minimum of 1" (25) and a maximum of masonry openings through wall or floors or round duct in square 2 (64) larger than the damper diameter. A round opening In openings through metal stud or wood stud fire rated walls. The masonry walls or floors shall be a minimum of 1" (25) and a FSDR25 is installed with the leading edge of the closed blade maximum of 2 (64) larger than the damper diameter. within the wall or floor. THE RETAINING "CINCH" PLATE MUST OVERLAP THE MOUNTING OPENING A MINIMUM OF 1 h" (13). Vertical or Horizontal. 2. Damper Sleeve MINIMUM SIZE The sleeve is integral to the damper and shall be of equal to or 6" (152) diameter. heavier than the gage of the duct as described in NFPA90A and as defined by the appropriate SMACNA duct construction MAXIMUM UL CLASSIFIED SIZE standard. 24" (610) diameter. 3. Damper Orientation The leading edge of the blade In the closed position must be INSTALLATION SUPPLEMENTS within the plane of the wall. Vertical installation Is illustrated and appropriate Ruskin installation instructions supple- honzontal Is similar (see General Installation). The damper may Refer to the a PP pp be installed with up to a 30 degree variance of the axle being ments for additional information or special requirements: horizontal (see Blade Orientation section) • Optional Sealant of Dampers in Fire Rated Wall or Floor Open- 4. Retaining "Cinch" Plates Ings DO NOT PLACE CINCH PLATES IN GROOVE • TS150 FireStat for "Reopenable" Combination Fire and Smoke The retaining 'cinch' plates are designed to grab and hold the Dampers sleeve while mounting flush against the wall or floor retaining • SP100 Switch Package the damper securely in the opening. The plates must overlap • EFL Electric Resettable "Fuse" Link the opening a minimum of 1 /2" (13) (see "Cinch" Plate section). • EFUSP100 Electric Resettable "Fuse" Link and Switch Package The "Cinch" plates are fastened to the wall or floor accord- • ing to the following: • PFL Pneumatic Fuse Link • Masonry Wall – "Cinch" plate required on only one side of the Dimensions shown in parentheses ( ) indicate millimeters wall fastened to the wall with a minimum of 1 1/4" (6) #10 masonry screw. • Masonry Floor – "Cinch" plate required on both sides of the floor fastened to the floor with a minimum of 1 1 /a" (6) #10 RETAINING "CINCH" PLATES masonry screw. • Metal Stud Wall – "Cinch" plate required on only one side of RETAINING "CINCH" PLATE the wall fastened to the wall by engaging the metal stud a minimum of 1 /2" (13) with a #10 screw. • Wood Stud Wall – "Cinch" plate required on both sides of the wall fastened to the wall by engaging the wood stud a min- • .1 • • mum of 1 (38) with a #10 screw. Cinch . (.o. 5. Duct/Sleeve Connections Device Fastener I (See Section 4 Round break -away connections must be used. Either a 4" (102) Note: \ for specific wide drawband or #10 sheet metal screws spaced equally • Diameter + requirements) around the circumference of the ducts as follows: • 6" (152) = . _ • Duct diameters 22" (559) and smaller – 3 screws. plate size Damper • • • I • • Duct diameters over 22" (559) to 24" (610) – 5 screws Note: When optional sealing of these joints is desired, the fol- _I lowing sealants may be applied in accordance with the sealant — "1 manufacturers instructions: Hardcast, Inc. - Iron Grip 601, Preci- 1 I2 » (13) sion - PA2084Tor ECO Duct Seal 44-52. `� / • • Minimum Overlap 6. Actuator Connections • o walVfloor Electric and pneumatic actuators are to be connected in accor- \ with opening dance with winng and piping diagrams developed In compliance \ applicable codes, ordinances and regulations. `---i! •\ 7. Installation and Maintenance \ . Retaining Do not compress or stretch the damper frame into the duct or \ ��/ "Cinch" opening. Lift or handle the damper using sleeve or frame. Do not Plate lift damper using blade or actuators. Each fire /smoke damper should be examined on a regular basis to ensure it is not rusted or blocked. In addition, each damper should be tested periodical- • ` ptas fp& y, (NFPA recommends annually or semiannually, depending on ®o SEE COMPLETE the application) to ensure It will perform as Intended. Care should MARKING ON be exercised to ensure that such tests are performed safely and PRODUCT do not cause system damage. 11- FSDR26-6021Rephaces il- FSDR25-102 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION *Ruskin 2002 GENERAL INSTALLATION Within 1 and 2 Hr. Rated Masonry Floors and Ceilings or Walls 4 - ITEM DESCRIPTION 7 1. FSDR25 Round Fire/Smoke Damper 2. Retaining "Cinch' Plate, 20 ga. steel \ \ \ (only one plate Is required on walls, as 0 0 (2 shown, and two plates are required on � ' floors). II 3. Duct o 4. Masonry Wall or Floor mt ?' 5 #10 Concrete Anchor, I I 1 ( min 11/4" (31) long Eij_::'.., 111 .: 6. Duct/Sleeve Connection .. I 7. Expansion Gap II �� U Note: Masonry walls require retaining • °• \ "cinch" plates on only one side of the 2 3 ( , �� ° wall, as shown. Floors require retaining . ° "cinch" plates on both sides of the floor. Figure 1 4 ' Figure 2 5 Within Square Opening in Metal or Wood Stud Framed I 1 and 2 Hr. Rated Drywall Partitions( Vertical Walls Only) - I 0 -0 O ITEM DESCRIPTION Q 1 0 ` 2. Retain ng °Cinch 20 gaDasteelr t d 't I• (only one plate Is required on metal su 0 r `, walls, and two plates ar required on wood i - l i stud walls). • 3. Duct I J 4. Metal Stud Wall (plate required on only one side) C 5. Wood Stud Wall (plate required on both ii �� sides) Inil � ` � • 6. #10 Sheet Metal Screw (refer to section 4 1 ` for fastener requirements). 7. Duct/Sleeve Connection 2 . 8. Expansion Gap Figure 4 Screws Note: Metal stud walls require retaining must pone- ) "cinch" plates on only one side of the wall. trate wood 1 Wood stud walls require retaining "cinch" or metal studs. Figure 3 plates on both sides of the wall. BLADE ORIENTATION Actuator Actuator Allik � `� 30' Axle - \ — _ / I 1 Axl \i• 30' / Axle Ar NORMAL 30° OFF HORIZONTAL Actuator 30° OFF HORIZONTAL (Maximum) (Maximum) ,,„. AMC A LICS ..,_ _ ,_ ,. RUSKIN® See Page 2 � R 3900 Dr. Greaves Rd. • Kansas City, MO 64030 • (816) 761 -7476 • FAX (816) 765 -8955 ° FSD36 COMBINATION FIRE AND SMOKE DAMPER 1 HOUR UL555 RATED, UL555S LEAKAGE CLASS 2 APPLICATION Model FSD36 meets the requirements for fire, smoke and The FSD36 is a combination fire and smoke damper designed with combination fire/smoke dampers established by: triple V- groove blades and controlled closure technology that pro- • National Fire Protection Association NFPA Standards vides point -of- origin fire containment and operational flexibility in 90A, 92A, 92B and 101 static and dynamic smoke management systems. • BOCA National Building Codes The FSD36 may be installed vertically in walls or horizontally in • ICBO Uniform Building Codes concrete floors. The FSD36 is designed for use In systems with air- flow In either direction with velocities to 2,000 fpm and pressures to • SBCCI Standard Building Codes 4" w.g. (Consult Ruskin for proper application if velocity and pres- • ICC International Building Codes sure exceed those listed above). • CSFM California State Fire Marshal Fire Damper Listing (#3225. 245:005 and Smoke Damper Listing (#3230 - STANDARD CONSTRUCTION 245:109) FRAME • New York City (BSA Listing #176 -82 -SM) 5" x 16 (127 x 1.6) gage galvanized hat - shaped steel channel structurally superior to 13 (2.3) gage channel frame. BLADES UL CLASSIFIED 6" (152) wide, 16 (1.6) gage galvanized steel. Triple V -groove shaped approximately 6" (152) on center. UL555 Listing R5531, UL555S Listing R10525 BEARINGS Stainless steel sleeve pressed Into frame. FEATURES JAMB SEALS Stainless steel, flexible metal compression type. The FSD36 offers: BLADE SEALS • EFL (Electric Fuse Link) or PFL (Pneumatic Fuse Link) heat- - Silicone edge type for smoke seal to 450 °F (232 °C) and galva- actuated release devices permit controlled (rather than instanta- nized steel for flame seal to 1900 °F (1038 °C). neous) closure through the damper actuator. The EFL and PFL UNKAGE allow the damper to automatically reopen after a test, smoke Concealed in frame. detection or power failure condition. - CONTROLLED CLOSURE DEVICE (HEAT- ACTUATED) • EFL is standard on dampers with electric actuators. 165 °F (74 °C) standard. 212 °F (100 °C), 250 °F (121 °C), 285 °F • PFL is standard on dampers with pneumatic actuators. (141 °C) or 350 °F (177 °C) are available at no additional cost. • EFL's may be ordered on dampers with pneumatic actuators but UL555S Elevated Temperature Rating require an additional EP switch. 250 °F (121 °C) or 350 °F (177 °C) depending on actuator • Actuators mounted either out or in airstream. DAMPER SIZES MINIMUM SIZE 1 8 "w x 6"h (203 x 152). MAXIMUM SIZE Iii* Vertical — 1261, x 96 "h (3200 x 2438) or 72"w x 122 "h (1829 x 3099). Horizontal Installation — 144'W x 96 "h (3658 x 2438). I,, — B= OPTIONS Height • TS150 FireStat for reopenable operation in dynamic smoke management systems. I • DSDF /DSDN Duct Smoke Detector (Flow rated or No -flow) I `` • SP100 Switch Package to remotely indicate damper blade posi- II ` i'- ' - `- I lion. • FAST Angle factory supplied for labor saving angle one -side ` I^ I = I installation. • PFMA Picture Frame Mounting Angle factory supplied for angle two-sides installation. K _ :,f �' I • G Style for grille applications. tea BIV • GA, Grille Access Type for „through the grille access" to actua- tor and control devices (see FSD36GA model). A - • OW, Out of Wall /Floor Type for outside the wall/floor "through Width. - penetrations" (See FSD360W model) NOTES 4 • • RA, Integral Retaining Angle Type for "fool proof' all from one 1. Dampers are furnished approximately Ye (6) smaller than side installation (see FSD36RA model) given opening dimensions • Factory Sleeves of various lengths and gages to insure compli- ance with UL installation requirements. 2. Dimensions shown In parentheses ( ) indicate millimeters. • Access Doors factory mounted in common sleeve to Insure - compliance with UL installation requirements. • MCP master control panels for test purposes or smoke manage- ment systems. • FireStop Caulk installations Spec FSD36- 703IRepleces F81)38-303 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGAT ION. ORusin July 2003 AMCA LICENSED LEAKAGE AND AIR PERFORMANCE DATA ` Ruskin certifies that the FSD36 shown CIMCCa hereon Is licensed to bear the AMCA OERTIf1ED Seal. The ratings shown are based on • RATIN% tests and procedures performed In accordance with AMCA Publication 511 and comply with the requirements AIR of the AMCA Certified Ratings Pro- °°`r°nn°°`° gram. The AMCA Certified Ratings m n Seal applies to air performance for ,MorEmEnT the opposed blade FSD36 sizes 12"w nno conrnot x 9 "h (305 x 229) through 36"w x 48 "h erinen ioon Inc. (914 x 1219). To determine the AMCA Licensed air performance Locate the applicable feet per minute face velocity on the bottom of the velocity vs. pressure drop chart below. Move up the chart to the most appropriate size damper line. From the intersection point, move left to determine the pressure drop on the left side of the chart. For other damper sizes refer to Air Performance Data For All Fire and Smoke Dampers spec sheet. VELOCITY vs. PRESSURE DROP 1.0 .7 - 0.9 u 0.8 7 0.7 0.6 0.5 /,, % 0.4 0.3 . § 0.2 v) / 5b z t 0 °- 0.1 / c c .09 O .08 cc ui .07 . N .06 W .05 . cc a- 04 .03 02 , 1; , y i .01 , 2 3 4 6 7 8 9 2 3 4 6 7 8 9 100 500 1000 5000 10000 FACE VELOCITY — FEET/MINUTE AMCA Fig. 5.3 SPACE ENVELOPE Externally mounted actuators require space outside the damper sleeve. The "S" dimension is the "side" clearance, the 'T' dimen- sion Is the "top' clearance and the "B" dimension is the 'bottom' . clearance required for the various actuators approved for use with — — Ruskin fire /smoke dampers. Actuators and accessories are factory T mounted on the right side when viewed from the actuator side of the wall or floor. Ruskin fire /smoke dampers can be rotated or I turned over to accommodate the application. If the actuator must min .- ■ I be mounted on top or bottom, select the FSD6OV. The most commonly used electric actuators are shown in the table below. Refer to the Actuators And Accessories Space I Envelopes For All Fire and Smoke Dampers data sheet for adu- i atom and space information not shown. H I — i ACTUATORS (Damper S T B Q Motor with Height) ■1.0.1 EFL or TS-150 � i _,O r ML4202, H2000, H2024 15" (381) 4" (102) 0° (0) N/A imimm i MS4209, MS8209 15" (381) 4" (102) 0" (0) N/A I i MS4120, MS8120 17" (432) 5" (127) 0" (0) N/A FSNF120, GGD221 17" (432 5" (127) 0" (0) N/A 1 i t NOTES: e 1. The "H " dimension represents the required height to encompass �1 - - the actuator and accessories with nothing protruding above or HS below the damper. 2. The e °B" (bottom) dimension does Not Apply to the "H" sizes shown. The MS4120, MS8120, FSNF120 and GGD221 will hang below the damper on sizes 10" (254) high and shorter. DAMPER SLEEVE DIMENSIONAL DATA The drawing and corresponding table show the position of the 'sleeve damper when mounted in a factory sleeve. The standard mounting Length locations provide enough space for the mounting of actuators, con- watt/ trots and allow space for installation of retaining angles and duct L , I Floor 3" (76) connections. The minimum factory sleeve length is 17" (432). Con- Dimension MIn. suit Ruskin for shorter sleeve lengths. Sleeve The standard location of a damper mounted in a factory sleeve ( "L" dimension) Motor is shown at right. . ; ; I N -motor 9 Side ! o i Side NOTE: ° The entire damper frame is not required to be installed within the J� 1 i ! I wall. The damper blades, when closed should be contained within I I ° I : the w a l l. / 1 �- 1 I /! \ � I I ° 1I ' ii a ! y ® 'Minimum Sleeve Length Formula: Sleeve Length = "L" dimension + wall /floor thickness + 3" sleeve non -motor side Note: See basic UL Installation Instructions for complete Installa- tion requirements. All dampers with All dampers with TS150 or SP100 EFL or PFL Electric Actuators Pneumatic Actuators Over 21" 21 "(533) (254) High 331- 4827(P) 331-2961(P) 331- 3060(P) Over 10" Hig h and and (533) 533 High and Over 28" 28" (711) Over 32" 32" (813) Over 40" 40" (1016) High Under High Under (711) High & (813) High & (1016) High & (see note) (see note) High Under High Under High Under "L" 7 (181) 10 (270) 7 (181) 10 /a" (270) 7 (181) 10 (270) 7 +I8" (181) 10 /," (270) 7th" (181) 10 (270) Note: The 21" (533) dimension becomes 32" (813) when the MS4120, MS8120, GGD221 or FSNF120 are utilized. DIMENSIONAL INFORMATION 17"(432) I\` : 20" � s08) 6" (152) 'I `I \ Min. Min. p „ I. \ i`n•\ L Y + '1 , Height I n ►` iN 8"(203) l \ \ �` ,, Min. 1 its, Ar °V �� i ►\ D 20” \ I `r (A L 4 or D + 51 I ) 508)\ Max. I► 'q „KM:. ) Width . .�`1 . �� ROUND, OVAL OR RECTANGULAR DUCT TRANSITION CONNECTION a° (102 Mm. ' \ MAXIMUM UL CLASSIFIED SIZE FSD36 dampers supplied with round connections (R for low pressure, CR for medium pressure or WR '�I` welded for high pressure) \ Single Section: Minimum 4" (11102) 02) in in diameter 36"w x 48 "h (914 x 1219) Maximum 94" (2388) in diameter Multiple Section Assembly The square size of the damper will be 2" (51) larger s' (152) Vertical Installation — than the diameter dimension ordered. 8 "(203) Min. 126"w x 96 "h (3200 x 2438) or Mln. 72'W x 122 "h (1829 x 3099) FSD36 dampers supplied with rectangular connec- Horizontal Installation tions (C for low to medium pressure or WC welded 144'w x 96 "h (3658 x 2438) for high pressure) are: For dampers exceeding these Minimum 6 "1x4 "h(152x102) - MINIMUM SIZES dimensions consult Ruskin. Maximum vertical 124'W x 94 "h (3150 x 2388) Maximum horizontal 142' \0/ x 94 "h (3607 x 2388) Nominal — 8 "w x 6 "h (203 x 152). The square size of the damper will be 2" (51) larger Actual — 73/4 "w X 53/4 "h (197 x 146) than the width and height of the damper A x B Dampers with heights (B dimension) dimensions. less than 6" (152) require Style B tran- sitions and a sleeve. The damper itself FSD36 dampers supplied with oval connections remains V (152) high (LO for low pressure, CO for medium pressure or WO welded for high pressure) will be 2" (51) larger than the width and height of the damper A x B dimensions. SPECIFICATION Combination fire/smoke dampers meeting or exceeding the follow- leakage and airflow in either direction through the damper. ing specifications shall be furnished and Installed at locations Each combination fire /smoke damper shall be equipped with a shown on plans or as described in schedules. Dampers shall meet "controlled closure" quick detect heat - actuated release device to the requirements of NFPA90A, 92A and 92B and shall be classified prevent duct and HVAC component damage. Instantaneous damper for use for fire resistance ratings of less than 3 hours, in accor- closure Is unacceptable. dance with UL555. Dampers shall further be classified as Smoke Dampers in accordance with the latest version of UL555S. The Damper frame shall be minimum 16 (1.6) gage galvanized steel leakage rating under UL555S shall be leakage Class 2. formed Into a structural hat channel reinforced at corners. Damper blades shall be single skin galvanized steel 16 (1.6) gage minimum In addition to the leakage ratings already specified herein, the with three longitudinal grooves for reinforcement. Bearings shall be dampers and their actuators shall be qualified under UL555S to an stainless steel sleeve turning in an extruded hole in the frame Blade elevated temperature of 250 °F (121°C) or 350 °F (177 °C) depending edge seals shall be inflatable silicone coated fiberglass and galva- upon the actuator. Appropriate electrir/pneumatic actuators (sped- nized steel mechanically locked into blade edge (adhesive or clip on fier select one) shall be installed by the damper manufacturer at seals not acceptable). Jamb seals shall be stainless steel compres- time of damper fabrication. Electric actuators shall have been ener- sion type. Each damper shall be supplied with a factory mounted gized hold open tested for a period of at least 1 year with no spring sleeve of 17" (432) minimum length. Dampers shall be Ruskin return failures. Damper and actuator shall be supplied as a single model FSD36 entity which meets all applicable UL555 and UL555S qualifications for both dampers and actuators. Each damper shall be rated for (Consult Ruskin for detailed CSI MasterFormat Specification). 9900 Dr Grooved Rd RusKIN. ( Kansas City. (816) 761-7476 FAX (816) 7858955 55 www ruskln corn RUSKIN® 3900 Dr. Greaves Rd. • Kansas City, MO 64030 • (816) 761 -7476 • FAX (816) 765 -8955 • FSD60, 60 -II, 60 -V, 37, 36, 35, 34 STYLE G MULTIPLE BLADE FIRE /SMOKE DAMPERS FOR GRILLES 11/2 HOUR RATING FOR USE IN DYNAMIC OR STATIC SYSTEMS STANDARD CONSTRUCTION QUALIFICATIONS FRAME 5" x 1' x 16 gage (127 x 25 x 1.52) galvanized • UL555 classification and labeling as a hat shaped channel. 1 hour fire damper. BLADES • UL555S leakage rated (smoke) damper Airidl shaped or triple -v groove. classification and label per FSD model. See individual model spec sheet. • California State Fire Marshal Listing for Ifire and leakage (smoke) dampers LINKAGE • Meets UBC, SBCCI, BOCA, NFPA90A Concealed In frame. and A requirements for fire/ AXLES smoke a dampers. 1 /i (13) plated steel hex I�. \ '-''\ • Elevated temperature qualified at 350 °F FINISH (177 °C) or 450 °F (232 °C) depending Mill galvanized. 110, �� �` upon the actuator Vertical. ` MINIMUM SIZE VARIATIONS FSD 60, 60 -11, 60 -V - 8'w x 6 "h (203 x 152). All UL classified fire/fire-smoke dampers FSD 34, 35, 36, 37 - 5'w x 6 "h (127 x 152). must be fabricated in accordance with UL MAXIMUM SIZE procedure. Available variations are limited FSD 60, 60-11- 37w x 4911(813 x 1245). to those Incorporated In the approved pro- 49'w x 32h (1245 x 813). cedures. FSD 60 -V • x 32'h (1245 x 813) Approved variations available at additional FSD 34, 35, , 36 36, /1• ( 19) Flange A , 37 - 32'w x 48 "h (813 x 1219) Typ. 4•Sides \ cost are: or 49 W x 32'h (1245 x 813). (Shipped loose) • The TS150 FireStat option which allows • FEATURES remote ovenide of fire Induced closure to • This specialized version of Ruskin's established permit reopenable operation In a Model FSD series features the fire - smoke dynamic smoke management system. damper offset in a sleeve with 3 /4" (19) full Requires an EP switch when damper Is length grlfe mounting flanges shipped loose for FSD60 SHOWN equipped with a pneumatic actuator. The field installation. It fits flush In the wall opening TS150 FireStat must be ordered with and the customer supplied grille Installs over 1 (44) Max. damper and Installed at time of manufac- and completely conceals the mounting flanges. —"" .I .— Grille Depth lure. r • The EFL or PFL heat - actuated release devices • The DSD Duct Smoke Detector option permit controlled dosure through the actuator and / which Is factory mounted for single point are automatic remote resettable after test, / II connection and ease of application. smoke detection or power failure conditions. / • The SP100 Switch Package provides • EFL Is provided as standard on dampers with / the ability to remotely Indicate damper electric actuators. / blade position. This option Is Included as • PFL is provided standard on pneumatically actu- / 6" (152) Max. an Integral part of the TS150 FireStat or aced dampers. / Blade Width supplied separately. • EFL with pneumatic actuator requires EP switch. / ...0 • Picture Frame Mounting Angles • Fail -safe design, which enables the damper to which are factory matched and shipped automatically assume the desired position when / with each damper. fire Interrupts operational power. / \y • Sleeve - Factory supplied sleeves from NOTES / e • l .1 10 (.5) to 20 (1.0) gage and various 1. Dimensions shown In parentheses ( ) indicate / lengths. Sleeve and damper are caulked millimeters. / j at factory to help assure field compliance 2. Damper /sleeve assemblies furnished actual ■ -- with Underwriters Laboratories Instalia- size to allow grille Installation. Lion requirements and to meet desired 3. Refer to the Grille Style Installation leakage performance. Instructions and supplements for complete —.- I 21h" (64) Set Back Installation details. IMPORTANT: This Installation requires a min. of 6" (152) wall depth. SIZE FUSE QTY. LINK SLEEVE SLEEVE VARIATIONS A" -WIDE B4-HIGH TEMP. LENGTH GAGE JOB LOCATION CONTRACTOR Spec F51360- G-9e7Mew ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION 0 Ruskin Manulaclunng 1997 STYLE G MULTIPLE BLADE FIRE DAMPERS FOR GRILLES HOW TO APPLY 1. Size the damper (A x B). EXAMPLE: 2. Determine the wall thickness The minimum wall thickness Application requires a damper which is less than 20" tall supplied is 6 ". For walls less than 6" consult factory. with an electric actuator and a TS -150. The wall depth is 6", there- fore, the required sleeve length is 17". If the wall depth is 8" deep, 3. Determine the gnlle depth. Grille must not exceed 1314 ". the required sleeve length is 19 ". 4. Choose the minimum sleeve length required from the table below Table is based on a 6" wall. For walls with depths greater than 6 ", add the difference to the sleeve length indi- cated (see the example). SLEEVE LENGTH (MINIMUM) ACTUATOR TYPE - WITH EFUPFL WITH TS150 /SP100 UNITS OVER 10" (254) HIGH UNITS OVER 20' (508) HIGH ELECTRIC (254) AND UNDER 20' (508) AND UNDER UNITS UNITS All Models 14" (356) 17" (432) 14" (356) 17" (432) UNITS OVER 10" (254) HIGH UNITS OVER 28" (711) HIGH PNEUMATIC 10' (254) AND UNDER UNITS 28 (711) AND UNITS UNDER 3314827 14" (356) 17' (432) 14" (356) 17" (432) UNITS OVER 32 " (813) HIGH 32" (813) AND UNDER UNITS 3312961 14" (356) 17' (432) 14" (356) 17" (432) UNITS OVER 40" (1016) HIGH 40' (1016) AND UNDER UNITS 3313060 14" (356) 1T' (432) 14" (356) 17" (432) 3900 Dr Greases Rd RUSKIN ® Kansas ) 64030 (818)761-7476 ( FAx (816) 765.8955 55 sm./ nngn.com RUSKIN® 3900 Dr. Greaves Rd. • Kansas City, MO 64030 ▪ (816) 761 -7476 • FAX (816) 765 -8955 • 'INSTALLATION INSTRUCTIONS . 11/2 HOUR UL CLASSIFIED STYLE G GRILLE INSTALLATION FOR RUSKIN (D)IBD AND FSD DAMPERS APPLICATION DYNAMIC FIRE DAMPERS Style G fire and combination fire and smoke damper Includes grille See label on damper for maximum air flow and pressure. mounting angles for flush installation of a minimum 26 gage (.021) MINIMUM SIZE steel frame grille with the wall or floor. No additional mounting Vertical Installation — 4"w x 4 "h (102 x 102). angles are required on the grille side of the wall or floor. The Horizontal Installation — 6"w x 6 "h (152 x 152) damper is offset in the damper sleeve for appropriate damper MAXIMUM SIZE placement within the wall or floor. Single section Vertical Installation CURTAIN FIRE DAMPERS DIBD2 - 331v x 36 "h (838 x 914) STATIC FIRE DAMPERS DIBD20 - 331v x 36"h (838 x 914) Not for use in dynamic (fans on) systems. Horizontal Installation DIBD2 - 241vx16 "h(610x457)or MINIMUM SIZE 181v x 24 "h (457 x 610). Vertical Installation —4'w x 4 "h (102 x 102). DIBD20 -241v x 18 "h (610 x 457) or Horizontal Installation — 6"w x 6 "h (152 x 152). 18'w x 24 "h (457 x 610). MAXIMUM SIZE COMBINATION FIRE AND SMOKE DAMPERS Single section Vertical Installation MINIMUM SIZE IBD2 - 48"w x 30 "h (1219 x 762) or FSD35 — 5"w x 6"h (127 x 152). 30"w x 48 "h (762 x 1219). FSD36, 37, 60, 60-2 — 8"w x 6 "h (203 x 152). IBD20 - 48"w x 30 "h (1219 x 762) or MAXIMUM SIZE 30 "w x 48 "h (762 x 1219). FSD35, 36, 37, 60, 60 -2 — 32"w x 48 "h (813 x 1219) or 48 "w x IBDT - 40"w x 32 "h (1016 x 813) or 32 "h (1219 x 813). 32"w x 48"h (813 x 1219). Horizontal Installation INSTALLATION SUPPLEMENTS IBD2 - 8" x 14 "h (410 x ) or 18"w Refer to the appropriate Ruskin installation operation instructions IBD20 - 24"w w x 18 "h (6 110 x x (457 1 supplements for special requirements: w x 24"h 4 61 577 610). or 457) 18 "w x 24 "h (457 x 610). • Drivemate No. 14880 Breakaway Connection IBDT - 24"w x 12 "h (610 x 305). • Flanged System Breakaway Connection • Optional Sealant of Dampers in Fire Rated Wall or Floor Note: Dimensions shown in parentheses ( ) indicate millimeters. Openings • Cavity Shaft Wall Metal Stud Framing • Extension of Fire and Combination Fire and Smoke Damper Sleeves OS SEE COMPLETE 0 MARKING ON �L us PRODUCT California State Fire Marshal Listing No. 3225-245:005 California State Fire Marshal Listing No. 3225 - 245:102 paBD Style G .705IRepieces 11•IBD20G •702 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. O Ruslun 2005 T :� Air Commodities /Oregon . Fig ° A DIVISION OF AIR COMMODITIES INC. HEATING • VENTILATING • AIR CONDITIONING EQUIPMENT • ° A n �, �, ; ,' "= PROJECT: '` FANNO 'CREEK P LACE - = BUILDIN '_ = je,R T. -.:' S 4 �. `9 . ,t :`� -,, z..n..:•• -+,' y' ,,;, ... -.. , � ..;.:ti '•; _ ..3• • deal :� r 4d'., , s., :dnr , r...,., � -:- LOCATION: TIGARD`OR,� �;',, ��";.� k. ✓:9.. i _ , a �7 :..A • \?:S , Nt •Crf�p'J -r--: - • ▪ • i• • . ,, . •-, a 4..1,- „ . ARCHITECT: ri ' - ,. ,,;,, �;,'r.;: -, ^; _x:- -- ~.l94 t. .., ENGINEER ;44,..1.,:,,,,i, `ti::�:,,-fi':f:..�,:; = ; . ,, - :1 i s'� Y, ti • . - a..it• .C c , ‘.,"1` � R .': : : q. • ?.',� 4, 4,:,7.....,....- ■ %, ,4- _ <d` • s ` r;3� .:1•-\'-‘,'”' ,o- + �.'`il.FC , a a1. , -, Y ' l ti xi $; ., 'x,z ▪ rr_ ;�i'� _, - d �'= - - -.ay.; - -;;. ,y:� ; a -C - '+ `_- rb‘.'x - ,;s. CONTRACTOR , H VAC I ��.•',� = - .. • . ` % ` - .' F ; . ;. t!4 `,1 A.. L r l '.:.J•N `r -y'l. yam r 'ly. �:.,,:;? y . =- ` - - - S '' F „ _ ,j •.. "1 m' ; •.ei�X- +- :•Y fl i➢:S:41..15..,i; °ki• 7_.11. , ,, `' , - -, ',. -;�> ctct'''j''t' '4"'"i,•a_ ;' :�t:;cl.. • :. 1,Y.t,., - ,0-- �' ,:, z, -.2, : ti . ;i 1 . i ! fL ` ., �... CONTRACTOR PO #: .. ; ,� r_'_:- :.,-,..;,- ,j k � ` •- :', ,._'. ,-.7 va ' - ; :: :,.,; .tip, = ,,',r •: 7 , —; � ,l - s= - -- ▪ r,-.. - : - :y ,= 1.i, :` r: � �':e,.r s ^ ft. r)•?�•'; •' t - a . y . ,... y .._ y - , .i - � a+`: •riv -. - • t.r , `;`;::>,: .,,,.! C- , ^ !“;:'.C•:', DATE SUBMITTED: r:,Se `200 � - ai ., . . a,., ,. �- -, �;; k 'c : f ,--o-+` - - - , � , .- x;i .; ,.. `:::-;,,,-...,.1,..,,,,,,,,,, r , '1' g.,. -r a,•. u',-i.. .1. i •. c .1 'i t'%. ; � +: s' '* - A•1. 'i j ? , ; ' : = ':.:�:1 ; AC /O CONTACT: !� I TH HAWKINS. ..p- :. .' . N -I' - � .: - ;1,-, :•5ti : - - y `�'^. t,_ s- x J, M1 -� i� � ,,, l r_ ? •,-..,-.-, �' ;k'.. r - ':- ••� - cri= ..,:�:,:axa'}'�:rvi$r^'. `.[� -. ;:,', �w•... ,. ,. -r dr i . ' ,• f- '" ti v ..4 • .• 4.. : ;i. .;1. . , te.': *._ .. ,. ,- - S.' •,: - ': .;,: �. y,'Y ti .3 r� �� L :w . :. j� , - ��JV V' ��.„ IZ,� 1 ▪ �i - � , w , •:-, : w •:: x AC/0 QUOTE # : S 99337 , , ' i' . �:' ,'•I . 0 ; ,,. r y. d ' , I:ir ,, , ... ' i1. *< .. . e1..i . i,� ; a ;, . 1; . � �. :' ' • ..- - : "Y �: ,H 7 •a .T d. '. • .;r:_ rr• > ' „r ^ l �'8 - ':'; ;r ,.. -`: a.a,, .. , . .- .._ -:,t 7, 6�7 '7 ;n-,: <u'+•; Y �i” - •' 1;,; � is : - 4.:,., , 'K,, y:;�.a <d;ei.�,;,-tv,L "- , ,v' ,l' \�,' li �r. � � i��, ■ 1.,: v`''i., :i1. ` e , `-';:: ` .7 �;;,, ITEM SUBMITTED: � XH A r U S Ti FAN & ;R +H ; , ,': `" ''�' ,.. �.3•� _:zy;.. .i ^ ,, w Y , NL :[. . v 1, : • ` 1, . MANUFACTURER LOREN COOK COMPANY ; ,� =- "' : {please see attached literature) , ,,,,tws,. „. 1. ,:,,,?' ?I,.- :4,,,'l. ;',T• i`^4. L 9..„ k. ,+31.: ...„.„,,,,: ,.„,,,,,_.....„,,,,,,,.„,.,,,,, ..,,,,:,,,:„.i.--ic...;t- 4 , 1500 N.E. SANDY BOULEVARD, PORTLAND, OR 97232 - (503) 238 -6900 FAX: (503) 238 -8764 1- 800 -575 -2473 • • �' MARK: REF -1 COMO S4 1� 1 O -1.."1' PROJECT: FANNO CREEK BLDG A Y, c �L us DATE: 09 -11 -2006 ACE-D • Downblast Centrifugal Exhaust Ventilator B Roof Mounted /Direct Drive AIMMIli ---- STANDARD CONSTRUCTION FEATURES: All aluminum housing - Backward inclined all aluminum wheel - Two piece top cap with stainless steel quick release latches amok (sizes 120 - 180) - Welded curb cap corners - Birdscreen - Permanently lubricated ball bearing motors - Corrosion d r w ilmilli I � �_ c resistant fasteners - Transit tested packaging. I1.MI ER. i A. } I- T Sq. —..i I Performance Dimensions (inches) Catalog Flow SP Fan Bhp A 3 -5/16 Qty Number (CFM) (inwc) RPM (HP) B 37 -11/16 1 180C1OD 2330 .375 787 .279 C 33 -15/16 Altitude (ft): 39 Temperature (F): 70 G 3 Motor Information T Sq. 30 HP RPM Volts /Ph /Hz Enclosure Roof Open. Sq.* 25 -1/2 3/4 1075 115/1/60 ODP Unit Wt(lbs)*** 143 Roof opening size for curbs supplied by Cook only "'Includes fen, motor 8 accessories Sound Data 8 Octave Bands dB (10 -12 Watts) 1 2 3 4 5 6 7 8 LwA dBA Sones 70 71 70 65 56 51 47 67 56 7.7 Accessories: Fan Curve STD DISCONNECT 1.25 .334 BD -24 DAMPER ROOF CURB RCG 28 -9.5 H FAN SPEED CONTROLLER 10 AMP 120 VOLT il'�\ 100 i Ellin .267 i 0.75 , , , .200 SP A Power (inwc) .-E■11111, (HP) 0.50 4.11111101111111 .134 Fan Curve Legend Aniiili, 1 CFM vs SP (787) 0.25 .067 f- - CFM vs HP 100% FSC (1075) 50% FSC (638) _ — 0.00 System Curve — — • 0 800 1600 2400 3200 4000 Point of Operation 0 Flow (CFM) v5 2 15 9721 M 1CookwarelJOBSlkeithhl 2 ..1, MARK: REF -2 C O OI PROJECT: FANNO CREEK BLDG A ;t:4 c ® us DATE: 09 -11 -2006 • ACE -D • Downblast Centrifugal B Exhaust Ventilator Roof Mounted /Direct Drive STANDARD CONSTRUCTION FEATURES: i AIRL. All aluminum housing - Backward inclined all aluminum wheel - Two piece top cap with stainless steel quick release latches : c (sizes 120 -180) - Welded curb cap corners - Birdscreen - __ Permanently lubricated ball bearing motors - Corrosion di Ir_iiii resistant fasteners - Transit tested packaging. IW l. d A 1 G r-- --...I _ T Sq. 1 4 Performance Dimensions (inches) Catalog Flow SP Fan Input A 2 -1/2 Qty Number (CFM) (inwc) RPM Watts . B 18 -3/4 1 100C15DH 430 .250 1135 - 110 C 16 -13/16 Altitude (ft): 39 Temperature (F): 70 G 2 Motor Information T Sq. 18 HP RPM Volts /Ph /Hz Enclosure Roof Open. Sq.* 13 -1/2 1/8 1550 115/1/60 ODP Unit Wt(lbs) * ** 54 • Roof opening size for curbs supplied by Cook only "'Includes fen, motor & eccessones Sound Data 8 Octave Bands dB (10 - 12 Watts) 1 2 3 4 5 6 7 8 LwA dBA Sones ,63 67 57 52 63 - 52 6.1 Accessories: Fan Curve STD DISCONNECT 1.25 150 BD -12 DAMPER ROOF CURB RCG 16 -9.5 H FAN SPEED CONTROLLER 5 AMP 120 VOLT 1.00 i 120 !bald 0 SP..;■,■■ Input ' (inwc) ..■.,u Wafts 0.50 1111112111111111N 60.0 Fan Curve Legend .■■,IIIIII', CFM vs SP (1136) 0.25 li,'® ,■- 30.0 CFM vs Watts 10 FCC (7 5) �� ®,",_ 0.00 60% FSC (775) System Curve - - • 0 200 400 600 800 1000 Point of Operation 0 Flow (CFM) v5 2 15 9721 M 1CookwareUOBSlkeithhl PROJECT: FANNO CREEK BLDG A DATE: 0941 -2006 • FSC • Fan Speed Controls STANDARD CONSTRUCTION FEATURES: PRODUCT DESCRIPTION - Through the "Quadrac" integrated semi - conductor device it is now possible to offer this system with many advantages. Fewer semi - conductor parts mean greater reliability and the passivation process used in the manufacture of the semi-conductor insures long life. Printed circuit construction eliminates wiring difficulties and guarantees workmanship. All of these factors serve to offer the most important of all features - quality. SPEED CONTROL - Positive Off /On action in the control dial. Speed range set to the customer's requirements. CONTROL RATING -120 volts, 60 cycles, 1 phase. Maximum ambient temperature - 120 degree F (5 AMP, 10 AMP, 15 AMP). 2201240 volt, 50160 cycles, 1 phase. Maximum ambient temperature -120 degree F (5 AMP, 10 AMP). 220/240 volt model not UL listed. Fan cannot have UL listing if furnished with prewired 2201240 volt FSC. 277 volt, 60 cycles, 1 phase. Maximum ambient temperature -120 degree F (5 AMP). WARNING - Power must be turned off before installing this unit. STANDARD INSTALLATION - Fits any standard single gang box. Turn off power and connect the two wires on the control to the two switch wires in the usual manner. The connection box is not supplied. SPECIAL FEATURES - Complete range control, solid state "Quadrac" integrated circuitry, solid state construction for long reliable operating life, saves on electric bills. FS -5 Dimensions (Inches) • 4-1/8" 2 1/4" Mark Qty Description . d - Y REF -1 1 FSC 10 AMP 120 VOLT - I - 1 - 1/2" I' 1 I 1/4" REF -2 1 FSC 5 AMP 120 VOLT O V O FS -10 ® 4-1/2" 2 -1/2" i l 4- 3/8 "---I 3/4 "--I I--- I -- i 1 -3/8" CD 0 Uh WIRING DIAGRAM FS' MOTOR CO L2 "`YYY VS 2 ' �' ' PROJECT: FANNO CREEK BLDG A i t !F S l ; ' '" L DATE: 09 41 -2006 BD Gravity Backdraft Damper STANDARD CONSTRUCTION FEATURES: .02 Aluminum blades - .06 aluminum frame - Aluminum hinge pins - Nylon bushings. : ,, „.,‘.„ ,, _ v I Air ;i �� Flow A I o B o : . Li I.. C Sq. -I Dimensions (inches) Mark Qty Description A Max. B C Sq. # Panels REF -1 1 BD -24 DAMPER 5 -3/16 1 -7/8 23 -3/4 1 REF -2 1 BD -12 DAMPER 5 -3/16 1 -7/8 11 -3/4 1 f V5 2 r '. �`' ' PROJECT: FANNO CREEK BLDG A /MMM 4 ..., Mr J I( DATE: 0941 -2006 RCG - Galvanized Steel Roof Curb STANDARD CONSTRUCTION FEATURES: C Wood Nailer 18 gauge galvanized steel - 1-1/2", V Sq. 3 lbs. density thermal and acoustical 1 F Sq. '1 j insulation - Continuously \ } Wood nailer. Y welded corners - \ \ 00 — -{ Options:(As noted below *) Ht. 1) No wood nailer (deduct 1 -112" for actual height). 4 2) Damper P Y Dam tray. I II:! A , _ __ 1 W S Optional Damper Tray Insulation Roof Opening Dimensions (inches) Roof Mark Qty Description Ht Options* A F Sq. V Sq. W Sq. Opening _ REF -1 1 RCG 28 9.5 1 -1/2 28 -1/2 32 -1/2 21 -3/4 25 -1/2 REF -2 1 RCG 16 9.5 1 -1/2 16-1/2 20 -1/2 9 -3/4 13 -1/2 V5 2 MARK: RH -1 4< ' ' 4 � .e � PROJECT: FANNO CREEK BLDG A ° " ' ,-. DATE: 09 -11 -2006 . Gravity Relief Ventilator \ \_ STANDARD CONSTRUCTION FEATURES: � � � Heavy gauge aluminum construction - Birdscreen - Radius throat - Rain gutter to prevent rain infiltration - Welded curb cap corners - Integral lifting lugs /tle down `��e points - Hinged hood standard on throat lengths less \ than 73" - Five year warranty. c D E I f ° 1- _ G e � H Performance Dimensions (inches) Catalog Flow SP A 24 Qty Number (CFM) (inwc) B 24 1 24X24GR 1350 .021 C 37 Altitude (ft): 39 Temperature (F): 70 D 39 Accessories: E 12.26 ROOF CURB RCG 28X 28 -9 5 H F 2 Notes: G 29.5 INC'S RUSKIN CD36 DAMPER, WIHAND QUAD, 24X24 H 29.5 J 4 Unit Wt(Ibs) * ** 135 "Includes aaessones L - v5 2 15 9721 M \Cookware\JOBS\keilhh\ , , ,.. RUSKIN® ... 3900 Dr. Greaves Rd. • Kansas City, MO 64030 • (816) 761 -7476 • FAX (816) 765 -8955 CD36 LOW LEAKAGE CONTROL DAMPER - GALVANIZED STEEL STANDARD CONSTRUCTION FEATURES FRAME The CD36 offers sturdy, steel construction with interlocking frame 5° x 1" x 16 gage (127 x 25 x 1.6) galvanized steel hat channel rein- design. Damper locks together without bolts, screws, or rivets that forced with corner braces for structural strength equal to 13 gage could shake loose. Frame corners are internally braced to reduce (2.28). Low profile 3 x 3 /a' x 16 gage (89 x 10 x 1.6) galvanized racking. steel channel top and bottom frame on dampers under 13" (330) high. Axles positively lock to blades without screws or welds. Non - stick, BLADES noncorrosive bearings assure long life and ease of operation. Axles 6" (152) wide, 16 (1.6) gage galvanized steel blades approximately 6° and bearings combine with a shake proof linkage for low mainte- (152) on center. Parallel or opposed action. nance operation. SEALS When tested In accordance with AMCA Standard 500, the CD36 Blade edge is PVC coated polyester fabric mechanically locked into also exhibits low leakage performance that exceeds the frequently blade edge. Jamb is flexible metal, compression type. specified, 10 cfm /sq. ft. at 4" w.g. requirement BEARINGS OPTIONS Synthetic. Options available at additional cost include: LINKAGE • Concealed In frame. Exposed linkage optional. Enamel and eedeu a • Factory-installed, ctory- installed, , pneumatic and electric actuators. AXLES • SP100 Switch Package to remotely indicate damper blade posi- 1 /2 " (13) plated steel hex. tion. CONTROL SHAFT • Heavier frame construction with U- channel frame. 6° (152) x 1 /2 ° (13) diameter. Outboard shaft support bracket supplied • Front, rear or double flange frame with or without bolt holes. with all single section dampers for field mounted actuators. Factory- • 304 stainless steel construction. installed jackshaft supplied with all multiple section dampers. • Thrust washers for vertical blade installation. MAXIMUM SIZE . Single section - 48 "w x 72 "h (1219 x 1829). Multiple section assembly - Unlimited size. - MINIMUM SIZE Single blade - 5"w x 5°h (127 x 127). Two blades, parallel or opposed action, exposed linkage - 8"w x 14 "h 0 (203 x 356). Two blades, parallel or opposed action, concealed linkage - 5'w x 10 "h (127 x 254). Illk- TEMPERATURE LIMITS -25 °F ( -32 °C) minimum and +180 °F (+83°C) maximum. SHIPPING WEIGHT Approximately 7 lbsisq ft. NOTES Or' • • Dimensions shown in parenthesis ( ) indicate millimeters. • Units furnished approximately 1/4° (6) smaller than given opening If il ■ 111411 't '... dimensions. ( ' Ili ` Height Width - Spec CD36- 70dIReplaces CD38 -104 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. ORuskln 2004 • '_ ti�r ,�.�� �, ;�) PROJECT: FANNO CREEK BLDG A _!�' ,.�. DATE: 09 -11 -2006 4 RCG Galvanized Steel Wood Nailer STANDARD CONSTRUCTION FEATURES: I- E x F 1 18 ga. galvanized steel -1- 112 "(3.81 cm), 3 lbs. /cu.ft.(1.36 kg /cu. meter) density B thermal and accoustical insulation - ( o 7 Continuously welded corners - Wood nailer. :0 , Ht Options:(As noted below *) Optional I i d 1) No wood nailer Damper P Tray 2) Damper tray gel Insulation Note: y — L c 1.- --1 c_}.-- a Roof Opening is (E - 3) X (F - 3) B B A — A Dimensions (inches) Roof Mark Qty Description Ht Options* A B C E F Opening - RH -1 1 RCG 28X 28 9 5 2 1.5 1.875 28 28 25 X 25 VS 2 , •w ELECTR CHI II II II ir. SS LIn 6 HVAC Advanced Products Division Sprrt- ductless A/C and Heat Pumps '"`*' - J' T� -J'" -n- , .F r.,w • r.... -. - "F_> • :',SUBMI DATA MSY ON-A & � 7100 L4NI�' , 3iii i tu%haW M'OU TED JAL,_,; GiiiiiiEMt Job Name: Location: Date: Purchaser: Engineer. Submitted to: For ❑ Reference ❑ Approval ❑Construction Unit Designation: Schedule No.: GENERAL FEATURES �" - r r = 7— °'' ! i Remote � - + -- . • Controller • Limited warranty: one year on parts and defects and six years on compressor , • Compact side discharge outdoor unit e :. I • Zone control ' 1 • Wireless remote controller c" - ^ e ' - "t .. r^ = � " - c ' ' • Automatic fan speed control - _ rr;< t,' - .. .; • Quiet operation 1.• ---.' ' - both ind oor and outdoor units =`* ice' =` ' %�~: `' s - iy^ _� \ ' `V � ~ � • Auto restart following a power outage • Self check function - onboard diagnostics Indoor Unit NSY A24NA Outdoor Unit MUY A24NA • Advanced microprocessor control Outdoor Unit Rated capacity 22,000 Btu/h Compressor DC inverter /twin rotary Minimum capacity 4,400 Btu/h MCA 17 SEER 16.0 Btu/h/W Fan motor 0.93 F.L.A. Total input 2880 W Sound level 55 dB(A) Power supply 208 / 230V, 1 Phase, 60 Hz DIMENSIONS INCHES MM . Breaker size 20 A W 33-1/16 840 _ Voltage D 13 330 Indoor - Outdoor S1 -S2 H 33 -7/16 849 Indoor - Outdoor S2 -S3 Weight (lbs/Kg) 128 / 58 Indoor - Remote Controller Refrigerant type R410A Indoor unit Refrigerant pipe size O.D. (inches/mm) MCA 1 0 A gas side 5/8 / 15.88 Fan motor 0.76 F.L.A. liquid side 1/4 / 6.35 Fan motor output Max. refrigerant pipe length (ft/m) 100 / 30 Airflow (Lo- Med -Hi) 296 - 431 -568 Dry CFM Max. refrigerant pipe height difference (ft/m) 50 / 15 265 -385 -508 Wet CFM Connection method flared Sound (level) (Lo- Med -Hi) 34 -40 -49 dB(A) DIMENSIONS INCHES MM inches W 43 -5/16 1100 D 10 -1/4 260 NOTES : H 12 - 13/16 325 •1. Rating conditions (coding)- Indoor : D.B. 80 °F, W.B. 67 °F outdoor : D.B. 95 °F, W.B. 75 °F. Weight (lbs/Kg) 37 / 17 Field drain pipe size I.D. (inches/mm) 1/2 / 12.7 Operating range Indoor intake air temp Outdoor intake air temp Cooling Maximum D.B 95 °F, W B 71 °F D B 115 °F Minimum D.B 67 °F, W B 57 °F D.B 0°F ' • With wind baffle ustatled. If not ineaned, the minimum temperance win be 23 1 ( Notes: r _ • DIMENSIONS ".-'7:':---- SY A 24N A ,& MUY ‘_-_.-I 24NA i ..„, • MSY -A24NA MUY -A24NA 42 -1/16 I Drainage hole [ 1-5/8 `{ 20 9/32 1 -9/16 _ I / �= ----- c4 ,' R irin ‘....... ■ltlllll.ttll..... �� . Air in {> I ' 43 -5/16 - - - -- - .:, I Air out : 4 -3/8 0 13/16 Oval hole 19 -11/16 co I 3 -3/16 iiramil 33- 1/16 c+i N a 2 -3/16 I ... 31 -1/8 j 9 -15/16 n I I 2.5/16 r - -}r3'4 thilltd:1\111 // -�� I I , �° --_, F. c :P1 kk or I Wireless remote controller 10 -1/4 3/16 — – Air in Installation plate Ilk Liquid line [ 1/4 19 -11/16 Ill/ Gas line [ 5/8 16 -15/16 Insulation [ 1- 15/160.D [ 1- 1/41.D 0 Drain hose [1/2 ID, 5/8 OD] Air out (Connected part O.D) Insulation [ 1 -1/8 pERFOR ANCE .'�' - :. , A MITSUBISHI , �•GERTIFIEp t'sTeo ® PARTNER' ELECTRIC HVAC Advanced Products Division ii • Mitsubishi Electric & Electronics USA. Inc. 3400 Lawrenceville Suwanee Rd Suwanee, GA 30024 i Tele. 678- 376 -2900 • Fax. 800- 889 -9904 Toll Free: 800 -433 -4822 (#3) www.mehvac corn C SD - MSY -A24NA / MUY -A24NA - 1 - 200604 0 MITSUBISHI ELECTRIC / HVAC 2006