Permit CITY OF T I G A R D MASTER PERMIT
r
PERMIT #: MST1999 -00315
n
��l DEVELOPMENT SERVICES DATE ISSUED: 10/21/1999
�� II 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171
SITE ADDRESS: 12005 SW TREEVIEW CT PARCEL: 2S110BB -06300
SUBDIVISION: REDWOOD VISTA ZONING: R -4.5
BLOCK: LOT: 005 JURISDICTION: TIG
REMARKS: PATH I: New single family dwelling w /attached garage.
BUILDING
REISSUE: STORIES: 2 FLOOR AREAS REQUIRED SETBACKS REQUIRED
CLASS OF WORK: NEW HEIGHT: 23 FIRST: 1,296 sf BASEMENT. sf LEFT: 5 SMOKE DETECTORS: Y
TYPE OF USE: SF FLOOR LOAD 40 SECOND. 1,270 sf GARAGE: 680 sf FRONT: 22 PARKING SPACES : 2
TYPE OF CONST: 5N DWELLING UNITS: 1 FINBSMENT. sf RIGHT: 6
VALUE: $ 194,811 42
OCCUPANCY GRP• R3 BDRM: 4 BATH. 3 TOTAL: sf REAR: 39
PLUMBING
SINKS: 1 WATER CLOSETS: 3 WASHING MACH: 1 LAUNDRY TRAYS. 1 RAIN DRAIN: 100 TRAPS:
LAVATORIES: 5 DISHWASHERS: 1 FLOOR DRAINS: SEWER LINES. 100 SF RAIN DRAINS 1 CATCH BASINS:
TUB /SHOWERS. 3 GARBAGE DISP: 1 WATER HEATERS: 1 WATER LINES: 100 BCKFLW PREVNTR. 1 GREASE TRAPS:
OTHER FIXTURES:
MECHANICAL
FUEL TYPES FURN < 100K: BOIL/CMP < 3HP: VENT FANS: 5 CLOTHES DRYER: 1
GAS FURN > =100K: 1 UNIT HEATERS: HOODS: 1 OTHER UNITS: 1
MAX INP: btu FLOOR FURNANCES: VENTS: WOODSTOVES: GAS OUTLETS: 1
ELECTRICAL
RESIDENTIAL UNIT SERVICE FEEDER TEMP SRVC /FEEDERS BRANCH CIRCUITS MISCELLANEOUS ADD'L INSPECTIONS
1000 SF OR LESS: 1 0 • 200 amp: 0 • 200 amp: W /SVC OR FDR: 1 PUMP /IRRIGATION: PER INSPECTION:
EA ADD'L 500SF: 5 201 - 400 amp: 201 - 400 amp: 1st W/O SVC /FDR: 00 SIGN /OUT UN LT: PER HOUR:
LIMITED ENERGY: 401 • 600 amp: 401 • 600 amp: EA ADDL BR CIR: SIGNAL/PANEL: IN PLANT.
MANU HM /SVC /FDR: 601 • 1000 amp: 601 +amps•1000v MINOR LABEL:
1000+ ampNolt :
PLAN REVIEW SECTION
Reconnect only:
>=4 RES UNITS: SVC /FDR> =225 A.: > 600 V NOMINAL: CLS AREA/SPC OCC:
ELECTRICAL • RESTRICTED ENERGY
A SF RESIDENTIAL B. COMMERCIAL
AUDIO & STEREO: VACUUM SYSTEM: X AUDIO & STEREO: FIRE ALARM. INTERCOM/PAGING: OUTDOOR LNDSC LT:
BURGLAR ALARM: X OTH: IRRIGATION BOILER: HVAC: LANDSCAPE/IRRIG: PROTECTIVE SIGNL:
GARAGE OPENER: CLOCK: INSTRUMENTATION: MEDICAL: OTHR:
HVAC: DATA/TELE COMM: NURSE CALLS: TOTAL # SYSTEMS:
Owner: Contractor: TOTAL FEES: $ 5,989.68
FOUR D CONSTRUCTION FOUR D CONSTRUCTION This permit Is subject to the regulations contained In the
FO R BOX CONSTRUCTION
FO FOUR
BOX CONSTRUCTION Tigard Municipal Code, State of OR. Specialty Codes and
BEAVERTON, OR 97075 BEAVERTON, OR 97075 all other applicable laws All work will be done in
accordance with approved plans. This permit will expire if
work is not started within 180 days of issuance, or if the
work is suspended for more than 180 days. ATTENTION
Phone: 590 -0805 Phone: Oregon law requires you to follow rules adopted by the
ORIGINAL Reg #: LIC 000710 Oregon Utility Notification Center. Those rules are set
forth in OAR 952 - 001 -0010 through 952 - 001 -0080 You
may obtain copies of these rules or direct questions to
OUNC by calling (503) 246 -1987 .
REQUIRED INSPECTIONS
Erosion 844 -8444 Underfloor insulation Plumb Top Out Low Voltage Water Line lnsp Mechanical Final
Footing Insp Crawl Drain /Backwater Electrical Service Gas Line lnsp Sprinkler Rough -In Plumb Final
Foundation Insp Footing /Foundation Dr; Electrical Rough In Gas Fireplace Sprinkler Final Final inspection
Post/Beam Structural PLM /Underfloor Framing Insp Insulation Insp Appr /Sdwlk Insp Building Final •
Post/Beam Mechanical Mechanical Insp Shear Wall lnsp Rain drain Insp Electrical Final
Issued B : 14w ` ---1 Permittee Signature : —/
i
Call (503) 639 -4175 by 7:00 p.m. for an inspection needed the next b , ness day
CITY OF TIGARD Residential Building Permit Application Plan Che -. ?.:. 1 /4 /L
• 13125 SW HALL BLVD. Additions or Alterations Recd By _ 1 1,i■
. _
Date Rec'd
TIGARD,'OR 97223 Single Family Detached or Attached (Duplex) Date to P.E. �
V 503 - 639 -4171 Date to DST y -2 / - l! 4
F 503 - 684 -7297 'Vr Permit #1tt5r /9% 31 3/5'
Print or Type Called 7 - p7 - j r �j
Incomplete or illegible applications will not be accepted 5. wR 1494 - 00 49
Atm
Name of Project Name
Job ?-P -- tJ ra U! S7', - .(2Z4A1 .41-/.1 CG c‘.2./ V-- „oss•a
Address Site Address Archite Mailing Address
1.2 0os .S u 7�ewtek7 et
/3 n s AKA). /
C
/► /� it /State Zip Phone
Name •
(4 le— -ia L.f. rh ST: eli— ��.�1ru� 97.643,' Z�S =J� /�
Owner M *g Add N e .
?, /S 7 7o 4./.4- Ak .e•-Jut-co;-:,
Engineer Mailing Address _ e
City/State -- ....,,�� Zip Phig�e g 1,1.5 _.C /a 2---- .0--o . h X97 S fO -Cat
/State Zip Phone
General Name ,e%G,�r,,v,( 97,2/ L' � 29Z
Contractor 3r-1,e e7 t .577 6... Describe work New X Addition 0 Alteration 0 Repair 0
/tailing Address to be done:
Prior to permit � r �)► 4.5-77 Additional Description of Work: �� _ 1
issuance, a copy /State 7 ' Zip Phone N
of all licenses . ,e 4 La. r 11 •o,. 97,7:r c
are required if Oregon Const. Cont. Board Exp. Date PROJECT , / ,/ Z
expired in COT Lic.# _ a VALUATION $ /
database 7/ 0.3 / - --- — —
Mechanical Name NEW CONSTRUCTION O�Y:
Sub- !re-/ , f /s,AeT /A y Sq. Ft. House: Sq. Ft. Garage
Contractor Maiess i ,! ,. s CC. (0 (9'Od
Prior to permit / 5.2e -CA) 7rogi Indicate the restricted energy installation by the electrical
issuance, a copy City /State Zip one subcontractor in the following areas
of all licenses 77q ,jJ q .3 4. - '3 Restricted Audio /Stereo
are required if Or n Const. Cont. Exp. Date Energy System Alarms
i expired in COT Lic.# r/ / s.7o Installations Vacuum Irrigation
database (p x System System
Plumbing Name (check all that Other:
Sub- -- . ' '+ ( 4 /e apply)
Contractor Mailing Address Corner Lot ` YES NO Flag Lot YES NO
(check one) A (check one)
)3,2 Si0 -511r / 1 ✓Z- Has the Subdivision Plat recorded? N/A YAS NO
Prior to permit City/State 4p Phone
issuance, a copy '?ice '' 644 . 3//
of all licenses are Oregon Const. Cont. Board Exp. Date
required if Lic.# f g o . ," .,
expired in COT ! I hearby acknowledge that I have read this application, that the
database Plumbing Lic. # Exp. Date information given is correct, that I am the owner or authorized agent
of the owner, and that plans submitted are in compliance with
7 Q' 4/c/ PO Oregon State laws.
Name Signat f Ow / nt Date
Electrical O G 9 /�39
/� �PG?S ,��Aa
Sub- Mailing Address AP ame Phone #
! 'T� „ f
Contractor ' 2.s- ' £dd
City/State Zip Phone 72 a - 745
Prior to permit te,TL A ^��
issuance, a copy �7e �,( FOR OFFICE USE ONLY:
of all licenses are Oregon Const. Cont. Board Exp. Date
required if Lic.# G 2 Plat # , : _ Map/TL #:
expired in COT / „3� C� � (l -A_3_ a / Oo'r - 4)54c
database Electrica � C Exp. Date Setback Zone: t . ` i � Solar:
5 J
Electrical auoprvisor Lic. # Exp. Date Engineering Approval: Planning Approval: TIF:
.a d'6 S D PArlc 4,97r
1-.1
is \dsts \forms\sfaddalt.doc 11/20/98
•
06/15/2000 Activities for Case #: MST1999 -00315 _
3:22:41 PM
Assigned Hold Updated
•
Activity Description Date 1 Date 2 Date 3 To Done By Disp. Level By Updated Notes
MSTA005 Application received 09/15/1999 DEB RECD No Hold GEO 09/20/1999
MSTA008 Permit Created 09/20/1999 GEO DONE No Hold GEO 09/20/1999
MSTA010 Check for prcl. restrict. 09/20/1999 GEO DONE No Hold GEO 09/20/1999 There is a 15' public storm drain
easement across the rear of the
property.
MSTA012 Plans routed to Plans Examiner 09/20/1999 GEO SENT No Hold GEO 09/20/1999
MSTA026 Plans approved by Pln Examiner 09/21/1999 BT2 DONE No Hold BT2 09/21/1999
MSTA030 Reviewed plans routed to DSTS 09/21/1999 BT2 DONE No Hold BT2 09/21/1999
MSTA700 Erosion 844 -8444 09/20/1999 09/20/1999 No Hold BT2 09/20/1999
MSTA705 Footing Insp 09/20/1999 09/20/1999 10/26/1999 KS FAIL No Hold JS 10/26/1999 Not rsapy.
MSTA706 Foundation Insp 09/20/1999 09/20/1999 10/26/1999 KS FAIL No Hold JS 10/26/1999
MSTA710 Post/Beam Structural 09/20/1999 09/20/1999 11/17/1999 LN PART No Hold VT 11/17/1999 CMA
1. install post bracing on 4' or
greater posts
2. extend all thread NW corner
3. install anchor bolt adjacent to
over notched green plate@
garage
4. clean debris & straighten
visqueen
Partial Approval
MSTA711 Post/Beam Mechanical 09/20/1999 09/20/1999 11/17/1999 LN PASS No Hold VT 11/17/1999 CMA, Mechanical Post & Beam
- Pass
MSTA712 Underfloor insulation 09/20/1999 09/20/1999 No Hold BT2 09/20/1999
MSTA713 Crawl Drain /Backwater valve 09/20/1999 09/20/1999 11/09/1999 MS PASS No Hold DGW 11/10/1999 Low points run to greenway
MSTA714 Footing /Foundation Drain 09/20/1999 09/20/1999 No Hold BT2 09/20/1999
MSTA717 PLM /Underfloor 09/20/1999 09/20/1999 11/09/1999 MS PASS No Hold DGW 11/10/1999
MSTA720 Mechanical Insp 09/20/1999 09/20/1999 03/01/2000 KBS FAIL No Hold AKJ 03/01/2000 1) gas piping not installed
2) conn exhaust fans
3) secure insul shield at attic
and maintain clearance
4) supp b vent at horiz at attic
5) supp ducts at attic
MSTA722 Plumb Top Out 09/20/1999 09/20/1999 02/11/2000 MRS PASS No Hold AKJ 02/13/2000 missing nail plates gar
MSTA723 Electrical Service 09/20/1999 09/20/1999 03/01/2000 CD PASS No Hold AKJ 03/01/2000
MSTA724 Electrical Rough In 09/20/1999 09/20/1999 03/01/2000 CD PASS No Hold AKJ 03/01/2000
MSTA725 Framing Insp 09/20/1999 09/20/1999 No Hold BT2 09/20/1999 WILL NEED SPRINKLER
PERMIT BEFORE FRAMING
INSPECTION CAN BE MADE
MSTA726 Shear Wall Insp 09/20/1999 09/20/1999 02/17/2000 KS FAIL No Hold AKJ 02/17 /2000 corr not complete
Page 1 of 4
06/15/2000 Activities for Case #: MST1999 -00315
3:22:41 PM
Assigned Hold Updated
Activity Description Date 1 Date 2 Date 3 To Done By Disp. Level By Updated Notes
MSTA728 Low Voltage 09/20/1999 09/20/1999 No Hold BT2 09/20/1999
MSTA735 Gas Line lnsp 09/20/1999 09/20/1999 03/01/2000 KBS FAIL No Hold AKJ 03/01/2000 not installed
MSTA736 Gas Fireplace No Hold BT2 09/20/1999
MSTA740 Insulation Insp 09/20/1999 09/20/1999 03/09/2000 KBS PASS No Hold AKJ 03/09/2000
MSTA752 Rain drain Insp 09/20/1999 09/20/1999 No Hold BT2 09/20/1999
MSTA760 Water Line lnsp 09/20/1999 09/20/1999 11/09/1999 MS . PASS No Hold DGW 11/10/1999 Water service OK
MSTA762 Sprinkler Rough -In 02/24/2000 KS PASS No Hold AKJ 02/24/2000 this insp also includes
installation of sprinkler sys
MSTA763 Sprinkler Final No Hold BT2 09/20/1999
MSTA765 APPr /Sdwlk lnsp 09/20/1999 09/20/1999 No Hold AKJ 04/09/2000 private d/w
MSTA790 Electrical Final 09/20/1999 09/20/1999 06/09/2000 BRP PASS No Hold AKJ 06/11/2000
MSTA795 Mechanical Final 09/20/1999 09/20/1999 06/12/2000 KBS PASS No Hold AKJ 06/12/2000
MSTA797 Plumb Final 09/20/1999 09/20/1999 06/08/2000 MRS FAIL No Hold AKJ 06/08/2000 1) house needs address
door locked
MSTA798 Final inspection 09/20/1999 09/20/1999 No Hold BT2 09/20/1999
MSTA799 Building Final 09/20/1999 09/20/1999 06/12/2000 KBS FAIL No Hold AKJ 06/12/2000 1) need final erosion control
2) post insul cert
3) seal all penetrations at garage
4) seal around storage doors at
upper level
MSTA032 DST Post- Review Completed 09/28/1999 GEO DONE No Hold GEO 09/28/1999
MSTA080 (F) Ready to issue 09/28/1999 GEO DONE No Hold GEO 09/28/1999
MSTA095 Issue plumbing signature form 10/26/1999 SLT RECD No Hold ST 10/26/1999
MSTA097 Issue electric signature form 10/27/1999 SLT RECD No Hold ST 10/27/1999
MSTA092 (F) Issue combination permit 10/21/1999 BON DONE No Hold BON 10/21/1999
MSTA705 Footing lnsp 10/28/1999 10/28/1999 10/27/1999 KBS PASS No Hold KBS 10/28/1999
#-1- see foundation notes
Page 2 of 4
06/15/2000 Activities for Case #: MST1999 -00315
3:22:41 PM
Assigned Hold Updated
Activity Description Date 1 Date 2 Date 3 To Done By Disp. Level By Updated Notes
MSTA706 Foundation Insp 10/28/1999 10/28/1999 10/27/1999 KBS PASS No Hold KBS 10/28/1999 #-1- initial erosion control
approved
#-2 -ufer rod ( tag)
#-3- install holdowns as shown
#-4- monolithic ftg /fdn
•
-3- install holdowns as shown
MSTA000 SF Detached Menu -1 unit No Hold KBS 10/29/1999
MSTA707 Slab Insp 10/29/1999 KBS PASS No Hold KBS 10/29/1999 #-1- suended garage floor slab.
protect all exposed wood
provide control joints
MSTA704 Sewer Inspection 11/09/1999 MS PASS No Hold DGW 11/10/1999
MSTA755 Rain drain Insp 11/10/1999 11/10/1999 11/09/1999 MS PASS No Hold DGW 11/10/1999
MSTA710 Post/Beam Structural 12/02/1999 12/02/1999 12/02/1999 TLP PASS No Hold TLP 12/02/1999
MSTA727 Exterior Sheathing Insp 02/16/2000 KS FAIL No Hold AKJ 02/16/2000 1) shear panel at gar not done
2) cros12x60 strap at nook
3) shear panel not done at fam
room
4) hd missed at corner of nook
wall
5) complete shear panel at
upper level to under side of roof
sheathing
6) nail shear panels per
schedule
MSTA727 Exterior Sheathing Insp 02/18/2000 KS PASS No Hold AKJ 02/21/2000
MSTA725 Framing Insp 03/02/2000 KBS FAIL No Hold AKJ 03/02/2000 1) mech corr not made
2) provide pos Conn
post/glulams both vertical /horiz
upper lower
3) provide truss detail
4) gas test ok
MSTA720 Mechanical Insp 03/02/2000 KBS FAIL No Hold AKJ 03/02/2000 see framing 3/2
MSTA725 Framing Insp 03/07/2000 KBS PASS No Hold AKJ 03/07/2000 install eave baffles
extend exhaust ducts to roof
jacks •
Page 3 of 4
06/15/2000 Activities for Case #: MST1999 -00315 ,
3:22:41 PM
Assigned Hold Updated
Activity Description Date 1 Date 2 Date 3 To Done By Disp. Level By Updated Notes
MSTA720 Mechanical lnsp 03/07/2000 KBS PASS No Hold AKJ 03/07/2000
MSTA797 Plumb Final 06/09/2000 MRS PASS No Hold AKJ 06/11/2000
MSTA799 Building Final 06/13/2000 KBS PASS No Hold AKJ 06/13/2000
MSTA960 (F) Issue Cert. of Occupancy 06/13/2000 KS DONE No Hold JMT 06/15/2000
•
Page 4 of 4
CITY OF TIGARD BUILDING INSPECTION DIVISION MST tq�t9 3/S
• 24 -Hour Inspection Line: 639 -4175 Business Line: 639 -4171
BUP
Date Requested (/'! 3 O o AM PM BLD
Location t1 � 2- 0 T L i �{) Suite MEC
Contact Person PVC Ph 720 _7(-/L/ S PLM
Contractor Ph SWR
Ett11CDIN) Tenant/Owner ELC
Retaining Wall ELR
Footing Access:
Foundation a FPS
Ftg Drain SGN
Crawl Drain Inspection Notes:
Slab SIT
Post & Beam
Ext Sheath /Shear
Int Sheath /Shear
Framing
Insulation
Drywall Nailing
Firewall
Fire Sprinkler
Fire Alarm
Susp'd Ceiling
Roof
Misc:
S S PART FAIL
PLUMBING
Post & Beam
Under Slab
Top Out
Water Service
Sanitary Sewer
Rain Drains
Final
PASS PART FAIL
IECFIA AL� -
Post & -am I
Rough n
Gas ine \q
/
Sm'- e Dam rs `!1' l/
•ASS PART FAIL
ELECTRICAL
Service
Rough In
UG /Slab
Low Voltage
Fire Alarm
Final
PASS PART FAIL
SITE
Backfill /Grading
Sanitary Sewer
Storm Drain [ ] Reinspection fee of $ required before next inspection. Pay at City Hall, 13125 SW Hall Blvd
Catch Basin
Fire Supply Line [ ] Please call for reinspection RE: [ ] Unable to inspect - no access
ADA Approach /Sidewalk
Other 4' D (� — �� Inspector e Ext
Final
PASS PART FAIL DO NOT REMOVE this inspection record from the job site.